DYCEEC
14 conditions · 2 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per AnnexureVIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Technical Eligibility Criteria: Given in Special Condition of Contract. (a) The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i) Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work each costing not less than the amount equal to 60% of advertised value of the tender. (b)(i) In case of tenders for composite works (e.g. works involving more than one distinct component, such as Civil Engineering works, S&T works, Electrical works, OHE works etc. and in the case of major bridges - substructure, superstructure etc.), tenderer must have successfully completed or substantially completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of each component of tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of each component of tender, or One similar work each costing not less than the amount equal to 60% of advertised value of each component of tender. Note for b(i): Separate completed works of minimum required values for each component shall also be considered for fulfillment of technical eligibility criteria for different components. (b) (ii) In such cases, what constitutes a component in a composite work shall be clearly predefined with estimated tender cost of it, as part of the tender documents without any ambiguity. (iii) To evaluate the technical eligibility of tenderer, only components of work as stipulated in tender documents for evaluation of technical eligibility, shall be considered. The scope of work covered in other remaining components shall be either executed by tenderer himself if he has work experience as mentioned in clause 7 of the Standard General Conditions of Contractor through subcontractor fulfilling the requirements as per clause 7 of the Standard General Conditions of Contract or jointly i.e., partly himself and remaining through subcontractor, with prior approval of Chief Engineer in writing. However, if required in tender documents by way of Special Conditions, a formal agreement duly notarised, legally enforceable in the court of law, shall be executed by the main contractor with the subcontractor for the component(s) of work proposed to be executed by the subcontractor(s), and shall be submitted along with the offer for considering subletting of that scope of work towards fulfilment of technical eligibility. Such subcontractor must fulfill technical eligibility criteria as follows: The subcontractor shall have successfully completed at least one work similar to work proposed for subcontract, costing not less than 35% value of work to be Sublette, in last 5 years, ending last day of month previous to the one in which tender is invited through a works contract.
Technical Eligibility Criteria: The meaning of similar work for the above work is: "Satisfactory execution of any HT/LT electrical work"
22 conditions · 3 needing a document upload
The tenderer shall upload scanned copies of mandatory credential such as Experience, Turn over certificates and any other documents as applicable, all documents related to Partnership Deed/Joint Venture/ Consortium/ MOU, Registration details, AoA, MoU, Certificate of incorporation, TIN No., registered address, email ID etc. should be uploaded in PDF format only at the time of submission of bid as per GCC. Nonsubmission of the certificate/credentials, shall lead to summary rejection of the offer
Please submit your bank details i.e.Name of the Bank along with Bank Branch Code, IFSC Code, Beneficiary name, Account Number, Type of account, PAN and GSTN Number
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
INSTRUCTIONS TO TENDERERS
The tenderer shall thoroughly go through the entire tender documents and strictly adhere the instructions and directions given at different pages.
If the Tenderer(s) deliberately give(s) wrong information/ incorrect documents in his/their tender or create circumstances for the acceptance of his/their tender, the Railway reserves the right to reject such tender at any stage. The entire EMD and any other dues available with Railway against that contract will be forfeited. Action will be taken to suspend the business with the tenderere for a period of one year. In addition, Administration reserves the right to prosecute under suitable law.
All terms and conditions in the tender documents are binding on the Tenderers.
The Tenderers are advised to visit the site of work in their own interest and acquaint themselves with the site conditions and expected quantum of work and assess all the site specific difficulties to be experienced while executing the same and the rate shall be arrived duly considering all the facts above and quoted in the tender. Any representation at a later date specifying the site difficulties shall not be considered.
Tenderers are advised to go through the tender booklet for detail condition, scope of work and other technical conditions/specification, maintenance schedule, all penalty conditions, make list, earthing drawing, approved/likely source of material related with the work before submitting their offer.
It shall not be obligatory on the said authority to accept the lowest tender and no Tenderer/tenderers shall demand any explanation for the cause of rejection of his/their tender.
It is the responsibility of the tenderer to see corrigendum, if any, to tender notice up to the date of tender opening.
Address of the Office: Office of Dy.CEE Con PRYJ, 2nd Floor, Ganga Building, NCR Headquater, Subedarganj, PIN-211015
PVC clause:- Applicable as per clause.
Augmentation of supply system, Solar system, Centralized AC for augmentation of Banda station and ORH railgaon subedarganj work of North Central railway under jurisdiction of Dy.CEE/C/PRYJ.
EL-C-PRYJ-07-25-26~NCR
EL-C-PRYJ-07-25-26
Open
Works - General
12 Months
Prayagraj, Uttar Pradesh
₹0
₹4.8 L
13 Feb 2026
21 Jan 2026
30 Jan 2026
72 items across 3 schedules · ₹6,50,00,000 total
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | Providing, and fixing of water fountain (size 16feet diameter) made of RCC and heigh qualitygranite with decorative elements andembellishment for the fountain along with custom design and construction of fountain including waterpump, installation, water jets or spouts, testingetc. Complete job as desired and approved byEngineer-in-charge. (1) Shooter Jet Nozzle withball Joint Brass with chrome Plated. (2). SumersiblePump with dust Grill Three Phase 2hp, are SuitableAccording Designed. ISI Marked. (3). All necessaryPlumbing material pipe fitting with 10Kg pressurein gray fitting elbow, tee, Socket, reducer, jointing all necessary plumbing item in water body's Make-Astral/ King/ /Supreme/prince or it's equivalent.(4). Electrical material likes bend wire, waterprooftape, four core 2mm wire, joints, tie, pvc tape,required size in water body's to operating paneldistance to be 10 mtr water body's wire make- Champion or its equivalent. Inspection by-Consignee. " | Numbers | 2.00 | 5,23,403.16 | 10,46,806.32 |
| 2 | Supply ,fixing, connecting and commissioning of 17/25 Watt Under Water Swimming Pool multi color LEDLights IP68.Inspection by- Consignee. | Numbers | 20.00 | 6,540.42 | 1,30,808.4 |
| 3 | LT. Distribution board comprising with MCCB 4 pole 200 Amp 35 KA = 1 no as incoming. Out going MCB SPN C series10 KA 32 Amp =15 nos. with volt meter, Ammeter and copper bus bar 40 mmx 5 mm complete. | Numbers | 10.00 | 95,413 | 9,54,130 |
| 4 | "Supply, erection, testing and commissioning of LT Switch gear panl board of 2mm thick dia prssed CRC steel sheet . Panl shall be treatd for anti corrosion treatment and finished with smoke gray paint as per technical specification No. Sr DEE/G/ALD/ Panel-94/113 comprising with as under- a) Incoming 01 No. 1600 Amps ACB, 415 Volt, 3 phase, 4 pole Manually draw out microproceeor basd type conforming to IS: 13947-2, IEC 60947-2 latest specification." | Numbers | 2.00 | 1,72,386 | 3,44,772 |
| 5 | Bus cupler 01 No.1600 Amps ACB, 415 Volt, 3 phase, 4 pole Manually draw out microproceeor basd type conforming to IS: 13947-2, IEC 60947-2 latest specification. | Numbers | 1.00 | 1,72,386.12 | 1,72,386.12 |
| 6 | ACB 630 A, 415 Volt, 3 phase, 4 pole Manually draw out microproceeor basd type conforming to IS: 13947-2, IEC 60947-2 latest specification. | Numbers | 5.00 | 1,33,270 | 6,66,350 |
| 7 | Supply of MCCB of 400 A, Standard Breaking capacity 415 Volt, 4P, 65 KA (simiar to cat no. CS400NATU*4P of C&S Make or similar ). | Numbers | 8.00 | 30,996 | 2,47,968 |
| 8 | MCCB of 250 A, Standar Breaking capacity 415 Volt, 4P, 36 KA (simiar to DU 250 type). | Numbers | 6.00 | 9,993 | 59,958 |
| 9 | Supply, fixing, testing, connecting and commissioning of Outgoing/Feeder Panel Mounted Multi-function meter with Accuracy Class 1 as per IEC 62053-21 or Class 0.5, 0.5S as per IEC 62053-22.LED meter Cl 1 with RS485: of similar model No.WL440521OOOO of L&T. Meter should have following features built-in LED • Flush mounting 96 x 96 mm • True RMS measurement • Password protection provision for security • Site selectable for 3 Phase 4 wire, 3 Phase 3 wire, 1 Phase, CT Secondary 1A/5A, Universal Auxiliary Supply 80-300 VAC/DC, Input Voltage Measurement 50-500 VAC, • 64 samples/ cycle The Meter should be able to read/display following parameters Instantaneous Parameters (V1, V2, V3, V12, V23, V31, Avg (VLN, VLL), A1, A2, A3, Aavg, F, PF-1, PF-2, PF-3, PF (Avg) W1, W2, W3, W (total) VA1, VA2, VA3, VA (total) Cumulative Parameters (Import Wh, Import Vah, Import load hours, Reset (old) Cumulative parameters (Import Wh, Import load hours, Communication (RS485 Modus RTU).complete with all accessories. | Numbers | 21.00 | 2,780 | 58,380 |
| 10 | supply of Indication lamps with suitable holder. | Numbers | 63.00 | 88 | 5,544 |
| 11 | Fabrication Work and insulated Aluminium bus bar of 2400 Amp. Capacity for phase and 1200 Amp for neutral. Bus bar shall be suitably insulated with heat shrinkabl slvs / epoxy coating / insulating tap to withstand the test voltage of 2.5KV . Copper strips for connection outgoing as well as incoming with suitabl size be provided. (Item No. 86-93 are parts of LT Panel) | Numbers | 1.00 | 97,018.26 | 97,018.26 |
| 12 | Horizontal boring of cable duct at more than 2.1 mtr depth from the bottom of pit and without DWC/GI pipes. The work shall be done as per extant practice and instruction of site Engineer. | Metre | 2800.00 | 1,038 | 29,06,400 |
| 13 | Supply and laying of HDPE pipe having working pressure PE 63, PN - 8 of outer diameter 110 mm in horizontal boring . | Metre | 5000.00 | 352 | 17,60,000 |
| 14 | Supply, fixing, testing, connecting andcommissioning of 100 Watt or above LED highbaylights fittings as per IS:10322. LED Luminaries: -(1) A complete LED lighting unit consisting of a lightsource and driver together with parts of distributelights, to position and protect the light source, andto connect the light source to a branch circuit. Thelight source itself may be an LED array and LEDmodule, or an LED lamp. (2): -Supplied LEDluminaries shall confirm to IS:16101(2012) IS:16106 (2012). Light Source (LED) in theLuminaries should be of make: - (1): -NICHIA/CREE/ OSRAM / SEOUL/PHILIPS/LUMILEDS/LEDNIUM. (2): -LEDs to IS:16105 (2012).IS:16108(2012), IEC: 62471.Type LED: - Highpower LED, SMD (Surface Mounting device)/COB(Clip on board).1. Input operating voltage: -105-295 V AC.2: - Normal Voltage-220V AC,3. Drivertype: constant current driver with short circuitprotection. 4.LED life: - >=50000 burning hours.5.Depreciation: - 30% max. after 50000 burninghours.6. Control of distribution: -Full cut off.7.Surge protection: 4KV.8. Drive component:Industrial grade only. 9.Efficiency of driverelectronic: >= 85%.10. Beam angle:>=140 degreealong with road and >=80 degree across theroad.11. Colour temperature:5000- 6500K. 12.Colour rendering index (CRI):>=75. 13.Ingressprotection: IP-66. 14.Lumen output: >=120lumens/watt.15.Power factor:->=0.95. 16.Totalharmonics distortion (THD):-<15%.17. Lamp cover:Toughened glass or UV stabilized poly carbonate.18.Finishing: Power coated/Anodized. 19.Secondryoptics: poly carbonate reflector/ poly carbonateslens.20. Construction of housing: extrudedaluminum/CRCA/Pressure die cast aluminum.21.Mounting: Suitable for existingpole/Truss/Lantern mounted. 22.Certificate: Firm tosubmit LM80(In respect of LED used) & LM79(Inrespect of luminaire used) test certificate fromNational/International accredited Laboratory andOEM certificate for compliance ofBIS/IEC.23.Warranty: Firm to submit warrantycertificate for five year along with the supply. Allfittings shall be fitted with new suitable bend/elbowwith clamp and proper nut and bolt and connectionwith twisted twin flexible cord of minimum size 16/1mm copper conductor as per relevant technicalspecification. Materials parameters must remainunchanged during entire warranty period. | Numbers | 150.00 | 4,180 | 6,27,000 |
| 15 | Supply, fixing, testing and commissioning of Fancytype Jhumar Light of 12x40 watt HalogenDimmable/12 x 2watt LED dimmable, lamp base -G9 mcomplete with driver and as per relevent ISstandard.Inspection by- Consignee. | Numbers | 4.00 | 53,218.99 | 2,12,875.96 |
| 16 | Supply, fixing, testing, connecting andcommissioning Trends Royal Brass Antique FinishGold Floor LED Lamp Standing 5Ft Height WithCream Lampshade 16 Inches of LED lamp 12 wattor above as per requirment for darbari tent and VIPtent.Inspection by- Consignee. | Numbers | 30.00 | 10,508.19 | 3,15,245.7 |
| 17 | Supply, testing and commissioning of fly catcherof size-63 x 17 x 45 cm3, 2 nos UV lights of 2feet 18 watt each as per relevant technicalspecification. Inspection by-Consignee. | Numbers | 20.00 | 2,847.79 | 56,955.8 |
| 18 | Supply, fixing, testing and commissioning of wallmounted distribution board (TPN MCB - Incoming& SP MCB - Outgoing), made up of steel sheet,phosphatised power painted complete withneutral link, earth point, Din rail conforming toIS:13032 & 8623 of approved make withfollowing items of matching make to be fixed indistribution board confirming to IS:8828 :1996 orlatest, IE rules and site requirement. TPN MCB 63Amps 10kA "C" series = 01 Nos. (incoming) SPMCB 6-32 Amps 10kA "C" series= 18 Nos.(outgoing). Inspection by-Consignee. | Numbers | 60.00 | 5,673 | 3,40,380 |
| 19 | Supply, fixing, testing, connecting andcommissioning of 09 Watt or above LED in -Groundburial light with die cast aluminium housing withtoughened glass , IP66. LEDLuminaries:-(1) Acomplete LED lighting unit consisting of alightsource and driver together with partsof distributelights,to position and protect the light source, andtoconnect the lightsource to a branch circuit.Thelight source itself maybe an LEDarray and LEDmodule, or an LED lamp.(2):-Supplied LEDluminaries shall confirm to IS:16101 (2012)IS:16106(2012).Light Source (LED) in theLuminaries should be ofmake:- (1):-NICHIA/CREE/OSRAM/ SEOUL/PHILIPS/LUMILEDS/LEDNIUM. (2):- LEDstoIS:16105(2012).IS:16108(2012),IEC:62471.Type LED:-HighpowerLED,SMD (Surface Mounting device)/COB (Clip onboard).1.Input operating voltage :-105-295 V AC.2:- NormalVoltage-220VAC, 3.Driver type: constantcurrent driver withshort circuitprotection. 4. LEDlife:-<=50000 burninghours.5.Depreciation:- 30%max. after 50000 burninghours.6.Control ofdistribution:- Full cutoff. 7.Surge protection: 4KV.8. Drive component :Industrialgradeonly. 9.Efficiency of driver electronic:>; 85%.10.Beamangle:>=140 degree along with road and>=80 degreeacrossthe road. 11.Colourtemperature: 5000-6500K.12. Colourrenderingindex (CRI):>=75. 13. Ingress protection :IP-66.14.Lumen output: >=120 lumens/watt. 15. Powerfactor:->;=0.95. 16.Total harmonicsdistortion(THD):-<15%. 17. Lampcover:Toughenedglass or UV stablised polycarbonate. 18.Finishing:Power coated/Anodized.19.Secondryoptics :poly carbonate reflector/polycarbonateslens. 20. Construction ofhousing:extrudedaluminum/CRCA/Pressure diecastaluminum. 21. Mounting:Suitable for existingpole/Truss/Lanternmounted. 22. Certificate:Firmtosubmit LM 80 (In respect of LEDused) & LM79(Inrespect ofluminaire used) test certificatefromNational/International accreditedLaboratoryand OEM certificate for compliance of BIS/IEC.23.Warranty: Firm tosubmit warranty certificate forfive year along withthe supply.All fittings should beembossed/sticker withmanufacturing date andwarranty details at time of supply.24.Theweight of fixture should be standard for better heatresistance of LEDPCB. All fittings shall be fitted withnew suitable bend/elbowwithclamp and proper nutand bolt and connection with twistedtwinflexiblecord of minimum size 16/1 mm copper conductorasperrelevant technical specification. Materialparameters must remainunchanged during entirewarranty period.Inspection by- Consignee. | Numbers | 30.00 | 3,338.33 | 1,00,149.9 |
| 20 | Supply, installation, testing, connecting and commissioning of LED base name board (Signage board) of different stations (01 set includes 01 No Hindi, 01 No English & 01 No Urdu name board) with power LEDs, Drivers & wiring of board. The signage board should have alphabet of vertical peak height of 600 mm and proportionate horizontal span. Maximum size of Hindi, English & Urdu signage panel shall have Length- 6400 mm, Height of panel shall depend on aspect ratio of letters and font style but shall be approx 850-975 mm as per specification. | Numbers | 2.00 | 5,25,629 | 10,51,258 |
| 21 | Provision of Sleek Wall Mountable Modular Mobile Charging Kiosk consisting of mobile carrying tray of adequate capacity and 01 switch for each 08 sockets of 2 pin. It has to be attached to any wall or placed on a table. Either white or black finish. Made up of high grade PVC or fiber-glass. Thickness of fiber sheet should not be less than 2 mm. Holding tray should have load bearing capacity of 10 Kg pereight-socket. Mobile holding tray should be very rigid, robust and transparent, scratch-proof fiber-glass material of not less than 10 mm thickness. During warranty-period if any scratch is generated, entire charging station shall have to be replaced. Each socket should be modular (Legrand, Anchor, Arkeylite, HPL, Havells only) 2 Pin type. (mounted vertically). Adequate space should be left for next row of sockets to start so that mobile chargers may be fixed without any space crunch. One bottle type fuse and one LED indicator for each set of 8 sockets and one MCB of adequate capacity for complete board shall have to be provided. One switch foreach set of 8 socket is required. Dimension of holding tray should not be more than 10 inches depth. However, multi-step holding may be provided with successive trays having increasing depth. Depth of entire unit should not be more than 1.5 feet after installation with trays in openposition......8 sockets x 2 row. Inspection by- Consignee. | Numbers | 25.00 | 1,454 | 36,350 |
| 22 | Design, manufacturing , supply, erection, testingand commissioning of pre-cooling switch boardcabinet made of Stainless steel body of minimum 16Gauge with following accessories. Switch Boardcabinet shall have door and locking arrangement deof stainless steel. Key should be common to all suchboxs and one extra key shall be provided fo eachsuch SBC. Work shall include fixing of switch boardcabinet either with he help of 02 nos 3 inch angle ofadequate length to be ground adjacent to track atspecified location or on the column of COP or anyother method as specified by sit incharge. Alumn.bus bar of required size 25x10 mm - for 415 V-04Nos. MCCB 100 A 4 POLE will be rating of 415Volt100A TPN 25 KA. One no. 125 A industrial type ironclad 5 pin (3P+N+E) 415 V plug socket with springlocked cover. Batten holder fixed on bakelite sheetbase plage with suitable lamp and controlled by 5 Apiano type switch. | Numbers | 10.00 | 13,837.3 | 1,38,373 |
| 23 | Supply, fabrication, erection, testing &commissioning of weather proof floor mounted dustand vermin proof Battery Charging points suitablefor operation on 150 Volts D.C. supply systemfabricated with 14 SWG MS sheet / GI sheet, MSchanel size 100x50 mm (weight 7.914 Kg.Mtr) 1200mm long, complete with locking arrangement,painted(inner & outer) inner connection with solidcore , PVC insulated copper conductor cable size 10sqmm, Alumn. bus bar of size 25x10 mm completewith one no. MCB DP 60 AMP (DC series) as perTech specification and drawing including verticalgrouting of MS channel 300 mm deep with cementsand and concrete mixture for erection. | Numbers | 10.00 | 3,504.51 | 35,045.1 |
| 24 | Collecting from SSE/PS store & Laying of LT cablesof above cable in ground (Including digging of cabletrench, sand cushioning, protection brick coveringand refilling the trench etc.), direct in RCC/Metalpipes in rod/track crossings and on surface/inwall/in concrete floor by cutting recessed andfinished originally as required, testing &commissioning as per relevant technicalspecifications. | Metre | 4000.00 | 73.1 | 2,92,400 |
| 25 | Supply, of 2x6 sq. mm PVC insulated coppercable single core 1100 v grade as per IS : 694(latest ) for sub mains with PVC conduit pipeheavy duty not less than 25mm dia. inrecessed /surface of the wall with earthcontinuity PVC copper wire including , erection testing and commissioning from LT panel topower SBDs | Metre | 1500.00 | 86.07 | 1,29,105 |
| 26 | Supply, erection, Testing & Commissioning ofsub main consisting of 2x4 Sq. mm (P & N)PVC insulated and sheathed copper wiremultistranded single core 1.1 KV grade alongwith 1.5 Sq. mm PVC insulated copper wire 1.1KV grade for earthing.(Quantity 1 Mtr. Equal to02 Nos., wire of 4 Sq.mm of 01 Mtr. each. and01 No. earth wire 1.5 Sq. mm. of 01 M) (Nocable joint is permitted inside the MS conduitpipe cable | Metre | 1500.00 | 55.6 | 83,400 |
| 27 | Supply , erection, testing and commissioningof metal clade SDB with 12way DB completewith 1x63 Amp MCB isolator 4 pole . & 4x20AMCB SP ,6x10 amp MCB SP & 01 No. RCCB of63 Amps with all other accessories required asper site.complete with all other accessories asper site requirement | Numbers | 14.00 | 5,710.15 | 79,942.1 |
| 28 | Supply, installation, testing andcommissioning of LED luminarie of 18 watt,110 VoltDC/AC Pit Light complete withpressure die cast alluminumhousing built in external heatsink with suitable cover touniform light distribution,integral high efficiency Leddriver complying the givenparameters complete inallrespect with required hardwarefor fixing on the wall /structure within connectionwith twin corePVC insulatedflexible copper conductor cableas per requirement on site.Thefitting should be confirming toCEE Specification NoCEE/NR/121- Elect/PS/2018(Rev-4) Dt:- 04.11.2019 /RDSO SpecificationNO.RDSO/PE/SPEC//TL/0091-2016 (Rev-1) 0r Latest.Theguaranty shall be Five yearsfrom date of commissioning.PIT LIGHT TO BE INSPECTEDBY M/S RITES. | Numbers | 100.00 | 3,168.82 | 3,16,882 |
| 29 | Supply & erection suitableenclosure duly painted forprotection of Pit light fittingmentioned vide SOR item N0.1, made of MS angle iron size25mmX25mmX3mm & MS wiremesh 25 mm 25mm x dia. 2mm. | Numbers | 100.00 | 565.13 | 56,513 |
| 30 | Supply, replacement, fixing, testing, connectingandcommissioning of 30 Watt or above LED floodlight fittingsas per IS:10322. LED Luminaries:-(1) A complete LEDlighting unit consisting of alight source and drivertogether with parts of distribute lights, to position andprotect the lightsource, and to connect the light sourceto abranch circuit. The light source itself may be anLEDarray and LED module, or an LED lamp.(2):- SuppliedLED luminaries shall confirm toIS:16101(2012) IS:16106(2012).LightSource(LED) in the Luminaries shouldbe ofmake:- (1):-NICHIA/ CREE/OSRAM/SEOUL/PHILIPS/LUMILEDS /LEDNIUM. (2):- LEDstoIS:16105(2012).IS:16108(2012),IEC:62471.TypeLED:- High power LED,SMD(Surface Mountingdevice)/COB(Clipon board).1.Input operatingvoltage :-105-295 V AC.2:-Normal Voltage-220VAC,3.Driver type: constant currentdriver withshort circuit protection. 4.LED life:->50000burning hours.5.Depreciation:- 30% max.after50000 burning hours.6.Control of distribution:-Fullcut off. 7.Surge protection:4KV.8. Drivecomponent:Industrial grade only.9. Efficiency ofdriver electronic: >85%.10. Beam angle:>=140degree along with road and>=80 degree acrossthe road.11.Colourtemperature:5000- 6500K.12.Colour renderingindex(CRI):>=75.13.Ingress protection: IP-66.14.Lumen output:>120 lumens/watt. 15.Power factor:->0.95.16.Total harmonics distortion(THD):-<15%.17.Lamp cover :Toughened glass or UVstablisedpoly carbonate.18.Finishing:Powercoated/Anodized.19.Secondry optics: polycarbonate reflector/poly carbonateslens.20.Construction of housing:extrudedaluminum/CRCA/Pressure diecastaluminum.21.Mounting:Suitable forexistingpole/Truss/Lantern mounted.22.Certificate:Firmtosubmit LM80(In respect of LED used)&LM79(In respect ofluminare used) test certificatefrom National/Internationalaccredited Laboratoryand OEM certificate for complianceof BIS/IEC. 23.Warranty:Firm to submit warrantycertificate for five year along with the supply. All fittingsshall be fitted with new suitablebend/elbow with suitablesize & length of MS Chanel and connection with twistedtwin flexible cord of minimum size 16/1 mm copperconductor as per relevant technical specification.Materials parameters must remain unchanged duringentirewarranty period. (for Cat Walk Lights) | Numbers | 100.00 | 1,909.38 | 1,90,938 |
| 31 | Supply erection, testing & commissioning of basic Earthing Kit 1set as per RDSO spec. No RDSO/PE/SPEC /PS/0109(REV.0)-2008, Amendment '1' or latest specification | Numbers | 42.00 | 13,358.76 | 5,61,067.92 |
| 32 | Supply,installation,testing and commissioning of recess/down mounting 15 Watt slim, compact with opal diffuser 6500 K LED Panel roundLuminaries of (Similar to Model No.LHEBHDP7IZ1W015 of Havell's make, make - Crompton, Bajaj, Hevells or Similar) complete in all respect with required hardware for fixing on the wall/structurewithin connection with twin core PVC insulated flexible copper conductor cable as per requirement on site. | Numbers | 500.00 | 1,209.41 | 6,04,705 |
| 33 | Dismantling of Existing LT/HT/ABC Over Head Line withConductor, Fittings,GIBrackets includingCutting ofvarious types of Pole whereverrequired as per Site Condition.(01 number = 1 span) | Each Span | 200.00 | 351 | 70,200 |
| 34 | Supply, fixing, testing, connecting andcommissioning of 40 Watt orabove Drop Down LEDLight fitting , front opening(Milky/Clear) withdiecast aluminium housing with toughened glass.LEDLuminaries:-(1) A complete LED lighting unitconsisting of alight source anddriver together withparts of distribute lights,to position and protectthelight source, and to connect the lightsource to abranchcircuit.The light source itself may be anLEDarray and LED module,or an LED lamp.(2):-Supplied LEDluminaries shall confirm toIS:16101(2012) IS:16106(2012). Light Source (LED) intheLuminaries should be ofmake:- (1):- NICHIA/CREE/OSRAM/SEOUL/PHILIPS/LUMILEDS/LEDNIUM. (2):- LEDstoIS:16105(2012).IS:16108(2012),IEC:62471.TypeLED:- Highpower LED,SMD(Surface Mountingdevice)/COB (Clip on board). 1.Inputoperatingvoltage :-105-295 V AC. 2:- NormalVoltage-220V AC, 3.Driver type:constantcurrent potted driver withshort circuit protection. 4.LEDlife:- >=50000 burninghours.5.Depreciation:-30% max. after 50000burninghours.6.Control ofdistribution:- Full cut off. 7.Surgeprotection: 4KV.8. Drive component :Industrial gradeonly.9.Efficiency of driver electronic>; 85%. 10.Beamangle:>=140 degreealong with road and&80> degree acrossthe road.11.Colourtemperature: 5000- 6500K.12.Colourrendering index (CRI):>75. 13.Ingressprotection :IP-66. 14. Lumen output: >;=120lumens/watt.15. Power factor>;=0.95. 16. Totalharmonics distortion(THD):-<15%. 17. Lampcover:Toughened glass or UV stablisedpolycarbonate. 18.Finishing:Power coated/Anodized.19.Secondryoptics :poly carbonatereflector/ poly carbonateslens.20. Construction ofhousing: extrudedaluminum/CRCA/Pressurediecastaluminum. 21. Mounting: Suitable forexistingpole/Truss/Lanternmounted. 22.Certificate:Firm to submit LM 80 (Inrespect ofLEDused) & LM79(In respect of luminaire used)testcertificate fromNational/International accreditedLaboratory and OEMcertificate for compliance ofBIS/IEC. 23. Warranty: Firm tosubmitwarrantycertificate for five year along with the supply.Allfittingsshould be embossed/sticker withmanufacturing date and warrantydetails at time ofsupply.24.The weight of fixture should bestandardfor better heat resistance of LED PCB. Allfittings shall be fitted withnew suitable bend/elbowwithclamp and proper nut and bolt andconnectionwith twisted twinflexible cord of minimum size 16/1mmcopper conductor as perrelevant technicalspecification. Materialparameters must remainunchanged during entire warrantyperiod.Inspectionby- Consignee. | Numbers | 70.00 | 6,888.39 | 4,82,187.3 |
| 35 | Transportationof less/heavy material and manpower including supply & running of one MUV to the sites of work as per requirement & direction of site incharge .The rates includes all the taxes,license fee,Road permit,driver wages,fuel,repair & maintenance cost etc.Complete in all respet. | Kilometre | 9000.00 | 40 | 3,60,000 |
| 36 | "Supply, erection, testing, connecting and commissioning of 500KVA 11/.415V Compact Sub Station comprising with (1) . 11KV 3 Way RMU, (2 Nos LBS + 1 No VCB with Transformer Protection Relay ) 2. 11/.415V 500KVA Oil type Transformer with OCTC 3. I/C 800A 4P 50KA MDO ACB With MP Based O/C , S/C & E/F Release - 1 No. I/C 800A 4P 50KA MDO ACB With MP Based O/C , S/C & E/F Release - 1 No. O/G 630A 4P 50KA MDO ACB With MP Based O/C , S/C & E/F Release - 3 Nos. 4. 800A Aluminium Bus Bar" as per relevant IS/BIS. | Numbers | 2.00 | 35,29,949.5 | 70,59,899 |
| 37 | Supply & erection of power coated perforated cable tray 300x50x1.6 mm thickfor protection of cabes comlete with all other accessories as per siterequirement ( for supply arrangement through FOB and COP) | Metre | 1000.00 | 510 | 5,10,000 |
| 38 | Shifting of the high mast from one place to otherplace and installation and commissioning of this High mast including foundation other necessaryitems which required for commissioning of the highmast. | Numbers | 4.00 | 14,050 | 56,200 |
| 39 | Shifting, dismantling charges of LT panels, transformers, DG set etc. | Job | 2.00 | 47,070 | 94,140 |
| 40 | Supply & erection, testing and commissioning of out door /indoor type cableend-termination kit/ straight through jointing kit with all accessories for 11kv(E) XLPE cable as per relevant IS specification. | Numbers | 4.00 | 7,640 | 30,560 |
| 41 | Collecting, transporting from SSE/C/GPS/ALD/ SFG store to site and laying,testing & commissioning of HT cables of all sizes in ground (including diggingof cable trench, send coushioning, protection brick covering and refilling thetrench etc. ) direct in RCC/Metal pipes in road/track crossing and onsurface/inwall/in cncrete floors by cutting recessed and finished originally asrequired, testing & commissioning as per Tech. Specfn. | Metre | 800.00 | 72 | 57,600 |
| Schedule total | ₹2,23,99,893.88 | ||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
ACS-1.pdf
ATTACHMENT
ACS-2.pdf
ATTACHMENT
ACS-3.pdf
ATTACHMENT
ACS-4.pdf
ATTACHMENT
ACS-5.pdf
ATTACHMENT
ACS-6.pdf
ATTACHMENT
ACS-7.pdf
ATTACHMENT
ACS-8.pdf
ATTACHMENT
ACS-9.pdf
ATTACHMENT
ACS-10.pdf
ATTACHMENT
SystemofVerificationofTendererCredentials.pdf
ATTACHMENT
GCC-April22.pdf
ATTACHMENT
TenderDocument07.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .