Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.1 LAccepted-AOC | ₹42.1 L Quoted ₹42.8 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹43.3 LRejected-Finance H 13 GEETANJALI PARK WEST SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | ₹43.3 L | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹46.9 LRejected-Finance | ₹46.9 L | L3 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | A B K Enterprises L3 | J.P. Enterprises L2 | Vijeta Solutions L1 |
|---|---|---|---|---|---|---|
| 1.00Maintenance of DG sets once including attending faults on call basis for normal repairs including replacement of defective & worn out parts by new spares such as filters, gaskets, V belts, Engine oil, rubber hoses, worm drive clamps, nut bolts and cleaning of alternator with vaccum cleaner and CTC attending faults of AMF panels and greasing of bearings of engine and alternator, checking of batteries, adding distilled water, checking of oil and coolant levels as directed by engineer-in Charge. Note : - (i) Spares required for above maintenance will be measured and paid separately under relevant item. (ii) All work pertains to DG set shall be executed only through authorised service provider of OEM of respective DG set. The contractor has to submit MOU with the authorised service provider. The authorised service provider shall give his complete investigation report of respective DG set seperately on his first visit to each DG set. (iii) Servicing of DG set to be carried out as per schedule specified by OEM . | ||||||
| 1.01 | D. G . Set 320 KVA, Make: Cummins | 6 | Per Month | 7,500 ₹45,000 | 7,000 ₹42,000 | 7,500 ₹45,000 |
| 1.02 | D. G . Set 250 KVA, Make: Cummins | 6 | Per Month | 6,500 ₹39,000 | 6,000 ₹36,000 | 7,500 ₹45,000 |
| 1.03 | D. G . Set 125 KVA, Make: Kirloskar | 6 | Per Month | 5,500 ₹33,000 | 5,000 ₹30,000 | 6,500 ₹39,000 |
| 2.00Supply only diesel filter element with O ring, suitable for following capacities of DG sets :- | ||||||
| 2.01 | D. G . Set 320 KVA | 1 | Each | 2,000 ₹2,000 | 1,500 ₹1,500 | 1,800 ₹1,800 |
| 2.02 | D. G . Set 250 KVA | 1 | Each | 1,800 ₹1,800 | 1,400 ₹1,400 | 1,500 ₹1,500 |
| 2.03 | D. G . Set 125 KVA | 1 | Each | 1,200 ₹1,200 | 1,000 ₹1,000 | 1,500 ₹1,500 |
| 3.00Supply only oil filter element with O ring, suitable for following capacities of DG sets :- | ||||||
| 3.01 | D. G . Set 320 KVA | 1 | Each | 2,000 ₹2,000 | 1,500 ₹1,500 | 1,800 ₹1,800 |
Updated dates
Tender Value
₹49.7 L
EMD Value
₹99,400
Closing Date
15 Nov 2025, 6:00 pmClosed
GE (AF) SUBROTO PARK
GE (AF) Subroto Park, Delhi Cantt Delhi-110010
As described in Bill of quantities
2025_MES_736024_1
GE/SP/TOKEN-50/2025-26
Open Tender
Electrical and Maintenance Works
180 days
GE (AF) SUBROTO PARK
As per NIT and tender documents
9 documents required · 9 mandatory
₹500
GE (AF) SUBROTO PARK
₹99,400
Yes
15 Jan 2026
18 Oct 2025
18 Nov 2025
18 Oct 2025
15 Nov 2025
3 Nov 2025
Amount
Maintenance of DG sets once including attending faults on call basis for normal repairs including replacement of defective & worn out parts by new spares such as filters, gaskets, V belts, Engine oil, rubber hoses, worm drive clamps, nut bolts and cleaning of alternator with vaccum cleaner and CTC attending faults of AMF panels and greasing of bearings of engine and alternator, checking of batteries, adding distilled water, checking of oil and coolant levels as directed by engineer-in Charge. Note : - (i) Spares required for above maintenance will be measured and paid separately under relevant item. (ii) All work pertains to DG set shall be executed only through authorised service provider of OEM of respective DG set. The contractor has to submit MOU with the authorised service provider. The authorised service provider shall give his complete investigation report of respective DG set seperately on his first visit to each DG set. (iii) Servicing of DG set to be carried out as per schedule specified by OEM .
D. G . Set 320 KVA, Make: Cummins
D. G . Set 250 KVA, Make: Cummins
D. G . Set 125 KVA, Make: Kirloskar
Supply only diesel filter element with O ring, suitable for following capacities of DG sets :-
D. G . Set 320 KVA
D. G . Set 250 KVA
D. G . Set 125 KVA
Supply only oil filter element with O ring, suitable for following capacities of DG sets :-
D. G . Set 320 KVA
D. G . Set 250 KVA
D. G . Set 125 KVA
Supply only by pass filter element with O ring suitable for following capacities of DG sets :-
D. G . Set 320 KVA
D. G . Set 250 KVA
D. G . Set 125 KVA
Supply only air filter element suitable for following capacities of DG sets :-
D. G . Set 320 KVA
D. G . Set 250 KVA
D. G . Set 125 KVA
Supply only fan belt suitable for following capacities of DG sets:-
D. G . Set 320/250 KVA
D. G . Set 125 KVA
Supply only battery charging alternator belt suitable for following capacities of DG sets :-
D. G . Set 320/250 KVA
D. G . Set 125 KVA
Supply only rubber hose pipe set for water circuit complete with clamps, suitable for 320/250/125 KVA capacities of DG sets
Supply and fixing in replacement PVC insulated multisranded , copper conductor 70 sqmm multistranded of 1.25 mtr long battery leads each duly fixed with brass clamps, copper lugs suitable for DG sets installed at different locations .
Supply only engine oil, multi grade 20w / 40.
Supply only coolant all as specified and as directed by the Engineer-In- Charge.
Supply and applying Petroleum jelly.(1 kg plastic sealed container.)
Supply and fill in batteries distilled water for topping up
M & L for Dismantling of radiator , taking it to work shop for overhauling & cleaning descaling with acid removal of leakage, welding brazing & refixing it duly repaired etc all as directed by Engineer- in- Charge
D. G . Set 320/250 KVA
D. G . Set 125 KVA
Calibration of FIP and injectors from the authorised dealer including petty repairs to make the FIP functional for the following capacities of DG sets including necessary spares required for smooth functioning of FIP :- Note : A Certificate to the effect that the calibration and repairs has been carried out by the authorised dealer shall be submitted by the contractor.
D. G . Set 125 KVA
D. G . Set 320/250 KVA
M&L for tappet setting of D. G . Set 320/250 KVA capacities
Supply only Oil Sump packing set suitable for following DG sets
D. G . Set 125 KVA
D. G . Set 320/250 KVA
Supply and fix solenoid valve suitable for following capacity DG sets
D. G . Set 125 KVA
D. G . Set 250/320 KVA
M&L for repair / overhauling of self starter incl. replacement of carbon brushes, bearing, bushes, rewinding of armature and field etc. and varnishing complete all as directed for the following capacity :-
24 Volts
12 Volts
Supply & Fix in replacement self starter for suitable 125 KVA DG set capcity including all necessary electrical connections complete all as specified and as directed by the Engineer-In- Charge.
Supply & Fix in replacement self starter for suitable of 250 KVA to 320 KVA DG set DG set capcity including all necessary electrical connections complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in repair automatic voltage regulator up to 125 KVA as directed by Engineer-In-Charge.
Supply and fix in repair automatic voltage regulator above 250 KVA upto 320 KVA as directed by Engineer-In-Charge.
Supply and fix in repair control wiring of the DG set above 250 KVA up to 320 KVA complete incl provision of additional auto cables heavy duty suitable for Gen set application .
Supply & Fix in replacement 24 Volts SMPS battery Charger complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in replacement lead acid maintenance free battery 180 AH, 12 V, complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in replacement lead acid maintenance free battery 88 AH ,12 Volt complete all as specified and as directed by the Engineer-In- Charge.
Supply & Fix in replacement of digital multi function meter to read voltage, current and power factor complete all as specified and as directed by the Engineer-In- Charge.
Supply & Fix in replacement of 3 pole power contactor MNX 400 complete all as specified and as directed by the Engineer-In- Charge.
Supply & Fix in replacement of solenoid switch suitable including all necessary arrangement complete all as specified and as directed by the Engineer-In- Charge.
S&F in replacement belt for water pump ( set ) in 125- 250 KVA DG set for greevs complete all as specified and as directed by the Engineer-In- Charge.
S&F in replacement PCB 24 Volt DC with engine start stop relay suitable for 250 KVA-320 KVA DG Set complete all as specified vol and as directed by the Engineer-In- Charge.
S&F in replacement stopper switch 24 Volt DC suitable for 160 KVA DG Set complete all as specified vol and as directed by the Engineer-In- Charge.
S&F in replacement PCB 12 Volt DC with engine start stop relay suitable for 30-125 KVA DG Set complete all as specified vol and as directed by the Engineer-In- Charge.
S&F in replacement stopper switch 12 Volt DC suitable for 30-125 KVA DG Set complete all as specified vol and as directed by the Engineer-In- Charge.
Supply and fix oil safety switch to engine of 125 KVA DG set KVA DG set as per existing complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix oil safety switch to engine of 250 KVA to 320 KVA DG set DG set as per existing complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in replacement the corrosion resistor as per existing to the Engine of DG set of any capacity complete all as specified and as directed by the Engineer-In- Charge.
S & F start and stop relay 12 V/24 V DC suitable for AMF Panel of any capacity of all as per manufacturers recommendations and complete all as specified and as directed by the Engineer-In- Charge.
S & Fix in repairs Low lub oil pressure sensor for 125 KVA DG set and connecting with DG set system complete all as specified and as directed by the Engineer-In- Charge.
S & Fix in repairs temperature sensor for 250 to 320 KVA DG set and connecting with DG set system complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in replacement Lub oil hoses set including neceaary clamps, nut ,bolts and washer for DG set of any capacity complete all as specified and as directed by the Engineer-In- Charge.
Supply and fix in replacement DG set controller for 250 KVA DG set of make Cummins, control panel model :- Power Command HMI211 , complete all as specified and as directed by the Engineer-In- Charge.
Supply & fix in replacement of Under Voltage relay E-210 ,suitable for 440 Volt complete all as specified and as directed by Engineer-in-charge.
Supply & fix in replacement of on delay timer suitable for 230 Volt AC complete all as specified and as directed by Engineer-in-charge.
M & L for replacement of unserviceable hinges of DG set canopy doors with the new SS hinges heavy grade including welding /screwing as required on site complete all as specified and directed.
Material and labour in replacement of aluminium cable thimbles with suitable nut bolt and double washer of size 240-400 Sqmm UG Cable including connection and crimping complete all as specified and directed.
All as per Item No 48 above but 120-185 Sqmm.
All as per Item No 48 above but 95 Sqmm.
All as per Item No 48 above but 70 Sqmm.
All as per Item No 48 above but 50 Sqmm.
All as per Item No 48 above but 35 Sqmm.
Taking down unserviceable light fittings from the high mast by lowering the high mast by winch & motor including checking the unserviceable parts like, electronic driver copper wire link unserviceable hight mast light, clamp and re-fixing the fittings back to its original position after carried out all necessary repairs to make the fitting serviceable.( Note:- Light fitting, connecting wire , driver etc to be replaced shall be measured and paid separately under respective items here-in- after).
Supply and fix in replacement junction box of size 200mmx150mmx100mm made out of FRP with double stud hinged door locking including electric connection for 3 phase out going cable and single phase connection for street light fitting incl controlled MCB SP-10Amps -01 Nos with dinrail for mounting of MCB inculding suitable connector for looping duly sealed with rubber plugs enclosed in thermo plastic inclosed shock proof safe IP-65 weather vermin proof dust and water proof complete with nos cable entry incl glands of standeard size with suitable size mild steel clamps to fixed on pole complete all specified and directed.
Supply only in replacement of electronic driver for LED flood light 100/120 watt, Suitable as per existing Flood light model complete all as specified and as directed by Engineer-in-Charge.
Supply only in replacement of electronic driver for LED flood light 150/250 watt, Suitable as per existing Flood light model complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement of digital type type time switch 3P module, DIN 24 hours programmable every 30 minutes of current capacity 16 Amps with one change over including connecting to existing power contactor complete .
Excavation in trenches in soft/loose soil not exceeding 1.50 Mtrs wide and not exc. 1.5 Mtr deep and getting out for taking out /laying cable, poles & stay etc complete all as specified and as directed by Engr-in-Charge.
Returning, filling in including spreading leveling, watering and well ramming in layers not exc 25 cm thick after the cable have been laid tested complete.
Removal of excavated surplus soil to a distance not exc. 50 Mtrs and depositing where directed at a level not exc 1.5 Mtr above the starting point complete.
M&L for sand cushioning to under ground cable provided with layer of sand (8 cm deep before laying the cable and 15 cm deep after laying the cable i.e total 23 cm).
Supply and laying reinforced precast concrete cable cover class LV ,type I,flat ,size 250mmx150mmx 40 mm for cable protection over cable perpendicular to direction of cable per complete all as specified and directed.
Taking out old unserviceable LT under ground cable of size 16 sqmm 4 core from trenches, pipes & poles complete all as specified and directed.
Taking out old unserviceable LT under ground cable of size 25 sqmm 4 core from trenches, pipes & poles complete all as specified and directed
Taking out old unserviceable LT under ground cable of size 50 sqmm 3.5 core from trenches, pipes & poles complete all as specified and directed
Taking out old unserviceable LT under ground cable of size 95 sqmm 3.5 core from trenches, pipes & poles complete all as specified and directed
Supply Laying and testing of cable XLPE insulated armoured heavy duty under ground 1100 volt grade with stranded aluminium conductor of 16 Sqmm 4 core sizes in trenches /passing through pipes/ on poles etc complele all as specified and directed.
All as per item no 68.00 above but 25 Sqmm 4 core
All as per item no 68.00 above but 50 Sqmm 3.5 core
All as per item no 68.00 above but 95 Sqmm 3.5 core
S&F LED flood light fitting 100 watt ,230V outdoor type with thermal management in multiple optics and equipped with IP66 protection with impact and corrosion resistant complete with driver and lamp all as specified and directed.
S&F LED flood light fitting 150 watt, 230V outdoor type with thermal management in multiple optics and equipped with IP66 protection with impact and corrosion resistant complete with driver and lamp all as specified and directed.
S&F LED flood light fitting 200 watt, 230V outdoor type with thermal management in multiple optics and equipped with IP66 protection with impact and corrosion resistant complete with driver and lamp all as specified and directed.
Supply and fixing in replacement of 3 core flexible copper conductor cable PVC insulated and sheathed of size 2.5 sqmm 1100 volt grade from junction box to LED street light connecting up with complete including drilling of holes in poles if required or through PVC conduit on PCC poles with clamps etc all as specified and directed by Engr-in-Charge.
M&L in replacement of PVC insulated service cable flat or round sheathed, aluminium, multistranded conductor 1100V grade size 16 Sq mm 2 core complete all as specified and directed.
All as per item no 76.00 above but of size 10 Sq mm 2 core complete all as specified and directed.
Supply and fixing motor of capacity 1 HP ,3 phase suitable for high mast pole light assembly lowering and rising complete all as specified and directed.
Taking down U/S street/securitylight fittings complete (HPSV/HPMV/MH/LED) from the pole ,tower,bldg etc for repair and refixing the same back to its original position after making the fitting serviceable .(Note: Spare parts like ballast ,igniter,control gear box,lamp,electronic driver etc required for making the fitting serviceable will be measured and paid seprately under relevant items of the schedule.)
Supply and fixing in replacement LED street light fittings 90 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver ,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete on existing street light poles.
Supply and fixing in replacement LED street light fittings 120 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver ,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete on existing street light poles.
Material and labour for preparation of old painted / rusted surfaces by scrapping of steel tubular LT pole 9 mtr long inculding cross arms and clamps of any size and applying one coat of aluminum paint (1st quality) including white /blue 30 cm wide strip upto the height of 1.5 mtr above ground level and marking the pole No in 4” dia white paint complete all as specified and directed by Engr-in-Charge
S&F of GI pipe light grade 40 mm dia bracket to make L type for bldg light fitting complete all as specified and direted by Engr-in-Charge.
S&F of MS flat clamp of size 30mmx5mm thick including nuts ,bolts and washer suitable for bldg light fitting complete all as specified and as directed by Engr-in-Charge.
Supply and fixing LED 25 watt post top IP 65,energy saving ,long life ,aesthically designed with symmetrical light distribution high power LED as source and connecting up with 3 core flexible copper conductor cable including PCC work complete all as specified and directed.
Supply, install, test and commissioning of free standing floor mounted, dust and vermin proof automatic timer switch box panel board, outdoor type, fabricated with 3.15mm thick CRCA MS Sheet for load bearing members and 2mm thick for doors and covers and shall be painted with epoxy powder paint by means of electro static gun after rigorous pre treatment comprising of cold phosphating process on all internal and external surfaces after due preparation of surfaces. Panel shall be front openable with double stud hinged door & locking arrangement and provided with suitable size of TPN bus bars of high conductivity copper alloy and shall be provided with colour coded heat shrinkable sleeves. The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B-1 using 20mm grade stone aggregate, 600 mm above ground level and comprising the following: (a) ML-4 Contactor, TP, 40 Amps, 415 Volts, 50 HZ - 01 Nos (b) Digital timer switch 20 Amps capacity - 01 Nos (c) MCCB, TP, 63 Amps, 415 Volts, 50 Hz, 10 KA Breaking capacity - 01 Nos [Incoming] (d) MCB, SP, 32 Amps, 240 Volts, 50Hz, 10 KA - 03 Nos
Dismantling concrete poles,struts of any size and keeping them in safe custudy for taking of schedule of credit complete all as specified and as directed by Engineer-in-Charge.
Supply, install erect in trench vertical position steel tublar swan neck seweaged welded poles complete with MS base plate of 6mm thick of size 450mm x 450mm final taper plug pole cap bolt nut and screwed, pole made out of ERW MS tubing confirming to IS 2713 Part II of 8.5 mtr long 410 SP-22 including drilling of holes of required size and nos for fixing of cross arms bracing support/ taking out of cables etc, with inbuilt junction box for 3 phase 4 wire AC supply and painting with one coat of red oxide primer and two coat of aluminium paint for exposed surface and two coat of black bituminious paint for the portion embeded in concerete complete all as specified and as directed by Engineer -in-charge including necessary PCC in foundation and coping all as per SSR part-I .
Supply and fixing LED ornamental type post light made out of spun sheet aluminium main housing , post of aluminium die cast, front cover of clear acrylic , 40 Watt Capacity, 240 Volts IP 65 complete all as specified and as directed by Engr-in-charge. Make:- Halonix cat part no HLOPT-04-40-CW-01 equivalent in all respect in surya/Bajaj/Crompton/Philips
Supply and erect street light pole 4.0 mtr post top made out of MS hot dip galavanizes with PU paint finish of approved colour including inbuilt junction box having window at base of pole having provision for 3 phase 4 wire electrical connection & SP MCB . The pole to be fixed on foundation as per approved drawings of manufacturer with four nos of anchor bolts complete all as specified and directed, the wall thickness shall 2.9 to 3.2 mm at top & 3.2 to 3.4 mm at bottom , the bottom dia of pole 83mm & top dia shall be 75 mm dia alll as specified and directed with necessary PCC in foundation complete all as specified and directed. Make:- Halonix cat part no HLPTP-46-4M-140/76-HDG or equivalent in all respect in surya/Bajaj/Crompton/Philips
Supply & fixing in replacement IP 65 die cast aluminium post top latern designed with long life LED engine & electronic driver,designed for glare free symeetrical light distribution of capacity 70 watt complete all as specified and directed. Make:- Havells cat part no TYCOONPT70WLED757PSYMTOPC or equivalent in all respect in surya/Bajaj/Crompton/Philips/Halonix/eveready
Supply & fixing in replacement IP 66 watt die cast aluminium post top latern designed with long life LED engine & electronic driver,designed for glare free symeetrical light distribution, of capacity 50 watt complete all as specified and directed. Make:- Havells cat part no VICTORIAPT50WLED757PSYMTOTG or equivalent in all respect in surya/Bajaj/Crompton/Philips/Halonix/eveready
Supply & layiing GI pipe light grade of dia 50mm complete all as specified and directed
Making good for road to existing surfaces with using of patch premix bitumenous 25mm thick polymer based material over WBM 75mm thick including rolling etc all as specified and as directed by Engineer-in-charge
Supply & fixing aluminium strip 25x3.15 mm with saddles and fixing screws etc.for roof conductors and down conductors having insulators at one meter interval complete all as specified and directed.
Supply & fix in replacement air termination single pointed aluminium rod 12mm dia and 300mm long all as specified and directed.
Supply & fix in replacement test point terminal block made of gun metal or phosphorous bronze size 75x75x25mm drilled and screwed includind 3 nos 8mm dia 25mm long hex.head screw all as specified and directed.
Material and labour for galvanised iron strip 25 X 4 mm with saddles and fixing screws including insulators of suitable size & ratings at one ,meter interval complete all as specified and as directed by Engineer-in-Charge.
All as per item no 102.00 but 32X6 mm GI stip.
All as per item no 102.00 but 20X3 mm copper stip.
All as per item no 102.00 but 32X6 mm copper stip.
All as per item no 102.00 but 4mm dia GI wire
Excavation in trenches in hard and dense soil n exc 1.5 mtr wide and n.exc 1.5 mtr in depth for laying of pipe,foundation for poles, stay, laying cables etc and getting out copmlete all as directed by engineer-in-charge.
M&L for augering of holes in true horizontal position under road /pavement by means of mechanical rig after doing ultrasound technique to prevent any damage to existing cables/pipe lines coming in route 1.5 Mtr deep and not exceeding 15 Mtrs long complete all as specified and directed.
Supply and laying GI pipe light grade galvanized with all fittings as required laid in trenches or fix on wall/pole for cable protection of 80 mm bore copmlete all as directed by engineer-in-charge.
Taking out old unserviceable LT under ground cable of size 185 sqmm 3.5 core from trenches, pipes & poles complete.
All as per item no 110.00 above but cable size 120 sqmm 3.5 core
All as per item no 110.00 above but cable size 70 sqmm 3.5 core
All as per item no 110.00 above but cable size 35 sqmm 3.5 core
Supply Laying and testing of cable XLPE insulated armoured heavy duty under ground 1100 volt grade with stranded aluminium conductor of 185 Sqmm 3.5 core sizes in trenches /passing through pipes/ on poles etc complele all as specified and directed.
All as per srl item No 114 above but size 120 Sq mm 3.5 core
All as per srl item No 114 above but size 70 Sq mm 3.5 core
All as per srl item No 114 above but size 35 Sq mm 3.5 core
M & L for finding out earthing with the connected equipment and marking to be done with synthetic enmel paint on earthing and making new pit chamber with cover complate all as specified and directed
S&F in replacement of MCCB 400 Amps FP 415 volts 3 phase 50 HZ,Ics=100%Icu , breaking capacity 36 KA including necessary links/lugs etc complete all as specified and directed.
S&F in replacement of MCCB 250 Amps FP 415 volts 3 phase 50 HZ, ,Ics=100%Icu,breaking capacity 35 KA including necessary links/lugs etc complete all as specified and directed.
S&F in replacement of MCCB 200 Amps TP 415 volts 3 phase 50 HZ ,Ics=100%Icu, breaking capacity 35 KA including necessary links/lugs etc complete all as specified and directed.
S&F in replacement of MCCB 160 Amps TP 415 volts 3 phase 50 HZ ,Ics=100%Icu, breaking capacity 35 KA including necessary links/lugs etc complete all as specified and directed.
Design, supply, install, testing and commissioning factory made LT Panel Outdoor type, cubical enclosure compartmentalized external and internal mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc.The enclosure shall be made of 2.00 mm thick stainless steel sheet SS 316 sheet. The fixing of double doors shall be on SS hinges with anti-theft provision. All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 316. Sliding handle and locking arrangement front and rear both side. Enclosure shall be suitable for AC supply system 415 volts, 3 phase, 4 wire, 50 Hz. Degree of protection shall be IP-54. The enclosure shall have provision of cable entry. Cable entry from bottom side including internal wiring with PVC insulated solid, copper wire, 1100 volts grade. The panel shall consist of 300 Amps rating TPN aluminium bus bars and shall be provided with colour coded heat shrinkable sleeves. The panel shall be provided with separate compartments for each switch grar, including instrumentation such as Multi Function meter, phase indicating lamps etc with double stud hinged door, front & rear openable with locking arrangement including interlocking with switch gears and suitable for 1100 Volts grade, 3 Phase, 415 Volts, 50 cycles, AC Supply and to with stand short circuit fault level of not less than 10KA. The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm, embedded 200 mm below ground level in PCC 1:2:4, Type B-1 using 20mm grade stone aggregate, 600 mm above ground level and comprising the following: (a) MCCB 160 Amp 4 pole,Ics=100%Icu -01 No (Incoming) (b) MCCB 100 Amp 3 Pole,Ics=100%Icu -01 Nos (c) MCB TP 63 Amp -05 Nos (Outgoing) (d) Digital timer switch -02 Nos (e) Contactor ML-4 TP 70 Amp for street light with necessary wiring etc. (f) Phase indicating LED -01 Set Note : (i) Rates are inclusive for fixing of suitable size cable gland if required in existing or new cable, CT/ PT and elctrcal connection complete to function multi functional meter. (ii) Danger notice plate must be fixed on panel . (iii) The manufacturer should have Govt. approved certificates:- (a) Panel should be according to IEC-61439, CPRI certificate Degree of protection IP-54. (b) IS/ IEC : 61439 (Part-I & Part-II) 2011 and all necessary certification as per relevant IS/IEC codes.
J.P. Enterprises (BID ID -3470061)
A B K Enterprises (BID ID -3469912)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.85 MB
Tender.pdf
Tender Documents • 1.26 MB
BOQ_824162.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid