Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance LEH | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
31 Jul 2021, 2:00 pmClosed
Executive Engineer EDD leh
Office of the Executive Engineer EDD Leh
Supply, Installation, testing and Commissioning of 250KVA Distribution transformer along with laying of 11KV HT line for Deskit Hospital under Untied-Grant 2021-22 on full turnkey basis.
2021_PDNRE_3521_1
NIT No 32 of ED Leh of 2021-22
Open Tender
Electrical Works
Turn-key
20 days
LEH
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Payable To Executive Engineer EDD Leh
Exempted
14 Dec 2021
29 Jun 2021
2 Aug 2021
30 Jun 2021
31 Jul 2021
30 Jun 2021
Amount
250KVA, 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level- 2, (Aluminium wound upto 200kVA, Copper wound for 250kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
185 mm² for Cable un Armoured single core cable XLPE,FRLS cable foer 250KVA
9 Mtr. Long Pole,ST-410 SP33)
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
LT Distribution Box for 250kVA DTR with TPN MCCB short ckt rating 16 KA/Sec for incomer 275Amp (250KVA) and suitable MCCBs for outgoing circuits with terminal extensions
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete.
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
3-Ø, 4-Wire Trivector Meter with CT(LTCT AMR compatible)
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole (as per drawing attached)
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Sundry items like aluminium lugs, Jumpers,binding Tape etc.
Laying of 11KV New Line
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm (75x40x6mm) with GI top Bracket (50x8 mm) including GI clamp (50x8)mm the standard as per enclosed drawing and specification as per Annexure "A")
30 mm² ACSR weasel Conductor (Single conductor length)
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative creepage distance 900mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Pole Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide (Single coat)
Aluminium Paint (Double Coat)
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole including muffing 0.2Mtr above the ground level plaster and curing of concrete as per drawing/Annexure "D"
ROYAL HAYAN CONSTRUCTION AND COMPANY
SS ELECTRICAL SERVICES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .