| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.8 LAccepted-AOC WARD NO 40 REGRON KA MOHALLA NEAR RAVI DASS JI MANDIR SHIV BARI BIKANER RAJSTHAN 334001 | BIKANER | RAJASTHAN | 334001 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹30.4 L+₹7.4 L (32.3%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L2 | Rejected-Finance Higher Rate Quoted | |
| 3 | L3₹30.6 L+₹7.6 L (33.1%)Rejected-Finance BEHIND POWER HOUSE WARD NO 6 UDASAR BIKANER RAJASTHAN 334022 | BIKANER | RAJASTHAN | 334022 | L3 | Rejected-Finance Higher Rate Quoted | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in b (iii) cat |
Tender Value
₹29.4 L
EMD Value
₹29.4 L
Closing Date
18 Jul 2023, 6:00 pmClosed
Col Shery Goel, CWE Bikaner
HQ CWE Bikaner, Bikaner Mil Stn
Repair/Maintenance of external electrification of HT installation at Zone B at Mil Stn Kanasar
2023_MES_604568_1
CA No CWE BKN-Token No. 10/2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
AGE (I) Kanasar
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
AGE (I) Kanasar
₹29.4 L
Yes
24 Aug 2023
20 Jun 2023
25 Jul 2023
20 Jun 2023
18 Jul 2023
4 Jul 2023
20 Jun 2023 - 30 Jun 2023
Amount
Notes applicable to Schedule ‘A’ :- (i) The items considered in this Schedule ‘A’ are for fault repair and maintenance of HT infrastructure at Kanasar Military Station. The rates quoted shall deemed to be included this aspect. (ii) The fault in HT electric supply system and requisite maintenance shall be intimated any time round the clock to the contractor through complaint slip and/or telephonically by the representative of AGE and same must be rectified by the contractor within 08 hours of intimation. If contractor fails to rectify the fault within 08 hours, a penalty at the rate of Rs. 200/- per hour shall be imposed on the contractor after 08 hours till the fault is rectified. A complaint Log Book in this regard shall be maintained by the contractor duly signed by the Engineer-in-Charge.
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.
M&L for Cutting/dismantling of PCC hardstanding/ WBM road with soling & premix carpet of any description for laying of cable and disposal of material to a distance not exc 250m and making good the same with & including black top of surface dressing renewal coat by spraying evenly paving bitumen at 12 Kg per 10 sqm chipping @ 0.10 cum per 10 sqm and rolling to required gradient and camber complete all as specified & as directed.
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of under ground electric cable complete all as specified and as directed. Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
Supplying and laying factory made, un-reinforced precast concrete cable cover, ISI marked, Class HV, Type 1, flat, size 300mm x 180mm x 40mm, laid as cable protection cover in trenches, complete all as specified & as directed.
Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 70 Sqmm, 3 Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc, including dismantling & taking out old unserviceable HT cable, complete all as specified & as directed. Notes :- (i) Sand cushioning, cable protection, GI protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
All as per serial item No 8.00 here-in-before but of size 95 Sqmm 3 Core complete all as specified & as directed.
All as per serial item No 8.00 here-in-before but of size 150 Sqmm 3 Core complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, including dismantling & taking out old unserviceable jointing kit, complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, including dismantling & taking out old unserviceable jointing kit, complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed.
M&L for ascertaining / pin pointing the fault in faulty 11 KV HT underground cables by using HT cable fault locator machine, removing the fault and testing HT underground cable complete all as specified & as directed. Note :- Excavation & earth work and cable jointing kit shall be measured & paid for separately.
M&L for taking down old unserviceable end portion of HT cables, cutting/dressing end portion of cable and making good end termination for HT cable size 95mm sqmm, 3 core with and including suitable size of aluminium lugs duly crimped with crimping tool and refixing its own same position, including Jumpers, insulation tape etc as required for the complete all as specified & as directed.
M&L for taking down old unserviceable end portion of HT cables, cutting/dressing end portion of cable and making good end termination for HT cable size 150mm sqmm, 3 core with and including suitable size of aluminium lugs duly crimped with crimping tool and refixing its own same position, including Jumpers, insulation tape etc as required for the complete all as specified & as directed.
M&L for cleaning, rubbing by amren paper and other foreign materials external surface of feeder pillar box/LT panels and preparing the old painted surface for new paint, spraying by gun one coat of synthetic enamel paint of existing colour code of panel on external surface, including minor repairing of panels like locking arrangement, door hinges with welding, nuts bolts etc complete all as specified and directed
M&L for cleaning, removing dust, pigeon poo and other foreign materials on external surface of VCB with required chemical and rubbing by micro amren paper and making surface rust free and aesthetic look complete all as specified and directed.
M&L for Boring of holes upto 110mm bore under road, pavement, hard standing, etc by trench less technology using necessary machine / manually without disturbing the top surface suitable for passing the GI protection pipe / cables, complete all as specified and as directed.
M&L for Galvanized iron tubing, 80mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of HT electric cable including taking down old unserviceable protection pipe with clamps complete all as specified & as directed. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for Galvanized iron tubing, 100mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of HT electric cable including taking down old unserviceable protection pipe with clamps complete all as specified & as directed. Note :- Excavation & earthwork shall be measured & paid for separately.
S&F Switch air break, gang operated outdoor, Horizontal operated type, HT 11 KV, Triple pole, 200 Amps, 3 insulator per phase, rotating vertical type, with fixed contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for vertical mounting, fixed in repairs, complete all as specified and as directed.
S&F Switch air break, gang operated outdoor, Horizontal operated type, HT 33 KV, Triple pole, 400 Amps, 3 insulator per phase, tilting/rocking horizontal type, with fixed contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, fixed in repairs, complete all as specified and as directed.
S&F Drop out expulsion fuse assembly with fuse carrier, triple pole, HT 11000 Volts, 25 Amps, outdoor type (having two Nos post insulator mounted on MS channel for each pole) and jumpers with conductors line taps, clamps, colour coated HT sleeves and fitting, fixed in repairs, complete all as specified and as directed.
Repair to existing switch air break, gang operated outdoor, vertical / horizontal mechanically operated type, HT 11 KV, Triple pole by cleaning of moving/static contacts with tetrachloride solution, scrapping and making smooth to existing spot points of the contacts by emery paper, providing grease on moving contacts, mechanical torque joint, tightening of canopy with drop out fuse assembly set (three contacts in each GOD switch) to make the GOD switch fully & smoothly functional, complete all as specified and as directed.
S&F Lightning arresters HT 33 KV 65 kilo Amp Non linear expulsion type transmission class with standard fittings confirming to IS-3070 (Part-I) 1985, fixed in repairs, complete all as specified & as directed.
S&F Lightning arresters HT 11 KV 65 kilo Amp Non linear expulsion type transmission class with standard fittings confirming to IS-3070 (Part-I) 1985, fixed in repairs, complete all as specified & as directed.
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized iron earth wire 4 mm dia as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted to earth plate at one end and other end of earth wire connected to transformer / GOD / Panel / equipment body / test point, GI earth wire encased in and including 15mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
Surface dressing not exceeding 15cm deep in soft/loose soil if required and clearing away all grass vegetation, saplings, shrubs, brushwood, undergrowth, roots, and trees not exceeding 30 cm girth (measured one metre above ground level) surrounding Transformers, 02 Pole structures, 04 Pole Structures, 33/11 KV structure etc at various sub stations / E&M installations and removing rubbish upto a distance not exceeding 50m outside the periphery of the area under clearance complete all as specified & as directed.
M&L for preventive maintenance / repairing by opening and taking out the Vacuum Circuit Breaker (VCB) 11/33 KV 630 Amp, type VMX from panel and carry out the general maintenance such as oiling & greasing the mechanical parts, motor, gear, lever spring, operating rod, cleaning the female contacts, tightening of nuts and bolts, cleaning the male and female contact of panel, oiling the bus bar shutter, checking the AC/DC wiring, circuit including control fuses and circuit jack, on/off push button, indicating lamp, voltmeter, ammeter, PF meter, replacement of minor parts (where required) and testing after re-inserting the VCB in panel complete all as specified & as directed. The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' as "Supply Only"
Supply only Electro mechanical Master trip relay Hand reset type Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5A CT input and auxuliary DC supply of 30/110/220 Volt complete all as specified and directed.
Supply only Over current and earth fault relay Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5A CT input and auxuliary DC supply of 30/110/220V with breaking capacity 2 KVA complete all as specified and directed.
Supply only Trip Circuit supervision Relay as existing Make :Alstom Model: VAX 31 complete all as specified and directed.
Supply only Anti Pumping Relay should not be plug in type & should have suffcient number of contact complete all as specified and directed.
Supply only alarm Annunciator enclosed in ABS enclosures with high strength for11 KV VCB panel Consists of 2 relays Trip relay (C-NC-NO),Alarm Relay (C-NC-NO), 04 window Annunciator with dual power supply (AC or DC) complete all as specified and directed.
Supply only Electronic hooter having similar specification & bezel size 96x96mm as per existing Make : Stelmec having model No. SLA74 complete all as specified and directed.
Supply only Tripping coil having copper material through actuating device rated for Substation DC voltage 12/ 24 /110 V ,burden value < 200 watt , Min operating Voltage of 70% for tripping and 85% for closing operation as per existing installed on site complete all as specified and directed.
Supply only Closing coil having copper material through actuating device rated for Substation DC voltage 12/ 24 /110 V ,burden value < 200 watt,, Min operating Voltage of 70% for tripping and 85% for closing operation as per existing installed on site complete all as specified and directed.
Supply only Resin cast/Dry type Potential transformer having 3 phase,Ratio 11000/√3V / 110√3V,vector group Star/Star with neutral earthed, burden/class: 100VA/0.5, Fixed type with HRC fuse protection, with IS: 3156-1992 complete all as specified and directed.
Supply only Resin cast, Dual ratio, Indoor type Current Transformer for breakers having ratio 100-50/5-5A, Burden value 15VA both for protection & metering core, Short-time circuting rating 25kA for 3 sec , Protection Core 5P10 complete all as specified and directed.
Supply only HT vaccum interrupted assembly bottle with flex connection suitable for VMX type VCB 630 Amps capacity for RYB phases complete all as specified and as directed.
Supply only Spring charging motor operated on Power 150-250 Watts ,220 V AC/DC supply having insulation Class B type complete all as specified and directed.
Supply only VCB trolly rack out Gear complete all as specified and directed.
Supply only Handcart chasis truck VCB trolly for withdrawable vaccum circuit breaker of 650 mm to 800 mm width size complete all as specified and directed.
Supply only Closing spring complete all as specified and directed.
Supply only Opening Spring complete all as specified and directed.
Supply only Trip clatch assembly complete all as specified and directed.
Supply only Holding clatch assembly complete all as specified and directed.
Supply only Spring charging Handle for Hand operating complete all as specified and directed.
Supply only PT/VT fuse 11/12 KV,breaking capacity 45 kA, rating 3.15 Amp complete all as specified and directed.
Supply only Power pack fuse 1 to 5 Amp complete all as specified and directed.
Supply only HRC fuse link type NSD type rating 02 Amps to 10 Amps, Rated voltage 550 Volt, breaking capacity 80 KA as per IS 13703 latest complete all as specified and directed.
Supply only HRC fuse link type NSD type rating 16 Amps to 32 Amps, Rated voltage 550 Volt, breaking capacity 80 KA as per IS 13703 latest complete all as specified and directed.
Supply only Fuse fitting (front+back+busbar) for LV BS(NSD) type of Fuse FA 20 Amps, Rated voltage 500 V as per IS 13703 latest complete all as specified and directed.
Supply only Space Heaters Thermostat having temp range 25-85°C complete all as specified and directed.
Supply only Auxillary switch for suitable for 11 KV breaker complete all as specified and directed.
Supply only Breaker control Switch Three position : Trip, close and neutral control switch with one trip and one close 32 Amp for operation of VCB complete all as specified and directed.
Supply only Standard push button, flush round head 22 mm dia and required number of N/O & N/C self returning contacts without locking arrangements for Emergency Trip functions bracket assembly complete all as specified and directed.
Supply only Emergency stop push button switches, Flush round Head 22 mm dia and required number of N/O & N/C self returning contacts without locking arrangements for Emergency Trip functions bracket assembly complete all as specified and directed.
Supply only Claster LED type Indicating lamps with built resistor holder and coloured lens with rating 30/110/220 Volt DC complete all as specified and directed.
Supply only Digital VAF + Power factor meter 3 phase,three element 4 wire, inbuilt CT 5 Amp , voltage 110/230/440 Volt having 4 Digit LED with auxiliary supply 230 Volt AC, Class 0.5 complete all as specified and directed.
Supply only Digital AC voltmeter 96x96mm AC Range 0-15 KV, Accuracy 1.0 PTR 11KV/110 Volt, Auxillary supply 230 Volt AC, 3 line display complete all as specified and directed.
M&L for replacing unserviceable parts of 33 KV transformer control panel and testing all parts after replacing and changing faulty wiring complete all as specified and directed. The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' as "Supply Only".
Supply only Electromechanical Master trip relay Hand reset type Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5 Amp CT input and auxiliary DC supply of 110/220 Volt complete all as specified and directed.
Supply only Over current and earth fault relay with 50/51 and earth fault protection 50N/51N), 1A & 5A CT input and auxiliary AC/DC supply 18 to 265 Volt complete as per existing Make: Avana, Model: NPA 422 complete all as specified and directed.
Supply only Under voltage relay Suitable for flush mounting, in temp 0 to 55°C, RH 50% to 100%, 1A & 5A CT input and auxuliary DC supply of 30/110/220 Volt complete all as specified and directed.
Supply only Auxiliary Relay for Two transformer control panel having supply of 30/110/220 V AC/DC supply as per existing Make Avana & Model EMR 261 complete all as specified and directed.
Supply only Trip Circuit supervision Relay should not be plug in type & should have suffcient number of contact complete all as specified and directed.
Supply only Alarm Annunciator enclosed in ABS enclosures with high strength for two transformer control panel inbuilt all functions i.e. push buttons for trip & non trip functions, 2 nos DC operated hooter, 01 no AC bell At Bus coupler and have provision of built in watch dog and fast fault indication with trip and Non trip Alarm functions, 24 window Annunciator with dual power supply(AC or DC) with overall Size: 216(W) x144(H) x121( D) mm. As existing Make:- Proton Power Control Pvt. Ltd Model No. 3X8N complete all as specified and directed.
Supply only Automatic Semaphore Indicators having 36 mm round buzzel for earth switch with high operating torque and positive action, Coils rated for 24-30 Volt DC, burden value(less than 15mA) 5, dust proof, For Low burden value 110 Volt DC with 6K Ohms 6W external resistor, For High burden value at 110 Volt DC-3K 6W resistor complete all as specified and directed.
Supply only Automatic Semaphore Indicators having 48 mm round buzzel for isolator with high operating torque and positive action, Coils rated for 24-30 Volt DC, burden value (less than 15mA) 5, dust proof, For Low burden value 110 Volt DC with 6K Ohms 6W external resistor, For High burden value at 110 Volt DC-3K 6W resistor complete all as specified and directed.
Supply only Automatic Semaphore Indicators having 63mm round buzzel for breaker with high operating torque and positive action,Coils rated for 24-30 Volt DC, burden value (less than 15mA) 5, dust proof, For Low burden value 110 Volt DC with 6K Ohms 6W external resistor, For High burden value at 110 V DC-3K 6W resistor complete all as specified and directed.
M&L for testing and adjusting the following relay including checking and rectifying the tripping circuit complete, Calibration of relay for 33 KV VCB panel including 33 KV VCB-02 Nos complete all as specified and directed. (a) Trip circuit supervision Relay(Auxiliary relay) - 02 Nos (b) Master Trip Relay, 110V DC - 02 Nos (c) Over current & earth fault relay - 02 Nos (d) Auxiliary relay for transformer - 04 Nos (e) Undervoltage relay - 02 Nos (f) Intelligent Panel Meter - 02 Nos (g) Annunciator -01 Nos (h) Ammeter & Voltmeter Note:- (i) The tripping system of relays are to be calibrated with MRS,kanasar (ii) The tripping timing of the relay to be adjusted less than 33KV system at MRS Kanasar (iii) The testing instrument whatever required to test the relays will be arranged by the contractor at his own cost. (iv) The test shall be provided from authorized agency.
M&L for testing and adjusting the following relay including checking and rectifying the tripping circuit complete Calibration of relay for 11 KV VCB at various place at Kanasar Mil Stn complete all as specified and directed. (a)Trip circuit supervision Relay (b) Master Trip Relay, 24 DC (c) Over current & earth fault relay (d) Intelligent Panel Meter (e) Ammeter & Voltmeter Note:- (i) The tripping system of relays are to be calibrated with MRS, Kanasar (ii) The testing instrument whatever required to test the relays will be arranged by the contractor at his own cost. (iii) The test shall be provided from authorized agency.
Supply and fixing in replacement of battery backed power pack having input 110 or 230V AC, output 24/110/220 Volt DC and continous load 100 VA as per IEC 60947-1 & IEC 61000-4/5 complete all as specified and directed.
Supply and fixing in replacement of Current transformer 33 KV oil filled having CT Ratio 400-400/5-5 Amp, burden value 15 VA, Accuracy class 0.5 and insulation level 36/70/170 kVP and rated for 25 KA for 1 sec complete all as specified and directed.
M&L for Earthing complete with CPRI tested 50mm dia copper cladded (250 micron) earth electrode 3000mm in length with NABL tested RoHS complaint earth enhancement compound 30 Kg in each bore hole with copper strip of 25x3mm inter connected by means of exothermic brazing & protected by GI pipe light grade 32mm bore upto the test point i.e 7.50mtr in length and top of earth pit cover with high density polymer Earth pit chamber of dimension (300mm x 300mm x 214mm) with locking seal as to achieve the desired connecting to test point & testing on ground complete including excavation, earth work, boring in any type of soil strata & cleaning of site including taking down old unserviceable GI strip 32x6mm earthing complete all as specified and directed. Make: JMV earthing/Daksh Power Solutions/Ashlok Note: (i) Copper strip of size 25x3mm required to connected to the electrode upto test point is deemed to be included in quoted rate by the tenderer. (ii) The boring will take place for 3mtr depth & 150mm dia. Earth enhancement compound to be filled around the earth electrode in 100mm dia in 3 layers of 1mtr each by means of PVC pipe of 100mm dia as casing/form work. The ramaning valume of bore shall be filled with clay soil (available from vicinity) in 3 layers of 1mtr each. The PVC pipe to be removed simultaneously. The cost of all this is deemed to be included in the quoted rates. (iii) Cost of excavation, earth work, boring, including testing & commissioning etc is deemed to be included in the quoted rates by the tenderers. (iv) Minimum distance between each earthing is not less than 3 RM (v) Testing of earthing shall be conducted and result should be less than 1.00 Ohm.
M/s Rohit Construction Co.
BIDAWAT ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .