Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | I₹61,650Accepted-Finance | I | Accepted-Finance Accept | |
| 2 | II₹63,500Rejected-Finance | II | Rejected-Finance REJECT | |
| 3 | III₹66,000Rejected-Finance | III | Rejected-Finance REJECT |
Tender Value
Refer Docs
EMD Value
₹1,000
Closing Date
3 May 2021, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE
132 KV S/S Bharua Sumerpur
Work OF MAJOR OVERHAULING AND REPAIRING OF 33 KV VACUUM CIRCUIT BREAKERS AT DIFFERENT 132 KV SUBSTATIONS AND 145 KV BREAKER OF 132 KV BANDA-BHARUA LINE UNDER ETD HAMIRPUR
2021_UPTCL_581189_1
TS-02/ETD(H)/2021-22
Open Tender
Electrical Works
Lump-sum
90 days
132 KV S/S Bharua Sumerpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹118
Yes
Executive Engineer
₹1,000
Yes
4 May 2021
9 Apr 2021
4 May 2021
9 Apr 2021
3 May 2021
9 Apr 2021
90 days
Amount
Details of Work.
Major overhauling and repairing of following 33 KV VCB type circuit breaker at 132 KV Substations under ETD Hamirpur:-
(A) 33 KV VCB ABB Make of LV side of 63 MVA T/F-I (B) 33 KV VCB CGL Make of Bharwara feeder at 132 KV S/S Panwari. (C) 33 KV VCB Shreem Make of Muskara feeder 132 KV S/S Rath (1) By doing following work in each circuit breaker :- (i) Cleaning of porcelain of drive insulator and porcelain of vacuum interrupter outside of each pole. (ii) Checking & adjustement of snatch gap, travel of drive insulator rod & tie rod of each pole. (iii) Opening, repairing of mechanism by welding, drilling, machning and filling of material as per requirement and proper fitting of it in breaker cubicle. (iv) Oiling & greasing of crank gears by opening of lock circlip etc (v) Replacement of worn out parts such as bush, rings, lock pins and latch etc. (vi) Checking & adjustment of oil daspot of breaker for its damping action. (2) After major overhauling and repairing of above VCB, following tests are to be carried out :- (i) Opening & closing time of breaker of each pole. (ii) Checking of megger values of breaker poles. (iii) Checking the CLOSE/OPEN operation of breaker from REMOTE & LOCAL. (iv) Prepare and submit the site ovehauling report of each breaker.
Gas leakage has been detected from Gas Density Monitor of 145 KV ABB Make, Sr. No. 17001719, Mgf. Year - 2007 of 132 KV Banda-Bharua Sumerpur line. This monitor will be repaired to stop Sf-6 gas wastage by distmantling the monitor from breaker pole and shorting the connect of gas supervision relay for tripping and closing. Replacing the 02 Nos. special flat O-rings of monitor with new one and applying hot soldering at adjoining area of nozzle of monitor. Checking the leakage from monitor by applying high presor air for checking lose of air for 48 Hrs. After checking, purging the monitor nozzle with Sf-6 gas and connect the monitor at pole and making all necessary connections and checking the operation of breaker and pressure of Sf-6 gas for 12 Hrs.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
N D ASSOCIATES
MAXWEL ELECTRICALS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .