Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.3 LAccepted-AOC HOUSE NO C 214 SECTOR C INDRA VIHAR COLONY TILAK NAGAR HOUSING SOCIETY AIRPORT ROAD LANDMARK NEAR BHOPAL GIRLS SCHOOL PANCHVATI BHOPAL MP 462030 | BHOPAL | BHOPAL | MADHYA PRADESH | 462030 | L1 | Accepted-AOC Lowest amount quoted | |
| 2 | L2₹45.0 L+₹2.6 L (6.25%)Rejected-Finance PLOT NO 81 SHANTAJI COLONY JANKI NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L2 | Rejected-Finance Second lowest amount quoted | |
| 3 | L3₹47.0 L+₹4.7 L (11.0%)Rejected-Finance 1257 SCHEME NO 5 NEAR HB COLLEGE VIJAY NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L3 | Rejected-Finance Highest amount quoted |
Tender Value
₹48.3 L
EMD Value
₹96,700
Closing Date
1 Feb 2024, 6:00 pmClosed
Lt Col P Aditya Deepak, GE
Garrison Engineer (East), Near COD Estate, Ranjhi, Jabalpur (MP)-482011
PROVN OF LT UG CABLE FROM L AND T POWER HOUSE TO CONTROL OFFICE AMN SUB DEPOT OF COD AND PROVN OF BOREWELL WITH 5 HP THREE PHASE MOTOR AND PLUMBING OF 1000M OF 506 ABW UNDER AGE EM OF GE (EAST) JABALPUR
2023_MES_622828_3
8581/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Garrison Engineer (East) Jabalpur
D b (i)
8 documents required · 8 mandatory
₹500
Garrison Engineer (East) Jabalpur
₹96,700
Yes
29 Apr 2024
11 Jan 2024
3 Feb 2024
11 Jan 2024
1 Feb 2024
19 Jan 2024
11 Jan 2024 - 13 Jan 2024
Amount
M&L for excavation in trenches for laying of cables, poles and stay in any type of soil n.exc1.5 mtr wide and n.exc 1.50 mtr deep and getting out in soft/loose soil complete all as specified and dirtected.
M&L for returning & filling in, including spreading and leveling, watering and well ramming in layers n.exc 25 cm complete all as specified and dirtected.
M&L for removing excavated materials (soil) n.exc 50 m and depositing where directed at a level n.exc 1.5m above the srarting point complete all as specified and dirtected.
M&L for unwashed sand cushioning to under ground cable provided with a layer of 8 cm deep before laying and 15 cm covering above the top edge of cable after laying including gently punning complete all as specified and dirtected. Note : Measurement shall be done after puning down of sand.
Supplying and laying unreinforced precast cement concrete cable covers, Class LV, Type - 1 Flat, size 250mm x 150mm x 40 mm in trenches for cable protection, embossed with "LT 1100 Volts Electric" on the top surface complete all as specified and as directed.
Demolition of cement concrete unreinforced in ground floors and pavings n.exc 15 cm thickness (below or above ground level) complete all as specified and directed.
M&L for PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate as in coping of pole ect including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified and dirtected.
M&L for PCC 1:2:4 type B-2 using 40mm graded crushed stone aggregate as in filling in surface channels and drains etc complete all as specified and dirtected.
M&L for crossing hole under road/hard stranding for passing cable through GI pipe including GI pipe light grade 40 mm dia with all fittings complete all as specified and dirtected.
M&L for crossing hole under road/hard stranding for passing cable through GI pipe including GI pipe light grade 50 mm dia with all fittings complete all as specified and dirtected.
M&L for crossing hole under road/hard stranding for passing cable through GI pipe including GI pipe light grade 80 mm dia with all fittings complete all as specified and dirtected.
S&F XLPE insulated armoured and PVC sheated heavy duty electric cable with aluminium conductor 1100 Volt grade laid in tranches passing through pipes /ducts including testing complete of following cross sectional area and size. Note- Rate shall be inclusive of cable gland & cable lugs.
25 Sqmm x 4 Core
35 Sqmm x 3.0 Core
35 Sqmm x 3.5 Core
50 Sqmm x 3.5 Core
70 Sqmm x 3.5 Core
240 Sqmm x 3.5 Core
S&F cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 4 Core XLPE armoured Al conductor cable of size 240 to 300 sqmm indoor/outdoor type complete all as specified and as directed.
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 630 Amps, 4 Pole, 50 KA with front operated locking device. - 01 Nos Make : Legrand catpart No -422075 , Havells, L&T
(b) OUTGOING
(i) Thermal magnetic MCCB 250 Amps, 4 Pole, 415V, 36 KA. Qty - 02 Nos. Make : Legrand cat part No. 420249, Havells, L&T.
(ii) Thermal magnetic MCCB 200 Amps, 4 Pole, 415V, 36 KA. Qty - 02 Nos. Make : Legrand cat part No. 420248, Havells, L&T.
(iii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415V, 25 KA. Qty - 01 Nos. Make : Legrand cat part No. 420053, Havells, L&T.
(iv) Thermal magnetic MCCB 25 Amps, 4 Pole, 415V, 16 KA. Qty - 01 Nos. Make : Legrand cat part No. 420011, Havells, L&T.
(v) MCB 32 Amps, 2 Pole. Qty - 01 Nos. Make : Legrand cat part No. 408617, Havells, L&T.
(c) Digital time switch including 3 phase power contactor 40 Amps. Make : Legrand cat part No. 412641 & 3 phase contactor 40 A, Code No - 412549, Havells, L&T. Qty - 01 Nos
(iii) Indicator Lamp - R - Y - B (Set of three).
(iv) Frequency meter 40-55 Hz - 01 Nos
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 200 Amps, 4 Pole, 36 KA with front operated locking device. - 01 Nos. Make : Legrand cat part No. 420248, Havells, L&T.
(b) OUTGOING
(i) Thermal magnetic MCCB 125 Amps, 4 Pole, 415V, 16 KA. Qty - 02 Nos. Make : Legrand cat part No. 42001656, Havells, L&T.
(i) Thermal magnetic MCCB 63 Amps, 4 Pole, 415V, 16 KA. Qty - 01 Nos. Make : Legrand cat part No. 420013, Havells, L&T.
(ii) MCB 32 Amps, 2 Pole. Qty - 01 Nos. Make : Legrand cat part No. 408617, Havells, L&T.
(c) Digital time switch including 3 phase power contactor 40 Amps. Make : Legrand Cat No. 412641 & 3 phase contactor 40 A, Code No. 412549, Havells, L&T.
(iii) Indicator Lamp - R - Y - B (Set of three).
(iv) Frequency meter 40-55 Hz - 01 Nos
M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level connecting to and including GI steel strip of size 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 40 mm dia medium grade pipe for protection of GI strip to the extent of 7.5 mtrs asearthing lead including charcoal dust and salt packed all around the earth plate in the earth pit all as per Electrical plate No 3 of SSR Part-I (2009) including PCC foundation/chamber in mix 1:2:4 type B-1 with angle iron frame CI frame, CI cover with provision of locking arrangement and 20 mm dia light grade GI pipe from top edge of the earth plate upto MS funnel with wire mesh provided inside the concrete earth pit for watering arrangement complete including excavation and earthwork in any type of strata and testing complete including fill up the earth pit with soil for best result and removal ( for LT Panels). Note :- Earth protection pipe & earthing strip upto and including 7.5 m length is deemed included in unit rate quoted by the contractor.
M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level connecting to and including GI earth wire of size 4.0 mm by means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 15 mm dia medium grade pipe for protection of GI wire to the extent of 7.5 mtrs asearthing lead including charcoal dust and salt packed all around the earth plate in the earth pit all as per Electrical plate No 3 of SSR Part-I (2009) including PCC foundation/chamber in mix 1:2:4 type B-1 with angle iron frame CI frame, CI cover with provision of locking arrangement and 20 mm dia light grade GI pipe from top edge of the earth plate upto MS funnel with wire mesh provided inside the concrete earth pit for watering arrangement complete including excavation and earthwork in any type of strata and testing complete including fill up the earth pit with soil for best result and removal ( for street light poles). Note :- Earth protection pipe & earthing wire upto and including 7.5 m length is deemed included in unit rate quoted by the contractor.
Supply and laying 50mm dia pipe galvanized, “medium grade”, including fittings complete all as specified and directed.
S&F Valves, Sluice, flanged of class 1.6 PN, 50 mm dia complete all as specified and directed.
S&F gun metal Glove Valve conforming to IS-9338, 50 mm dia complete all as specified and as directed.
Supply, installation, commissioning and testing CPRI approved factory fabricated, floor mounted outdoor type LT feeder pillar box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame and 750 mm above the normal ground level complete factory made totally enclosed dust and vermin proof double door both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from botton with cable glands and gaskets, aluminium bus bar 250 Amps rating (01 Set) fixed on procelain insulator with internal wiring with suitable size of aluminium strips to be used for incoming and outgoing connection of all switches/MCCB's and Bus bar. Bus bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surface ecternally and internally over a coat of red oxide primer paint including necessary PCC 1:3:6 type C-2 as in foundation complete all as specified and directed comprising of the following :-
(a) INCOMING
(i) MCCB 3 Pole, 415 V,fixed type, 42 Amps with breaking capacity 16 KA - 01 Nos.
(b) OUTGOING
(i) MCB 32 Amps, TPN/FP. Qty - 01 Nos.
(ii) Thermal mangetic MCCB 32 Amps, TPN/FP pole, 415 V, 25 KA, Qty - 01 Nos.
(iii) Indicator Lamp - R - Y - B (set of three) - 01 Nos
(iv) Frequency meter 40-55 Hz - 01 Nos.
M&L for 25 mm dia flexible PVC Heavy Duty Garden pipe/ Garden Water Pipe/PVC Pipe/Garden Outdoors Pipes/Hose Connector Long Flexible Pipe for Watering Home Garden complete all as specified ad dirtected.
M&L for Spraying nozzle 25mm for gardening complete all as specified and as directed
M&L for Cleaning and removing of all silt, dirt, mud, stone, etc. from inside the borewell and Flushing out / desilting of the bore well by using compresser hydro pressure jet for six hours till clear the silt in the casing pipe by achiving clear water, and washing with hydro pressure jet using foam/oils, disinfecting the bore using sodium hypochloride solution and washing out till water is obtained to the required turbidity (clean water) to the entire satisfacton of Engr-In-Charge complete all as directed,including Lowering and re-fixing of submersible pump set of capacity upto 15 HP at different places including pump set fitting commissioning and testing after replacement of defective parts with new one alongwith coloumn pipe 50/80 mm bore with cable by suitable arrangment of chain pully system and connection with startor electrically and connection with pipe line mechanically complete all as specified and ditected.
Supply, fixing testing and commissioning of submersible pumps 415 volts, three Phase system of size 5 HP( KS6B-0508) , LPM 120 to 170 LPM Head 90 to 130 Mtr capacity 50 Hz, 8 to 12 stage with delivery size upto 80mm suitabelfor 6 " to 8" bore complete all as specified and as directed.
M&L fully Automatic Star Delta Motor starter 5 HP in sheet-steel enclosure type MK-1 .feature (Motor Rating AC-3 Duty, 415V, 50Hz, three -Phase) and Relay Range 11-18 complete all as specified and directed. Make : L&T/SKN/SIEMENS
Schedule of credit amount of Rs. 0.00 to be deducted during AOC
shri krishna traders
Sachdeva Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .