Superintending Engineer PWD
Office of the Superintending Engineer PWD Buildings Construction and Maintenance Circle Chepauk Chennai 5
Provision of Electrification arrangements to the G.D.P. Hall in Master Plan Complex at Collectorate, Tiruvallur in Tiruvallur District.
2025_PWD_534869_1
TNPWD/50-3 BCM/2024-25
Open Tender
Electrical Works
Lump-sum
Tiruvallur
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹26,900
26 Mar 2025
22 Mar 2025
25 Mar 2025
22 Mar 2025
25 Mar 2025
22 Mar 2025
Amount
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) ( 4 points / Coil) (crab tree / legrand myrius/Equ)
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) ( 6 points / Coil) (crab tree / legrand myrius/Equ)
Supply and Fixing of 1X18w/22w 4 feet LED fitting with 1 No.20W Direct LED Tube with complete set on ceiling or on wall with TW round block with PVC unsheathed copper leads from terminals to the Fittings. (Philips / Havells/Equ)
Supply and Fixing of Twin type 1X18w/22w 4 feet LED fitting with 2 Nos.20W Direct LED Tube with complete set on ceiling or on wall with TW round block with PVC unsheathed copper leads from terminals to the Fittings. (Philips / Havells/Equ)
Supply and fixing of 42W LED 2x2 square type Recessed fitting with LED on false Ceiling with suitable frame with hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting. (Philips / Havells/Equ)
Supply and fixing of Bulk Head LED fitting with suitable 9W LED Bulbs on wall with suitable necessary connections.
Supply and fixing of 1200mm (48") sweep AC ceiling fan complete ( Higher end) with 2 module 100W fan step regulator (Higher end) with 1 metre down rod with fan clamp with side plates and cross arm of size 450mm (18") (Crompton/Equ)
Supply and fixing of 600mm wall mounting air circulator fan with suitable clamps and copper end terminals. (Almonard/Equ)
Supply and fixing of 300 mm (12") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall (Crompton/Equ)
Supply and fixing of louvers shutters arrangements for 300 mm (12") sweep (light duty) AC exhaust fan
Supply and fixing of 375 mm (15") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall (Crompton/Equ)
Supply and fixing of louvers shutters arrangements for 375 mm (15") sweep (light duty) AC exhaust fan
Supply and fixing of 24W LED round type Surface fitting with LED on Ceiling with suitable clamps support from ceiling with PVC unsheathed copper leads from terminals to the fitting. (Philips / Havells/Equ)
Supply and fixing of 20A DP plug and socket in sheet enclosure with 32A DP MCB in flush with wall with earth connection.(For AC plug) (Hager / Legrand)
Supply and fixing of 1 no.6/16 A two module socket, 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI) in flush with wall with connections.
Supply and fixing of 2 nos.6A two module 5 pin socket , 2 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box ( GI ) in flush with wall with connections. (crab tree / legrand myrius/Equ)
Supply and fixing of 1 no.6A two module socket , 1 no. 6/16A two module socket , 1no. 6A one module switch, 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box ( GI ) in flush with wall with connections.) (crab tree / legrand myrius/Equ)
Supply and fixing of 2 nos.6/16A two module socket , 2 nos. 16A one module switch with module cover plate (plastic) on suitable module concealed Box ( GI ) in flush with wall with connections. (crab tree / legrand myrius/Equ)
Supply and fixing of 48W LED street light fitting with LED with 32mm dia. GI pipe (class B) with 1 no.32 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting. (Havells/Equ)
Supply and erection of 1.5 TR capacity high wall mounting Split Air –conditioner conditioning to IS 1391 (part-2) 1992 with amendment No.1 except power consumption (norms) fixed with hermetically sealed compressor operation R 32 Non CFC for wall mounting with minimum guaranteed cooling capacity and maximum power consumption suitable for operation on 230 Volt , 50 Hz, Ac power supply complete performing following functions. 1. Cooling 2. De- humidifying 3. Air circulating 4. Filtering (Make: Carrier / Blue star/Equ)
Supply and fixing of 4KVA wall mounting type Automatic voltage stabilizer with time delay arrangements suitable for operation at 230 Volt, 50 Hz, AC power supply (Make: V –Guard / Equivalent)
Supply and fixing of suitable MS angle iron frame work support to the outdoor unit
Supply and laying of 5/8” & 3/8” copper with 3 core cord wire and insulation etc.
supply and fixing of 1 inch PVC water drain pipe line on wall with suitable Clamp as required.
supply and fixing of 32A DP Change over MCB with suitable Sheet steel enclosure on with wall with necessary earth connection.
Supply and fixing of 32A DP MCB with suitable Sheet steel enclosure in flush with wall with necessary earth connection. (Hager / Legrand)
Supply and run of 2 of 1.5sq.mm.PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in rigid pipe concealed in wall and ceiling with continuous earth wire connection of 1.5sq.mm copper wire and making good of the concealed portion with suitable colour
Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire and making good of the concealed portion with suitable colour. (RR / Polycab/Eq.)
Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour. (RR / Polycab/Eq.)
Supply and run of 2 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with contiinuous earth wire connection of 6 sq.mm copper wire and making good of the concealed portion with suitable colour. (RR / Polycab/eq.)
Supply and Run of 4 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection by 6 sq.mm. PVC insulated SC unsheathed FRLS copper wire with painting of suitable colour. (RR / Polycab/Equ)
Supply and Run of 4 of 10 sq.mm. PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 10 sq.mm copper wire with painting of suitable colour. (RR / Polycab/Equ)
Supply and fixing of 8way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) 1No. 32A DP MCB as incoming and 6Nos. 6A to 32A SP MCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be with ISI mark (like standard make)(Hager/legrand)
Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 10 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End. (Hager/legrand)
Supply and fixing of Three phase Seven Segment type 4 way 63A distribution board with Metal Door cover Code IP42 Protection, with 63A 4 pole MCB as incoming and Sub incomers 3 Nos 40A DP MCB and 12 Nos 6-32A SPMCB as Outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB’s should be with ISI mark. (Hager/legrand)
Supply and fixing of Three phase Seven Segment type 6 way 63A distribution board with Metal Door cover Code IP42 Protection, with 63A 4 pole MCB as incoming and Sub incomers 3 Nos 40A DP MCB and 18 Nos 16-32A SPMCB as Outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB’s should be with ISI mark. (Hager/legrand)
Supply and Laying of 3 1/2 x 185 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. (RR/ polycab/ KEI/Equ)
Supply and clarnping of 3 1/2 x 185 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps. (RR/ polycab/ KEI/Equ)
Supply and fixing of brass cable gland for 3-1/2 x 185 sq.mm. PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3-1/2 x 185 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete.
Supply and fixing of 250 A Three phase 500V 4 Pole Change over Switch on suitable angle iron frame work with MS cable entry boxes with earth connection only.
glands cable adopter box etc, bus should be mounted on synthetic enamel compound bus supports at equal interval as per ISI specifications. The incoming 250A switches should be connected to the bus with same size of 1 x 1/4 fixed copper flat and 125A, 100A & 63A switches should be connected to the bus by 1x1/8 fixed copper flat. The switch should be separated by 6mm thick hylem sheet separators and properly (double) earthed as per IE rules, CEIG specification. The panel should be powder coat painting Siemens grey complete with LED Digital Display for VAF Meter chamber. The cable size, capacity of switch and location should be marked with Computers Stickers .
Earthing as per ISI specification with an earth electrode of 2.1 mtr class ‘B” GI pipe of dia not less than 40mm with copper earth plate of size 125mm x 50mmx6mm with necessary funneling arrangement with necessary masonry work with 38 mm RCC cover slab for brick masonry works.
Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection.
Supply, erection,testing and commissioning of 5 KVA UPS system make (Numeric/fuji electric) (single phase input & Signal phase output) 2 hours back- up for the following configuration 1) True ON LINE –UPS SYSTEMS with Pulse width modulation(PWM) Technology using IGBT Inverter. 2) INPUT VOLTAGE RANGE : 230V 3)OUTPUT VOLTAGE : 220V ± 1% 4)DC Volt:120V 5)INPUT FREQUENCY : 50Hz ± 5% 6)Out put Frequency: 50Hz ± 2% 7) Out put Waveform:Pure Sine Wave 8) LOAD POWER FACTOR : 0.8 to Unity 9)HarmonicDistoration: Less than 5% 10)Over Load: : 125% for 10Minutes 11)Inverter Operation : PWM-IGBT 12)Invertor Efficience : Better Than 90% 13)OPERATING TEMPERATURE : 0 to 50 Degrees centigrade’s on Full Load
14)Digital Panel Meter : To Read output A/C Volts,Output D/C Volts Frequency 15)By pass : Manual 16)PROTECTION (INBUILT) : a. Output Under Voltage b. Output Over Voltage c. Output Overload d. Output Short Circuit e. HRC Fuses, Output & Battery f. Battery Low trip g. Battery Charging Current Limit. 17)INDICATIONS : 1. Mains On, 2. Inverter On, 3. Load on U.P.S. 5. Battery Low 6.Over load 7.Inverter Trip. 18) MS Rack for Batteries.
GST at 18%
BHARAT CORP (BID ID -1277834)
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .