| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.9 LAccepted-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹25.1 L+₹2.2 L (9.61%)Rejected-AOC | L2 | Rejected-AOC Not lowest bidder. | |
| 3 | L3₹26.3 L+₹3.4 L (15.0%)Rejected-AOC | L3 | Rejected-AOC Not lowest bidder. | |
| 4 | L4₹28.9 L+₹6.0 L (26.1%)Rejected-AOC | L4 | Rejected-AOC Not lowest bidder. | |
| 5 | L5₹29.8 L+₹6.9 L (30.0%)Rejected-AOC GROUND BALURGHAT COMPOUND NEAR TRIPURA ROAD KHANAPARA ROAD GUWAHATI KAMRUP METROPOLITAN ASSAM 781029 | KAMRUP METRO | ASSAM | 781029 | L5 | Rejected-AOC Not lowest bidder. |
Tender Value
₹29.1 L
EMD Value
₹58,300
Closing Date
17 Jun 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE BIKANER
HQ CWE Bikaner, Bikaner Military Station
Provn of HT Capacitor Bank at KLP and Udasar Power House at Mil Stn Bikaner under GE (N) Bikaner
2021_MES_444620_1
CWE BKN TOKEN NO 07 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
GE NORTH BIKANER
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE North Bikaner
₹58,300
Yes
27 Jul 2021
21 May 2021
19 Jun 2021
21 May 2021
17 Jun 2021
5 Jun 2021
21 May 2021 - 31 May 2021
60 days
Amount
Supply and fixing HT outdoor type Capacitor unit with Expulsion fuses 643 KVAr at 12.87 KV designed to deliver 500 KVAr at 11 KV, consists of 03 Nos of 1-Ph, external fused capacitor units connected in single star (Y) configuration with & including followings items followings items complete all as specified & directed :- (a) HT 11 KV outdoor type capacitor bank single phase 3 Nos as per IEC 60871:2012 with followings specifications:- (i) HT Capacitor for Power factor improvement. (ii) Supply voltage 11KV (± 10%), Frequency 50 HZ (± 3%). (iii) Ambient Temperature maximum 50 deg C and minimum -5 deg C. (iv) Rated output (installed) 12.87 KV 643.62 KVAR and Rated output (Effective) 11 KV 500 KVAR. (v) No of units per bank – 03. (vi) Structure mounting type. (vii) Power frequency withstand voltage 28 KVrms and Impulse withstand voltage 75 KVpeak. (viii) Capacitor unit - 1 Phase, Rated output - 214.54 KVAR, Rated Voltage 7.43 KV, Rated Current 28.87 Amps, Number of bushing – 02, Losses (in capacitor unit only) – 0.2 Watt/KVAR, All poly propylene dielectric type, Permissible load Voltage 110%, Permissible load Current 130%, Directly connected internal discharge resistor. (ix) Creepage distance – 25 mm/KV. Make of HT Capacitor : ABB / SCHNEIDER / SEIMENS
Serial item No. 1.00 Contd…. (b) 11 KV Outdoor type, Dry Type Aluminum wound Series Reactor 6%, Dry type Aluminum wound (1 set = 3 Nos) with followings specifications:- (i) Inrush current limiting & Harmonic detuning. (ii) Suitable mounting structure. (iii) Non-shielded open execution type. (iv) Rated fundamental current 28.87 Amps. (v) Max permissible continuous current 130% (of rated current). (vi) Short time current (for 2 secs) for winding and terminal 16.66 times of rated current. (vii) Max temp rise of winding over ambient temp 90 deg C. (viii) Class of insulation – Class F. (ix) Insulation level of Power frequency withstand voltage 28 KVrms and Impulse withstand voltage 75 KVpeak. (x) Creepage distance – 25 mm/KV. Make of Reactor : Shrihans/ Quality Power / Mehermangoldt
Serial item No. 1.00 Contd…. (c) 11KV, 3 Phase, 10/1A, Class 1.0 Outdoor Oil cooled (Residual Voltage Transformer) RVT of suitable capacity – 01 No with followings specifications:- (i) RVT for Unbalance Protection. (ii) Supply voltage 11 KV (± 10%), Frequency 50 Hz (± 3%). (iii) Ambient Temperature Max 50 deg C and minimum 5 deg C. (iv) Connection - Star-Star-Open delta (v) No. of cores - 1, Burden 100 VA and accuracy 3 P. (vi) Structure mounting type. (vii) Over voltage factor 1.2 Continuous/1.5 for 30 sec. (viii) Insulation level of Power frequency withstand voltage 28 KVrms and Impulse withstand voltage 75 KVpeak. (ix) Pollution level (Creepage distance) Heavy (25 mm/kV). Make of RVT : Kalpa / Pragati /Reputed
Serial item No. 1.00 Contd…. (d) 11 KV, 400 Amp outdoor structure mounted isolator with manual Earth Switch – 01 No. (e) 9 KV, 10 KA Lightening Arrestor without surge Counter – Set of 3. (f) GI Mounting rack & Inter Connecting Aluminum Busbar for capacitor Bank – 01 Set. (g) GI elevating frames for Capacitor Bank, Reactor, RVT, Isolator and lighting conductor as per OEM specifications and relevant IS. Notes : (i) Scope of this item also include the Design of unit and Routine & Factory Acceptance test as per relevant IS. (ii) The contractor shall produce and get the detailed drawings for mounting structure, connection arrangement and all components of capacitor bank approved from GE before execution of work. (iii) The quoted rates shall deemed to include all allied standard works required to complete the Job. (iv) The minor parts & standard accessories not mentioned above but required to complete the job shall deemed to include in quoted rates. The decision of Accepting Officer in this regard shall be final and binding. (v) Excavation & Earthwork and concrete shall be measured & paid for separately under relevant items of this Schedule.
Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 95 Sqmm, 3 Core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified & as directed. Notes :-(i) Sand cushioning, cable protection, GI protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately.(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, including dismantling & taking out old unserviceable jointing kit, complete all as specified & as directed.
M&L for cement concrete 1:3:6 type C1 using 20mm graded crushed stone aggregate as in copings, pedestal of poles, blocks under MS framed structure and the like including use and waste of form work (straight or curved), all exposed surface of concrete finished even & smooth without using extra cement, complete all as specified & as directed. Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment.
M&L for PCC 1:4:8 type D2 using 40mm graded crushed stone aggregate as in foundations of poles, filling, mass concrete and similar works, complete all as specified and as directed. Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment.
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
All as per serial item No. 6.00 here-in-before but depth exc 1.5m and not exc 3m.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of underground electric cable complete all as specified and as directed. Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
Supplying and laying factory made, un-reinforced precast concrete cable cover, ISI marked, Class HV, Type 1, flat, size 300mm x 180mm x 40mm, laid as cable protection cover in trenches, complete all as specified & as directed.
M&L for Galvanized iron tubing, 80mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of HT electric cable complete all as specified & as directed. Note :- Excavation & earthwork shall be measured & paid for separately.
S&F cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections conforming to Grade E-165 (Fe 290) including nuts, bolts, washers, welding, bending cold or hot, drilled holes for bolts, in any shape or size with & including two coats of aluminium paint over a coat of red oxide zinc chrome primer, complete all as specified & as directed. Notes :- (i) Size, section and shape of steel sections shall be as directed. (ii) Weight of paint shall not be considered for payment purpose and quoted rate shall deemed to be included this aspect.
M/s Chopra Associates
Aman Enterprises
M/S BIKANER CHEMICAL LABORATORIES
M/S SHREE SHYAM TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .