GE Minniebay
GE Minniebay Junglighat Post Minniebay Port Blair 744103
REPAIR AND MAINTENANCE OF LOW VOLTAGE ELECTRIC FIXTURES AND OTHER CONNECTED WORKS AT MD ACCN UNDER AGE EM-I AT GE MINNIE BAY PORT BLAIR
2023_MES_623546_1
8309/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Minniebay Port Blair
As per tender documents
10 documents required · 10 mandatory
₹500
GE Minniebay
₹89,000
Yes
17 Jan 2024
16 Oct 2023
15 Nov 2023
17 Oct 2023
13 Nov 2023
31 Oct 2023
Amount
Servicing / cleaning the LT panel boards of any size/type upto 2.5 cum, clearing vegetation up to 1.5m around the panel, spraying glyphosate herbicide of suitable concentration, inspecting all cable terminations, lugs, insulation, busbars,LT switchgears, meters etc, cleaning the busbars/panel with CRC solution for removing carbon contents, replacing pitted lugs with proper crimping pressure,insulating the peeled off insulation with superior quality high grade rubber insulation tape with proper colour code, replacing pitted/damaged busbar insulators all as per existing, marking radium stickering for all outgoing/incoming feeders with location, radium stickering of danger notice board on panel as per standards, replacing pitted control wiring of metering, replacing defective CTs/ meters /glands /indicator lamps, replacement of rusted doors with hinges/locking arrangements, tightening the cable end terminals with bus bar / connector links / MCCB / MCB end terminals with proper torque for avoiding loose connections, checking for any abnormal heating in the cables / MCCBs including applying a coat of red oxide primer after preparation of rusted surfaces only and applying two coats of synthetic enamel/aluminium paint of approved colour by Enginner in Charge on entire surfaces outer side and inner side after preparation of surfaces , including making good broken PCC pedestals/ foundation, applying two coats of white/colour wash complete all as specified and as directed by Engineer in Charge.
Servicing / cleaning the LT panel boards of any size/type greater than 2.5 cum, clearing vegetation up to 1.5m around the panel, spraying glyphosate herbicide of suitable concentration, inspecting all cable terminations, lugs, insulation, busbars,LT switchgears, meters etc, cleaning the busbars/panel with CRC solution for removing carbon contents, replacing pitted lugs / reducer terminals / in line connectors with proper crimping pressure,insulating the peeled off insulation with superior quality high grade rubber insulation tape with proper colour code, replacing pitted/damaged busbar insulators all as per existing, marking radium stickering for all outgoing/incoming feeders with location, radium stickering of danger notice board on panel as per standards, replacing pitted control wiring of metering, replacing defective CTs/ meters/glands/indicator lamps, replacement of rusted doors with hinges/locking arrangements, tightening the cable end terminals with bus bar / connector links / MCCB / MCB end terminals with proper torque for avoiding loose connections, checking for any abnormal heating in the cables / MCCBs including applying a coat of red oxide primer after preparation of rusted surfaces only and applying two coats of Synthetic enamel paint/ aluminium paint of approved colour by Enginner in Charge on entire surfaces outer side and inner side after preparation of surfaces , including making good broken PCC pedestals/ foundation, applying white/colour wash complete all as specified and as directed by Engineer in Charge.
Note for Items 1 & 2:- (i) Cable lugs, reduced terminals (bottle lugs), in line connectors, glands, fabrication of doors, hinges/locks/tower bolts, meters, CTs, indicator lamps, insulators and insulation tape shall be measured and paid seperately as per site requirement under relevant items as 'Supply only". (ii) The quoted rate deemed to be inclusive of cost for removing loop of all cables for defect rectifications of end terminations,painting, radium stickering, making good of broken PCC and any other related materials required for operational of panel. iii) Each panel board will be measured as one job only. (iv) Each servicing attended shall be measured as one job through job card and after completion the same shoud be signed by Engineer in Charge. (v) The contractor shall depute necessary man power on top priority as per the direction of Engineer-in-Charge for rectifying the task detailed eventhough in sundays and holidays till attaining the condition of panel/equipment operational.
Supply only for carrying out repairs under item No.1 & 2 above with fabrication for LT Feeder Piller Box/ Panel Boards doors made out of 2.00 mm thick mild steel sheet by applying two coats of synthetic enamel paint over a coat of red oxide primer with minimum two hinges for fixning purpose complete all as specified and directed by Engineer in Charge.
Supply only for carrying out repairs under item No.1 & 2 above with fabrication for LT Feeder Piller Box/ Panel Boards doors made out of 3.15 mm thick mild steel sheet by applying two coats of synthetic enamel paint over a coat of red oxide primer with minimum two hinges for fixning purpose complete all as specified and directed by Engineer in Charge.
Supply only for carrying out repairs under item No.1 & 2 above with aluminium tower bolts, 200mm long bright bolt including connected accessories for fixing on front/rear side of the doors for locking LT FP Boxes complete all as specified and as directed by Engineer-in-Charge.
Supply only for carrying out repairs under item No.1 & 2 above with door hinges of LT feeder pillar/Panel box complete with welding complete all as specified and as directed by Engineer-in-Charge.
Supply only for carrying out repairs under item No.1 & 2 above with aluminium cable lugs for fixing of armoured LT UG cables in panels for the following capacities complete all as specified and as directed by Engineer-in-Charge:-
Supply only for carrying out repairs under item No.1 & 2 above with aluminium reduced terminals (bottle lugs) for fixing of armoured LT cables in panels complete all as specified and as directed by Engineer-in-Charge:-
Supply only for carrying out repairs under item No.1 & 2 above with aluminium in line connectors/ ferrules for maximum current rating for fixing of armoured LT cables in panels complete all as specified and as directed by Engineer-in-Charge:- Note: Each phase / pole connector will be measured as one unit.
Supply only for carrying out repairs under item No.1 & 2 above with Cable gland of LT UG cables in panels complete all as specified and as directed by Engineer-in-Charge:-
Supply only for carrying out repairs under item No.1 & 2 above with CTs of rating 50-800 Amps with suitable turns ratio complete all as specified and as directed by Engineer-in-Charge.
Supply only for carrying out repairs under item No.1 & 2 above with LED Indicating lamp (R-Y-B) complete all as specified and as directed by Engineer-in-Charge.
Supply only for carrying out repairs under item No.1 & 2 above with LT superior quality high grade rubber insulation tape 25cm width 2.5m long complete all as specified and as directed by Engineer-in-Charge.
Supply only for carrying out repairs under item No.1 & 2 above with insulators for supporting Bus bars of voltage grade 550 Volts complete all as specified and as directed by Engineer-in-Charge.
Supply and fix as in repair of MCCB 630 Amps,TPN/ 4 pole, 415 volt, breaking capacity 36 KA, Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix in repair of MCCB 400 Amps,TPN/ 4 pole, 415 volt, breaking capacity 36 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix in repair of MCCB 250Amps,TPN/ 4 pole, 415 volt, breaking capacity 36 KAThermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix in repair of MCCB 200Amps,TPN/ 4 pole, 415 volt, breaking capacity 25 KA Thermal magnetic type complete all as specified and as directed by Engineer in Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix in repair of MCCB 160 Amps, TPN/4 pole, 415 volt, breaking capacity 25 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix as in repair of MCCB 100 Amps, TPN/4 pole, 415 volt, breaking capacity 16 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Supply and fix as in repair of MCCB 63 Amps, TPN/4 pole, 415 volt, breaking capacity 16 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge. Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
Dismantling of any grade Concrete of any description and in any position not otherwise specifically provided complete all as specified and as directed by Engineer-in-Charge.
Material and labour Plain Cement Concrete (1:3:6) nominal mix type C-1 (using 20 mm graded broken stone aggregate) as in coping/collar of poles including necessary form work complete all as specified and as directed by Engineer-in-Charge.
Material and labour Plain Cement Concrete (1:2:4) type B-2 (using 40 mm graded broken stone aggregate) as foundation of poles including necessary form work complete all as specified and as directed by Engineer-in-Charge.
Material and labour Plain Cement Concrete (1:4:8) type D-2 (using 40 mm graded broken stone aggregate) as foundation of poles including necessary form work complete all as specified
S & F as in repair onload change over switch 4 pole 63 Amps in sheet metal enclosure complete all as specified and as directed by Engineer-in-Charge.
S & F as in repair on load change over switch 4 pole 250 Amps in sheet metal enclosure complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of LT feeder pillar box in replacement factory made outdoor type, double door, slopy canopy, fabricated out of 3.15 mm thick CRCA sheet with suitable angle iron base frame made of 6 mm thickness, 45 cm height from ground elvel after erection,dust and vermine proof, suitable for voltage 415 V, 3 Phase 4 wire weather proof, with IP-54 protection, with back door openable (screwed), legs grouted in PCC, including painting with two coats of epoxy power paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing,descaling in dilute sulphuric acid or any other acid and phosphate and with 600 Amps aluminium busbar (TPN) with PVC insulation mounted on porcelain insulators, suitable double compression copper cable glands and suitable size cable lugs complete in all respect including PCC work and dismantling old LT panel complete and provn of the following :- Note : (i) The panel shal be CPRI type tested. (ii) The GA drawing approval shall be obtained from GE before placing order INCOMING (a) 4 Pole, 400 Amps ON Load hange over switch,Motorized type suitable for operation on, 415 volts, 50 Hz - 01 No (b) LED indicating lamp R-Y-B - 06 Nos (c) Digital Ammeter with CT's (0-600A)- 01 No (set of Three) (d) Digital Volt meter 0-500 volt - 01 No
Suppy,laying testing and commissioning of electric LT cables, XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables with stranded aluminium conductors 1100 Volts grade in trenches, fixed on walls, passing through pipes, jointing and testing including taking down complete all as specified and as directed by Engineer-in-Charge for the following size :- Note: (i) The rates shall be inclusive of Cable lugs at both ends of cable and end termination kits will be measured and paid seperately. (ii) Excavation earth, return and re filling shall be measured and paid seperately. (iii) Joint kit if required shall be measured and paid seperately. (iv) Insulation Resistance value of cable shall be recorded before and after laying of cable.
4 Core 6 Sqmm
4 Core 10 Sqmm
4 Core 16 Sqmm
3.5 Core 25 Sqmm
3.5 Core 50 Sqmm
3.5 Core 70 Sqmm
3.5 Core 95 Sqmm
3.5 Core 120 Sqmm
3.5 Core 150 Sqmm
3.5 Core 240 Sqmm
Taking down and relaying of serviciable power cable of XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with saddling / on pole / through DWC pipe including all necessary fixing arrangement such as lugs and end termination etc of size 10 Sqmm to 35 Sq mm 3.5/4 Core complete all as specified and as directed by Engineer-in-Charge.
Taking down and relaying of serviciable power cable of XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with shaddling / on pole including all necessary fixing arrangement such as lugs and end termination etc of size 50 Sqmm 3.5 core to 95 Sq mm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Taking down and relaying of serviciable power cable of XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with shaddling / on pole including all necessary fixing arrangement such as lugs and end termination etc of size 120 Sqmm 3.5 core to 240 Sq mm 3.5 core complete all as specified and as directed by Engineer-in-Charge. Note For Item Nos. 33.00, 34.00 & 35.00 (i) Excavation earth work, returning and refilling shall be measured and paid seperately under relevant items. (ii) M & L for DWC pipe /cable defective shall be measured and paid seperately under relevant item. (iii) Quoted rate inclusive of laying only serviceable portion of DWC pipe.
Supply & Laying as in repair of DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and profiled external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
Supply & Laying as in repair of DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 63 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and profiled external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
Supply & Laying of DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 77 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and profiled external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
Supply and laying in repair GI pipe of light grade ISI marked 40 mm dia all fitting fixture for fixing with wall / road crossing etc. complete all as specified and as directed by Engineer-in-Charge.
Supply and laying in repair GI pipe of light grade ISI marked 50 mm dia all fitting fixture for fixing with wall / road crossing etc. complete all as specified and as directed by Engineer-in-Charge.
Supply and laying in repair GI pipe of light grade ISI marked 63 mm dia all fitting fixture for fixing with wall / road crossing etc.complete all as specified and as directed by Engineer-in-Charge. Note for Item Nos 39.00 TO 41.00: (i) Road cutting / excavation work shall be measured and paid separately.
Excavation in trenches any soft/loose soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, pipe, laying of cable etc not exc 10 Sqmtr on plan and not exc 1.5 mtr in depth and getting out complete all as specified and as directed by Engineer-in-Charge
Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil all as specified and as directed by Engineer-in -charge.
Removing excavated materials (soil) to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point all as specified and as directed by Engineer-in -charge.
M & L for Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C2 matching with the surroundings all as specified and as directed by Engineer-in -charge.
S & F for cable jointing kit for 1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F for cable jointing kit for 1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F for cable jointing kit for 1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 70 to 120 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F for cable jointing kit for 1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 150 to 185 Sqmm 3.5 Core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F for cable jointing kit for 1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 240 to 300 Sqmm 3.5 Core as in repairs complete all as specified and as directed by Engineer-in -charge.
Material and labour for repair and making the continuity of supply after rectifying the defects of the electrical network from LT side of transformer to Distribution boards such as (i) cable faults : disconnecting the both ends of cable and check the insulation resistance value. If the value is low check for any cable damage by physical inspection / tracing the cable by excavation and if not found, fault can be located by fault finding machine and the same can be rectified by fixing suitable size joint kit and make the cable serviceable, the same can be ascertained by insulation resiatnce value and make the cable connection at both ends to restore the power supply. (ii) unserviceable control switch gears / MCCBs / MCB: remove the MCCB/MCB from the panel board and clean the carbonized / burnt surfaces with varnish / CRC solution to make good and fix the new MCCB of suitable rating and connect the cable to MCCB terminals with proper lugging and by applying proper torque to avoid loose connections. spreader links shall be provided if necessary as per site requirement. (iii) neutral failure, phase failure: check for any cable terminal damage / melting by over heating, loose contacts. the damaged portion of cable shall be removed and fixing the lugs and terminate the cable by applying proper torque to avoid loose connections and over loading of cable shall be done by redistributing the load down side after approval from Enginner in charge complete all as specifed and as directed. Note :- (i) cable joint kit, MCCB/MCB, lugs and cable fault detection by fault finding machine, any excavation earth work shall be measured and paid seperately under relevant items. spreader links shall be deemed to be included in the rate quoted. (iii) Each complaint attended shall be measured as one job through job card and after completion the same shoud be signed by Engineer in Charge. (iv) The contractor shall depute necessary man power on top priority for rectifying the task detailed,eventhough on sundays and holidays for attaining the condition of LT panel operational.
Material and labour for cable fault finding of LT UG Cable by fault locator machine including excavation, returning refilling after rectification of fault with fixing of Straight through joint kit, extra UG Cable and DWC (Double Wall corrugated) HDPE pipe as per site requirement complete all as specified and as directed by Engineer-in -charge. Note:- LT UG Cable, Straight through joint kit, excavation work and DWC (Double Wall corrugated) HDPE pipe measured and paid separately under relevant items.
S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 70 to 120 Sqmm 3.5 core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 150 to 185 Sqmm 3.5 Core as in repairs complete all as specified and as directed by Engineer-in -charge.
S & F in repair for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 240 to 300 Sqmm 3.5 Core as in repairs complete all as specified and as directed by Engineer-in -charge.
Taking down and rerouting / Discipline the serviciable Power Cable on wall /cable duct of size 16 to 50 Sqmm 3.5/4 core with saddling, aluminium patti with requard size of screw inside cable duct / on wall complete all as specified and as directed by Engineer in Charge.
Taking down and rerouting / Discipline the serviciable Power Cable on wall /cable duct of size 70 to 185 Sqmm 3.5 core with saddling, aluminium patti with requard size of screw inside cable duct / on wall complete all as specified and as directed by Engineer in Charge.
Supply & fixing in repair IP 65 / 66 thermoplastic-polycarbonate cable junction box of size 205X255X112 with terminal which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on pole / surface / frame with the help of GI calmp of required size / self drill screw, with 32 Amp four way connector and one no of MCB SP 6 Amp complete all as specified and as directed by Engineer-in -charge
Supply & fixing in repair IP 65 / 66 thermoplastic-polycarbonate cable junction box of size 155X210X92 with terminal suitable for 10 to 16 Sqmm ,which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on pole / surface / frame with the help of required size / self drill screw and four way 32 Amp Connector and 01 No of MCB SP 6 Amp complete all as specified and as directed by Engineer-in -charge
Supply & fixing in repair IP 65 / 66 thermoplastic-polycarbonate cable junction box of size 130X180X77 with terminal suitable for 4 to 10 Sqmm which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on pole / surface / frame with the help of required size / self drill screw, four way connector and 01 No MCB SP 6 Amp Connector complete all as specified and as directed by Engineer-in -charge.
Material and labour earthing with copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to20×3mm copper strip as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe,Copper earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing and dismantling old defective earthpit.
Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 25 mm x 3 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead, 20 mm dia GI pipe for watering and earth plate surrounded by packed layer of coal and common salt, 15cm thick all around bottom and top, watering pipe of 20 mm bore of light grade with funnel all as shown in electrical plate No 3 of SSR Part-I (2009) and connecting to earthing test point, main switch board, transformer neutral and testing on completion as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar, wire mesh and testing complete all as specified and as directed by Engineer-in -charge. Note: (i) Cost of GI earth Strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation.returninng & filling. PCC chamber pit,RCC cover & test point. (iii) If the desired earth resistance is not achived during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissable.
Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 32 mm x 6 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead, 20 mm dia GI pipe for watering and earth plate surrounded by packed layer of coal and common salt, 15cm thick all around bottom and top, watering pipe of 20 mm bore of light grade with funnel all as shown in electrical plate No 3 of SSR Part-I (2009) and connecting to earthing test point, main switch board, transformer neutral and testing on completion as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar, wire mesh and testing complete all as specified and as directed by Engineer-in -charge. Note: (i) Cost of GI earth Strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation.returninng & filling. PCC chamber pit,RCC cover & test point. (iii) If the desired earth resistance is not achived during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissible.
Material and labour as in repair for Earth pit indicator for existing earthing pit made out of 16 mm dia and 60 cm long MS Squre Bar embeded in PCC (1:3:6) type C-1 using 20 mm graded stone agreegate in PCC block of size 30 X30 X30 cm including CI/MS plate of size 25X30X 3 mm thick fixed on side of earth pit cover complete painting and writing over the plate ie. Type , Result, Date of measurement and pit number with Black letters on white and complete all as specified and as directed by Engineer-in -charge.
M & L as in repair for Earth pit cover of conventional earthing and S&F PCC earthing pit in PCC (1:3:6) type C-1 of outer size 300X300 X200 MM and inner Size 200X200X200 MM and pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar including necessary earth work complete all as specified and as directed by Engineer-in -charge.
Dismantling old RCC / rusted poles including PCC and Supply & erect minimum 7 mtr height above GL / foundatin made out of Hot dip Galvanised signle section octogonal pole with foundation base plate of size 250 x 250 x 16 mm, foundation bolts 04 Nos of size M 24 x 700/750 mm, with single type arm bracket 1500 mm long,the pole shaft shall be patered with single longitudinal welding and door opening for cable with 01 No MCB SP 6 Amp and 32 Amp connector and 03 run of 1.5 sqmm PVC wire for connecting street light fitting from MCB complete all as specified and as directed by Engineer-in-charge. Note: (i) Earth work, PCC foundation, coping, junction box shall be measured and paid seperately under relevant items. (ii) GI bracket, 3 runs of PVC wire are deemed to be included in the quoted rate.
Supply and laying in repair 1.5 Sq.mm (nominal area) PVC unsheathed multi strandard copper conductor PVC insulated 1100 volt FRLSH grade three core cable drawn through UPVC Pipe not less than 20 mm dia for connecting the street light fittings including minimum 03 No alluminium clamps for support of UPVC pipe complete all as specified and as directed by Engineer-in -charge.
Supply and fix in repair GI bracket for street lights made out of light grade ISI marked GI pipe 40mm dia, not less than 1.2 mtr long bend to shape as directed, fixed on poles with two Nos GI clamp of size 40 x 6mm flat iron suitable for steel tubular pole / RCC pole including suitable GI nuts and bolts washers complete all as specified and as directed by Engineer-in -charge.
Taking down old unserviceable street light fittings roadway lumanarie type from any height and Supply & fixing LED street light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame, (with total lumen output not less than 8400 lumens and suitable wattage for efficiency not less than 120 lumens/Watt, having secondary optics, min wattage 70 watt, with ingress protection IP 65/66 and potted electronic driver of minimum IP 67 with THD less then 10%, CRI > 80, P.F> 0.9, IK> 08, SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Make:Crompton /Phillips/C&S /Havells/ Wipro/ Henolix/Luker . Note : The GI pipe bracket if required will be measured and paid separately under relevant schedule items all as specified and as directed by Engineer-in-charge.
M&L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity 800 to 1250 Amps ,415 V 50 HZ of L&T Make/C&S/GE/ABB make, strip opening the Air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- a) Cleaning the insulation parts including bushings with CRC solution.b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual c) Check the bolts, nuts,d) Check arc chutes for damage . washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts.e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual . f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation.j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functionalNote : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like Shunt release & trip coil etc will be measured & paid separately under relevant items.
Supply only for carrying out repairs under item No. 72.00 above with CT suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above withauxiliary contact block suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above with arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above with arc chutes (for 415 V) suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above with shunt release / under voltage release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above with cluster contact suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 72.00 above with trip coil suitable for air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed by Engineer in Charge.
Servicing of electronic control panel along with all connected items connected through wires / comminication cables which includes preventive maintenance schedule of panel and connected items, cleaning of electronic panel and all connected items, checking the functionality of all modules, checking for any malfunction of the system and rectifying the same, replacing any damaged wire / comminication cable upto 30 mtr length, checking for receiving the notofications properly and if not rectifying the same and changing the mapping location with the item as per site requirement complete all as specified and as directed by Engineer in Charge. Note: (i) The quoted rate is inclusive of minor parts and all major parts like control module, monitor module, power supply board, loop card, mother board and display board shall be measured and paid seperately under "Supply only" item only. (ii) The servicing shall be done by authorised representative of OEM only and certificate in this aspect shall be submitted along with RAR/FB.
Supply only for carrying out repairs under item No. 80.00 above with control module suitable for the existing electronic control panel complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 80.00 above with monitor module suitable for the existing electronic control panel complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 80.00 above with power supply control board suitable for the existing electronic control panel complete all as specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 80.00 above with display board suitable for existing electronic control panel complete all a s specified and as directed by Engineer in Charge.
Supply only for carrying out repairs under item No. 80.00 above withmother board suitable for existing electronic control panel complete all a s specified and as directed by Engineer in Charge.
Supply and fixing as in repair service wire aluminium conductor Weather Proof 06 Sqmm two core complete all as specified and as directed by Engineer-in -charge.
Supply and fixing as in repair service wire aluminium conductor Weather Proof 10 Sqmm two core complete all as specified and as directed by Engineer-in -charge.
Supply and laying broken stone or Boulders filling of Gauge not exc. 63 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed by Engineer-in -charge.
Material and labour in repair cross arms, bracing, supports, clamps and back plate fabricated from structural MS section for gate including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts in any shape or size as indicated or directed complete all as specified and as directed by Engineer-in -charge.
Suply & fix as in repair of Danger notice plate of PVC sheet, vitreous enamelled with letters, figures (English, Hindhi,Tamil) and conventional skull and bones in signal red colour and fixed with self threaded screws / bolts and nuts of approved size / GI wire, for LT of voltage 440 Volts, 25x20cm size complete all as specified and as directed by Engineer-in -charge.
Supply and fixing as in repair for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 20 mm x 3 mm thick, copper strip using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in -charge.
Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 32 mm x 6mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in -charge.
Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 25 mm x 3 mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in -charge.
Supply and fix as in repair MCB 40 to 100 amps TPN/4 pole, 415 volt, breaking capacity 16 KA complete all as specified and as directed by Engineer-in-Charge.
Surface dressing not exceeding 15 cm deep including removing the debris to a distance not-exc 60m from site including clearing of vegetation/scrubs complete all as specified and directed by Engineer-in -charge.
Supply, installation, testing and commissioning LT panel board consist of cubicle indoor type suitable for 3 phase 415 Volts of suitable size bus bar of rating 2500 Amps Indoor type made out of 2.00 mm thick CRCA sheet, similar CPRI type tested type panel, Degree of protection minimum-IP 43 with angle iron frame of size 50X50X 6mm cubical type floor mounted factory made including of complete including PCC foundation as per site requirment complete all as specified and as directed by Engineer-in-Charge and to accomodated to the following:- INCOMING ACB (1000-1250) A FP MDO 50 K (Fixing arrangement only) MFM with RS485 - 02 Nos CT 1250/5A, CL-1 set of thee - 02 Nos Phase indicator lamp R/Y/B Set of three - 06 Nos ON/OFF/TRIP LED Indicating lamp - 06 Nos T/N/C Switch - 02 Nos Digital smart Three phase energy meter for remote monitoring compatible OUTGOING:- Out put Through Bus Bar Digital Voltmeter - 01 No Digital Ammeter - 01 No CT 1250/5A, CL-1 set of thee - 01 No Phase indicator lamp R/Y/B Set of three - 01 No complete all as specified and directed by Engineer in Charge Note: Supply and fixing of ACBs shall be measured and paid seperately.
Supply and fixing in repair of ACB, 1000 amps, 50 KA, 4 pole, MDO with microprocessor based relay complete all as specified and as directed by Engineer in Charge
Supply and fixing in repair of ACB, 1250 amps, 50 KA, 4 pole, MDO with microprocessor based relay complete all as specified and as directed by Engineer in Charge.
Material and labour for servicing,comprehensive maintenance and testing of vLED surgical OT lights at OT-1 and Minor OT of INHS Dhanvantari Note : (i)Minimum two service visits and other emergency breakdown visits shall be performed on the system at equally spaced interval during the contract period. (ii) Servicing,comprehensive maintenance and testing of both surgical OT lights at OT-1 and Minor OT shall be treated as one job. (iii) The comprehensive maintenance (Platinum Agreement) shall be done through respective OEM of existing lifts i.e of M/s Steris Pvt Ltd. (iv) The contractor will have to submit MOU on stamp paper of Rs 100/- duly notarized, as per specified perform given on Particular Specification from respective OEM of existingsystem i.e of M/sSteris Pvt Ltd. within Twenty Eight days from date of receipt of acceptance of tender, failing which the contract will be liable to be cancelled and further action to be taken as per policy in vogue of the contractors default. (v) Contractor will conclude comprehensive maintenance with OEM and copy of the agreement along with Tax invoice will be submitted to Engineer-in-charge and GE before commencement of work. No payment will be made to contractor without submission of valid agreement. (vi) The above maintenance include complete maintenance of existing equipment by regularly and systematically examining adjusting fabricating as and attending complaints within respective time frame as catered in Particular specification for smooth and efficient functioning of the equipment. (vii)The contract includes for repair, replacement of spare parts & repair / replacement of UPS / batteries of OT lights including wiring complete (vi) Contractor will prominently display his contact/ mobile number and OEM contact number nearby the equipment for call in emergency. (viii) The OEM will also detail one technician staff to inspect the equipment at equal interval regarding functioning of equipment or any other issues araised later. The details of technician shall be forwarded for approval before commencement of work. The problem noticed if any to be informed immediately to JE E/M / Engr-in-charge.monthly/Quartely/Half maintenance check will be carried out by OEM as per monthly/Quartely/Half maintenance check list mentioned in particular specification.
NAVJEEVAN ENTERPRISES
MK ENGINEERING
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .