Jammu
Repair to 63 KVA Voltage Stabilizer along with allied works at lift irrigation station Harapeer
2020_IFC_108658_1
MID/J/e-NIT/2020-21/62
Open Tender
Repair and Maintenance Works
Lump-sum
10 days
harapeer
As per tender notice
7 documents required · 7 mandatory
₹200
Executive Engineer MID Jammu
₹1,600
Yes
jammu
9 Dec 2020
7 Nov 2020
21 Nov 2020
7 Nov 2020
19 Nov 2020
12 Nov 2020
7 Nov 2020 - 19 Nov 2020
10 Nov 2020
Amount
Carriage & shifting of the disconnected 63 KVA voltage stabilizer from L.I.S. Harapeer on head load through path in fields to roadside (approx distance 2 KM ) using manual labour and then to workshop by carriage vehicle. Shifting back repaired voltage stabilizer to site. The job includes loading, un-loading, manual labour, carriage charges of vehicle (to & fro), tools & tackles etc. Complete job.
Repairs to 63 kva voltage stabilizer by way of dismantling of all components of voltage stabilizer such as coils, rotary switch. Rewinding of 03 no.’s damaged coils with standard gauge wire and proper insulation & tapping. Varnishing of coils with standard quality varnish and allowing it to dry. Heating of repaired coils in oven to get required megger value. Replacing of 3 pole rotary switch. Making all the internal connections and checking its continuity. Reassembling the voltage stabilizer at workshop. Filtration of existing transformer oil and toping up with 75 liters of fresh transformer oil after cleaning the tank to remove carbon deposits. Installation of the voltage stabilizer by connecting incoming and outgoing power cables. Testing of voltage stabilizer on no load and full load conditions. Job includes cost of material including rebate on old copper scrap/ material, labour charges, hire charges of tools and tackles, installation and testing charges at site.
Repair to oil immersed starter of 40 HP motor , double contact of pumping unit no II by way of extracting the damaged contact points of copper both moving and fixed thimbles, no volt coil, tripping system , overload relay and replacing the same with new ones. Providing /filling of 10 liters fresh Transformer oil. Providing and replacement of 24 meter 7/16 copper cable from motor to starter of unit No II and dividing it to six lengths with providing and crimping of new thimbles. Replacing of nuts and bolts. The job includes cost of material, labour charges, installation and testing charges at site.(Complete job).
Rebate on Old Parts
PERFECT ELECTRICAL WORKS
M/S FASTTRACK ENGINEERS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .