Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹43.7 L
EMD Value
₹87,500
Closing Date
1 Dec 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
GE (MIS) Mhow
Garrison Engineer (Maint) Infantry School Mhow (MP) - 453441
SPL REPAIR REPLACEMENT OF LT PANEL AND CONNECTED WKS AT CERTAIN LOCATIONS UNDER GE MIS MHOW
2026_MES_798073_1
8998/GE (MIS)/Mhow
Open Tender
Civil Works - Others
Item Rate
150 days
GE (MIS) Mhow
All as per Tender document
8 documents required · 8 mandatory
₹500
GE (MIS) Mhow
₹87,500
Yes
10 Nov 2026
10 Nov 2026
3 Dec 2026
10 Nov 2026
1 Dec 2026
24 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for fabrication, supply, installation, testing and commissioning CPRI approved electrical cubical control panel board (in replacement) factory assembled made outdoor type feeder pilar box double door type wheather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthing termimal with suitable rating aluminum strips for incoming/outgoing MCCB's including and mounting measuring instrument such as Volt meter, Ammeter, selector switch, CTs phase indicator lamp with holder, toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 30cm Complete in all respects as specified and directed by the Engineer-in-Charge. The feeder pillar box shall comprise the following components:-
(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of suitable for 1600 Amps rating ,(RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set.
(b) Phase indication lamp, LED type(set of 3) -1 Set , Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) Ammeter digital type having measuring range (0-500) Amps with CTs etc including rotary switch to measure load of each phase. Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE. | 1 | Each Job | - | - |
| 1.01 | (d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4) cement sand etc complete.
(f) INCOMMING: MCB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1000 Amps spreader both side as Incomming control device : 01 Nos.
(g) OUTGOING: MCCB 3 Pole, 415 V, with Microprocessor release 400 Amps with breaking capacity 36 KA & spreader both side as outgoing cotrol device : - 02 No. (01 Nos Spare),
(h) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 250 Amp & spreader both side as outgoing cotrol device : - 02 Nos.
(i) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 200 Amp & spreader both side as outgoing cotrol device : - 02 Nos.
(j) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 160 Amp & spreader both side as outgoing cotrol device : - 02 Nos.
(k) MCCB 4, pole 16 KA with adjustable thermal setting, 415V, 125 Amp & spreader both side as outgoing cotrol device : - 02 Nos. | - | - | - | - |
| 2 | M&L for fabrication, supply, installation, testing and commissioning CPRI approved electrical cubical control panel board (in replacement) factory assembled made outdoor type feeder pilar box double door type wheather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthing termimal with suitable rating aluminum strips for incoming/outgoing MCCB's including and mounting measuring instrument such as Volt meter, Ammeter, selector switch, CTs phase indicator lamp with holder, toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 30cm complete in all respects as specified and directed by the Engineer-in-Charge. The feeder pillar box shall comprise the following components:-
(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of suitable for 1000 Amps rating ,(RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set.
(b) Phase indication lamp, LED type(set of 3) -1 Set, Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) Ammeter digital type having measuring range (0-500) Amps with CTs etc including rotary switch to measure load of each phase : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE. | 1 | Each Job | - | - |
| 2.01 | (d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4 )cement sand etc complete.
(f) INCOMMING: MCB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 630 Amps spreader both side as Incomming control device : 01 No.
(g) OUTGOING: MCCB 3 Pole, 415 V, with Microprocessor release 400 Amps with breaking capacity 36 KA & spreader both side as outgoing cotrol device : - 02 Nos. (01 No Spare)
(h) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 250 Amp & spreader both side as outgoing cotrol device : - 05 Nos.
(j) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 200 Amp & spreader both side as outgoing cotrol device : - 01 No. | - | - | - | - |
| 3 | M&L for fabrication, supply, installation, testing and commissioning CPRI approved electrical cubical control panel board (in replacement) factory assembled made outdoor type feeder pilar box double door type wheather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthing termimal with suitable rating aluminum strips for incoming/outgoing MCCB's including and mounting measuring instrument such as Volt meter, Ammeter, selector switch, CTs phase indicator lamp with holder, toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 30cm complete in all respects as specified and directed by the Engineer-in-Charge. The feeder pillar box shall comprise the following components:-
(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of suitable for 1600 Amps rating ,(RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set.
(b) Phase indication lamp, LED type(set of 3) -1 Set, Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) Ammeter digital type having measuring range (0-500) Amps with CTs etc including rotary switch to measure load of each phase :AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE. | 1 | Each Job | - | - |
| 3.01 | (d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4 )cement sand etc complete.
(f) INCOMMING: ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 1000 Amps spreader both side as Incomming control device : 01 No.
(g) OUTGOING: MCCB 3 Pole, 415 V, with Microprocessor release 400 Amps with breaking capacity 36 KA & spreader both side as outgoing cotrol device : - 02 Nos. (01 Nos Spare)
(h) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 250 Amp & spreader both side as outgoing cotrol device : - 04 Nos. | - | - | - | - |
| 4 | M&L for fabrication, supply, installation, testing and commissioning CPRI approved electrical cubical control panel board (in replacement) factory assembled made outdoor type feeder pilar box double door type wheather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthing termimal with suitable rating aluminum strips for incoming/outgoing MCCB's including and mounting measuring instrument such as Volt meter, Ammeter, selector switch, CTs phase indicator lamp with holder, toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 30cm complete in all respects as specified and directed by the Engineer-in-Charge. The feeder pillar box shall comprise the following components:-
(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of suitable for 630 Amps rating ,(RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set.
(b) Phase indication lamp, LED type(set of 3) -1 Set, Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) Ammeter digital type having measuring range (0-500) Amps with CTs etc including rotary switch to measure load of each phase : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE. | 1 | Each Job | - | - |
| 4.01 | (d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4 )cement sand etc complete.
(f) INCOMMING: ON LOAD change over switch 415V, 4 pole of capacity 400 Amps as Incomming control device : 02 Nos.
(g) OUTGOING:MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 250 Amp & spreader both side as outgoing cotrol device : - 02 Nos.
(h) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 200 Amp & spreader both side as outgoing cotrol device : - 01 No. | - | - | - | - |
| 5 | Supply, fixing ( in replacement ), connecting to electrical system & testing of Busbar panel board ,cubical type for out door use, made out of 3.15 mm thick CRCA sheet factory made, totally enclosed of size not less that 900x600x500mm and supported with 4 Nos MS Angle legs , duly painted with two coats of powder coated paint over one coat of red oxide primer effectively PVC gaket and sealed mounted on PCC blocks double door type with locking arragnedment with handle at front and openable at front &back bothe side with required hinges heavy duty, compartemtalised suitably including provision for tapping incoming & outgoing electric connections with suitable size of aluminium lugs glands and comprising of the following accessories :-
(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of 300 amps rating (RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set.
(b) Phase indication lamp, LED type(set of 3) -1 Set, Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) Ammeter digital type having measuring range (0-300) Amps with CTs etc including rotary switch to measure load of each phase : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(d) Volt meter digital type having measuring range (0-500) volt with rotary switch to measure voltage of phase R.Y.B make : AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(e) MCCB 4, pole 36 KA with adjustable thermal setting, 415V, 250 Amp- 02 Nos.
(f) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4) cement sand etc complete | 2 | Each Job | - | - |
| 6 | Supply, fixing & testing of LT distribution panel board (in replacement), made out of 2 mm thick MS sheet of size not less than 600x450x200mm duly painted with two coats of synthetic enamelled paint over one coat of red oxide primer wall mounted/semi-grouted in wall with locking arrangement, double door type, compartmentalised and provision for tapping incoming & outgoing electric connections with suitable size of lugs, glands, one MCCB will be mounted on proper din railes and comprising of the followings :-
(a) Aluminium busbar chamber TPN of 200 amps rating (set of 4 strips)
(b) Phase indication lamp-set of 3, Make: AE / L&T / Schneider / make as per Particular Specification (list of Make) as approved by GE.
(c) MCCB 4 pole 415 Volts, 50 Hz, 100 amps rating, 25 KA breaking capacity - 01 No.(Incomming )
(d) MCB TPN 63 A -2 No and MCB SPN 32 A -3Nos as out going cotrol | 2 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_895279.xls
BOQ • 0.35 MB
Tenderandspecialcondition8998.pdf
Tender Documents • 0.54 MB
ParticlularSpecifications8998.pdf
Tender Documents • 0.31 MB
DetailsOfWorkInAndInHand.pdf
Additional Documents • 0.10 MB
ListOfMake8998.pdf
Tender Documents • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .