Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.2 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹5.2 L+₹2,782 (0.54%)Rejected-AOC VILL PO BALGONA PURBA BARDHAMAN | BALGONA | PURBA BARDHAMAN | WEST BENGAL | L2 | Rejected-AOC Being L1 | |
| 3 | L3₹5.3 L+₹7,336 (1.41%)Rejected-Finance | L3 | Rejected-Finance Being L3 |
Tender Value
Refer Docs
EMD Value
₹12,400
Closing Date
2 Jul 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Bardhaman Electrical Division,
Purta Bhavan, 1st Floor, Purba Bardhaman
Electrical Installation work for Setting up of new Manifold room named as (Manifold Room-3) for Paediatric Building of BMCH, Purba Bardhaman
2025_WBPWD_867516_1
WBPWD/EEBED/NIQ-06/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
10 days
Purba Bardhaman
Please refer Tender documents.
4 documents required · 4 mandatory
₹12,400
19 Aug 2025
20 Jun 2025
4 Jul 2025
20 Jun 2025
2 Jul 2025
20 Jun 2025
Amount
S&F 415 Volt Industrial type Panel on angle iron frame on wall with nuts bolts/grouting,Metering arrangment and Internal connection bus-bar to out-going switch with Cu bar arrangment, Phase indicator box ( RYB LED type) as per G.S. Incoming :- a) S/F of 415 Volts 250 Amp TPN SFU Breaking capacity 50KA fuse switch with enclosure on angle iron frame as per G.S.(Make –L&T/Siemens/ABB)---1 no. Bus bar chamber :-a) Supply & Fixing sheet metal(16 SWG) Iron clad Busbar chamber with 415 Volt, 315 Amp capacity [4x(40x5mm)] 4 bar electrolytic tinned copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for four(04) nos.out-going TPN SFU Connections on angle Iron Frame on wall.---1 set Out Going: a) S/F of 415 Volts 200 Amp TPN,SFU with HRC Fuse. (Make – L & T/Siemens/ABB).---1 no b) S/F of 415 Volts 100 Amp TPN, SFU with HRC Fuse. (Make – L & T/Siemens/ABB).---1 no c) S/F of 415 Volts 63 Amp TPN,SFU with HRC Fuse. (Make – L & T/Siemens/ABB).---1 no Metering :- a) S&F 3 ph Communicable Multifunction Metering (KWH,KW,KVA,Volt,I,F,PF) Device (Make-Schneider-Conzerv/L&T)--1 set. b) 300/5A ratio 10VA, Current Transformer (Mk-AE/Kappa) --3 Nos. c) LED Type Indicating Lamp(RYB) for Incoming and Out-going indication.---03 Nos. (Mk-L&T) d) E.I danger board .---1 no
Supplying and fixing 415V, 200 A,TPN SFU with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. S&F 3 nos. DIN type HRC fuse as per rating. (Make-L&T/Havells/Siemens).(D3/4a)
Supplying and fixing 415V, 315/320 A,TPN SFU with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. S&F 3 nos. DIN type HRC fuse as per rating. (Make-L&T/Havells/Siemens).(D3/4a)
Supplying and fixing 8 Way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand/Schneider/ABB ITUS)(D10/14)
Supplying and fixing 2+16 way double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand/Schneider/ABB ITUS)(D9/13)
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. (Make- Legrand/Schneider/ABB ITUS) (D-5/ 6) i) 63 A FP Isolator.
ii) 40 A DP Isolator.
Supplying and fixing 240/415 V SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand/Schneider/ABB ITUS)(D6/7) i) 6-32 A
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works (E4/11) i) 150 mm x 100 mm x 65 mm
Supply & Fixing bakelite / perspex top cover on existing Inspection board by Brass screws(E5/13) i) 150 mm x 100 mm x 65 mm
Cutting channel of 40 mm x 40 mm size on masonry wall incl.S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works.(E2/3a) a) 19 mm dia 3 mm thick polythene pipe without earth continuity wire
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make: Havells/Polycab/KEI/ RR Kabel) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.(E9/1) i) 3x22/0.3(1.5 sqmm).
ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
iii) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.(F5/9) i) 2.5 sq mm
ii) 4 sq mm
iii) 6 sq mm
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make: Havells/Polycab/KEI/ RR Kabel) partly in 20mm size PVC rigid conduit 'FR' (Precision MMS make) [for ceiling portion only] and in19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm)single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch (Anchor) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed.] (Average run 6 mtr.)(E16/6)
Supply & delivery TMC 501 P 1xT-LED 22W P3242, 250 volt. 4 ft. long Single Tube Light fittings complete with all accessories. Bottom cover of the fittings must be screwed at both ends. (Make: Philips/Crompton/Wipro/Bajaj)
Supply & delivery TMC 501 P 2xT-LED 22W P3242, 250 volt. 4 ft. long Single Tube Light fittings complete with all accessories. Bottom cover of the fittings must be screwed at both ends. (Make: Philips/Crompton/Wipro/Bajaj)
S&D LED type tube lamp 18/20 Watt Polycarbonate Body with inbuilt driver and Metal Heat Sink having length 1200mm, T8, Iumen Output - Min. 2100 Lumen. Bottom cover of the fittings should be screwed at both ends. (Make: Philips / Crompton /Orient / Bajaj/ Wipro). [03(Three) years on-site Warranty Certificate is to be provided from the Manufacturer].
Supply & Delivery of 48" (1200 mm) ceiling Fan as per IS 374:1979 complete with all accessories including S3 type capacitor as per IEC 60252-1 with upto date amendents,and with safety wires for secondary suspension of fans complete with blades,canopy,fork,rubber bush etc. (Make:Usha Striker PWD/ Orient / Crompton Greaves). [02(Two) years on-site Warranty Certificate is to be provided from the Manufacturer].
Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling with HW block and ceiling plates, nipples etc. as required(C2/14C)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.(C2/17)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.(E6/18.b))
Supply & Fixing Socket type fan regulator (Step type) (Anchor) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc(E18/10)
S&D 23 cm (9") 1420 rpm sweep A.C single phase heavy duty exhaust fan complete set ready to use. (Make : E.P.C/Orient/USHA)
Fixing only exhaust fan (9") after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. Length of PVC insulated wire and making connection for exhaust.(C4/28
Supply & Fixing louver shutter(GI) on wall for 23 cm Exhaust fan (9")with necy. bolts & nuts (6 mmdia x 62 mm long).[D14/32b]
Supply & Fixing 240 V, 3 nos. 20A plug socket with separate 3 nos. 20A Piano key type switch, indicator & 16A kit-kat flush type fuse (Anchor) on sheet metal switch board embedded in wall incl. S & F 300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.(E7/29)
Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. (E6/21)
Supply & Delivery 1.1KV grade LT Aluminium PVC Armoured cable ( Make- Havells/polycab/RR Kabel) as per choice of EIC. The cable shall conform to IS 7098/ Part I with anti termite and anti rodent features. i) 4 core X 150 sq. mm.
ii) 4 core X 120 sq. mm.
iii) 4 core X 35 sq. mm.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables.(F4/7c) i) 4 core X 150 sq. mm.
ii) 4 core X 120 sq. mm.
iii) 4 core X 35 sq. mm.
Finishing of the XLPE/PVC insulated armoured cable ends by crimping method with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc.(F5/8b) i) 4 core X 150 sq. mm.
ii) 4 core X 120 sq. mm.
iii) 4 core X 35 sq. mm.
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting.(F1/2e)
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting.(F1/2c)
Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core.(F1/3b)
Supplying & fixing medium gauge 65 mm dia GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required.(F5/11e)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI-Medium GI pipe.(G1/2)
Excavation of soil for installation of Earth Electrode and filling & ramming for Soft Soil.(G1/1a)
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.(G2/3a)
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.(G2/4b)
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. (G3/c)
Dismantling the existing electrical installation (TPN,SPNDB, L.T Panel, Switch Board, Wiring, Fan, Light Fitings, Old DG Set etc). as per requirement Civil/PWD dismantaling work, by co's own tools,takles & manpower maintaining normaly as far as possible and depositing the dismantalled damaged materials to the section office of PWD and mending good the damages upto the satisfaction of Authority/PWD as per direction of EIC. [4 nos. Semi-Skill Labour & 4 nos. Un-Skilled Labour for 5 days]
Rates to be quoted will be inclusive of all the taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
D.D ELECTRICALS (BID ID -6658917)
S.S. ELECTRICAL ENTERPRISE (BID ID -6658883)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .