MMD PRAVEEN NANDIKATTI GE AF SARSAWA
Garrison Engineer (AF) Sarsawa, Distt. Saharanpur (U.P)
SPECIAL REPAIR/REPLACEMENT OF ELECTRICAL FITTINGS AND CONCEALMENT OF WIRING IN MD ACCN AT AF STN SARSAWA
2021_MES_497765_1
8121/SAR-60/E8
Open Tender
Civil Works
Item Rate
183 days
GE(AF) SARSAWA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(AF) SARSAWA
₹68,000
Yes
14 Mar 2022
28 Dec 2021
27 Jan 2022
28 Dec 2021
25 Jan 2022
11 Jan 2022
28 Dec 2021 - 11 Jan 2022
Amount
Taking down carefully copper / aluminium point wiring light / fan, socket or power point complete including fittings such as switches, sockets, ceiling rose, bell push bell buzzer lamp holder bracket etc. removing from site and making good disturbed surface of wall, floor etc. as exists complete all as specified and as directed.
Taking down old us tube light fittings / bulk head fittings / light fittings retrieved complete all as specifed and directed.
M&L for concealed Point wiring with 1.5 Sqmm copper conductor cables (multistranded) FRLS PVC insulated and unsheathed in and including concealed PVC conduit of (ISI marked) 25mm dia for one LIGHT/FAN controlled by one, one way switch including continuous 1.5 Sqmm copper conductor (multistranded) FRLS PVC insulated and unsheathed cable connected to earth dolly complete all as specified conforming to IS-694 including Ms sheet Metal box with earth dolly including 3 mm thick ISI marked, plastic laminated sheet for mounting switches and socket etc all concealed including finishing the disturb plaster surface and painting 2 coat of white wash/ distamper to meet the existing surface complete all as specified and as directed.
All as per item No. 3 here in before but for one 3 pin socket outlet 5 Amps on the same board with other switches.
All as per item No. 3 here in before but for one 3 pin socket outlet 5 Amps independent.
All as per item No. 3 here in before but for one bell point controlled by one switch.
All as per item No. 3 here in before but for Two way point wiring controlled by two way switch
Point wiring with 2.5 Sqmm copper conductor cables (multistranded) FRLS PVC insulated and unsheathed in and including concealed PVC conduit of (ISI marked) 25mm dia for one 5 pin socket outlet 15 Amps independent controlled by one, one way switch including continuous 2.5 Sqmm copper conductor (multistranded) FRLS PVC insulated and unsheathed cable connected to earth dolly including finishing the disturb plaster surface and painting 2 coat of white wash/ distamper to meet the existing surface confirming to IS-694 complete all as specified and as directed.
S&F in replacement of Electronic fan regulator flush type 300-400 Watts switch size having 4 step to regulate/ control speed of ceiling fan complete all as specifed and as directed.
S&F in replacement of piano type switch 1 way 6A complete all as specifed and as directed.
S&F in replacement switch 1 way 16A, Piano Type complete all as specifed and as directed.
S&F in replacement switch 2 way 6A/16A, Piano Type complete all as specifed and as directed.
S&F in replacement socket 6A -5 pin Piano Type complete all as specifed and directed.
S&F in replacement socket 6A /16A- 6pin Piano Type complete all as specifed and directed.
S&F in replacement Ceiling rose, PVC / Polycarbonate 65mm x 50 mm with 3 plate three terminals, ISI Marked complete all as specifed and directed.
S&F in replacement piano type bell push complete all as specifed and directed.
S&F in replacement of bell ding-dong, AC, 230 volts, single pole complete all as specifed and directed.
S&F in replacement of MCB single pole of 6 to 32 Amp capacity, 'B' curve,10KA, 240 volt complete all as specified and directed.
S&F in replacement Double Pole SPN 40 -63 Amp 10KA ,240v ac complete all as specified & Directed..
S&F in replacement of Sheet metal enclosure factory made shutter type double door 8 way SPN distribution board (when MCBs are to be used) , 240 Volts, with 200 Amp rated busbar, IP 43/IK09 (MCBs are to be measured & paid separately) complete all as specified and directed.
S&F in replacement of sheet metal enclosure VTPN DB Double door 4 way made out of CRCA sheets 1.6 mm thick, phosphatised powder coated with copper Bus Bar 200 Amps, 415 V, Earth Stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box ,ground terminal blocks ,duly prewired with thimbled flame retardant copper conductors and poly layer for protection complete all as specified and directed. (Note:- Single Phase MCBs & incomer MCCB are to be measured and paid for seperately)
S&F MCCB 415 V 100Amp ,16kA 4 pole with fixed thermal and magnetic release complete all as Specifed and directed
S & F in replacement submain wiring with two single core 6 sq mm FRLS PVC insulated, unsheathed, cable 1100V grade heavy duty, copper conductor multistranded, drawn in PVC conduit, medium grade, 25 mm bore having 2mm wall thickness including one single core FRLS PVC insulated copper cable multistranded of size 6 sq mm as earth wire fix to wall etc including finishing the disturb plaster surface and painting 2 coat of white wash/ distamper to meet the existing surface complete all as specified and as directedcomplete all as specified and as directed.
S&F in replacement of enviroment friendly indoor decorative 20 Watt LED polycarbonate Batten with 140V-270V , Driver efficiency more than 80%, lumen 100lm/W, THD<=20, CRI more than 80 , in built surge protection 2.5 kV, colour temperature 6500K , zero mercury content including all accessaries complete all as specified and directed.
S&F in replacement of enviroment friendly indoor decorative 10 Watt LED polycarbonate Batten with voltage range 140V-270V , Driver efficiency more than 80%, lumen 100lm/W, THD<=20, CRI more than 80 , in built surge protection 2.5 kV, colour temperature 6500K , zero mercury content including all accessaries complete all as specified and directed.
S&F in replacement of enviroment friendly inbuilt LED bulkhead fitting 10 Watt with 140V-270V , Driver efficiency more than 80%,850 lm lumen with lumen efficiency 80 lm/W, in built surge protection 2.5 kV, colour temperature 6500K , including all accessaries complete all as specified and directed.
S & F in replacement of Lamp holder bakalite type ISI marked with back plate complete all as specified as directed
S&F 10 watt five star rating LED bulb with B22 Base cap, 1200 lumens ,Colour rating Index 80,colour temp F 6500K,satrtup time less than 2 sec,In built surge 3.0 kV, voltage range 140V to 270 V , Lamp life 15000 hours complete all as specified and directed.
Supply and fixing in repair of Earthing to panel with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead 4.0 sqmm galvanised iron wire by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead shall be protected by GI pipe 15 mm dia medium grade and connected to distribution board including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and as directed.
M & L for Earth continuity conductor or main earthing lead of 4.0 Sqmm galvanized iron wire, buried in ground or fixed to wall complete all as specified and directed..
M&L for Shifting of electric Energy Metrer from existing location to directed location complete all as specifed and directed
S&F in replacement of Energy meter Box Flame retardent polycarbonate body including all fixing arrangement like DIN rails mounting plate connection boxes fastning screw protection plate extra suitable to accomodate single Phase energy meter with locking arragement complete all as specified and directed.
S&F in replacement of single pole and neutral enclosure with 2 pin and earth plug and socket complete with one single pole MCB 20 Amp of same make complete all as specified and as directed.
Supply & fix exhaust fans heavy duty 300mm dia 1400 RPM, 50 Hz 230 volt for domestic use,dynamically balance blade , epoxy powder coated confirm to IS 2312-1967 with ISI marking IP-55 with class B insulation motor including suitable size louver and making arrangement for fixing such as making holes in brick wall/wooden/aluminium windows and making good the disturbed surface and all fixing accessories such as fastners nut bolts and electric connection with 3 core cable complete all as specified and directed.
NAQLI LAL SHARMA AND ARUN SHARMA
sheetal engineering
Sharma Electrical and Engineering Works
SUBHASH CHAND CONTRACTOR
M/S PRABHUKESHVAM (OPC) PRIVATE LIMITED
BRIJ CONSTRUCTIONS
RADHA ENTERPRISES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .