Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.0 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹38.3 L+₹4.3 L (12.8%)Rejected-Finance | L2 | Rejected-Finance Not Lowest Bidder | |
| 3 | L3₹38.5 L+₹4.5 L (13.3%)Rejected-Finance H NO 698 SECTOR 10 PANCHKULA HARYANA 134109 | PANCHKULA | PANCHKULA | HARYANA | 134109 | L3 | Rejected-Finance Not Lowest Bidder | |
| 4 | L4₹40.8 L+₹6.8 L (20.2%)Rejected-Finance RCP GURUDWARA ROAD WARD NO 29 SURATGARH SRI GANGANAGAR 335804 | SURATGARH | SRI GANGANAGAR | RAJASTHAN | 335804 | L4 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹45.9 L
EMD Value
₹91,800
Closing Date
19 Sept 2024, 6:00 pmClosed
GE (Army) Suratgarh
SURATGARH MIL STN
SPL REPAIR FOR LT OH LINE INTO UG CABLE AND CERTAIN SANCTIONED WORK UNDER GE (ARMY) SURATGARH AT ASCON PHASE IV HARI SINGH PURA AND SURATGARH MIL STN
2024_MES_666596_1
GE (A) SOG Token No -35/24-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Suratgarh
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE(Army) Suragarh
₹91,800
Yes
29 Nov 2024
19 Jul 2024
21 Sept 2024
19 Jul 2024
19 Sept 2024
2 Aug 2024
Amount
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft / loose soil & getting out complete all as specified and directed by Engineer-in-Charge.
All as per serial item No. 1 here-in-above but depth exc 1.5 mtr & not exc 3mtr
Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soft/loose soil complete all as specified and directed by Engineer-in-charge.
Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and directed by Engineer-in-charge.
M&L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation of poles, filling & mass concrete including necessary form work complete all as specified and directed by Engineer-in-charge .
M & L for PCC (1:3:6) typeC-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing complete all as specified and directed by Engineer-in-charge
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge
S&F 15mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified and directed by Engineer-in-charge.
S&F 25 mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified and directed by Engineer-in-charge.
Taking up or down 100mm dia, steel tubing & connections including cleaning for refixing after repairing joints complete all as specified and directed by Engineer-in-Charge.
S&F 25 mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified and directed by Engineer-in-charge.
S&F 40 mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified and directed by Engineer-in-charge.
S&F 50mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors / trenches complete all as specified and directed by Engineer-in-charge.
S&F 80mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors / trenches complete all as specified and directed by Engineer-in-charge.
S&F 100mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors / trenches complete all as specified and directed by Engineer-in-charge.
S&F 150mm bore galvanized steel water tubing medium grade with & including all fittings and fixed complete to walls and ceilings or laid in floors / trenches complete all as specified and directed by Engineer-in-charge.
M&L cutting existing GI/CI/DI water main pipe line in position of 50mm bore and making connection of new pipe line of 40mm bore with & including insertion of new GI Tee of size 80mm x 80mm x 50mm including excavation & earth work in any type of soil complete all as directed.
S&F gun metal globe or gate valve 25mm bore with iron wheel head, screwed both ends for iron pipes complete all as specified and directed by Engineer-in-charge.
S&F gun metal globe or gate valve 40mm bore with iron wheel head, screwed both ends for iron pipes complete all as specified and directed by Engineer-in-charge.
S&F 15 mm bore bib tap, cast copper alloy, chromium plated, long body, fancy type screwed down and screwed for iron pipe or for brass ferrule complete all as specified and directed by Engineer-in-charge.
S&F 15mm bore stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle screwed both ends for iron pipe or for unions complete all as specified and directed by Engineer-in-charge.
Taking down carefully or drawn out from conduit, existing copper / aluminium point wiring for light, fan, bell, socket, power point etc complete including fixture and fittings such as switches, sockets, ceiling rose, pendent holder, light fittings, top sheet covers, fan regulators, MCB, DB, lamp, earth plug etc (excluding MS sunken boxes) and making good the disturbed surfaces of wall/ceiling complete all as specified and as directed by Engineer-in-charge. Note : Taking down of serviceable fittings shall be measured and paid separately.
M&L for Modular point wiring complete with 1.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in and including concealed PVC rigid conduit medium grade 20mm dia, pipe hooks, elbows, junction covers and junction boxes including cutting chases in walls for conduits and for sunken pressed steel terminal boxes and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer for mounting modular switches, sockets, fan regulator including suitable size modular plates fixed flush with wall including 1.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for one light point, fan point, bell point controlled by one switch complete all as specified and directed by Engineer-in-Charge. Note : The quoted rate shall be deemed to included with modular cover plates with frame of any colour and metal flush boxes of suitable size as directed by Engr-in-Charge.
All as per serial item No. 23 here-in-before but for One 3 pin 5 Amp socket outlet one light point controlled by one switch on the same board with other switches.
All as per serial item No. 23 here-in-before but for One 3 pin 5 Amp socket outlet one light point controlled by one switch on independent board.
All as per Srl item No. 23 above, but wiring with cable of cross sectional area 2.5 Sqmm (nominal area) multi-stranded copper conductor FRLSH, PVC sheathed cable 1100 Volts shade for one switch socket combination 6 pin, 5/15 Amps on independent board including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth dolly.
S&F Modular switch piano 6 Amps single pole, one way, 01 Module complete all as specified and directed by Engineer-in-charge.
S&F Modular switch piano 16 Amps single pole, one way, 01 Module complete all as specified and directed by Engineer-in-charge.
S&F Modular socket 2 / 3 pin, 6 Amps, 230 volts, combined 2 Module complete all as specified and directed by Engineer-in-charge.
S&F Modular socket 6 pin, 6 / 16 Amps, 230 volts, combined 2 Module complete all as specified and directed by Engineer-in-charge.
S&F Lamp holder, insulated body with back plate etc complete all as specified and as directed by Engineer-in-Charge.
S&F ceiling rose surface bakelite 65mmx50mm with two or three terminal complete all as specified and directed by Engineer-in-charge.
S&F Modular electronic fan regulator suitable for ceiling fan 2 Module, 1200mm / 1400mm sweep, socket size, rotary type complete all as specified and directed by Engineer-in-charge.
S&F Energy efficient decorative ultra slim, prewired, lumiline 18 watt LED light fitting (Day cool light), batten type with drive & polycarbonate housing including tube rod and all accessories prewired fixed on wall / hanging complete all as specified and as directed by Engineer-in-charge. Make :- Havells Cat part No LUMILINEPLUSNEOBS18W LED865SSIND / Syska Cat part No SSK-RA1801 Wipro cat part No LL20-221-XXX-65-NE / Philips cat part No 61009 BL CDL or equivalent in makes mentioned in Appendix 'A' here-in-after.
S&F Energy efficient decorative ultra slim prewired 9 / 10watt (600mm length) LED light fitting (Mirror light) (Day cool light), surface and wall mounted LED batten, extruded aluminium housing with polycarbonate diffuser & integrated electronic driver and all accessories fixed on wall / hanging complete all as specified and as directed by Engineer-in-charge. Make :- Havells Cat part No LUMILINEBS9WLED865S PCWH / Syska cat part No SSK-T5T-9W / Crompton cat part No LCTLN-10-CDL or equivalent cat part No of makes mentioned in Appendix 'A' here-in-after.
Supply, fixing and testing LED Street / Security light fitting of 45 Watt, 5700K - 6500 K (including LED drive and internally prewired) complete with body robust, corrosion resistant, superior finish and without any cracks or through holes, made in a single piece by high pressure die cast aluminum alloy. The luminaries shall be monolithic construction totally enclosed dust and water proof with IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distortion THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second including 10 KV surge protection in built or external. Driver should be constant current constant voltage driver. Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection, no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degree Centigrade to 50 degree Centigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection. Cover should not degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including connection for street light from pole box with 1.5 Sqmm, 3 core PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked including addition / alteration in bracket (if required) for fixing light fitting complete all as specified and directed by Engineer-in- charge.
All as per Srl item No 36 above but including taking down old unserviceable street light
All as per Srl item No 36 above but LED street / security light of 25 watt including taking down old unserviceable street light Notes for srl Item No 36 to 38 :- (a) Tenderer shall submit test report of LED street light fitting from Government accredited test laboratory for LM - 79 and LM - 80 . (b) Contractor has to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. Contractor shall obtain warranty from the manufacturer of product on their letter head and submit the same to deparment alonwith his letter head. The product will be replaced free of cost in the following case :- (i) Manfacturing defects (ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (c) All LED light/luminare must meet the provision laid down in IS - 16101 , 16102 Part -I/II ,16103 Part -I , 16104 ,16105 ,16106 , 16108/2012 and 15885 Part -II / Section 13. (d) Scope of work shall include supply and fixing street light fittings on street light bracket fixed on poles, If street light fitting requires to fixed on existing street light bracket and any addition alterration required in bracket for fixing street light, In that case cost of additional / alteration is included in the unit rate of this item, which also includes needful T & P and required accessories such as 1.5 sqmm, 3 core PVC insulated stranded copper conductor cable for connection from pole box to light fitting etc complete including making connection, testing etc complete .No extra payment is admissible on this account. (e) Light fittings shall be provided with 10 KV surge protection as mentioned in description of item. If 10 KV surge protection is not provided in light fitting for which cat part is mentioned in BOQ. Contractor has to provide light fitting with 10 KV surge protection without any extra cost to department. (f) Contractor shall write CA No on street light fitting with synthetic enamel paint which should be visible from ground level. Cost of the same is included in the unit rate of this item nothing shall be extra paid on this account.
S&F as in repair flush mounting factory made SPN DB 8 way, 240 Volt, Single door, IP-43 protection, IK-09 with metal door with 100 Amps copper bus bar, with neutral bar, earth bar and cables ties for cable management fully insulated bus bar complete all as specified and directed by Engineer-in-charge.
S&F as in repair flush mounting factory made VTPN DB 4 way, 415 Volt, Double door, IP-43 protection, IK-09 with metal door with 160 Amps copper bus bar, with 02 neutral bar, 02 earth bar and cables ties for cable management fully insulated bus bar complete all as specified and directed by Engineer-in-charge.
S&F MCB 6 to 32 Amps, Single Pole 240 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
S&F as in repair MCB 40 Amps, Single Pole & neutral 240 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
S&F as in repair street light bracket made out of 40mm dia GI pipe light grade 1.5m long , bent to shape at 120 degree angle from vertical fixed along pole with and including required number of clamp made out of Flat iron 25mm x 6mm with nuts, bolts ,washers etc. duly painted with two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed by Engineer-in-charge.
S&F in replacement sheet metal plug & socket DB, SP, with a two pin and earth plug with socket, 230 Volts with & including one MCB SP ‘C’ Curve 10 kA, 20 Amps complete all as specified and directed by Engineer-in-charge.
S&F MCCB 4 Pole 100 Amps, thermal magnetic release having, breaking capacity 25 KA, 415 Volt in the existing feeder pillar box including any addition / alteration to the panel to accommodate the new MCCB & making connections with 25x3 mm copper strip as required from main bus bars, making necessary welding work, metal work for fixing base plate etc and connections complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement Sub main wiring complete with 2 single core 4 Sqmm (Nominal area) multi stranded copper conductor PVC insulated unsheathed cable FRLSH drawn in and including heavy duty PVC conduit ISI marked not less than 25mm dia concealed including single core multistranded copper conductor 4 Sqmm size cable as earth continuous wire drawn in same conduit complete all as specified and directed by Engineer-in- charge Note : Two runs of 4 Sqmm single core cable and one run of 4 sqmm copper wire earth continuty conductor and conduit with fittings shall be measured as one length.
S&F street light bracket made out of 40mm dia GI pipe light grade 1.20m long , bent to shape at 120 degree angle from vertical fixed along pole with and dirlling holes including required number of clamp made out of Flat iron 25mm x 6mm with nuts, bolts, washers etc. duly painted with two coats of aluminium paint including any addition / alteration (if required) for fixing street light complete all as specified and as directed by Engineer-in-charge.
S&F as in repair LED flood light of 200 watt with high pressure die cast housing with lens with lument output 6000K complete (including LED, drive and internally prewired) with on board 5 KV surge protection with 10 KV external SPD. The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP 65 protection as per IS 10322-1982 (part-I) with latest amanedments and input voltage range 140-300V AC, frequency 50-60 Hz, P.F should be more than 0.9. The efficiency of LED luminaries system shall be more than 100 lumens per watt and FRLSH cable PVC insulated stranded copper conductor, 1100 volts grade, 2.5 sqmm x 3 core of ISI marked for light to ceiling rose complete including arrangement of mounting for street light as required at site complete all as specified and directed by Engineer-in-charge.
S&F exhaust fan 300 mm sweep,900 RPM trans air, with louver shutter, double ball bearing copper wound , steel body suitable for operation on 230 volts, single phase , AC and connecting up including 2 core,1.0 sqmm PVC insulated & PVC sheathed copper conductor flexible cable drawn in flexible conduit complete all as specified & directed by Engr-in-charge.
S&F Desert cooler of size not less than 66 cm x 66cm x 94cm having single phase, electric driven, cooler body made out of GI sheet 1.22mm thick 18 gauge fitted with fan motor capacity 250 watt, 1400rpm including 2" thick wood wool pad, front grill (approximate weight 2.5 Kg) made of GI sheet, one submercible pump, speed retulator of suitable size, one piano switch 6 Amp, indicator and 1.50 metre long connection lead 3 core with 5 Amp plug top complete all as specified and as directed by Engineer-in-charge. Make of fan motor & submercible pump :- Crompton, Khaitan , Havells Note :- Cooler body shall be internally painted with one coat of black bituminous paint.
M&L for Construction of brick masonry valve pit of internal size 90cm x 90cm x 90cm including necessary excavation and earth work in soft/loose soil, brick work, plastering, white wash, PCC coping, MS frame made out of angle iron of size 40mmx40mmx6 mm, MS sheet cover of 3 mm thick fixed to angle iron frame by means of hinges welded to frame and painting with 2 coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces and grouting the frame in PCC 1:2:4 type B-1 including handle and locking arrangement with one number 50 mm dia brass pad lock complete all as specified and directed by Engineer - in - Charge Note :- (i) Brick wall shall be 23 cm thick built in cement mortar (1:4) (ii) Internal plaster shall be 15 mm thick in cement mortar (1:4) and external plaster upto 450mm from top shall be 20mm thick in CM (1:6) and remaining external surface shall be flush pointing in CM (1:6) as the work proceeds. (iii) PCC in foundation shall be 15 cm thick in cement concrete (1:4:8) type D2 using 40 mm graded stone aggregate extended 15 cm all around from the external face of the walls. (iv) PCC coping shall be 15 cm thick in cement concrete ( 1:2:4) type B1 using 20 mm graded stone aggregate including grouting of angle iron frame in PCC. (v) Three coats of white wash to internal surfaces of valve pit. (vi) Depth of valve pit shall be reckoned from the top of PCC in foundation.
All as per Srl item No 51 above but valve pit of internal size 110cm x 110cm x 110cm
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed layer of charcoal dust and common salt, connected to earth lead of GI wire 4 mm dia (8 SWG) by means of bolts, nuts and washers of the earth wire galvanised iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia and water pipe 20mm dia GI light grade top of pipe with funnel & wiremesh, and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009 including taking down old eathing complete all as specified and directed by Engr-in-charge. Notes :- (i) Cost of GI wire upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item. (iii) Cost of GI tubing upto 7.5m is included in the quoted rate of this item. (iv) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (v) Minimum weight of reinforcement for RCC cover shall be 1 KG.
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 25mm x 4mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required Nos of mild steel clamp made out 25mm x 3mm flat iron and perforated water pipe 20mm dia GI medium grade and top with socket & plug and bottom connected to earth plate by slit and two bolts / nuts / washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed by Engr-in-charge. Notes :-(i) Cost of GI strip upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item. (iii) Cost of GI tubing upto 7.5m is included in the quoted rate of this item. (iv) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (v) Minimum weight of reinforcement for RCC cover shall be 1 KG.
M&L for earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 3.50m length buried directly and preferably vertically in ground with top edge not less than 0.25m below ground level, pipe surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 25mm x 4mm thick as earth lead by electric welding and connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required Nos of mild steel clamp made out 25mm x 3mm flat iron, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete all as shown in electrical plate No. 2 of MES Schedule Part-I of SSR-2009 complete all as specified and directed by Engr-in-charge. Notes:- (i) GI strip upto earth test point/equipment is included in this item. (ii) Minimum weight of reinforcement for RCC cover shall be 1 KG. (iii) Pipe electrode shall be tapered at the bottom and provide with 12mm holes (staggered) at 75mm centre to centre up to 2 meter height.
S&F three phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights with three number two pole power contractors 40 Amps (Type - MU40-2P, Cs90119) with coil voltage 220 / 240 V and incoming MCBs single pole - 03 Nos, outgoing MCBs single pole - 03 Nos of rating 32 Amps & circuit wiring with single core multi stranded of size 10 Sqmm. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. The sensor along with suitable power contactor (S), Incoming -outgoing MCB's should be enclosed in a Rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure with hinged lid confirming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass option). The enclosure sould be mounted on 40mm x 40mm x 5mm angle iron structure and the structure height minimum 600mm and must be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer in charge. Make :- KAKATIYA ENERGY SYSTEM PVT LTD (Swadeep 02EC5KW3P) or equivalent cat part No in makes mentioned in Appendix 'A' here-in-after
Supplying, testing, cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel stripor wire armoured, electric powder cable (heavy duty) with stranded aluminium conductor, 11000 volts grade of cross sectional area 70 sqmm x 3 core laid in trenches / through pipe in road crossing / paths / drains / ducts / floors / along poles / wall / ceiling equipments etc and fixing with suitable clamps made out MS flat of size 25mm x 3mm and provision of CI cable route indicators of size 100mm dia, 6mm thickness duy embossed LT/HT attached with 45 cm long angle iron of size 25x25x5mm fixed along the route of cable at a distance of 40 meter and at turning points complete all as specified and directed by Engineer-in-charge. Notes :- (i) Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ (ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions.
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 16 sq mm 4 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge. Notes :- (i) Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ (ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions.
All as per item No 58 above but cable of cross sectional area 35 sq mm 3.5 core
All as per item No 58 above but cable of cross sectional area 50 sq mm 3.5 core
All as per item No 58 above but cable of cross sectional area 70 sq mm 3.5 core
All as per item No 58 above but cable of cross sectional area 95 sq mm 3.5 core
All as per item No 58 above but cable of cross sectional area 120 sq mm 3.5 core
Supplying, laying, jointing, commissioning and testing PVC insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 16 sq mm 2 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge. Notes :- (i) Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ (ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions.
All as per item No 64 above but cable of cross sectional area 25 sq mm 4 core
All as per item No 64 above but cable of cross sectional area 16 sq mm 4 core
All as per item No 64 above but cable of cross sectional area 10 sq mm 2 core
M&L for lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp stuitable for 11000 volts including bracket, clamps, nuts, washer and connecting to 4 mm GI earth wire complete all as specified and directed by Engineer-in-charge.
Supplying, testing, commissioning & testing of automatic intelligent power factor corrector (AIPFC) capacitor bank of capacity 70 KVAR with staging 2+2+2+3+3+3+5+5+10+10+10+15 LT 3 Phase 440 voltages 50 Hz AC supply system to improve power factor 0.80 to 0.98 automatic step wise switches capacitor panel platform mounted outdoor type, weather proof, dust vermin proof, made out of M.S. sheet 3.15mm thick and MS angle iron 40mm x 40mm x 6mm frame, factory fabricated as modulate in construction duly power coated light grey / cream color paint, front openable panel shutters with locking arrangement to facialite easy maintenance, exhaust fan cooled, having cable entry gland, provision of 750mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC (1:2:4) type B-1 using for mounting of panel in platform (as & where required) and necessary internal connections with 10 sqmm, 4sqmm & 1.5 sqmm insulated standered copper conductor complete comprising of the following:-
Contd/-… item No 87 (a) 200 Amps aluminium bus bar for phases and 100 Amps for neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set (b) MCCB 250 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 01 No (c) AIPFC micro processor based relay 12 stage - 01 No Make :- Epcos / Siemens / Neptune (d) Capacitor duty contactors 3 phase suitable for 2,2,2,3,3,3,5,5,10,10,10,15 KVAR = 12 Nos (e) MCB 32 Amps, Triple Pole 240 Volts, 10 KA, ‘C’ Curve - 12 Nos (f) indicator lamp LED type complete - 12 Nos (g) Voltmeter flush type 0-500 Volts square type 96mm x 96mm - 01 No (h) Ampere meter flush type 0-100 Amps square type 96mm x 96mm - 01 No (j) LT 415 Volts current transformer (CT) of ratio 160/5, 15VA - 04 Nos (k) 440 volts 3 phase power capacitor double dielectric heavy duty 2,2,2,3,3,3,5,5,10,10,10,15 KVAR = 01 No
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed by Engineer-in-Charge.
Supplying, jointing and testing heat shrinkable type, out door, end termination jointing kit, suitable for cable of size 25 to 50 Sqmm, 3.5 core aluminium conductor 1100 Volts including making connections complete all as specified and directed by Engineer-in-Charge.
Supplying, jointing and testing heat shrinkable type, out door, end termination jointing kit, suitable for cable of size 70 to 120 Sqmm, 3.5 core aluminium conductor 1100 Volts including making connections complete all as specified and directed by Engineer-in-Charge.
All as per item No 72 above but suitable for cable of size 150 sqmm to 185 sqmm.
M&L for dry sand (Tibba sand) and punning for cushioning to underground cable complete all as specified and directed by Engineer-in-charge Note: - For payment purpose thickness after punning shall be measured.
M & L for brick protection with old size sub class 'B' bricks laid flat, length of bricks across the route of underground cable all as specified and directed by Engineer-in-Charge.
M & L for brick protection with old size sub class 'B' bricks laid flat, length of bricks across the route of underground cable including taking out old bricks all as specified and directed by Engineer-in-Charge.
S&F Galvanized iron tubing, 40mm bore light grade, ISI marked, including all fittings and laid in trenches / under road / drains, fixed to poles / walls with required numbers of clamps made out of 25x3mm flat iron, bolts, nuts and washers for protection of LT electric cable complete all as specified and as directed by Engineer-in-charge. Notes :- (i) Excavation & earthwork shall be measured & paid for separately under respective items of BOQ (ii) Cost of flat iron clamp if required is included in the unit rate of this item. Nothing extra shall be paid on this account..
All as per item No 77 above but including taking out old tubing
All as per item No 77 above but 50mm dia bore
All as per item No 77 above but 80mm dia bore
All as per item No 77 above but 32mm dia bore
All as per item No 77 above but 15mm dia bore
Supplying, fixing and testing of 80mm bore cast iron sluice valve with langed ends drilled ISI marked class PN - 1.6 conforming to IS 14846-2000 with stainless steel spindle with iron wheel, CI gate with brass nut, bolts, washers and rubber packing for connecting pieces etc complete all as specified and as directed by Engineer-in-Charge.
All as per Srl item No 83 above but 100 mm dia bore.
Suppyling, installing, testing and commissioning of factory made outdoor type bus bar chamber having MCCB 125 Amps, 4 pole, 415 volts, 3 phase, 4 wire, 50 Hz, outer shell shall be made out of 3.15mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 160 Amps aluminium bus bar fixed horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 160 Amps MCCB including provision for taking out incoming and outgoing cable detacheable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer-in-Charge. Note :- (i) Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account. (ii) All cables to be connected with busbar will be properly thimbles.
Suppyling, installing, testing and commissioning of factory made outdoor type bus bar chamber having MCCB 100 Amps, 4 pole, 415 volts, 3 phase, 4 wire, 50 Hz, outer shell shall be made out of 3.15mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 160 Amps aluminium bus bar fixed horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 100 Amps MCCB including provision for taking out incoming and outgoing cable detacheable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer-in-Charge. Note :- (i) Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account. (ii) All cables to be connected with busbar will be properly thimbles.
Suppyling, installing, testing and commissioning of factory made outdoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 3.15mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :-
Contd/-… item No 87 Incoming (a) 400 Amps aluminium bus bar including Neutral and three phase - 01 Set (b) MCCB 250 Amps, 36 KA, 4 Pole, thermal Magnetic release type - 01 No Outgoing (a) MCCB 100 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 01 No (b) MCCB 63 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 03 Nos (c) Timer for security light - 01 No (d) Digital voltmeter - 01 No (e) Ampere meter - 01 No (f) CTs 200/5 Amps - 01 Set (Set of three) (g) Internal all links & control cable and indicators - set of three Note :- Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account.
All as per item No 87 above but comprising of following accessories :- Incoming (a) 160 Amps aluminium bus bar including Neutral and three phase - 01 Set (b) MCCB 100 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 01 No Outgoing (a) MCCB 63 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 02 Nos (b) MCCB 40 Amps, 16 KA, 4 Pole, thermal Magnetic release type - 01 Nos (c) MCB 40 Amps, double pole 240 Volts, 10 KA, ‘C’ Curve, - 04 No (d) Digital voltmeter - 01 No (e) Ampere meter - 01 No (f) CTs 160/5 Amps - 01 Set (Set of three) (g) Internal all links & control cable and indicators - set of three Note :- Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account.
All as per item No 87 above but comprising of following accessories :- Incoming (a) 160 Amps aluminium bus bar including Neutral and three phase - 01 Set (b) MCCB 100 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 01 No Outgoing (a) MCCB 63 Amps, 25 KA, 4 Pole, thermal Magnetic release type - 01 No (b) MCCB 40 Amps, 16 KA, 4 Pole, thermal Magnetic release type - 01 No (c) MCB 40 Amps, double pole 240 Volts, 10 KA, ‘C’ Curve, - 03 No (d) Digital voltmeter - 01 No (e) Ampere meter - 01 No (f) CTs 160/5 Amps - 01 Set (Set of three) (g) Internal all links & control cable and indicators - set of three Note :- Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account.
M&L for construction of brick masonary platform of size 2.0m x 2.0m x 1.20m including necessary excavtion and earth work in soft/loose soil, brick work, plastering, white wash, PCC work complete all as specified and directed by Engineer-in-charge. Note :- Below ground level (i) Sub base shall be 10cm thick and 70 cm width with concrete (1:4:8) type D-2 using 40mm graded store aggregate. (ii) Brick wall all around shall be 46 cm thick built in cement mortar (1:4) for a depth of 60cm. Above Ground level (i) Brick wall all around shall be 34.5 cm thick built in cement mortar (1:4) for a height of 100.50cm. (ii) 100mm thick PCC with concrete (1:3:6) type B-1 using 20mm graded store aggregate (iii) 150mm thick RCC slab on top with concrete (1:2:4) type B-1 using 20mm graded store aggregate, 12mm MS bar C/C 100mm. (iv) Plastering 15mm thick with cement mortar 1:4 with fair finishing without using extra cement. (v) Plinth protection 60cm all around the platform.
S&F cross arms, bracings, stiffeners, supports, clamps and back plates fabricated from structural steel confirming to Fe-290 (Gde E-165) including nuts, bolts, washers, welding, binding cold or hot, drilling holes for bolts, in any shape or size complete all as specified and directed by Engr-in-Charge. Note :Exposed steel surface shall be treated with two coats of synthetic enamel paint over a coat of red oxide primer and unexposed surface of steel sections shall be applied one coat of red oxide primer.
S&F cable junction box of size not less then 300x200x105mm, made of high quality thermo plastic polystyrene, weather proof, dust, jet water proof, chemical, acid corrosion, impact, insulated & shock proof IP 65 for outdoor Installation with internallly embedded gasket (PUR) including MCB SP 6 Amps 01 No along with left side hinge door (notch arrangement not acceptable) & premoulded knockout all sides including back of the base must. The box fitted with 10 sqmm stud type terminal - 04 Nos including Elimex stud type TB 4 Nos. Note :- (i) Cost of flat iron clamp is deemed to included in unit rate of this items. Nothing extra shall be paid on this account. (ii) Size of junction box for different mafufacturer may slightly varried from size mentioned in description of item. Contractor has to provide junction box as per cat No mentioned against make of junction box. where cat No is not mentioned against any make, in that case junction box of size mentioned in description has to provide, if exact size of junction box is not available, then next higher size junction box has to be provided. Nothing extra shall be paid on this account.
S&F weather proof PVC insulated, sheathed three core stranded aluminium conductor cable of size 1.5 Sqmm, 1100 Volts grade conforming to IS:9968 (Part-I) 1988 or IS:694-1990 complete all as specified and directed by Engineer-in-Charge.
Disconnecting both HT & LT connection from existing transformer of capacity upto 63 KVA, 11/433 KV and taking down the same and deposit to AGE E/M store yard at Suratgarh. Shifting of transformer of capacity upto 160 KVA transformer from AGE E/M store yard to site and installing the same on plinth / 4 pole structure including electric connection on both HT & LT sidewith thimble and PG clamps with cable / conductor / earthing and commissioning & testing the same directed by Engineer-in-Charge. Note :- (i) Transformer for fixing shall be issued under Schedule 'B' free for fixing only. (ii) Cost for transportaion to AGE E/M and carry back to site is inlcuded in the unit rate of item nothing extra shall be paid on this acount.
Dismantling existing unserviceable Aluminium conductors, steel reinforced (ACSR conductor) from overhead lines on LT poles, of any type and any size complete all as specified and as directed by Engineer-in-charge
Dismantling existing unserviceable insulators any type, any size on LT pole complete all as specified and as directed by Engineer-in-charge
Dismantling existing unserviceable stay assembly complete (demolition of concrete, etc. and excavation measured separately) complete all as specified and as directed by Engineer-in-charge
Dismantling existing unserviceable service bracket any type and any size on LT / HT poles complete all as specified and as directed by Engineer-in-charge.
Dismantling existing unserviceable continuous GI earth wire / guard / cradles of any size complete all as specified and as directed by Engineer-in-charge.
Dismantling existing unserviceable cross-arms of M.S. channel or angle sections etc. of any size and type complete all as specified and as directed by Engineer-in-charge.
S&F in replacement pre-stressed cement concrete pole, 9 metre long of cross section 102mm x 172mm at top and 102mm x 279mm at bottom, class 10, complying with requirements of IS-1678-1998 erecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and yellow colour up to 1.5 metre height from top of PCC pedestal/coping of poles including numbering of poles with synthetic enamel paint black in 80mm high letters over 150mm x 230mm yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. Note : PCC for foundation and earth work shall be measured and paid for separately.
M&L for preparation of old painted surfaces of PCC pole and applying two coats of synthetic enamel paint in black and yellow colour in alternate strips of 30 cm each upto 1.50 metre height from top of PCC coping and applying two coat of aluminum paint over cross arms, brackets, bracings, clamps, hooks etc. and marking pole number with white synthetic enamel paint in 80mm high letters, over black synthetic enamel paint base of size 20cm x 20cm including applying two coats of white wash to coping of poles all as specified and directed by Engineer-in-Charge. Note :- Pole number shall be marked with white enamel paint over a base of size 20cm x 20cm prepared with two coats of black enamel paint on pole surfaces.
Taking down street light fitting safely and refixing the same on new pole including connection with cable PVC isulated stranded copper conductor, 1100 volts grade, 2.5 sqmm 3 core size of ISI marked from security light to pole box complete all as specified and directed by Engineer-in-Charge. Notes :- Any T & P and Ladder wheel required for the work shall be arranged by the Contractor. The rate of this aspect is included in this item and nothing extra shall be paid on this account. ---------------------------------------------------------------------------- Note :- A sum of Rs. 70038/- will be deducted on account of credit for dismantled/ demolished / taken down material. Please refer details on Srl Page No. 28 & 29 (Schedule of Credit) of Tender documents.
BHADU BUILDERS (BID ID -3093361)
bharat contrectors (BID ID -3099949)
SRI SAI CONSTRUCTION COMPANY (BID ID -3076422)
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .