Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.5 LAccepted-AOC 262 1 NEAR MANAV CHOWK NEW GRAIN MARKET AMBALA CITY HARYANA HARYANA 134003 | AMBALA | HARYANA | 134003 | L1 | Accepted-AOC The lowest bidder | |
| 2 | L2₹26.7 L+₹2.7 L (11.3%)Rejected-AOC 3838 2ND FLOOR SECTOR 46 C CHANDIGARH UT 160047 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160047 | L2 | Rejected-AOC Other than the lowest bidder | |
| 3 | L3₹27.9 L+₹3.8 L (16.0%)Rejected-AOC | L3 | Rejected-AOC Other than the lowest bidder |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
12 Sept 2024, 6:00 pmClosed
GE (I) JUTOGH
GE (I) JUTOGH, JUTOGH CANTT SHIMLA (HP) - 171008
REPAIR AND MAINTENANCE OF INTERNAL ELECTRIFICATION, FIXTURE, FITTINGS ALONGWITH ALLIED WORKS IN MD AND OTM ACCN AT JUTOGH UNDER GE (I) JUTOGH
2024_MES_666057_1
GE(I)/JUT-28 OF 2024-25
Open Tender
Civil Works
Item Rate
180 days
JUTOGH
CLASS D CATEGORY b (i)
6 documents required · 6 mandatory
₹500
GE (I) JUTOGH
₹60,000
Yes
12 Nov 2024
15 Jul 2024
14 Sept 2024
15 Jul 2024
12 Sept 2024
29 Jul 2024
15 Jul 2024 - 22 Jul 2024
Amount
Taking down carefully copper/ aluminum point wiring (light, fan socket or power) complete incl. (fitting such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc.), removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc, complete all as specified and directed.
M&L for point wiring 1.5 Sqmm (nominal cross sectional area) with colour coding multistranded copper conductor cable, PVC insulated (FRLS-H) and unsheathed cable and including drawn through PVC conduit 20mm concealed wiring with all fittings and accessories, terminated to sunken box and laminated sheet of suitable size for housing/mounting the switches/sockets including 1.5 Sqmm PVC insulated unsheathed multistranded copper conductor cable earth wire connected to common earth dolly for one light/fan point control by one, one way switch complete all as specified and as directed.
All as per Srl item No 2.00 above but One bell point controlled by one bell push button, complete all as specified and as directed.
All as per Srl item No 2.00 above but two way swithces complete all as specified and as directed.
All as per Srl item No 2.00 above but one 3 pin socket oulet 5 amps, on same board with other switches, complete all as specified and as directed.
All as per Srl item No 2.00 above but one 3 pin socket oulet 5 amps, on independent board, complete all as specified and as directed.
All as per Srl item No 2.00 above but for one 3 pin 15 Amps power point on independent board with 2.5 Sqmm complete all as specified and directed.
M&L for point wiring with multistranded copper conductor cable, PVC insulated and unsheathed (FRLS-H) size 1.5 sqmm drawn in and incl PVC casing and caping with fixing accessories for one light /fan point controlled by one switch with pressed steel concealed terminal boxes covered with 3 mm thick laminated sheet incl continous earth wire of PVC insulated unsheathed multi stranded copper conductor cable size 1.5 Sqmm for earth wire connected to common earth dolly incl making good disturbed surface as per existing complete all as specified and directed. Note: Cost of making good disturbed surface as per existing deemed to be included in quoted rates.
All as per Srl item No 8.00 above but for one Bell point controlled by one bell push switch on independent board, complete all as specified and as directed.
All as per Srl item No 8.00 above but two way swithces, complete all as specified and as directed.
All as per Srl item No 8.00 above but one 3 pin socket oulet 5 amps, on same board with other switches, complete all as specified and as directed.
All as per Srl item No 8.00 above but one 3 pin socket oulet 5 amps, on independent board, complete all as specified and as directed.
All as per Srl item No 8.00 above but for one 3 pin 15 Amps power point on independent board with 2.5 Sqmm complete all as specified and directed
M&L for point wiring with in existing concealed conduit/ casing caping multistranded copper conductor cable, PVC insulated and unsheathed (FRLS-H) size 1.5 sqmm drawn in and all fixing accessories for one light /fan point controlled by one switch with pressed steel concealed terminal boxes covered with 3 mm thick laminated sheet incl continous earth wire of PVC insulated unsheathed multi stranded copper conductor cable size 1.5 Sqmm for earth wire connected to common earth dolly incl making good disturbed surface as per existing concealed conduit/ casing caping, complete all as specified and directed.
All as per Srl item No 14.00 above but for one Bell point controlled by one bell push switch on independent board, complete all as specified and as directed.
All as per Srl item No 14.00 above but two way swithces, complete all as specified and as directed.
All as per Srl item No 14.00 above but one 3 pin socket oulet 5 amps, on same board with other switches, complete all as specified and as directed.
All as per Srl item No 14.00 above but one 3 pin socket oulet 5 amps, on independent board, complete all as specified and as directed.
All as per Srl item No 14.00 above but for one 3 pin 15 Amps power point on independent board with 2.5 Sqmm complete all as specified and directed
S & F switch piano flush type single pole, one way 5 Amp ( ISI marked) complete all as specified and directed.
S & F Bell push, flush type, 5 amp ( ISI marked) complete all as specified and directed.
S & F switch piano flush type single pole, two way 5 Amp ( ISI marked) complete all as specified and directed.
S & F switch piano flush type single pole, one way 15 Amp ( ISI marked) complete all as specified and directed.
S & F socket (ISI Marked) 2 in 1, 3 pin 5/6 amps flush type complete all as specified and directed.
S & F socket 2 in 1, 5 pin 5 and 15 amps (ISI marked) flush type universal complete all as specified and directed.
S & F Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush type universal complete all as specified and directed.
S&F switch socket combination 2 in 1, 3 pin 5 Amp, complete all as specified and as directed.
S & F Modular switch 1 way 6 A, module complete all as specified and as directed.
S & F Modular switch 1 way 16 A, module complete all as specified and directed.
S & F Modular Bell push 6 A, 1 Module complete all as specified and directed.
S & F modular Socket, 6A-2/3 pin combined 2 module complete all as specified and directed.
S & F modular Socket, 6A/16A-2/3 pin combined 2 module complete all as specified and directed.
S&F white cover plate with frame 1 Module complete all as specified and directed.
S&F white cover plate with frame 2 Module complete all as specified and directed.
S&F white cover plate with frame 3 Module complete all as specified and directed.
S&F white cover plate with frame 4 Module complete all as specified and directed.
S&F white cover plate with frame 6 Module complete all as specified and directed.
S&F white cover plate with frame 8 Module complete all as specified and directed.
S&F for Metal flush box 1 module complete all as specified and directed.
S&F for Metal flush box 2 module complete all as specified and directed.
S&F for Metal flush box 3 module complete all as specified and directed.
S&F for Metal flush box 4 module complete all as specified and directed.
S&F for Metal flush box 6/8 module complete all as specified and directed.
S&F in repair PVC conduit of 20mm dia complete all as specified and directed.
S&F in repair PVC conduit of 25mm dia complete all as specified and directed.
S & F in repair PVC casing capping of 25mm (1") width complete all as specified & directed
S & F ceiling rose, 3 phase, PVC polycarbonate, insulated body (ISI Marked) complete all as specified and directed.
S & F Buzzer, Ding dong Bell AC 230 volts single pole complete all as specified and directed.
S & F bell multi music type/ Ding dong, complete all as specified and directed.
M&L for lamp holder (Angle) PVC/Polycarbonate type with back plate suitable for batten/ bulb fittings incl 9 wall LED bulb, complete all as specified and directed.
S&F LED tube light along with fixture, 1x 17 watt, (4 Feet) wall mounted LED battern, integrated electronic driver with heat sink provided for efficient heat dissipation, optics diffussed, complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings and all fixing arrangements complete all as specified and directed.
S&F LED tube light along with fixture, 1x 10 watt, (2 Feet) wall mounted LED battern, extrudedd PVC, heat sink provided for efficient heat dissipation & integrated electronic driver, optics diffussed, complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings and all fixing arrangements complete all as specified and directed.
S&F in replacement 18W LED (Size minimum 210mmx210mm or 1'x1') square shaped surface/ Recess mounting luminaire suitable for hanging on any surface inclluding connecting twin core copper cable up to ceiling rose complete with separate electronic driver & high brightness LEDs white colour complete all as specifed and directed.
S&F in replacement 36W LED(4 x 1) surface / Recess mounting luminaire suitable for hanging on any surface including connecting twin core cable up to nearest point complete with separate electronic driver & high brightness LEDs white colour complete all as specifed and directed.
S&F in replacement 36/40W LED (Size 2'x2') square shaped Recess mounting type luminaire having white polycarbonate body & Alumium heat shink with PMMA diffuser, 5700K including connecting three core copper cable up to ceiling rose complete with separate electronic driver & high brightness LEDs white colour complete all as specified and directed.
S&F in replacement round type recessed mounting LED luminaire 18/20 Watt including making arrangment in ceiling as per the size of fittings and connecting twin core cable up to nearest point complete with Inbuit/separate electronic driver & high brightness LEDs Natural white colour complete all as specifed and directed.
S&F LED Bulkhead luminaire 10W Decorative type as per sample complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings all as specified and directed.
S&F LED building securtiy light 25 watt fixed on wall suitable bracket with all connected accessories complete including electrical connection with copper cable from ceiling rose to fittings and including taking down existing fittings and all fixing arrangements complete all as specified and directed.
S&F for LED die cast aluminium housing opal white PC diffuser IP 65 with in built LED Bollard light for staircase complete all as specified and directed.
M&L for submain wiring with 2X6.0Sqmm+1X6.0Sqmm Earth Wire single core PVC insulated FRLS-H PVC sheathed cooper cable connecting to common earth dolly in and including heavy duty PVC Concealed Conduit as per site requirement and direction by EIC, with all accessories complete including taking down to old unserviceable, complete all as specified and directed. Note: Three runs of copper wire for phase , neutral, earth & one run PVC conduit/ casing shall be measured one unit length.
All as per Srl item No 60.00 above but for 2 run of single core 4 Sqmm FR PVC insulated unsheathed multistranded copper conductor cable and one run of 4.0 Sqmm FR PVC insulated unsheathed multistranded copper conductor earth wire complete all as specified and directed.
S&F in repair VTPN MCCB distribution board 4 way fabricated out of thick high quality CRCA sheet, DBs shall be totally enclosed, suitable for 240V/415V, having polyurethane (PU) foam gasket to ensure IP-54 degree of protection for indoor application as pre IEC 61439-3:2012 (CI. 10.3)/IEC 60529.DB shall be robust with tested for impact resistance IK09as per IEC 61439-3:2012(CI.No. 10.2.6).DBs shall be provided with prefitted cement Guard. DB Door shall have detachable gland plates provided with proper knockout holes of 26mm/35mm diameter for intsertion of cable /conduits. Distribution Boards shall bre provided with wire set of copper along with the insulated fork type bus bars. DB shall heve reversible hinged doors and possibility to allow door opening from left to right or right to left for convenience on site. DB shall have type test reports as per IEC 61439-3 from ERDA or NABL laboratery complete all as specified and directed.
S&F in repair TPN Distribution board 4 way fabricated out of thick high quality CRCA sheet, DBs shall be totally enclosed, suitable for 240V/415V, having polyurethane (PU) foam gasket to ensure IP-54 degree of protection for indoor application as pre IEC 61439-3:2012 (CI. 10.3)/IEC 60529.DB shall be robust with tested for impact resistance IK09as per IEC 61439-3:2012(CI.No. 10.2.6).DBs shall be provided with prefitted cement Guard. DB Door shall have detachable gland plates provided with proper knockout holes of 26mm/35mm diameter for intsertion of cable /conduits. Distribution Boards shall bre provided with wire set of copper along with the insulated fork type bus bars. DB shall heve reversible hinged doors and possibility to allow door opening from left to right or right to left for convenience on site. DB shall have type test reports as per IEC 61439-3 from ERDA or NABL laboratery complete all as specified and directed.
All as per Srl item No 63.00 above but for SPN DB 12 way complete all as specified and directed.
All as per Srl item No 63.00 above but for SPN DB 8 way complete all as specified and directed.
All as per Srl item No 63.00 above but for SPN DB 4/6 way complete all as specified and directed.
S & F sheet metal enclosures DB's 2 way SPN single door suitable for 240 V complete all as specified and directed.
S & F MCB Single pole 6A Tto 25A rating, 240/415V, having short circuit breaking capacity icn = 10kA, " B" curve characterstics, suitable for resistive & inductive load. MCB shall have true position indicator on the front facia. MCB shall have bi-connect arrangement on top & bottom for simultaneous connection of cable and busbar.MCB shall have line load reversibility. MCB shall have ISI marking with latest type test reports as per IS/IEC 60898/IEC 60947-2 standard complete all as specified and directed.
All as per Srl item No 68.00 above but for MCB SPN 40 Amps complete all as specified and directed.
All as per Srl item No 68.00 above but for MCB SPN 63 Amps complete all as specified and directed.
S&F MCB TP 415 volt 25 to 63 amp 'B' Curve with 10 kA for inductive load connected through cable lugs of suitable size complete all as specified and directed.
S&F MCB TPN/FP 415 volts 40 to 100 amp 'B' Curve with 10 kA for inductive load connected through cable lugs of suitable size complete all as specified and directed.
S&F MCCB 3 Pole 415 V fixed type 25 to 100 Amps with breaking capacity 16 KA for inductive load connected through cable lugs of suitable size complete all as specified and directed.
S&F MCCB 3 Pole 415 V fixed type 125 to 160 Amps with breaking capacity 16 KA for inductive load connected through cable lugs of suitable size complete all as specified and directed.
S & F Single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB with 240 volt, 20 amps, including taking out complete all as specified and directed.
S&F MS conduit medium grade 20 mm dia for passing electric wires/ fixing of tube light suspension type including necessary swivel joints and connecting up complete all as specified and as directed including taking out old unserviciable one, complete all as specified and directed.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthling etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed.
All as per Srl item No 77.00 above but for 32x6mm galvanised iron strip, complete all as specified and directed.
S&F in repair Surge protection device (SPD) Voltage protection level Up upto 1.3 kV, suitable for protection of all terminal equipments Both Common & Differential Mode Protection complete all as specified and directed.
S&F in repair exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250mm including fixing all arangements complete all as specified and directed. Note : Old unservicable material obtained shall be deposited to AGE E/M store yard by the contractor.
S&F in repair exhaust fans AC single phase 230/ 240 V of size 300 mm sweep metal body with louver including fixing all arangements complete all as specified and directed. Note : Old unservicable material obtained shall be deposited to AGE E/M store yard by the contractor.
S&F in repair exhaust fans AC single phase 230/ 240 V of size 450 mm sweep metal body with louver including fixing all arangements complete all as specified and directed. Note : Old unservicable material obtained shall be deposited to AGE E/M store yard by the contractor.
S&F AC single phase static energy meter of accuracy class 1.0, 240 V, 50 Hz back light LCD display of rating 5 - 30 A, (measures and displays KWH ,V, Current I, KW, pf last month history of KWH, MD in KW) with special features like TOD, temper logging, optical communication port display in absence of power with transparent hinge type box made up of GI sheet thickness 3.15mm / sheet metal enclosure, including fixing all arangements complete all as specified and directed.
Earthing complete with galvanised steel earth plate electrode, 60x60cmx 6.3mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.
S & F in repair Plug Top 15 Amp 3 pin 230 volt complete all as specified and directed.
S & F in repair Plug Top 5 Amp 3 pin 230 volt complete all as specified and directed.
S & F in repair LED 7 watt lamp complete all as specified and directed.
S & F in repair LED 9 watt lamp complete all as specified and directed.
S & F in repair Single core PVC Insulator with Copper stranded Conductor Cable 1100V grade ISI size 1.5 Sqmm complete all as specified and directed.
S & F in repair Single core PVC Insulator with Copper stranded Conductor Cable 1100V grade ISI size 2.5 Sqmm complete all as specified and directed.
S & F in repair Single core PVC Insulator with Copper Conductor Cable 1100V grade ISI size 4.0 Sqmm complete all as specified and directed.
S & F in repair Single core PVC Insulator with Copper Conductor Cable 1100V grade ISI size 6.0 Sqmm complete all as specified and directed.
S & F in repair Twin flexible twisted with Copper stranded Conductor Cable 230V grade ISI size 23/0.0036 complete all as specified and directed.
S & F in repair service cable 6.0 sqmm x 2 core PVC Insulator with Aluminium Conductor Cable 230V grade ISI complete all as specified and directed.
S & F in repair service cable 10.0 sqmm x 2 core PVC Insulator with Aluminium Conductor Cable 230V grade ISI complete all as specified and directed.
naina devi constructions (BID ID -3092526)
J D ENTERPRISES (BID ID -3094163)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .