| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.3 LAccepted-AOC | L1 | Accepted-AOC L1 bidder and rates were reasonable | |
| 2 | L2₹17.0 L+₹48,889 (2.97%)Rejected-Finance | L2 | Rejected-Finance HIGHER THEN L1 BIDDER | |
| 3 | L3₹17.3 L+₹82,307 (5.00%)Rejected-Finance NEAR PAYAL CINEMA P O SEVOKE ROAD SILIGURI 734 001 | DARJEELING | WEST BENGAL | 734001 | L3 | Rejected-Finance HIGHER THEN L1 BIDDER | |
| 4 | L4₹17.3 L+₹85,886 (5.22%)Rejected-Finance OPPOSITE GHOOM DRC PO GHOOM DISTT DARJEELING WB PIN 734 102 | DARJEELING | WEST BENGAL | 734102 | L4 | Rejected-Finance HIGHER THEN L1 BIDDER | |
| 5 | L5₹17.4 L+₹91,312.50 (5.54%)Rejected-Finance | L5 | Rejected-Finance HIGHER THEN L1 BIDDER |
Tender Value
₹15.2 L
EMD Value
₹31,000
Closing Date
10 Dec 2021, 6:00 pmClosed
CWE
HQ 136 WORKS ENGINEERS PIN - 914136 C/O 99 APO
REPAIR/ MAINT OF 11 KV INSTALLATIONS, VCBs, DISTRIBUTION SYSTEM AND TRANSFORMERS AT JALAPAHAR UNDER AGE(I) DARJEELING
2021_MES_486601_1
CWE/136-WE/39 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Darjeeling
Class E, Category b(ii)
8 documents required · 8 mandatory
₹500
Yes
AGE (I) Darjeeling
₹31,000
Yes
12 Jan 2022
6 Nov 2021
11 Dec 2021
6 Nov 2021
10 Dec 2021
26 Nov 2021
6 Nov 2021 - 16 Nov 2021
Amount
Material and labour in repair for triple pole, mechanically gang operated air break switch 11KV mounted on 12 nos. insulator and steel frame with operating mechanism worked from ground level, for current rating upto 400 amps with drop out fuse (set of three) complete all as specified and directed.
Servicing / calibration / trouble shooting / repairing / adjustment of over current relay, earth fault relay, Spring, spring charge mechanism, close coil, trip coil, including connected accessories cleaning of all contacts with CTC, of the 11KV HT VCB panel of 630A, 50 Hz by qulified technical personel to make functional in all respects including identifying the deffective parts complete all as specified and directed.
Supply and fixing following spares in repairs suitable for 11KV HT VCB of maximum short circuit current rating 25/26.3 KA 630A/400A after taking down the old spares all as specified and directed.
LED indicating lamps R/Y/B
LED indicating lamps amber
LED indicating lamps white
Trip circuit push button with NO contracts.
Limit switch
Tripping Coil assembly
Closing Coil assembly
Gear Assembly
PT fuse
12NO + 12NC auxiliary Contact
Space heater
Thermostat
HRC control fuse 2A, 4A, 6A 10A
Holding catch assembly
Breaker controler Switch
ON/OFF push button plate assembly
Breeze rectifier
Fuse base with carrier
Test & service Limit switch
Single phase power pack with capacitor backup, 110V DC
Spring Charge motor coil Supply 230V AC
Material and labour for microprocessor based numerical communicable (MODBUS) protection relay without port with the following protection : 50,51,50N,51N,27,59, Type-micop127, complete all as specified and directed. Make Schinder or equivalent model of ABB/ Siemens/ M/s Larsen & Toubro Ltd
Material and labour for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion all as specified and directed.
Material and labour for earthing complete with galvanized copper earth plate electrode 60X60X3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to 20X3mm copper strip as earth lead (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion all as specified and directed.
Disconnecting and removing transformer from mounting platform/structure after disconnecting HT/LT side cable connections, draining out transformer oil for repair/periodical maint of transformer of following capacity all as specified and directed.
50 KVA to 100 KVA
150 KVA to 200 KVA
250 KVA to 350 KVA
400 KVA to 500 KVA
Disconnecting and removing transformer from mounting platform after disconnecting HT/LT side cable connections and transporting of unserviceable transformer for rewinding from MES sub station to contractors/civil workshop and vice versa by arrangement of necessary crane for taking down loading / unloading and refixing at site of following capacity all as specified and directed.
50 KVA to 100 KVA
150 KVA to 200 KVA
Opening the top cover lid and taking out the core with winding by means of Crane/Chain Pulley without any damage to core and winding after disconnecting all internal connection of coil with outgoing/incoming terminals and keeping aside for periodical maint such as cleaning of transformer core and winding, cleaning of oil tank, repair/replacement of unserviceable /Burnt parts of following capacity all as specified and directed.
50 KVA to 100 KVA
150 KVA to 200 KVA
250 KVA to 300 KVA
400 KVA to 500 KVA
Periodical maint of transformer such as cleaning of core and winding by means of washing by hosing down with clean dry oil to remove dust/sludge on core and coil, including cleaning of oil tank to remove sludge deposit, replacement of rusted gasket set, burnt spindle, broken/unserviceable HT and LT ceramic bushing , broken arc horn surge arrester, replacement of silica gel for transformer of following capacity all as specified and directed. Note: (i) Cost of Transformer oil for cleaning by hosing down shall be deemed included in the rate quoted. (ii) Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side and arc horn surge arrester for replacement shall be measured and paid under relevant item
50 KVA to 100 KVA
150 KVA to 200 KVA
250 KVA to 300 KVA
400 KVA to 500 KVA
Re-fixing of transformer core and windings by means of Crane/Chain Pulley without any damage to core/windings including re-filling/ topping up dehydrated new transformer oil after carrying out the maintenance/repair and making internal connection on LT/HT side and re-fixing of top lid cover, installing on mounting platform, making connections with HT/LT feeder and testing on load for transformer of following capacity all as specified and directed. Note: New transformer oil for topping up shall be measured and paid under relevant item. The dielectric strength of the same shall be tested by contractor before filling in transformer.
50 KVA to 100 KVA
150 KVA to 200 KVA
250 KVA to 300 KVA
400 KVA to 500 KVA
Rewinding of transformer of under mentioned capacities by super enameled copper wire as per existing guage of primary coil with `E’ class insulation, varnishing and heating the coil properly, fixing on core and making connection to achieve rated voltage and current of followings all as specified and directed.
50 KVA to 100 KVA
150 KVA to 250 KVA
Rewinding of transformer of under mentioned capacities by super enameled copper wire as per existing guage of secondary coil with `E’ class insulation, varnishing and heating the coil properly, fixing on core and making connection to achieve rated voltage and current of followings all as specified and directed.
50 KVA to 100 KVA
150 KVA to 250 KVA
Supply only brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformer of following capacity all as specified and directed.
63 KVA to 100 KVA
150 KVA to 250 KVA
300 KVA to 500 KVA
Supply only brass spindle for terminal on LT side threaded complete with nut, washers etc of suitable dia for transformer of following capacity all as specified and directed.
50 KVA to 100KVA
150 KVA to 250 KVA
300 KVA to 500 KVA
Supply only ceramic bushing on LT side of transformer of following capacities all as specified and directed. Make : Mysore potteries/BHEL/ Bikaner ceramic's.
Supply only ceramic bushing on HT side of transformer of following capacities all as specified and directed. Make : Mysore potteries/BHEL/ Bikaner ceramic's.
Supply only gasket set for transformer top lid cover, LT and HT terminal bushing suitable for transformer of following capacity all as specified and directed.
50 KVA to 100KVA
150 KVA to 200 KVA
250 KVA to 300 KVA
400KVA to 500 KVA
Supply and fixing for lightning arrestor expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for HT 11 KV power supply distribution line with all fitting for outdoor use, including disconnecting and taking out existing unserviceable lightening arrestor complete all as specified and directed.
Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 35 to 40 KV at 2 mm gap in existing possession of transformer of any capacity and transformer oil for topping up at various sub-station all as specified and directed.
Supply only transformer oil of approved quality having dielectric strength not less than 60 KV, tested in 4.0mm gap, IS marked (Make: Savita/Poweroil) for filling in transformer for topping up all as specified and directed.
Supply, laying & testing in repair XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts Earthed grade, 3 core of cross sectional area 95 sq. mm complete all as specified and directed.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm after cutting out the faulty joint complete all as specified and directed.
Material and labour for pin type, grey polymer insulator in repair including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia suitable for 11000 volts grade complete all as specified and directed.
Material and labour for disc type, grey polymer insulator In repair including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 145mm high and 255mm dia suitable for 11000 volts grade complete all as specified and directed.
Cleaning of 11 KV main receiving station and (Main Power House area) and substations by removing unwated grass/cutting bushes or any unwanted materials all as specified and directed.
Material & labour for sand filling spreading, levelling in layers including watering and consolidation complete all as specified and directed.
Material and labour for spreading and leveling of unbroken river stone aggregate for loose filling of gauge 40mm to 80mm graded complete all as specified and directed.
Supply & laying for electrical rubber mat 1m X 2m (3.0mm thick) suitable for 11 KV grade made of highly electrical resistant elastomer as per IS 15652: 2006 complete all as specified and directed.
Supply & laying for electrical rubber mat 1m X 2m (2.0mm thick) suitable for 3.3 KV grade made of highly electrical resistant elastomer as per IS 15652: 2006 complete all as specified and directed.
Note 1:- (Applicable for all parts/items) : The biidders/contractors are advised to read tender document, all drawings & all corrigendum/amendments and general condition of contracts before entry/quoting the rates. Note 2:- Attention to bidder is hereby invited to upload revised BOQ if published during their bid submission. Uploading of incorrect/ pre-revised BOQ shall be treated as non bonafide and rejected. Note 3:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
SANJAY KAUSHIK
Janata Enterprises
Damdoo Bhutia
SANJAY SAW MILL
S K ENTERPRISES
KAMLESH ENTERPRISE
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .