Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Rejected-Technical | Rejected-Technical Not fulfilling PQC |
| 5 | Rejected-Technical | Rejected-Technical Disclosing rates in technical bid, rejected as per NIT terms |
Tender Value
Refer Docs
Closing Date
7 Dec 2021, 2:30 pmClosed
ABHISHEK PAREEK
HCL/KCC
RFQ 9487 Contract for making new Earth pits, and miscellaneous jobs in overhead lines at KCM
2021_HCL_95155_1
RFQ9487 Contract for making new Earth pits
Open Tender
Electrical Works
Fixed-rate
365 days
HCL/KCC
Enclosed in Annexure
6 documents required · 6 mandatory
₹0
Exempted
15 Apr 2022
17 Nov 2021
8 Dec 2021
17 Nov 2021
7 Dec 2021
17 Nov 2021
Earthing electrode shall consist of a GI pipe (class B of approved make), not less than 65 mm dia. and 3 meters long. GI pipe electrode shall be cut tapered at the bottom and provided with holes of 12 mm dia. drilled at 75 mm interval up to 2.5 meters length from bottom. The electrode shall be buried vertically in the ground as far as practicable below permanent moisture level, but in any case not less than 3 meters below ground level. The electrode shall be in one piece and no joints shall be allowed in the electrode. As per detail mentioned in scope of work, masonry enclosure on the top i.e as per CPWD code of practice .
Excavation of old pits of size 1 mtr x 1 mtr x 3.5 mtr deep as per instruction of Engineer in charge including back filling with available excavated earth free from sharp edged stones and ramming as required in ordinary soil.
Back filling from 150mm layer of salt and charcoal powder up to 2.5 meter around the pipe electrode shall be installed buried below permanent moisture level not less than meter.. Alternate layer 150mm layer of salt and charcoal powder shall be used. At least 120Kg of salt and 120Kg of charcoal powder shall be used in each earth pit.
Supply & fixing of 6 mm GI earth wire(154 kg/km) with hardware
Supply & Fixing of 6 MM GI 4-Guard Wire (154KG/KM) with lacing and Hardware as per standard (Approx span of 30 meter
Supply & Erection of MS channel 75 mm X 40 mm X 6 mm (7.14 kg per metre - total 4 feet long) cross arm for ladder support & working on line on 60/90 lb. rail pole as per requirement complete with MS clamps, bolts, nuts and washer etc including welding & side collar at both ends and painting with Red Oxide primer
Supplying and erection of galvanized stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I.stay wire and 11 KV strain insulator etc in approx.0.5 cu.m. cement concrete 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required
PRITESH ENTERPRISES
ANUKOM ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .