Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.5 LAccepted-AOC | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹29.0 L+₹6.5 L (28.6%)Rejected-Finance C 56 6 ANAND VIHAR COMMERCIAL COMPLEX MAHOLI ROAD MATHURA UP PIN 281004 | MATHURA | UTTAR PRADESH | 281004 | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹42.7 L+₹20.1 L (89.4%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 4 | L4₹42.9 L+₹20.4 L (90.4%)Rejected-Finance 1331 GENERAL GANJ OPP WATER TANK MATHURA 281001 | MATHURA | UTTAR PRADESH | 281001 | L4 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
27 Jan 2024, 6:00 pmClosed
GE EAST MATHURA
Garrison Engineer East Military Engineer Services Mathura Cantt Mathura 281001
REPAIR MAINTENANCE OF MAIN DISTRIBUTION BOARDS SERVICE CONNECTIONS SUBMAIN WIRING BLDG SECURITY LIGHTS BLDG EARTHING AND IMPROVEMENT OF EM INSTALLATIONS INCLUDING RENEWAL OF EARTHING AND ALLIED WORKS UNDER GE (EAST) MATHURA
2023_MES_634844_1
8200-1405/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE EAST MATHURA
AS PER TENDER DOCUMENTS
10 documents required · 10 mandatory
₹500
GE EAST MATHURA
₹90,000
23 Feb 2024
29 Dec 2023
29 Jan 2024
29 Dec 2023
27 Jan 2024
13 Jan 2024
29 Dec 2023 - 20 Jan 2024
Amount
Taking down carefully copper/aluminum copper point wiring (light, fan, socket or power, bell etc.) complete including fixtures & fittings such as ceiling rose, socket, Pendant, regulator, sockets, etc and removing the material from site and making good the disturbed surfaces of walls, ceiling etc complete all as directed.
Taking down carefully old unserviceable submain wiring of any size & type complete all as specified and as directed.
Taking down old unserviceable existing SP/SPN/TPN DB/ enclousers any size and type/descriptions including MCB and making good disturbed surface of walls to match the surrounding surface complete all as specified and as directed.
S&F Sub main wiring with two runs single core 4 Sqmm PVC insulated unsheathed (FRLS) cable with multistranderd copper conductor, 1100 votls grade drawn in and including suitable size rigid non metalic PVC conduit (not less than 20mm dia) and all its accesories concealed in wall/roof including cutting & chases in brick wall bilt in cement mortar and making good the disturbed surface, including PVC insulated 4 sqmm unsheathed stranded (FRLS) copper conductor cable for earth wire complete all as specified and as directed. Note : Two runs of 4 Sqmm cable, one run of 4 Sqmm earth wire & 20mm PVC Conduit shall be measured as one unit.
S&F of Sub main wiring with two run of single core 6 Sqmm cable PVC insulated unsheathed (FRLS) cable with multistranderd coper conductor, 1100 votls grade drawn through and including PVC conduit not less than 25 mm dia and its all accessories concealed in wall/roof including cutting & chases in brick work built in cement mortar and making good the disturbed surface including PVC insulated 6sqmm unsheathed stranded (FRLS) copper conductor cable for earth wire complete all as specified and as directed. Note : Two runs of 6 Sqmm cable, one run of 6 Sqmm earth wire & 25mm PVC Conduit shall be measured as one unit.
S&F Sub main wiring with two run of single core 10 Sqmm cable PVC insulated unsheathed (FRLS) cable with multistrandard copper conductor, 1100 votls grade drawn through and including concealed PVC conduit not less than 25 mm dia including all its acessories concealed in wall/roof including necessary cutting/chase in brick wall built n cement mortar and making good distured surface including 10 Sqmm PVC insulated unsheathed stranded (FRLS) cable for earth wire complete all as specified and as directed. Note : Two runs of 10 Sqmm cable, one run of 10 Sqmm earth wire & 25mm PVC Conduit shall be measured as one unit.
S&F TP&N Vertical Loadline distribution board, 4 Way, Double door, sheet steel, phosphatised, powder coated with bus-bar 200Amp, neutral link, earth bar and din rail ,blanking Plates, cable ties for cable management, 440 V, complete all as specified including fitting suitable MCBs with connections complete all as specified and as directed. Note : MCB /MCCB, DBs shall be of same make and measured and paid seperately under respective items of Sch A. DB shall be fixed in flush pattern by cutting the wall and making good disturbed surface all as directed.
S&F powder coated CRCA steel sheet MCB distrbution board, IP-43 IK-09 protection, double door recess mounted, triple pole and neutral 4 way with 100 Amps rated copper bus bar, type complete all as specified and as directed.
S&F in repair MCCB 4 pole 415 Volts thermal magnetic based adjustable type 160 Amp, with breaking capacity 25kA Complete all as spccified and as directed.
S&F in repair MCCB 4 pole 415 Volts thermal magnetic based adjustable type 125 Amp, with breaking capacity 16kA Complete all as spccified and as directed.
S&F in repair MCCB 4 pole 415 Volts thermal magnetic based adjustable type 100 Amp, with breaking capacity 16kA Complete all as spccified and as directed.
M&L for point wiring with 1.5 Sqmm (nominal area) FRLS PVC insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core, in universal colour code with & including suitable size of rigid non-metallic PVC conduit (not less then 20mm dia) and its all accessories complete concealed in wall/roof including cutting & chases (making good all to the disturbed surfaces as per existing) including with modular flush metal boxes with modular cover plates & frame for mounting modular switches, sockets, regulators etc or including sunk cast iron/pressed steel/terminal box for mounting flush type switches/sockets etc with 3mm thick phenolic laminated sheet covers and including earth wire of PVC insulated (FRLS) copper conductor multistranded of 1.5 Sqmm size in green colour complete all as specified for followings:-
One light/fan point controlled by one way modular switch 5 amp complete all as specified and as directed.
One 3 pin 5 Amps socket point controlled by one way modular switch 5 amp on same board complete all as specified and as directed.
One 3 pin 5 Amps socket point controlled by one way modular switch on independent board complete all as specified and as directed.
One bell point controlled by one push button on independent board complete all as specified and as directed.
One light point controlled by two way switchs complete all as specified and as directed.
All as per item No. 12.00 here-in-above but for 3/5 pin 16 Amps socket outlet independent with 4 Sqmm PVC unsheathed (FRLS) copper conductor cable complete all as specified and as directed .
S&F Modular switch single pole one-way, 6 Amps 1 Module complete all as specified and as directed.
S&F Modular bell push single pole one-way, 6 Amps 1 Module with indicator complete all as specified and as directed.
S&F Modular switch single pole one-way, 16 Amps 1 Module complete all as specified and as directed.
S&F Modular fan Regulator electronic step type 1 Module complete all as specified and as directed.
S&F modular socket 2-in-1, 5 Pins, 6 Amps combined 2 module complete all as specified and as directed.
S&F modular socket 2-in-1, 3 and 5 Pins, 6/16 Amps combined 2 module complete all as specified and as directed.
S&F Modular switch single pole Two-way, 6 Amps 1 Module complete all as specified and as directed.
S&F in repair switch piano type, SP, one way, flush type 5 Amps complete all as specified and as directed.
S&F in repair socket out let 2-in-1 flush type 5 pin 5 Amp complete all as specified and as directed.
S&F in repair socket out let 2-in-1 flush type 3 pin 5 & 15 Amp complete all as specified and as directed.
S&F in repair switch piano flush type 15 Amp, SP, 240 volt, one way complete all as specified and as directed.
S&F in repair bell push siwtch piano flush type, SP, one way, 5 Amps complete all as specified and as directed.
S&F in repair ceiling rose surface bakelite 65mm x 50mm three terminals complete all as specified and as directed.
S&F in repair lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings complete all as specified and as directed.
S&F in repair mini MCB enclosure with one DP MCB 16 Amp, 'C' curve type complete all as specified and as directed.
S&F in repair Bell Ding dong type, 230 Volts including connections complete all as specified and as directed.
S&F in repair step type electronic fan Regulator piano flush type (Switch/socket type as per existing) complete all as specified and as directed.
S&F in repair indoor decorative ultra slim surface/Wall mounted LED batten tube light fitting with 1x 20 watt LED Tube including polycarbonate channel housing & integrated electronic driver,energy efficient, 140V-270 volts,co- related colour temperature (CCT) of 6500K warm white colour complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F in repair indoor decorative ultra slim surface /Wall mounted T5 LED batten tube light fitting 1X9 watt LED Tube fitting (size within 600x25x40 mm) suitable for mirror light with polycarbonate channel housing & integrated electronic driver,energy efficient, 140V-270 volts,co- related colour temperature (CCT) of 6500K,>100Lm/Watt complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F in repair surface mounted LED Bulk Head light fitting of capacity 10 Watt complete with all accessories and connection complete all as specified and as directed.
S&F LED 9W suitable for B-22 type holder, warm white/cool white/natural white complete all as specified and as directed.
S&F LED 7W suitable for E-14 type holder, warm white/cool white/natural white complete all as specified and as directed.
S&F in repair 30W LED building security light fitting with lens & driver, powder coated pressure die cast aluminium, top opening and maintainable with heat resistance toughened glass, built-in Short-Circuit Protection, Over voltage Protection and Surge Protection, IP-65 proction with luminaire efficiecy of greater than 80Lumen/Watt, Colour rendering (CRI) of ≥ 70 and co- related colour temperature (CCT) of 5700K (±500K) . The luminaire should have 10 KV surg protection, PF ≥ 0.9 and total harmonic distortion of THD ≤ 10%, voltage range of 140-280V including all connections complete all as specified and as directed.
S&F recess type, 36/34 watt LED panel light (600x600 mm) complete with fittings integrated electronic driver,energy efficient, 230 volts,co- related colour temperature (CCT) of 6500K, natural white complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F in repair indoor wall mounted fitting, brushed nickel finish fixture with opal glass diffuser, with LED retrofit bulb of capacity 09 watts complete all as specified and as directed.
S&F Post top LED light fitting 30 Watt IP-65 rated complete all as specified and as directed. Make : Surya Cat Part No SLE PT 30W-ETPP.
S&F in repair LED Round/square recess mounted slim down lighter 12 watt, integrated electronic driver, co- related colour temperature (CCT) of 6500K, warm white/ cool white/natural white complete all as specified and as directed.
S&F in repair LED Round/square recess mounted slim down lighter 18 watt, integrated electronic driver, co- related colour temperature (CCT) of 6500K, warm white/ cool white/natural white complete all as specified and as directed.
S&F in repair building security light bracket made out of 40mm dia medium grade GI pipe of 1.2 m length bent to required shape suitable for fixing street light fitting on Steel tubular pole including two Nos clamps made out 40mm X 6mm flat with suitable nuts and bolts including applying two coats of aluminium paint over a coating of red oxide primer complete all as specified and as directed.
S&F in repair MCB distribution board, SPN 12 Way, Double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail , cable ties for cable management, 240 V, complete all as specified and as directed.
S&F in repair MCB distribution board, SPN 8 Way, Double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail , cable ties for cable management, 240 V, complete all as specified and as directed.
S&F in repair MCB distribution board, SPN 4 Way, Double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail , cable ties for cable management, 240 V, complete all as specified and as directed.
S&F MCB SPN 63 Amps, 'C' series , breaking capacity10KA, 240V complete all as specified and as directed.
S&F MCB SPN 40 Amps, 'C' series, breaking capacity 10KA, 240V complete all as specified and as directed.
S&F MCB SPN 6-32 Amps, 'C' series , breaking capacity 10KA, 240V complete all as specified and as directed.
S&F MCB SP 6-32 Amps, 'C' series , breaking capacity 10KA, 240V including complete all as specified and as directed.
S&F SP enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp complete all as specified and as directed.
S&F in repair metal clad SPN plug top 20 Amp for fixing on AC Box complete all as specified and as directed.
S&F in repair Modular MCB DP 16 Amp, 'C' series, 240 Volt complete all as specified and as directed.
S&F in repair Plastic Surface mounting box 1/2 module gang box for mounting switches, sockets, fan regulator etc complete all as specified and as directed.
S&F in repair Plastic Surface mounting box 3/4 module gang box for mounting switches, sockets, fan regulator etc complete all as specified and as directed.
S&F in repair Plastic Surface mounting box 6/8 module gang box for mounting switches, sockets, fan regulator etc complete all as specified and directed.
S&F in repair 3 mm thick laminated mica sheet top cover suitable for switch board 3 way to 6 way including removing & re-fixing of existing switch / socket and connection complete all as specified and as directed. Note :- Switch/socket/regulator etc required to be replaced shall be measured & Paid separately under relevent item of BOQ.
S&F in repair 3 mm thick laminated mica sheet top cover suitable for switch board 8 way to 12 way including removing & re-fixing of existing switch / socket and connection complete all as specified and as directed. Note :- Switch/socket/regulator etc reqiored to be replaced shall be measured & Paid separately under relevent item of BOQ.
S&F Modular metal flush box 1/2 Module complete all as specified and as directed.
S&F Modular metal flush box 3 Module complete all as specified and as directed.
S&F Modular metal flush box 4 Module complete all as specified and as directed.
S&F Modular metal flush box 6 Module complete all as specified and as directed.
S&F Modular metal flush box 8 Module complete all as specified and as directed.
S&F modular white cover plate with frame, 1/2 module complete all as specified and as directed.
S&F modular white cover plate with frame, 3 module complete all as specified and as directed.
S&F modular white cover plate with frame, 4 module complete all as specified and as directed.
S&F modular white cover plate with frame, 6 module complete all as specified and as directed.
S&F modular white cover plate with frame, 8 module complete all as specified and as directed.
M&L for point wiring with 1.5 Sqmm (nominal area) PVC insulated, unsheathed, (FRLS) 1100 Volts grade copper conductor cable single core, drawn through and including PVC Casing and Caping and its all accessories of suitable size on wall/roof surfaces ( making good all to the disturbed surfaces as per existing) including one run of 1.5 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing including gang box for fixing switches, sockets, fan regulators etc complete all as specified and as directed for the following:-
One light point/fan point/bell point controlled by one switch.
One 3 pin 5 Amps socket point controlled by one way switch on same board.
One 3 pin 5 Amps socket point controlled by one switch on independent board.
All as per item No. 68 here-in-before but with 4.0 Sqmm for 3 pin 15 Amps socket point controlled by one switch on independent board and 4.0 Sqmm copper conductor green in colour as earth continuity conductor complete all as specified and as directed.
S&F switch piano flush type 5 Amps, SP, one way complete all as specified and as directed.
S&F socket out let flush type 2-in-1, 5 pin 5 Amp complete all as specified and as directed.
S&F socket out let flush type 2-in-1, 3 pin 5/15 Amp complete all as specified and as directed
S&F switch piano flush type 15 Amp, SP, 240 volt, one way complete all as specified and as directed.
S&F piano flsh type electronic step type fan regulator complete all as specified and as directed.
S&F in repair modular switch 6 Amps, SP, one way, 1 Module complete all as specified and as directed.
S&F in repair modular switch 16 Amps, SP, one way, 1 Module complete all as specified and as directed.
S&F in repair modular fan regulator electronic step type complete all as specified and as directed.
S&F in repair modular socket 2-in-1, 5 pin 6 Amp combined 2 module complete all as specified and as directed.
S&F in repair modular socket 2-in-1, 5 pin 6/16 Amp, combined 2 module complete all as specified and as directed.
Supply and fix SP enclosure modular type with a two pin and earth plug and socket complete with Single Pole MCB of rating 20 Amps, 240 volts complete all as specified and as directed.
S&F in repair SP enclosure modular type with a two pin and earth plug and socket complete with Single Pole MCB of rating 16 Amps, 240 volts complete all as specified and as directed.
Taking down carefully service connection of any type complete all as and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide for laying of cables etc and getting out complete all as specified and as directed.
All as per item serial No 83 here in before but depth exc 1.5m but not exe 3.00mm complete all as specified and as directed.
Removal of excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed.
Returning, filling in including spreading, levelling,watering and well ramming excavated soil in layers not exceeding 25 cm thick each after cables have been laid and tested complete all as specified and as directed.
Supply, laying, jointing and testing of XLPE insulated, sheathed, armoured, heavy duty LT 1100 volts grade cable with aluminium conductor laid in trenches/duct/fixing on walls/poles or passing through HDPE double wall corrugated pipe (outer dia should not be less then 40 mm) including connecting with suitable lugs, glands, nuts and bolts in existing Panel from pole/Main Panel Box and testing complete all as specified and as directed of following sizes :- Note:- (i) HDPE pipe rate shall deemed to be included in quoted rate. (ii) Excavation and earth work shall be measured and paid separatly under appropriate item(s) of this Schedule
10 sqmm 2 core.
10 sqmm 4 core.
16 sqmm 4 core.
25 sqmm 4 core.
S&F in repair LED Bollard light fitting IP-65 rated flare fitted with low glare diffuser 10 watt with PC diffuser, made up of MS pipe and integrated driver energy efficient complete with all accessories and connection internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed.
S&F 70W LED midbay light fitting with wide beam optics & driver, aluminium PDC housing built in short-circuit protectiion, over voltage protection and Surge Protection, IP-65 protection suitable for ceiling mount (surface/suspended) including all connections and fixtures complete all as specified.
Material and labour for Earthing complete with GI earth plate 600mm x 600mm x 6 mm thick electrode buried directly in ground (earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level connected to GI wire 4.0 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES schedule Part-I and incl 15 mm bore light grade GI protection pipe (upto 7.5 metres beyond outer edge of earth pit) PCC M-10 grade (Nominal Mix) using 40mm graded stone aggregate in pit with 40mm thick RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced with 8mm dia bar both way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, common salt and chaarcoal filling, necessary excavation and earth work complete all as specified and as directed.
Supply and fixing in repair/replacement of unserviceable power pack unit capacity 40 AH, input power supply 220 Volt, 50 Hz AC and output supply 24 V DC suitable for VCB Rating upto 630 Amp complete all as specified and as directed.
Supply and fixing cable tray suitable for supporting and carrying out LT cable upto transformer of size upto 240sqmm complete all as specified and as directed.
Supply and laying electrical insulation rubber mating as per ISI and size 1mx2mx25mm thick complete all as specified and as directed.
Supply, and laying electrical insulation rubber mating as per ISI and size 1mx2mx20mm thick complete all as specified and as directed.
Supply and fixing and laying in replacement 1100 volts grade heavy duty copper control cable PVC insulated armoured stranded of sizes 2.5 sqmm 2 core complete in duct/ceiling/roof with proper clamping etc complete all as specified and as directed.
Supply, fixing laying in replacement 1100 volts grade heavy duty copper control cable PVC insulated armoured stranded of sizes 2.5 sqmm 4 core complete in duct/ceiling/roof with proper clamping etc complete all as specified and as directed.
Supply, fixing and laying in replacement 1100 volts grade heavy duty copper control cable PVC insulated stranded of sizes 2.5 sqmm 8 core complete in duct/ceiling/roof with proper clamping etc complete all as specified and as directed.
Supply and fixing Over current and earth fault protection relay, Vx=24 -240 V AC/24-250 V DC,In=1A/5A(0,1In-40In), Ion=1 A/5A(0,01Ion-2Lon) after disconnected of electric supply to VCB complete all as specified and as directed. Note:- Fixing and clabiration of protection relay shall be carried out through O.E.M of manufacturer's engineer/technician only .
M&L for dismantaling of old/unserviceable PCC poles/struts any type and size complete all as specified and as directed.
Supply and erecting steel tubular swaged pole with cast iron base plate, finial taper plug, bolts, nuts & washers as per IS 2713 (Part-II) 1980 made out of mild steel tubing, type 410 SP-55 (11.00 metre long) including marking pole No on pole including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of red and white colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height complete all as specified and as directed. Note : Earth work and PCC in foundation shall be measured separately.
Supply and erecting steel tubular swaged pole with cast iron base plate, finial taper plug, bolts, nuts & washers made out of mild steel tubing, type 410 SP -31 (9 Mtr long) including marking pole No on pole including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of red and white colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height complete all as specified and as directed. Note : Earth work and PCC in foundation shall be measured separately.
M&L for cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) as in foundations filling and mass concrete complete all as specified and as directed.
M&L for cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) as in foundations filling and mass concrete complete all as specified and as directed.
M&L for cement concrete 1:2:4 type B1 (using 20mm graded stone aggregate) as in coping complete all as specified and as directed.
Material and labour for Earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not than 1.5mtr below normal ground level connected to GI earth strip of size 32x6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, PGI funnel, wire mesh and 20mm bore GI water pipe medium grade and 40mm bore medium grade GI pipe for protection of earth strip from plate to main LT panel/pole/Electrical equiptment, common salt, charcoal dust including testing on completion and all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost complete all as specified and as directed.
M&L for chemical earthing in replacement with copper earth plate electrode 90 cm X 60 cm X 5 mm buried directly in ground (earth pit not less than 3.0 mtr deep beliow ground level) with top edge of the plate not less than 2.25 mtrs below normal ground level,connecting to copper strip 32 X6 mm as earthing strip by means of bolts, nut check nut and washers protected with and including 40 mm dia medium grade GI pipe, necessary excavation and earth work, magnesium sulphate (80 Kg) ), charcoal (2 Qtl) and common salt (4 Qtl) filling, watering arrangement with 20 mm GI pipe medium grade including PCC pit with pre cast RCC (1:2:4) cover, GI funnel with test point, testing (all as shown in electrical plate No 5 and commissioning all as specified and as directed. Note : On testing, after completion, if the earth resistance below 1 Ohms is not obtained, earthing will rejuvenated at no extra cost till the desired earth resistance is obtined.
M&L for replacement of any type/sizeTest point terminal block made of Gun Metal or Phosphorous bronze size 75 x 75 x 25 mm drilled & screwed incl 3 Nos, 8mm dia, 25mm long Hexagonal head Screw complete all as specified and as directed.
Supply and fix in replacement of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25X4 mm galvanised iron strip complete all as specified and as directed.
Supply and fixing HDPE pit cover in replacement of old unserviceable Iron/HDPE pit cover complete all as specified and as directed.
S & F porcelain insulators with fixing on floor/walls/roof etc by grouting by nuts,bolts,washers,screws etc complete all as specified and as directed.
Supplying, installing, testing and commissioning OUT door type HT Bus bar chamber, suitable for 11KV,50 Hz AC Supply made out of MS sheet of 3.15mm thickness for outer sheet and CPRI approved, factory made in an approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns provided with suitable gasket to make it dust / vermin proof double door type including locking arrangement bus bar chamber enclosed complete having legs 45 cms made out of 65X65X6 mm angle iron grouted on PCC (1:3:6) type C-2 foundation upto 30cm above the ground level comprising the followings:- (a) 650mmx50mmx10mm (03 No's)aluminium bush bar with heat shinkable sleeves, duty colour coded. (b) Bakelite insulators having short circuit with stand capacity of 26.3 kilo Amp-01 (Set of three) Note:- (i) The panel shall be front operated with cable entry from bottom with cable glands. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the main feeder pillar. (ii) width of feeder pillar pillar box shall not be less than the panel not less than 60 cm.(iii) Cost for construction of plateform for panel of PCC 1:3:6 type C-2 including plaster work,PCC copping 1:2:4 (40 mm thick stone aggerate), deemed to be included in the item rate and no extra payment will be made.(iv) Danger Sign Board of 11000 KV should be enclosed on panel with red colour.
M&L for GI strip of size 32x6mm as earth continuity conductor burried in ground or drawn in pipe or fixed to wall on saddle complete all as specified and as directed.
M&L for earth continuity conductor galvanised iron wire 4 mm dia complete all as specified and as directed.
Supply and fixing GI funnel complete with wire mesh for earthing water pipe complete all as specified and as directed.
M&L for earth pit cover of size 450x450x50mm thick of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape complete all as specified and as directed.
S&F Pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as per IS 15965: 2012 in roof covering/cladding to wall/fencing, fixed with self tapping screws complete all as specified and as directed.
M&L for framed work as in MS sheet section,hinges, angle iron etc complete confirming to Fe-410-O or Fe 310-0 complete all as specified and as directed.
M&L for painting and minor repair to LT panels including welding work/repair to door/ hinge etc as required at site complete all as specified and as directed.
S&F in repair 20 mm dia Gun metal, globe or gate valves,with iron wheel head,screwed both ends for iron pipes and fixed complete all as specified and as directed.
S&F in repair 15 mm dia Gun metal, globe or gate valves,with iron wheel head,screwed both ends for iron pipes and fixed complete all as specified and as directed.
Taking up or down 15 mm bore steel tubing and connections including cleaning for refixing complete all as specified and as directed.
Taking up or down 20 mm bore steel tubing and connections including cleaning for refixing complete all as specified and as directed.
S&F in repair bib cock cast copper alloy, chromium plated, fancy type with capstan head, screwed down, screwed for 15 mm bore dia pipes or union complete all as specified and as directed.
Supplying & fixing steel tubing ,galvanised, medium grade 15 mm bore with all fittings and fixed complete to walls and ceiling or laid under floor complete all as specified and as directed.
Supplying & fixing steel tubing ,galvanised, medium grade 20 mm bore with all fittings and fixed complete to walls and ceiling or laid under floor complete all as specified and as directed.
M&L for glow sign boards for E/M installtions made up of retroreflective material (blue colour) fixed on stainless sheet of size 1.5 mtr x 1.0 x 3 mm including mounting arrangement with stainless steel pipe of 20 mm for board beadings and 40 mm size for vertical erection of length 2.5 mtrs including connected civil work like digging foundations, PCC etc required for vertical erection of sign board and writing the letters on sign board in white complete all as specified and as directed.
Supply & Fixing Heat shrinkable PVC sleeve suitable for XLPE LT UG cable fo following sizes complete all as specified and as directed.
M&L for preparation of old steel surfaces of any description, not otherwise described. over 10 cm width or girth, and applying one coats of synthetic enamel paint complete all as specified and as directed. Note:- The tools like ladders etc for painting of pole structures at MRS upto height 11 metre sheet be included in quoted rate.
Supply and fixing pin type insulator suitable for 11 KV, procelain vitreous white, brown or green of size 150 mm height and 150 mm dia, ISI marked including one galvanised steel spindle, two galvanised iron washers and one galvanised iron nut complete all as specified and as directed.
Supply and fixing in replacement of unserviceable 11 KV CT, 3 Phase, 50 HZ, Epoxy cast, 200-100/5A ratio, burden 15 KVA, class-1.0 rated current 630 Amp complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV grade (Earthed) cable for outdoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of 95 sq mm,outdoor complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV grade (Earthed) cable for outdoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of 120 sq mm, outdoor complete all as specified and as directed.
M&L for carrying out calibration of Air Circuit Breaker 630 Amp to 1000 Amps,over fault relay,earth fault relay,checking of alignment of ACB isolating contacts,servicing of electronic operating mechanism including tripping and closing system of the breakers,dehydrating,decorbonising of panel,bus section & circuit section. Removing perished monoplus compound cleaning and re-insulating with LT taps wherever necessary ,also supply and fixing Outdoor/indoor type ACB mounting panel conopy as per suitable size 2.00 mm thick CRCA sheet ,front and back opening and locking arrangement of ACB mechanism,with fixing arrangement at foundation and including replacement of burnt out/defective spares like tension springs,tortion springs,nut bolts,washers of suitable size,lingers etc,underthe supervision of authorised dealer/representative,and refixing the ACB breaker in its original position and testing entire satisfaction of Engineer-in-charge.
Supply and fix in replacement LT heavy duty 4 pole OFF load change over break switch ,415 volts 50 hz complete with handle assembly having door interlock and pad locking arrangement in sheet steel enclosure. of 400 Amps, incl electric connections to the extg cables complete all as specified and as directed.
Supply and Fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and as directed.
Supply and Fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and as directed.
Supply and Fixing notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures in signal red colour and fixed with M.S. clamps/wire and nuts/bolts for hanging at working VCB/RMU/HT Panel etc of approved size, for HT, 25x20cm size complete all as specified and as directed.
Ms Kamal Kant Agarwal
m/s meetu enterprises
JWALA ELECTRIC CONTRACTORS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .