Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹52.6 Cr 15 1516 DLF CORPORATE GREENS TOWER 4 SECTOR 74A GURUGRAM HARYANA 122004 PH NO 91 9810730770 | ₹52.6 Cr |
Tender Value
₹67.9 Cr
EMD Value
₹67.9 L
Closing Date
11 Dec 2024, 11:00 amClosed
Execution of Interior works including furniture, fitout works, cabling and other infrastructure work at Grand Rue, Ayur vigyan Nagar, August Kranti Marg, New Delhi.
NBCC/CPG/GrandRue/AyurvigyanNagar/Delhi/2024/442
NBCC/CPG/GrandRue/AyurvigyanNagar/Delhi/2024/442
Open Tender-Domestic
Civil Works General
New Delhi, Delhi
₹1.2 L
₹67.9 L
20 Nov 2024
20 Nov 2024
11 Dec 2024
11 Dec 2024
1 Jan 2025
Grand Total ( DSR Amount + 67,92,79,937.77
Grand Total 210018433.21
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 1.0 - CONCRETE WORK)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached
pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping,
bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor all level, excluding the cost of
1 centering, shuttering and finishing : 47.00 47.00 cum 8482.00 398654.00
1:5:10 (1 Cement : 5 coarse sand (zone-III): 10 broken AAC 40 mm nominal size). 40 mm nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and
2 4.1.3 shuttering - All work upto plinth level 1:2:4 (1 Cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 10.00 10.00 cum 7878.50 78785.00
mm nominal size)
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using
cement content as per approved design mix, manufactured in fully automatic batching plant and transported to
site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of
specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of
laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in
recommended proportions as per IS : 9103 to accelerate/manufacturer's specifications/ approved design mix
retard setting of concrete, improve workability without impairing strength and durability as per direction of the
Engineer-in-charge.
(Note: Cement content considered in this item is 330 Kg/cum. Excess/less cement used as per design mix is
payable /recoverable separately)
b) All works above plinth level upto floor V level .
5.22A Steel reinforcement for R.C.C. work including straightening, cutting, bending,placing in position and binding
all complete above plinth level.
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500 or more. 5000.00 5000.00 kg 107.85 539250.00
5 Providing and fixing Following fasteners in RCC/ Brick work as per drawings.
MR M24 600 mm long chemical fastener Base plate for Col 12.00 12.00 each 2432.76 29193.00
6 MR M24 300 mm long chemical fastenerFace plates on Col 88.00 88.00 each 1405.00 123640.00
MR M12 mechnical fasteners 250 mm long 40.00 40.00 each 618.00 24720.00
TOTAL SUB HEAD -1 1111055.00 576207.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 3 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: -2.0 - BRICK WORK)
Providing and laying autoclaved aerated cement blocks masonry with 100mm/150mm/200mm/230mm/250mm
thick or as desired size/ thickness AAC blocks conforming to IS 2185 Part 3 (1989) having density in oven dry
condition 551 - 650 Kg/Cum, Grade -I, minimum Compressive strength 4 N/mm2, thermal conductivity in air dry
condition 0.23 W/mK in super structure above plinth level up to all floor level with RCC band at sill level
7 6.47 and lintel level with approved block laying polymer modified adhesive mortar (minimum 3-4mm thick) all 100.00 100.00 cum 8333.65 833365.00
complete as per direction of Engineering-Charge. (The payment of RCC band and reinforcement shall be made
for separately).
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in super
8 6.13.2 structure above plinth including RCC band as required in 250.00 250.00 sqm 1123.80 280950.00
Cement mortar 1:4 (1 Cement : 4 coarse sand)
Extra for providing and placing including drilling where as requred in position 2 Nos. 6 mm dia M.S. bars at
9 6.15 every third course of half brick masonry 250.00 250.00 sqm 104.80 26200.00
TOTAL SUB HEAD -2 1140515.00 0.00
(SH: - 3.0 - WOOD WORK)
Providing factory made wood work in frames of doors, windows, clerestory windows and other frames, wrought
framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length including cut and
10 9.1.1 groove ( hold fast lugs or dash fastener shall be paid for separately). 6.00 6.00 cum 142949.70 857698.00
Natrual class teak wood
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double
threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide PA 6
11 10.27.4 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge. 866.00 866.00 Each 182.20 157785.00
(Size-10x140mm)
Providing and fixing factory made ISI marked 40mm thick flush door shutters with both side of the door
decorative high pressure 1.0 mm thick laminated sheet of plain / wood grain in gloss / matt/ suede finish
with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046
Type S, including cost of adhesive of approved quality of approved shade and colour of approved make
conforming to IS : 2202 (Part I) core of block board construction with frame of 1st class hard wood and well
matched commercial 3 ply veneering with vertical grains or cross bands and face decorative laminate on both
12 MR faces of shutters including lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush 598.00 598.00 sqm 4595.00 2747810.00
door shutters : 40mm thick flush door shutters with both side decorative high pressure 1.0 mm thick laminated
sheet of plain / wood grain in gloss / matt/ suede finish including ISI marked Stainless Steel ball bearing hinges
with necessary ss screws complete with all respect as desired and direction of Engineer in charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 4 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing stainless steel (grade 316) tower bolts ( nominal dia of sliding rod -10mm) of approved
make with necessary screws etc complete.
13 MR In stainless steel satin / polished finish 230.00 230.00 Each 518.70 119301.00
Providing and fixing stainless steel (grade 316) tower bolts ( nominal dia of sliding rod -10mm) of approved
make with necessary screws etc complete.
14 MR In stainless steel satin / polished finish 230.00 230.00 Each 518.70 119301.00
Providing and fixing bright finished 85-100 mm horizontal depth mortise latch and lock with six levers/ Euro
profile double cylinder in stainless steel satin finish and a pair of stainless steel lever handles of approved make
with necessary s.s. screws etc. complete as per direction of Engineer in charge.
Providing and fixing bright finished 85-100 mm horizontal depth mortise latch in stainless steel satin finish with
16 MR one dead bolt and pair of stainless steel (grade 304) lever handles with necessary s.s. screws etc. complete of 30.00 30.00 Each 3625.25 108758.00
approved make with necessary s.s. screws etc. complete as per direction of Engineer in charge.
Providing and fixing Stainless Steel (grade 304) floor door stoppers in stainless steel satin finish (Twin) of
17 MR approved make with necessary ss screws etc. complete as per direction of Engineer in charge. 115.00 115.00 Each 495.40 56971.00
Providing and fixing aluminum extruded section body tubular type universal hydraulic door closer (having brand
logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to
1100 mm), with double speed adjustment with necessary accessories and screws etc. complete. The
manufacturer certificate for Life cycle of the door closer has to be 500000 cycle tested certificate has to be
submitted by agency) .
Providing and fixing wooden moulded beading to door and window frame with iron screws, plugs and priming
19 9.40.1.2 coat on unexposed surface etc. complete.( 2nd class teak wood) 648.00 648.00 metre 271.75 176094.00
50x20mm or 80x12.5mm as desired
Digitally signed by ANUJ
Abstract of Cost (Civil ) 5 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
20 Toilet cubical made up of thermosetting resign treated high pressure, self-supporting 18mm thick decorative
compact laminates board of approved makes with permanently incorporate anti-bacterial agents during
manufacturing. Compact board should be resistance to water immersion through permissible increase on
thickness and mass <0.60% and board density >1.35kg/cm3 and fulfilled the criteria of FSC and green guard
gold certification and manufactured under EN438-2&3:2005 standard. 18mm thick compact board should be
Moisture resistant, Impact resistant, termite resistant ,Scratch resistant ,Weather and climatic shock resistant.
Finish of compact laminates should be suede finish which includes door, pilasters and intermediate panels
finished with approved texture/shades as per IS2046 and fulfilled the criteria of fire retardant under BS-476/97
and EN438-6 with classification of BS1D0 standard. Pilaster to be supported with SS(grade316) adjustable foot
and intermediate panels will attached to the wall with the help of approved SS(grade 316) channels and all
required hardware, made up of stainless steel as per manufacturer’s specification. Door knob, gravity hinges,
Thumb turn locksets with occupancy indicators, coat hooks with door stopper, U channel, top rail with corner
connector, adjustable foot/pedestal, Rubber noise deafening tape, screw & wall plugs should be approved under
the instruction of Engineer-in- charge. The top fitting should consist of SS. All screw will of 304 grade in SS with
stain finish. All pilasters are supported by SS bottom cladding. The base of the stainless steel bottom cladding
will be anchored to the floor with a clearance height upto 150 mm. Finish and colour of Toilet cubical should be
approved under guidance of engineer-in-charge.
Note: Only exposed area of laminated board in sqm shall be measured for payment purpose)
a) MR L-shape panel having door opening 600 mm 86.00 86.00 sqm 13260.00 1140360.00
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door
21 9.23 shutters/ (over all area of door shutter to be measured). 598.00 598.00 sqm 462.35 276485.00
Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall
22 9.24.1 area of door shutter to be measured) rectangular or square: 191.00 191.00 sqm 199.15 38038.00
23 9.26 Extra for cutting rebate in flush door shutters (Total area of the shutter to be measured).: 456.00 456.00 sqm 106.70 48655.00
Providing and fixing in wall partition/lining medium density fibre board IS:14587:1998 marked, Pre-laminated one
side decorative lamination and other side balancing lamination, with necessary fixing arrangement and screws/
Digitally signed by ANUJ
Abstract of Cost (Civil ) 6 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing
and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120
gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm
and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm center to center with dash fastener of
12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48
mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges
of floor and ceiling channel and placed at a spacing of 610mm center to center by 6 mm dia bolts and nuts,
including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal
screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work
by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. .
The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of
99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two
boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish
with recommended jointing compound, jointing tape, angle beads at corner (25 mm x 25 mm x 0.5 mm), joint
finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in
charge all complete.
75 mm overall thickness full height partition with 12.5 mm thick double skin fire rated gypsum board of approved
make conforming to IS: 2095: part I
Dry wall (1) Full height Laminated partation
Supply & fixing (12+6)mm thick BWP board with 1.0mm laminate ( one side decorative lamination and other
side balancing lamination) dry wall double skin Partitions overall thickness 88mm thick upto false ceiling with
6mmx6mm thick groove as per approved design over MS tubular frame section 50mm x 50mmx1.60mm thick
including 50mm thick fiber glass wool insulation board ( 600x1200) wrapped in 200 G virgin polythene bags fixed
26 MR to wall/frame/ board with screw, rawl plug, insulation holders & washers having density 24 kg/ m3 confirming to 1889.00 1889.00 sqm 4286.00 8096254.00
IS: 8183, aluminium channel etc complete in all respect as per detailed drawings and direction Engineer in
charge.(For payment purpose one side area shall be measured .( only MS Frame shall be separately paid under
Dry wall (P2) Low Height partation ( 1200 MM Laminated + Abvoe 300 MM Height 12mm
Supply & fixing (12+6)mm thick BWP board with 1.0mm laminate ( one side decorative lamination and other
side balancing lamination) dry wall double skin Partitions overall thickness 88mm thick Low Height partation
with 6mmx6mm thick groove as per approved design over MS tubular frame section 50mm x 50mmx1.60mm
thick including 50mm thick fiber glass wool insulation board ( 600x1200) wrapped in 200 G virgin polythene
27 MR bags fixed to wall/frame/ board with screw, rawl plug, insulation holders & washers having density 24 kg/ m3 494.00 494.00 sqm 3927.00 1939938.00
confirming to IS: 8183 , 12mm thick toughened clear glass ( 300 height ) partation with aluminum frame, SS
channel, backer rod, silicon etc complete in all respect as per detailed drawings and direction Engineer in
charge. For payment purpose one side area shall be measured .( only MS Frame, glass shall be separately paid
under relevant item)
Digitally signed by ANUJ
Abstract of Cost (Civil ) 7 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing 12 mm thick frameless toughened glass door shutter/ Parations of approved brand and
manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making
28 21.18 necessary holes etc. for fixing required door fittings, all complete as desired and direction of Engineer-in-charge 40.00 40.00 sqm 5325.90 213036.00
(Door handle, lock and stopper etc.to be paid separately).
GLASS PARTATION
Single Glazed 12mm Toughened Glass Partition with dormakaba System 50 Frame Profiles
Supply and Fixing of Single Glazed Glass partition of 12mm Toughened Glass using dormakaba System 50
Frames to a height of maximum 3mtrs or as per drawing.The Fixed glass to be fixed using natural anodised
aluminium sections of size 50mm x 30mm . H Junction profile to be used at all Glass to Glass vertical joints, 90
Deg L Junction Profiles ,T Junction profiles . In case of Glass overall panel Overpanel Profile to be used.
29 MR The Profile shall be natural anodized, the Profile Manufacturer to supply all the necessary clips, seals and fixing 512.00 512.00 sqm 6689 3424768.00
accessories for the system.
All Profiles to be with minimum 1.5mm thickness and 20 microns of Anodizing/ poweder coating System should
meet Environmental product declaration (EPD).
SMART LAMINATED SWITCHABLE GLASS PARTATION
Supply and Fixing of Glass partition of extra clear toughened /heat strenghned Smart Laminated switchable
Glass (2 nos 5mm thick of 120 ppm extra clear toughened /heat strenghned glass + 4 nos 0.38mm thick PVB
interlayer + 1 layer 0.40mm thick smart film layer ) confirming to EN 356 standards. The SGG - Priva Smart
Laminated Glass should be able to confirm to a haze level of less than 6% during ON condition and 99% during
OFF condition. It should be able to provide an acoustic reduction of (RW (C;Ctr)) 36dB. The smart glass
assmebly should be IP68 rated. The Smart Glass system should be able to switch for 3 million cycles (ON/OFF).
(B) Supply and fixing of electrical cables (upto 20m).
The cables should be UL 2464 certified and the connectors should be IP67 certified.
(C) Supply and fixing of power supply units to control the smart glass.
30 MR The power supply units should confirm to electrical safety standard of EN 60335-1, EN 55014-1:2021, EN 61558- 35.10 35.10 sqm 132281 4643063.00
1 .The frame using dormakaba System 50 Frames to a height of maximum 3mtrs or as per drawing.The Fixed
glass to be fixed using natural anodised aluminium sections of size 50mm x 30mm . H Junction profile to be
used at all Glass to Glass vertical joints, 90 Deg L Junction Profiles ,T Junction profiles . In case of Glass overall
panel Overpanel Profile to be used.
All Profiles to be with minimum 1.5mm thickness and 20 microns of Anodizing/ poweder coating System should
meet Environmental product declaration (EPD).
Digitally signed by ANUJ
Abstract of Cost (Civil ) 8 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Single / double Leaf Aluminium Glazed Door of 12mm Toughened Glass with Frame Profiles
Supply & Fixing of Aluminium Glazed Door (Single Leaf) with Glass infill of 12 thk toughened glass with
dormakaba rebate door frame System with frame size 50 x 54mm Aluminium Stile door to be formed out of
70x35mm. Horizontal and Vertical Door Profile frame with clips & seals including Door Hardware - Flush
Hinges (4 Nos), Pure 8906 Lever Handle with 952 Narrow stile Lock package and dormakaba TS70 Slide Arm
Door closer with Hold Open unit complete with all respec as desired. Necessary seals to be provided all around
the door frames. The profiles shall be suitable for Glass thickness of 12mm. The Profile shall be matt natural
anodized finish, the Profile Manufacturer to supply all the necessary clips, seals and fixing accessories for the
All Profiles to be with minimum 1.5 mm Gauge thickness and 20 Micron of Anodizing.
Providing and fixing stainless steel handle H type ( grade 316 ) of approved make fixed with SS screws etc.
32 MR complete as per direction of Engineer-in-charge. 18.00 18.00 each 3249.00 58482.00
450mm @ 25 mm dia
Providing and fixing stainless steel grade 304 corner lock, strike plate and Euro Profile Cylinder of approved
33 MR make in glass door shutters etc with necessary accessories/screws etc. complete as per the directions of 18.00 18.00 Each 4644.00 83592.00
Engineer-in-charge.
TOTAL SUB HEAD -3
Digitally signed by ANUJ
Abstract of Cost (Civil ) 9 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 4.0 - STEEL WORK)
AR over Structural steel (grade 350) work riveted, bolted or welded in built up sections, trusses and framed
34 DSR Item work,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all 16740.00 16740.00 Kg 140.55 2352855.00
10.2 complete.
AR over Steel work (grade 350) in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including
DSR Item cutting, hoisting,fiXing in position and applying a priming coat of approved steelprimer, including welding and 18790.00 18790.00 Kg 201.25 3781541.00
10.16 bolted with special shaped washers etc. complete.
Electric resistance or induction butt welded tubes
AR over Providing and fixing M20 grade 8.8 bolts including nuts and washers complete as per drawing
10.25 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a
priming coat of approved steel primer using structural steel etc. as required.
10.25.1 In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete
Supply & erection of Metal decking sheet as floor / roof decking with a crest height of 76 mm at a pitch distance
of 295 mm c/c having a cover width of 885 mm and with special emboss marks rolled into the profile for creating
bonding between concrete and steel decking. The steel feed material should of metal thickness of 1.20 mm
(including thickness of coating and galvanizing) galvanized to grade 180 (minimum) as per IS 277 of minimum
yield strength of 250 MPA of drawing grade as per IS:513, colour coated with total min. coating thickness of 30
38 MR microns (nominal) comprising of Regular modified polyester (RMP) paint of 16-20 microns (nominal) DFT on one 165.00 165.00 sqm 2773.00 457545.00
side over 5 microns (nominal) primer coat and 5 micron (nominal) primer coat on back surface, and of approved
profile, sectional properties (suitable for the specified loading/ deflection and purlins / runner spacing), colour and
shade, at all levels, including all labour, materials, handling, transportation, fasteners (including shear studs dia
19mm, length 125mm), scaffolding, equipment, end and side laps, cutting of openings, preparation of working
drawings, testing, etc., all complete, as per specifications, drawings and instructions of Engineer-in-Charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 10 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Supplying and applying waterbased Fire intumescent paint, fire tested in accordance with BS 476 Parts 20-
22/UL/ASTM E 119/ISO 834-1 as selected and approved by the Engineer In charge of approved make. Fire
Paint DFT/ Fire Board Thickness dependent on HP/a or W/D or ISO 834-1 ratio of structural steel. Fire Paint to
use zinc phosphate primer to give additional anti-corrosive protection having VS of 73% - 83% as approved
applied over abrasive blasted surface and surface preparation up to a standard of Sa2.5 (ISO 8501-1:1988) or
SSPC-SP6 at 75 micron and GIRIHA/ LEEDV4 /Green Building norms Compliant for VOC Content and VOC
39 Emissions polyurethane finish paint as approved having volume solid of 72% - 73% or water based acrylic finish
@ 50 micron of the required shade over Structural Steel Works at all levels including storage, surface
preparation by sand blasting, degreasing, cleaning, drying, providing temporary staging, scaffolding, testing etc.,
all complete with all respect as desired and as per manufacturer specification and direction of Engineer in
charge. For Fire Proof Boards no surface preparation of any kind required on the steel surface for Fire Proof
Boards .Fire Proof board to have maximum average dry density of 220 Kgs/cubic mt , minimum compressive
strength @10% of 35 KN/sq mt ,
Maximum moisture absorption of 1% by volume, Corrosion and Fungal resistance. Fire Proof Boards to be cut in
desired size and fixed on the beams and columns as per manufacturer installation manual using manufacturer
approved screws and fittings all complete with all respect as desired and as per manufacturer specification and
MR direction of Engineer in charge. 440.00 440.00 sqm 5109.00 2247960.00
The above products should confirm to GIRIHA/ LEEDV4 /Green Building norms. Application to be carried out by
authorized manufacturer applicator or any other trained applicator as approved by the manufacturer and direction
of Engineer in charge.
Providing firefixing
and ratingframe work for partitions/ wall lining etc. made of 50x50x1.6 mm hollow MS tube, placed
along the walls, ceiling and floor in a grid pattern with spacing @ 60 cm centre to centre both ways (vertically &
horizontally) or at required spacing near opening, with necessary welding at junctions and fixing the frame to
wall/ ceiling/ floors with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for
40 9.154 opening for doors, windows, electrical conduits, switch boards etc., including providing with two coats of 28596.00 28596.00 Kg 166.80 4769813.00
approved steel primer etc. complete, all as per direction of Engineer-in-charge..
Digitally signed by ANUJ
Abstract of Cost (Civil ) 11 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 5.0 - FLOORING WORK)
Kota stone slab flooring over 20mm (average) thick base laid over and jointed with grey cement slurry mixed
with pigment to match the shade of the slab including rubbing polishing and groove complete with base of
25 mm thick (Size of stone 1200 mm x 600 mm )
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement
42 11.27 mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade 20.00 50.00 sqm 2354.70 117735.00
of the slabs, including rubbing polishing and groove complete.
Providing and laying modular carpet of approved make and shade and made with 100% solution dyed nylon
6/6.6 tufted textured tip sheared/ cut & loop piles, tiles of minimum 500mm x 500mm in size, stain resistant, anti
microbial, and having colour fastness to water, fastness to light, rubbing fastness and castor chair suitability as
per relevant standard for heavy commercial usage, with Non PVC / Recycled PVC backing, nominal total
thickness of minimum 6.50 mm, pile height minimum 3.4 mm, minimum Total Pile weight – 680gm/sqm).
43 MR Material shall be CRI GREEN LABEL PLUS certified, and shall have recycled content complying to GRIHA 933.00 933.00 sqm 3703.00 3454899.00
requirement, including fixing with GRIHA compliant adhesive of approved make, minimum 15 years
manufacturer's warrantee, all complete as per drawings, manufacturer's specifications and direction of Engineer
Providing and laying full body / homogenous Vitrified tiles of approved make ( Polish / satin Finish/ anti skid/
Matt) in flooring with different sizes ( thickness to be specified by the manufacturer),with water absorption less
than 0.08% and confirming to IS; 15622, of approved brand & manufacturer, in all colours and shade, laid with
44 cement based high polymer modified quick set tile adhesive ( water based ) conforming to IS; 15477 , in average
6-10 mm thickness, including grouting of joints .( payment for grouching of joints to be made separately)
Providing and laying Vitrified tiles of approved make in different sizes (thickness to be specified by the
manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand &
manufacturer, in all colours and shade, in skirting, riser of steps,dado laid with cement based high polymer
45 modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including
grouting of joints .
Polish finish vitrified tile
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having
with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in
for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement
46 16.90 mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement 50.00 50.00 sqm 2017.60 100880.00
mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 12 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing 18mm thick gangsaw cut mirror polished (premoulded and prepolished) machine cut for
kitchen platforms, vanity counters ,window sills , facias and similar locations of required size of approved shade,
colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated
with white cement, mixed with matching pigment, epoxy touch ups, including rubbing,groove making, curing,
47 8.2.2.2 moulding and polishing to edge to give high gloss finish etc. complete at all levels.. 50.00 50.00 sqm 5136.30 256815.00
(Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent as approved)
Granite of any colour and shade (Area of slab over 0.50 sqm)
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity
48 8.5 counter and similar location in marble/ stone work including necessary holes for pillar tabs etc including rubbing 28.00 28.00 Each 978.70 27404.00
& polishing of cut edges etc complete
Providing and fixing machine cut, mirror/ eggshell polished , granite stone work for wall lining (veneer work) ,
dado,cladding, skirting, risers of steps etc., in required design and pattern wherever required, stones of
different finished surface texture, with average 10mm thickness high polymer modified quick set adhesive (white
Based on base) of make Weber of m/s Saint Gobian /Ferrouscrete / MYK Laticrete or equivalent laid and jointed with
DSR-11.27 white cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching
shade, including groove ,rubbing, curing, polishing etc. all complete as per Architectural drawings, and as
directed by the Engineer-in-Charge.( Basic rate of granite stone -1800/- per sqm )
18mm thick Granite in all shade / colour / size (Area of slab over 0.50 sqm) as approved by Engineer in charge.
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand ( Zone III) : 4 graded stone aggregate) finished with a
50 11.3.1 floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 933.00 933.00 sqm 614.20 573049.00
40 mm thick with 20 mm nominal size stone aggregate
Grouting the joints of flooring / Wall tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic
coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and
51 11.48.2 finishing complete as per direction of Engineer-in-charge. 5462.00 5462.00 sqm 309.05 1688031.00
600mm x 600mm/ 300x600 tiles
Providing & fixing in position Phenol bonded Bamboowood in wall skirting with planks of sizes 14mm thick,
1900mm length (minimum) and 85mm wide(minimum), in approved colour, texture and finish, having
Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council
(BMTPC). The skirting shall be fixed with SS screws & rawl plugs, over underlayment of 4mm thick, expanded
52 26.2 polyethylene foam sheets having 40kg/cum density over prepared surface. The bamboowood planks shall have 84.97 84.97 sqm 6033.55 512659.00
minimum density of 1000Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as
per direction of the Engineer in-charge.
Providing and fixing removable raised/false access flooring with system and its components of approved make
for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor
53 panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the
architectural drawings, as specified
and as directed by Engineer-in-charge consisting of :
Digitally signed by ANUJ
Abstract of Cost (Civil ) 13 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness
minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100mm x 100mm x
3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully
threaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto
50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to
the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with
b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80mm thick
having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring
maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the
floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall
provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and
wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in charge.
c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high
pressure Lamination of . Access Floor panel shall be steel welded construction with an enclosed bottom pan with
uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom
0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The
panel should be corrosion resistant epoxy coated for lifetime rust protection and cavity formed by the top and
bottom plate is filled with non combustible Portland cementitious core mixed with lightweight foaming
compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp
technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm. The panel is to
withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the
panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL)
minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification
and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to
ensure the quality of the product.
11.54.2 450 mm Finished Floor Height (FFH). 153.00 153.00 sqm 5977.35 914535.00
Providing & Fixing flexible PVC vinyal sheet sports flooring of approved make in 6.5 mm thickness( minimum ) in
the size of 2mx20-23mtr . Results from independent testing demonstrate that product inherently inhibits the
growth of microbial strain MRSA. It shall be homogeneous in construction. The flooring shall incorporated a
specially formulated polyurethane reinforced to give lifetime polish free maintenance. Imported PVC Vinyl
flooring static electrical charge < 2kv,impact sound reduction approx ,good resistance of scratch, slip, chemical
and fire doesn't favor in growth of fungi & bacteria , Material should 100% recyclable and at least 25% recycled
materials complete with all respect and as per manufacturer specifications & direction of Engineer in charge. .
Digitally signed by ANUJ
Abstract of Cost (Civil ) 14 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 6.0 - ROOFING / FALSE CEILING WORK)
Providing and fixing GI Clip in Metal Ceiling System of approved make of 600x600/ 600x1200 mm module
which includes providing and fixing ‘C’ wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel
along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre,
suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of
soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier
bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made
of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm
centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and
55 12.54.2 spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive),fixing 600.00 600.00 sqm 2354.65 1412790.00
with clip in tiles into spring ‘T’ with :
GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600/600x1200 and 0.5 mm thick
with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20%
perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of
thickness 60 microns (minimum), including factory painted after bending and perforation.
Providing and fixing GI Clip in Metal Ceiling System of approved make of 600x600/ 600x1200 mm module
which includes providing and fixing ‘C’ wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel
along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre,
suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of
soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier
bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made
of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm
centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and
spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive),fixing
with clip in tiles into spring ‘T’ with :
GI Metal Ceiling Clip in plain Beveled/tegular edge global white color tiles of size 600x600/600x1200mm and 0.5
mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and
electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after
Digitally signed by ANUJ
Abstract of Cost (Civil ) 15 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special
sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive)
as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and
37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long
with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with
nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm
running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of
80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in
a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm
long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of
20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm
57 centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section
and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and
finishing to a flush finish of tapered and square edges of the board with recommended jointing compound ,
jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two
coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making
openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed,making
cove & slit etc, all complete as per detailed drawings, specification and direction of the Engineer in Charge but
excluding the cost of painting with :-
12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) : 2011 (Board with BIS
a) 12.45.1 certification marks) of approved make or equivalent as approved). 2040.34 2040.34 sqm 1355.80 2766293.00
b) 12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board. 22.00 22.00 sqm 1529.10 33640.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 16 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Mineral Fiber Anti-microbial false ceiling :
Providing and fixing mineral fibre false ceiling tiles of approved make at all heights of size 595X595mm of
approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light
Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in
true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm
thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size
15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form
grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised @ 80
gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000
mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’.
58 26.27.2 The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size 1441.54 1441.54 sqm 2671.20 3850642.00
24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm
centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false
ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried
out as per CPWD specifications, drawings and as per directions of the engineer-in charge.
All work shall be done with fully perforated 16 mm thick beveled tegular mineral fiber Anti-microbial false ceiling
tile confirming to ISO-5 ( CLASS 100) specification.
Tounge & Groove wooden laminated False Ceiling:-
Providing & fixing Tounge & Groove Wooden Laminated False Ceiling (HPL-Mica) of per approved make of
size- 190 mm X 2440 X 12 mm in true horizontal level suspended on interlocking White/Black 'T'-Grid hot
dipped galvanized iron section of 0.30 mm thick (galvanized @120 gsm) comprising of main T runners of 24 x32
mm of length 3000 mm. The second 'T' should be hanged at an Interval of 450 mm from first main'T'.
Suspension of 'T'Grid from ceiling using galvanized mild steel item (galvanised@80gsm) M-6 dash fasteners, 6
mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm,
spaced at 600 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the
help of GI perimeter wall angle of size 22 mm x 22 mm X 3000 mm made of 0.40 mm thick sheet, to be fixed to
the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The
Wooden Panel made of High Density Fiber Board (HDMR) Substrate with HPL facing as per the approved
Shade/species and finish and a Melamine balancing layer over the reverse side. The density of HDMR board
should be more than 800kg/m3 . The HDMR board should be passed through vertically flammability test (UL94)
& should be tested as for Anti-Fungal. The work shall be carried out as per specifications, drawings and as per
directions of the Engineer-In-Charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 17 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
ACOUSTICAL GLASS FIBER FALSE CEILING - SOUNDSCAPES
Providing and Fixing SoundScpaes Acoustical blades which are 40 mm thick, flat glass fibre panels as approved
make with Humidity Resistance RH 90%, with factory fitted embedded metal insert with ¼” – 20 threading for
fixing cable adjuster for hanging application. Acoustical blades shall have sizes of 200x1200mm, 200x1600mm
with 200mmC/C distance, with both side laminated scrim finished with uniform water based paint on all surface
(including edges). Acoustical performance of upto 0.65 NRC) as per ASTM C-423 (Average value of Absorption
Co-efficient readings taken at 250 Hz, 500 Hz, 1000 Hz and 2000 Hz) in standard White color with Light
reflectance 87% or in the color specified by the Architect (Shell / Tangerine / Cranberry / Moss / Kiwi / Reef /
Lagoon), Fire Performance Class B2 – s1, d0 as per EN 13501-1 .The blade shall be made of Glass fibre panel
with density of 110-120 Kg/ m3. SUSPENSION: The panel shall be hung using hanging kit comprising of griper
structure anchor & cap of dia 20mm, spring loaded bottom end cable adjuster of dia. 9mm and 2.4m long aircraft
cable of 1/16” dia. Components 1) Griper structure anchor 2) Gripper anchor cap 3) Cable adjuster 4) Aircraft
Cable Cable adjuster Spring loaded bottom end cable adjuster of dia. 9mm and 45mm long Aircraft cable
60 MR Material Galvanized Steel Aircraft cable dimension 1/16” Ø x 2.4m Tolerance ±1mm. INSTALLATION:Hanger 154.00 154.00 sqm 9292.00 1430968.00
Wire Attachment to Structure: Attach the gripper structure anchor to the structure with an appropriate fastener
(1/4"-20 Threading) that will carry the full weight of the blades. Insert the end of the cable into the gripper anchor
cap. Screw the gripper anchor cap completely into the gripper structure anchor. Insert Suspension Cables: The
panel is to be suspended using the aircraft cables which are suspended from the soffit using the gripper
structure anchors and its other end passing through the bottom end cable adjuster. The height & level of the
panels can be adjusted using the bottom end cable adjusters.Suspension of Blade: Locate the two factory fitted
female inserts on the blades. Suspend the Blades by screwing the bottom end of the cable adjuster into the
female inserts. Installation should be carried out as per Manufacturer recommended procedure.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 18 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and Fixing Channelled Woodworks perforated panels approved make of width 192mm, thickness of
15mm and length 2400 mm, made of a Moisture resistant fibre board substrate with a laminated facing as per
the approved shade (Portland Maple, Sea Beech, Siam Wood & Mystique Walnut, Interior White, Alumina Pearl)
and a melamine balancing layer on the reverse side. The boards shall have a special perforation pattern where
the reverse surface has a “Helmholtz” fluted perforation with consecutive 3mm wide groove followed by 5mm of
visible pane. The edges of the panel shall be “tongue-and-grooved” to fix special clips for installation and
seamless visual. The back of the perforated panel shall have sound absorbing non-woven Soundtex acoustical
fleece hot pressed to achieve NRC of 0.65. (Average value of Absorption Co-efficient readings taken at 250 Hz,
500 Hz, 1000 Hz and 2000 Hz) as per ASTM C423 and Humidity Resistance (RH) of 70% with camber limit less
than 1mm/1000mm and bow less than 1mm/300mm.The panels shall be mounted on special aluminium splines
(keel) using inside clips provided by Knauf and approved by the Architect/ Engineer-in-Charge.
Properties of TileRelevant Standards
Base MaterialMoisture Resistant Medium Density Fibre board
61 Panel Dimensions2400mm x 192mm x 15mm
Panel Weight≅ 8.5kgs/m2
Perforation Details “Helmholtz” fluted perforation on reverse side with consecutive of 3mm wide groove followed
by 5mm of visible pane.
Panel Finish Laminate (Portland Maple, Sea Beech, Siam Wood & Mystique Walnut, Interior White, Alumina
Pearl) finish Noise Reduction Co-efficient 0.65 ASTM C423 (Average value of Absorption Co-efficient readings
taken at 250 Hz, 500 Hz, 1000 Hz and 2000 Hz)
Humidity ResistanceRH 70%
Dimensional tolerances± 5mm
Digitally signed by ANUJ
Abstract of Cost (Civil ) 19 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
The panel shall be mounted by tongue and groove mechanism using inside clip on Knauf aluminium extruded
keel made of Grade 6063-T5 having dimensions 3000(L) x 24(H) x 15.5(W). The keel shall also be used for
transition of the butt end of adjacent panel at every 7.2m.
Installation System Details
Aluminium Keel/ Transition Profile
Base MaterialExtruded Aluminium Grade 6063-T5
Construction MethodAluminium Extrusion
Dimensions3000(L) x 24(H) x 15.5(W) mm
Clip Inside Clip
An appropriate vapour barrier (by others) shall be applied/installed on the vertical surface before the installation
to properly seal against entry of any moisture. Vapour barrier (by others) shall be installed as per Manufacturer’s
recommendation. Install wooden batten grid (provided by others) of section 50x50mm or as approved by the
Architect on the solid wall/partition to provide level and plumb surface for fixing Knauf Keel. Install Keel vertically
using screws and plugs at spacing of not more than 600mm centre-to-centre. The first and last keel should not
be more than 150mm from the ends. Trim the tongue of the first bottom panel and install using headless nail
with groove side upward. Subsequent panels are installed with tongue side downward by engaging with each
other using tongue and groove mechanism and secured by inside clip. Continue this process until required
height is achieved. Shorter butt edges need to be joined using industrial/wood glue. The keel shall also be used
for transition of the butt end of adjacent panel at every 7.2m. Install the skirting (provided by others) of width
50mm or more as required by the Architect/ Engineer-in-Charge. Finish off the edges using wooden moulding of
matching colour (by others). Installation should be carried out as per Knauf recommended procedure. .
Providing & fixing in position Phenol bonded Bamboowood in wall cladidng at all heights with planks of sizes 10
mm thick, minimum 1800 mm length and minimum 100 mm wide, in approved colour, texture and finish, having
Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council
(BMTPC), with necessary profiled edges fixed with40 mm SS Screws 5 nos in each tile to framework made of
second class teakwood of size 20 x 15 mm in centre of each tile and bottom & top of work height, 40 x 15 mm
placed at end of each tile> The cladding shall be laid over back layment of 1.00 mm thick expanded polythyline
foam of density 40 kg/sqm in two layers, first layer on wall surface before fixing wooden frame and second layer
on frame under cladding. The bamboowood planks shall have minimum density of 1000Kg/cum & minimum
Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 20 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and Fixing of Veneer Ply paneling ( 18 marine ply / board + 4mm thk veneer ) Over columns and walls
using Aluminium /MS frame and melamine polish and 4mm x4mm grooves . Panelling shall consist of approved
MS frame 50x25x1.6 mm sections and 600x600 mm centres to centers in both the directions as required
covered with 18 mm thick approved brand marine ply/ board with necessary 4x4 mm thick vertical and horizontal
grooves and 80 mm x 12 mm rubberwood/ steambeach half round moulding and finished with approved shade
63 MR matt melamine polish finished. The item shall be completed including making cut outs for electrical switches and 241.00 241.00 sqm 8319.00 2004879.00
appliances , Polish etc. as per detail drawings. The framework shall be anchored using anchor fastners and
screws etc. Complete in all respect as desierd and directed by the Engineer in charge / Consultant of work at
Providing and fixing wall/column paneling with 18 marine ply / board + 1mm thick decorative laminate as
approved shade /colour( one side decorative lamination of approved shade and other side balancing lamination)
and conforming to IS; 12823 grade I Type II with internal Kiln seasoned and chemically treated hollock wood
hard wood frame of adequate and approved section and size. Hard wood framework shall be treated with anti-
64 MR termite and fire retardant paint. All the edges of board should be eased with maple wood, including making cut 889.00 889.00 sqm 8028.00 7136892.00
outs for electrical switches and appliances etc., all complete as per architectural drawings and direction of
Engineer in Charge
Digitally signed by ANUJ
Abstract of Cost (Civil ) 21 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
ACOUSTICAL WALL PANEL IN FABRIC FINISH
Providing and Fixing of Acoustical Wall Panel with square edges made of fiber glass substrate 25mm thick,
Acoustical Wall Panel as approved make shall be of custom made sizes and per design ( subject to
manufacturing Limitations, need to check from manufacturer first) wrapped on the front side with an acoustically
transparent fabric as per the approved shade (Husk, Copper, Sangria, Sesame, Coffee, Charcoal, Titanium,
Flame, Peanut and Shell). The panel shall be classified for Fire Class A, as per ASTM E-84. The Acoustical Wall
Panel shall be of sizes 600x600mm (Nominal) or 600x1200mm (Nominal) and shall achieve an NRC of 0.85
(Average value of Absorption Co- efficient readings taken at 250 Hz, 500 Hz, 1000 Hz and 2000 Hz) with 50mm
airgap as per ASTM C423 to be fixed to wall on a framework of wooden battens and using Wall panel Impalers
(supplied by the manufacturer) or by using construction adhesives (as per the instructions laid down by the
65 MR manufacturer). The fiber glass substrate shall have a recycle content of 85%. INSTALLATION: An appropriate 150.00 150.00 sqm 7444.00 1116600.00
vapour barrier (by others) shall be applied/installed on the vertical surface before the installation to properly seal
against entry of any moisture. Vapour barrier (by others) shall be installed as per Manufacturer’s
recommendation. Install wooden batten grid (provided by others) of section 50x50mm or as approved by the
Architect on the solid wall/partition to provide level and plumb surface. The Impalers shall be fixed to the battens
using self- tapping screws. Silica based construction adhesive (by others) to be dabbed on to the projecting
elements (spikes) of the Impalers. Wall Panels shall be pierced through the spikes of the Impalers ensuring the
line and level of the panels are maintained.
Providing & fixing first class teak wood skirting of size 25 x 150mm to be installed on GI Studs (50mmx50mm)
.5mm thickness or better including polyurethene polish complete as per drawing and to the entire satisfaction of
66 MR Engineer-in-charge/Architect. Complete in all respect as desierd by the Engineer in charge / Consultant of work 250.00 250.00 metre 827.00 206750.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 22 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 7.0 - FINISHING WORK)
6 mm plaster on cement concrete or reinforced cement concrete work with white cement based polymer
67 13.86 modified self curing mortar of approved make including making groove where ever required as per the direction 965.00 965.00 sqm 269.15 259730.00
of Engineer-In-Charge :
12 mm cement plaster of mix :
68 13.4.2 1:6 (1 Cement : 6 Coarse sand) including groove where ever required 850.00 850.00 sqm 343.65 292103.00
15 mm cement plaster on the rough side of single or half brick wall of mix :
69 13.5.2 1:6 (1 Cement : 6 Coarse sand) including groove where ever required 850.00 850.00 sqm 395.35 336048.00
Painting with synthetic enamel paint of approved of approved make brand and manufacture to give an even
70 13.62.1 shade. Two or more coats on new work 50.00 50.00 sqm 226.25 11313.00
Finishing with Epoxy paint (two or more coats) of approved make at all locations prepared and applied as per
71 13.52.1 manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete.( a) on 100.00 100.00 sqm 241.75 24175.00
Providing and applying white cement based putty of approved make average thickness 1mm minimum two coat
72 13.80 ,of approved brand and manufacturer ,over the plastered wall surface to prepare the surface even and smooth 3165.00 3165.00 sqm 156.05 493898.00
Wall painting with premium acrylic emulsion paint of approved make of interior grade having VOC ( Volatile
Organic Compound ) content less than 50grams/litre of approved brand and manufacturer, including applying
73 13.83.2 additional coats wherever required to achieve even shade colour. 3165.00 3165.00 sqm 142.80 451962.00
Two or more coats on new work
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections as per direction of
Applying priming coats with primer of approved brand and manufacture of approved make , having low VOC (
75 13.85.3 Volatile Organic Compound) content with water thinnable cement primer on wall surface having VOC content 3165.00 3165.00 sqm 73.95 234052.00
less than 50grames/ litre.
Providing and applying 12 mm thick (average) premixed formulated one coat gypsum lightweight plaster of
approved make having additives and light weight aggregates as vermiculite/ perlite respectively conforming to
76 13.78 IS: 2547 (Part - 1 & II) 1976, applied on hacked / uneven background such as bare brick/ block/ RCC work on 500.00 500.00 sqm 468.90 234450.00
walls & ceiling at all floors and locations, finished in smooth line and level etc. complete.
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of
approved manufacturer, of required shade and colour all complete :
77 13.41.1 New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC 2665.00 2665.00 sqm 185.65 494757.00
content less than 50 gram/litre
Melamine polishing on wood work
Digitally signed by ANUJ
Abstract of Cost (Civil ) 23 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and applying water-based special two-tone velvet/ Preimistic Pearl finish of interior grade having low
VOC made up of special pearl pigments of make as approved by engineer in charge having special wipeable
properties and finish to be equivalent to :- a. Damascus/Alba/Palmyra of UltraTech (UTTPL) or equivalent as
approved, b. Perlata of Armour Coat c. R-Stone fondo of Nova Color The finish should have anti-algae and UV
resistance properties in the desired pattern after scrapping and properly cleaning the surface to remove loose
particles from the plastered surface. The following process to be followed : a. Initial coat of Masonry primer of
79 MR approved colour and shade ( Min. 0.9 ltr /10 sqm). b. Two coats of base coat with roller and brush ( Min. 0.9 ltr 392.00 392.00 sqm 2287.00 896504.00
/10 sqm). c. Final finish in 2 coats of Preimistic pearl finish (Wipeable grade) ( Min. 1.1 ltr/10 sqm).
Cost of work shall be inclusive of all materials, labor etc. as per manufacturers specification and finish up to the
entire satisfaction of the Engineer in Charge.
TOTAL SUB HEAD -7 3521296.00 896504.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 24 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 8.0 - ALUMINIUM & GLAZING WORK)
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard
tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:
1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e.
at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. aluminum sections shall be smooth,
rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminum snap
beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and
the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately):
For fixed portion
Polyester powder coated aluminum (minimum thickness of polyester powder coating 50 micron).
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard
tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:
1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e.
at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. aluminum sections shall be smooth,
rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminum snap
beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and
the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately):
For Openable portion
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision
for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings
shall be paid for separately).
Polyester powder coated aluminum (minimum thickness of polyester powder coating 50 micron).
Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. with PVC/neoprene
gasket, aluminum snap beading, aluminum channel etc. complete as per the architectural drawings and the
82 21.3.3 directions of engineer-in-charge . (Cost of aluminum snap beading, channel shall be paid in basic item) 250.00 250.00 sqm 1685.40 421350.00
With float glass panes of 8 mm thickness.
Filling the gap in between aluminium/ stone/ wood/ upvc frame and adjacent RCC/ Brick/ Stone/ wood/ Ceramic/
Gypsum work by providing weather / structural non sag elastomeric PU sealant over backer rod of approved
quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920,
Upto 20 mm depth and 20 mm width
Digitally signed by ANUJ
Abstract of Cost (Civil ) 25 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and supplying aluminum extruded tubular and other aluminum sections of approved make as per the
architectural drawings and approved shop drawings , the aluminum quality as per grade 6063 T5 or T6 as per
BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour
and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves,
84 25.1 screws etc. necessary for fabrication of extruded aluminum frame work. Nothing extra shall be paid on this 7369.50 7369.50 kg 414.30 3053184.00
account). The weight of aluminium extruded section shall be taken for purpose of payment.
Designing,Providing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of
structural glazing/ Curtain wall/ Glazing (with open joints) for linear as well as curvilinear portions of the building
for all heights and all levels, including :
85 a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS
875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure),
including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminum
cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather
silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water
tightness, pressure equalisation & drainage and protection against fire hazard including:
b) Fabricating and supplying serrated M.S. hot dip galvanised / aluminum alloy of 6005 T5 brackets of required
sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and
fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using
stainless steel anchor fasteners/ bolts, nylon separator to prevent bimetallic contacts with nuts and washers etc.
of stainless steel grade 316, of the required capacity and in required numbers..
c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant
compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop
environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand
and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass
d) Providing and fixing in position flashings of solid aluminum sheet 1 mm thick and of sizes, shapes and
profiles, as required as per the site conditions, to seal the gap between the building structure and all its
interfaces with curtain glazing to make it watertight.
e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight,
by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required),
making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all
inputs of designing, labour for fabricating and installation of aluminum grid, installation of glazed units, T&P,
scaffolding and other incidental charges including wastages etc., enabling temporary structures and services,
cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the
structural and functional design including shop drawings checked by a structural designer, dully approved by
Engineer-in-charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 26 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Note:- 1. The cost of providing extruded aluminum frames, shadow boxes, extruded aluminum section capping
for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for
separately under relevant items under this subhead. However, for the purpose of payment, only the actual area
of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two
decimal places.
Note:-2. The following performance test are to be conducted on structural glazing system if area of structural
glazing exceeds 2500 Sqm from the certified laboratories accredited by NABL(National Accreditation Board for
Testing and Calibration Laboratories),Department of Science & Technologies, India. Cost of testing is payable
The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test
and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the
NABL accredited lab or by any other accreditation body which operates in accordance with ISO /IEC 17011 and
accredits labs as per ISO/ IEC 17025.
1. Performance Laboratory Test for Air Leakage Test (-50pa to –300pa) & (+50pa to +300pa) as per ASTM E-
283-04 testing method for a range of testing limit 1 to 200 mVhr”.
2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testing method for a range up to 2000
3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000
4. Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure
without any failure) as per ASTME-330-10 testing method for a range upto 50 mm”
5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test” Tests to be
conducted on site
6. Onsite Test for Water Leakage for a pressure range 50 kPa to 240 kPa (35psi) upto 2000ml”
Digitally signed by ANUJ
Abstract of Cost (Civil ) 27 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Designing,Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed
28mm thick D.G.U. consisting of outer high performance 6mm thickheat strengthen (HS)/ toughened glass +
16mm air gap with argon + Inner 6mm glass heat strengthen (HS)/ toughened glass insulated glass (double
glazed) vision panel units of size and shape as required and specified, comprising of an outer 6mm thick
heatstrengthen high performance glass , of approved colour and shade with reflective soft / hard coating on
surface # 2 , spacer tube 16mm wide, Inner 6mm glass heat strenghten ( HS), dessicants, including primary
seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the
Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-
Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor.“(Payment for fixing of
IGU Panels in the curtain glazing is included in cost of relevant item )“For payment, only the actual area of glass
86 MR on face # 1 of the glass panels (including the areas of the grooves and weather silicone sealant)provided and 867.00 867.00 sqm 5431.00 4708677.00
fixed in position, shall be measured in sqm.“.
(i)Glass type A - 28mm thick D.G.U. consisting of outer high performance 6mm thick heat strengthen (HS)/
toughened glass + 16mm air gap with argon gas + Inner 6mm heat strenghten ( HS)/ toughened clear glass
(properties shall visible Light transmittance (VLT) of minimum 45%, Light reflection internal 10 to 20%, light
reflection external 10 to 20 %, SHGC less than or equal to 0.25 and U value of less than 1.10 W/m2 degree K
Providing and fixing of façade at all heights with extruded hollow Clay / Terracotta as per approved make
ventilated rainscreen tiles of height 300/ 400mm and length of 1190/1200 mm of approved texture,design and
pattern having Flexural Strength/ Modulus of Rupture of ? 14 N/m² and maximum water absorption of 10%
tested as per ISO 10545-4:2004(E) and ISO 10545-3:1995 respectively in true level fixed to a supporting
aluminium framework (Alloy 6063 T5/T6) consisting of vertical 'T' (for intermediates)/ 'L' (for ends/ termination)/
Tubular sections (at corners)of size 80x60x2mm/ 40x60x2mm/ 40x40x2mm respectively, spaced at maximum
87 spacing of 1200mm c/c matching to the tile vertical grid, and horizontal aluminium 'C'-clamps of size 56x34x2mm
thickness of length 150mm at junction of tiles and of length 75mm at wall ends/ corners fixed on top of the
vertical sections at spacing of 250/ 300/ 400mm c/c matching to the tile horizontal grid with two numbers of self-
drilling / self-tapping SS screws of size 5.5x25 mm with EPDM washers.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 28 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
The vertical 'T'/'L/ Tubular' sections shall be fixed to the wall using HDG (hot-dip-galvanized) steel Lbrackets
(galvanizing thickness of minimum 80 microns) of size 110x80x6 mm at intermediate vertical aluminium profiles
and of size 220x110x12 mmat outer corners and stainless steel grade 304,M10 full threaded anchor fasteners
with nylon sleeve 100mm long (for brick work) and M8 expansion anchor fasteners 75mm long for concrete
surface, spacing of brackets to be based on a structural/ static calculation. The brackets shall be of length
175mm at junction of two vertical aluminium profiles and of length 100mm at intermediate points of vertical
profiles and shall be fixed to the vertical aluminium T / L / Tubular profiles using two numbers self-drilling/ self-
tapping SS screws of size 5.5x25 mm with EPDM washers.“EPDM gaskets to be fixed in between brackets and
vertical profiles. The tiles shall be mounted on the ‘C’ clamps such that the tiles are supported at top and bottom
at both ends. The tiles shall be mounted on the Cclamps with EPDM profiles in between such that the tiles are
supported at top and bottom at both ends. The vertical joint open groove between two adjacent tiles shall be
The tiles and system shall be designed to resist wind load as per IS 875 (Part 3) according to different zones.
The tiles shall be installed using the ventilated rain screen principle with provision for natural ventilation of the
space between the façade tiles and the structural wall. The work shall be carried out as per specification,
drawing and as per direction of the Engineer-in-Charge. Note: Scaffolding wherever required to be paid
With 18-24mm thickness (+/- 10%) terracotta tiles of grey colour or as approved colour
Digitally signed by ANUJ
Abstract of Cost (Civil ) 29 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing, fabricating, testing, installing and fixing in position Curtain Wall with aluminum Composite Panel
Cladding / ceiling,as per approved make- with open grooves for linear as well as curvilinear portions of the
building , for all heights and all levels etc. including:
Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle
as required, proper drainage of water to make it watertight including checking of all the structural and functional
Providing, fabricating and supply and fixing panel of aluminum composite panel cladding in pan shape in metallic
colour of approved shades made out of (5XXX series, H-24 BARE aluminum coil temper) - 4mm thick aluminum
composite panel (0.5mm+3mm+0.5mm) material consisting of 3mm thick FR(AlMg1) grade mineral core(70%
non combustible Mineral filled and 30% virgin polymer) sandwiched between panel cladding sheet shall be coil
coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin (Minimum70% of resin) coating of
approved colour and shade on face # 1( Pencil hardness EN 13523-2 is HB-F) and polymer (Service) coating on
face # 2 as specified. The peel of strength of ACP should be 150Nmm/mm . Stainless steel screws, nuts, bolts,
washers, cleats, weather silicone sealant, backer rods etc. “weather silicone sealant, backer rods etc.
88 8.32 The fastening brackets of aluminum alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated 300.00 300.00 sqm 5015.05 1504515.00
washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS
316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and
drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all
samples of the individual components for testing in an approved laboratory, field tests on the assembled working
curtain wall with aluminum composite panel cladding, cleaning and protection of the curtain wall with aluminum
composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding
is payable under the relevant aluminum items The Contractor shall provide curtain wall with aluminum composite
panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per
item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge.
However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum
Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places."
Providing and fixing stainless steel ( Grade 316) railing ,fender,bollords, gate, door or any other item made of
Hollow tubes, channels, angle ,plates etc.as per approved make- including , grinding, buffing, polishing and
making curvature (wherever required) , making necessary arrangement for fixing of glass of 13.52 thickness
and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary
accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or
the side of waist slab with suitable arrangement as per drawings and approval of Engineer-in-charge, (for
payment purpose only weight of stainless steel members ( lowest of actual and standard weight) shall be
89 MR considered etc.), (Note : (i) Please note that no site welding of SS pipes will be allowed and longitudinal joints 2000.00 2000.00 Kg 924.00 1848000.00
shall be made by arrangement of internal SS sleeves, in vertical pipes no joints are permitted) (ii) Rate includes
preparation and submission of shop drawings by contractor. work shall be executed on the basis of approved
shop drawings, nothing extra shall be payable for shop drawings. (iv) ( One sample of each section shall be
tested for every 5000 kg or part thereof for confirmation to SS grade 304 ).
Digitally signed by ANUJ
Abstract of Cost (Civil ) 30 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Fabrication, supply & installation of Floor mounted SS-316 grade glass railing made up of 50mm dia top rail
mounted on SS soild flat baluster of 54x12mm width to hold the top rail, Height of the railing shall be 1200 mm
from the floor to the top of the top rail,The baluster shall have infill of 10.89mm thick ( 5+0.89 SGP+5) laminated
Toughened glass with height of 800mm high and length as per the layout plan connected to the baluster with
SS 304 grade Glass holders.The balusters shall be mounted on the floor with SS Grade 316 base plate of 100x
90 MR 100mm x 8mm thick fixed on the floor with 4 No. M-8 grade GI threaded chemically grouted SS-316 grade 100.00 100.00 sqm 18050.00 1805000.00
fasteners.The work shall be done upto the satisfaction of the Engineer-in-Charge. (Please note that no welding
of SS pipes will be allowed and work shall be done by a specialized agency on modular and component basis).
Providing & Fixing Frosted Translucent, cast PVC, self-adhesive vinyl, special CRYSTAL-effect film to
reproduce Sand-blasting effect on glass with customised designs, thickness of 2 mil (0.05mm) without adhesive
& 2.5 -3mil (0.8)with adhesive having minimum tensile strength of 2.9-3.5 pound/inch at 71F/73 F(0.6 kg/cm at
91 MR 23 C). Adhesion after 24-36hrs of installation should be 4 pounds/inch (0.7 kg/cm) on Acrylic, Glass 350.00 350.00 sqm 3024.65 1058628.00
Polycarbonate: Product performance/MCS warranty of 3yrs (if exposed to direct sunlight) to 10 yrs-15yrs
(indoors) must be endorsed by the manufacturer.
Providing and fixing stainless steel ( grade 304 ) floor stop half dome with 45mm dia with all necessary
92 MR accessories , screws etc in satin chrome of dorma or equivalent make. 12.00 12.00 Each 482.10 5785.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 31 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: -9.0 - WATER PROOFING)
Note : All water proofing work ,Contractor shall give 10 years guarantee for water proofings.
Waterproofing Application for sunken portion of WCs, bathroom,kitchen, balc etc etc
Providing and laying water proofing treatment in sunken portion of WCs,kitchen, bathroom, balc etc.and like aea
consisting of applying :
a) Making the surface free of all thedepression / undulations, dust dirt, laitance and all the adhesion inhibiting
material and making surface even by removing undulation on the entire surface by treating / filling with high
strength polymer for reparing and getting surface leveled.
b) Teating joints of wall and slab and around pipe junction of wall / floor with Velosit DB 830 joint tap or
equivalent as approved 200mm wide fixed in place with VELOSIT WP 124 Applyiing Ist coat of waterproofing
slurry on the wall -slab joint and immediately placing the tap over it and press it into the still wet slurry with steel
trowel to enxure adhesion and release and trapped air , Remaining area/ water outles to be treated in the same
93 MR c) After the entire surface preparation has been done, prewetting of the entire concrete surface and providing 396.67 396.67 sqm 925.00 366920.00
and application of the Ist coat of Velosit WP or equivalent as approved with a masons brush.After the Ist coat
has sufficently dried the 2nd coat of Velosit WP cna be approed . The total consumption of the product should
not less than 2.5kg / sqm in 2 coats.
d) After completion of the above said application , the waterproofed coating should be left to air cure for
minimum of 48 hours . Care should be taken that during this curing period walking or any other activities should
be avoided on it.
a) Surface area treated with Velosit wp 124 or equivalent as approved complete applying @ 2.5kg / sqm
Digitally signed by ANUJ
Abstract of Cost (Civil ) 32 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Waterproofing Application for sunken portion of WCs, bathroom,kitchen, balc etc etc
Providing and laying water proofing treatment in sunken portion of WCs,kitchen, bathroom, balc etc.and like aea
consisting of applying :
a) Making the surface free of all thedepression / undulations, dust dirt, laitance and all the adhesion inhibiting
material and making surface even by removing undulation on the entire surface by treating / filling with high
strength polymer for reparing and getting surface leveled.
b) Teating joints of wall and slab and around pipe junction of wall / floor with Velosit DB 830 joint tap or
equivalent as approved 200mm wide fixed in place with VELOSIT WP 124 Applyiing Ist coat of waterproofing
slurry on the wall -slab joint and immediately placing the tap over it and press it into the still wet slurry with steel
trowel to enxure adhesion and release and trapped air , Remaining area/ water outles to be treated in the same
94 MR c) After the entire surface preparation has been done, prewetting of the entire concrete surface and providing 100.00 100.00 sqm 827.00 82700.00
and application of the Ist coat of Velosit WP or equivalent as approved with a masons brush.After the Ist coat
has sufficently dried the 2nd coat of Velosit WP cna be approed . The total consumption of the product should
not less than 2.5kg / sqm in 2 coats.
d) After completion of the above said application , the waterproofed coating should be left to air cure for
minimum of 48 hours . Care should be taken that during this curing period walking or any other activities should
be avoided on it.
b) Joint Treatment with TAPE -VELOSIT DB 830 or equivalent as approved , 200 wide tap
TOTAL SUB HEAD -9 0.00 449620.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 33 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
SUB-HEAD:10: MISCELLANEOUS WORK:-
Providing and fixing 6mm thick bevelled edge mirror of superior glass of approved quality and approved make
with VHP tap 25mm dia stainless steel stud and 10mm brush finish stainless steel trims machine cut in required
95 MR size and shape as approved shade colour etc complete at all levels as per detailed drawings and direction of 20.00 20.00 sqm 1067.00 21340.00
Engineer in Charge.
Providing and fixing counters (Reception ,Wash basin or other similar location) with 12 mm thick antibacterial
anti fungal, boiling water resistant heat resistant, impact resistant, insulative non conductive, stain resistant,
scratch resistant, Green Guard certified Acrylic solid surface of approved make (LG Himac, Dupoint, Neonnex,
Hanex or equivalent as approved) in approved colour and design, confirming to relevant standards, and having
minimum Specific Gravity 1.65 g/cm3, fixed over MS supporting structure with all mechanical fixtures as per
manufacturer's specification and guideline, including fascia and back splash area as per approved drawings and
96 MR design, including fixing of solid acrylic surface over 12 mm thick (BWP) with suitable Low VOC adhesive, 30.00 30.00 Sqm 15988.40 479652.00
moulding of edges, buffing of surface, making of holes for plumbing fixtures, flushing of joints, necessary
hardware, silicon sealants, etc. all complete as per direction of Engineer In charge. The plan and elevation area
(horizontal and vertical) excluding wash basin area will be measured for payment.
Extra over above item , for providing oval/ rectangular shaped ( Below counter / above counter) wash basin of
size 550x450 /550 x 400 mm in Wash basion counter or other similar location, made of molded surface of 12
97 MR mm thick Acrylic solid of same specification as above, and in approved color and design, all complete as per 54.00 54.00 Each 10797.35 583057.00
drawings, specification and direction of Engineer in charge.
Providing and fixing Urinal Partition of 12mm thick board both side decorative compact laminate of required
colour ,shade and sizes as manufactured of approved make including all stainless steel accessories/ fittings (
98 MR SS-304 grade) like L clamp with ss screws etc as desired. all complete as per drawing and direction of 12.00 12.00 Each 4402.00 52824.00
Engineer in charge. (size =(450x900)mm
Providing and fixing wall cladding with 12 mm thick antibacterial anti fungal, boiling water resistant heat
resistant, impact resistant, insulative non conductive, stain resistant, scratch resistant, Green Guard certified
Acrylic solid surface of approved make in approved colour and design, confirming to relevant standards, and
having minimum Specific Gravity 1.65 g/cm3, fixed with aluminum frame over wall in true line and level, as
99 MR per manufacturer's specification , drawings and design, including suitable Low VOC adhesive, buffing of 75.00 75.00 Sqm 16957.40 1271805.00
surface, making of holes for plumbing fixtures, flushing of joints, necessary hardware, silicon sealants, etc. all
complete as desired and direction of Engineer In charge. Note :-Only surface area of acrylic solid surface panel
alongwith its groove shall be measured for payment.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 34 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing of 6mm thick toughned lacquered glass as per approved of approved color / shade on a
perfectly leveled on the existing wall fixed with clips (either of I/J1/J2, or equivalent as approved made of
polycarbonate, grey backing foam to accommodate substrate undulation, with a horizontal load capacity of
30Kg/100mm and vertical pullout load > 200kg/100mm). Glass should be supported with 1mm thick lip covering
upto 3mm of glass surface; clips should be fixed using durable, non-corrosive, strong screw 45mm long .
Lacquered glass must be made industrially (via curtain coating process); opaque (if viewed against a support
wall), coated with PU lacquer (minimum 50 micron thick); color consistency (measured by Minolta
spectrophotometer CM5081); highly durable (passes PERSOZ hardness test for minimum 220 oscillations);
humid resistant (conforms to BS EN 1036 1999); environmentally friendly (no lead, no arsenic, no copper, no
formaldehyde); appropriate recycled content (12% post industrial / 6% post consumer); compressive strength
100 MR (1000 MPa) & tensile strength (40 MPa),same as float glass. Contacts all complete required to perform as per 148.00 148.00 Sqm 5108.00 755984.00
specification and drawing Nothing shall be paid in this account.
The Contractor shall provide glass having all the performance characteristics all complete , as per the
Architectural drawings, as per Item description, as specified, as per the approved shop drawings and as directed
by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the
glass (including width of groove) shall be measured in sqm up to two decimal places.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 35 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Supplying and installing roller blinds of approved make model and shade at all heights and location and required
width and comprising of approved shade and quality fabric, 1 mm thick anodized extruded Aluminium alloy roller
tube of 38-mm O.D , a bidirectional operating Clutch mechanism designed for adjustment-free, slippage-free,
crash proof smooth operation for all heights, high strength fiber glass reinforced polyester idler, powder coated
steel Insert type brackets fitted with roller tube, round bottom rail, control unit engrooved with a Ball Pitch of
minimum 6.5mm, Stainless Steel Ball Chain, and powder coated atomized steel installation brackets. The clutch
mechanism comprises of a SS beaded chain and carbon steel spring wrapped by means of a high strength fiber
glass reinforced polyester assembly to transmit motion from driving to driven members. The installation brackets
shall facilitate overhead, side or face mounting with clutch assembly on either end of the roller. Idler shall
consist of a centre shaft and outside sleeve which provide bearing surface for roller tube and rotate freely on
centre shaft for smooth and quiet operation. Bottom rail along with the fabric shall be enclosed in a suitably
created pocket and shall be of powder coated aluminium tube and closed from sides with end caps. The item
includes all fittings, accessories, brackets, screws, anchor fasteners, fabric as per approved sample and shade
all complete as per drawings, tender specifications, relevant standards and direction of Engineer in charge.
101 MR (Height of blind from top bracket to bottom tube and width from bracket to bracket shall be measured for 324.00 324.00 Sqm 2092.00 677808.00
Manual Roller Blinds
Perforated Screen Blinds
Composition- 30% Polyester (max),70% PVC on Polyester(min),
Openness factor- 3-5%(as approved)
Weight (gram/ sqm)- min 440 gm/sqm
Thickness- min 0.60 mm
Fire Classification- Class A( NFPA 101 or Class 1 (UNE EN 13773) or equivalent as per relevant standards and
Fastness to light- 6-7/8 or higher
Indoor Air Quality- GreenGuard / Eco-Codice Certified.
Manufacturer's warrantee- minimum 5 years
Supplying and installing of Seclusion Blockout fabric made up of 100% Polyester with Acrylic coated of
0.32mm(PVC free) of thickness 0.50mm ±5% and weighing 270-295gsm with openness factor of 0%
.Shrinkage % Warp<0.5 & Weft <0.5,Color fastness>5-6.Fire Classification- NFPA-701 or equivalent,
GREENGUARD certified fabric. The Roller blind system consists of 38mm OD extruded out of Aluminium alloy
6063 T6 with silver anodized to provide an everlasting finish and luster, the rotary unit shall be 36mm in OD
incorporating a clutch mechanism composed of low – flexing braided polyster cord with nylon core, Control Ball
chain shall be composed of braided nylon cord (2mm dia) with high engineering grade plastic beads of 4.5mm
diameter mounted co-axially on the cord with a pitch of 6.2mm (C-T-C) Bottom rail should be powder coated
102 MR Aluminium flat bottom rail of 290 gm to finish it from the ends it should have rail end caps. The clutch will be at 324.00 324.00 Sqm 1897.00 614628.00
the tube. The return end cap bracket shall incorporate snap spring design to facilitate easy installation and
removal for maintenance activities. The bracket shall be finished with a flush mounting cover on each side
providing an aesthetic finish. It should handle up to 5 Kgs of material. The clutch should mount flush to the face
of the bracket which minimize the light gap between the shade and the window frame. Complete as per direction
of Engineer -in –Charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 36 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Extra for supplying, installing, testing and commissioning remote operated motor of approved make and model,
in each roller blind and having following minimum specification. The item includes all fittings, accessories,
brackets, screws, tube of appropriate size, anchor fasteners, making electrical connections, all complete as per
drawings, tender specifications, relevant standards and direction of Engineer in charge
Torque(Nm): Minimum 3-6
Speed(rpm): Minimum 30-32
Rated Voltage(V):230, 50 Hz
Rated Power Consumption(W):120
Rated Current(A):0.5
Running Time Before Thermal Cut Off(min): 4
Average Running Noise(dbA):52 or less
Index Protection: 31 or 44(as per manufacturer's specification)
Extra for printing as per approved design over rollar blinds as per manufacturer specifications and direction of
104 MR Engineer in charge . 324.00 324.00 sqm 1384.00 448416.00
Supplying remote control of approve make and model (for each room with motorized blinds) capable of providing
individual as well as group Control (upto 16 channels) for the motors of the roller blind mentioned in above item,
105 MR including batteries all complete, as per direction of engineer in charge. (Multi Channel Remote) 12.00 12.00 each 8271.00 99252.00
Providing and laying aluminum dust buster matting (whipping & scrapping -moisture & dirt recessed ) for main
106 MR entry as per manufacturer specifictions and direction of Engineer in charge. 20.00 20.00 Sqm 18901.00 378020.00
Core cutting in RCC slab in core cutting machine in insert upto 200mm dia pipes in toilets slabs including
107 MR finishing leak proof after insertion of pipes as per direction of Engineer-in-charge 12.00 12.00 each 1168.49 14022.00
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index)
> 78, solar reflection >0.70 and initial emittance >0.75 on waterproof and sloped surface of terrace, laid on 20
mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4coarse sand) and grouting the joints with mix of
108 12.55 white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts 970.00 970.00 sqm 1703.95 1652832.00
complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 37 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Supply and Installation of Multi cell Polycarbonate Panels 16 mm thick( minimum) with 5 cells ‐ 6 walls structure
over MS Supporting structures. Panel Width shall be 900-1000mm to ensure best performance for wind uplift.
The panels shall be uniform in color with an integral Microcell core with soft light finish to give diffused light. In a
cross section, the core shall be constructed of microcells not exceeding 4mm x 4mm and shall be square/
rectangular/ or in truss bridge design commonly known as X‐Structure in appearance. Panels shall be
coextruded with UV Protection layers with thickness and concentration to filter and block more than 99% of the
UV rays (UVA and UVB) through a clear panel. The weight of the only panel shall not be less than 3250 gram
per square meter. Panel shall have U value not more than 1.9 W/m2k and UV transmission of less than 0.1%
with UV filtration test AS No.1067‐1990 or equivalent test available in India. Panel and system should have
impact and shock resistance with D1‐ 10j ‐M 50 ,300 J ‐ M 50 400 J or as per IS 6892:1998 and IS 1608: 2005.
Panel system shall have Vertical Standing Seam 15mm at both sides and snap on connector to interlock the
panels with a grip‐lock 1/2 tooth locking mechanism to ensure maximum uplift capability. Panels shall be fixed
on Purlins with special SS Expansion fastener and polycarbonate U/2 connectors. Panel system shall be sealed
with additional Tape / End caps / Aluminium U‐Profile (mill finish) at the ends. Panel should pass through
Sandbag impact test ASTM E 695‐03 or as per IS 14443-97 after 25,000 hours/should be read as minimum 500
hours of environmental exposure and Hailstone impact test ASTM E 822‐81 or as per ASTM G 155. The panel
system shall pass water penetration test ASTM E – 331 or as per equivalent test available in India. The panel to
have classification under B S1 D0 for reaction to fire as per test standard EN 13501 1:2002 or equivalent test
available in India tested by an independent, recognized testing laboratory. Panels shall have Yellowness Index
as per ASTM D‐1925; the change shall not be more than 10 points after 60 months of exposure in comparison to
The Color of the panel shall change no more than 3 units as per ASTM D2244 after 60 months of exposure in
comparison to original. The Light Transmission of panels shall not change more than 10% after exposure of 60
months in comparison to original.. Panel shall be fixed over MS structural steel/MS purlin (paid separately)
conforming to the detail technical specifications as per approved architectural drawings. Trained and factory
authorized labour with supervision to complete the entire panel installation as per drawing and direction of the
engineering in charge.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 38 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
Providing and fixing Rebaring by using various diameter 12mm to 25mm.Dia, hilti/ fisher make chemical (Re-
500) max.depth 300 mm. The main reinforcement using rebars of designated dia for column/beam/Shear
walls/Foundations at designed embedement length wherever required , including power drilling, cleaning of
holes, then rebars should be inserted in holes that should be filled with FIS EM Plus of Fischer or equivalent, a
heavy duty pure epoxy based rebarring chemical with ETA approval, DIBt, approved for diameter range from 8
mm to 40 mm reinforcement bar as per manufacturer's specification as per the direction of Engg In-charge.
Drilling of hole should be done upto provided embedment depth as per the design from manufacturer approved
110 MR by EnC, followed by cleaning with blow pump, wire brush and blow pump for 4 times, complete as per the 100.00 100.00 each 850.00 85000.00
manufacturer's methodology. The chemical shall be approved for diamond-drilled and water-filled drill holes as
well as seismic applications in performance categories C1, C2 for rebar connections. Product shall have test
certificate for 120years of service life & shall have ETA complying to EAD 332402-00-0601-v01.
Digitally signed by ANUJ
Abstract of Cost (Civil ) 39 GULIA
ABSTRACT OF COST
DETAILED ESTIMATE FOR THE CONSTRUCTION OF GRID INDIA
SH: INTERIOR WORKS
Refer RATE (DSR NON DSR AMOUNT (NON-
S.No. Office QUANTITY UNIT AMOUNT (DSR)
(DSR'23) '23) RATE DSR)
(SH: - 11.0 - DISMANTLING & DEMOLISHING
Demolishing AAC/brick work manually/ by mechanical means including stacking of serviceable material and
111 disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. 50. 50.00 cum 2060.20 103010.00 0.00
15.7.4 In Cement Mortar
15.30 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of
unserviceable material within 50 metres lead as per direction of Engineer - in- charge. 20. 20.00 cum 3551.25 71025.00 0.00
15.23 Dismantling tile work in floors/ wall and roofs laid in cement mortar including stacking material within 50 metres
15.23.1 For thickness of tiles 10 mm to 25 mm 1 335. 1335.00 sqm 73.40 97989.00 0.00
Dismantling doors, windows, glazing and clerestory windows (steel /wood/ Aluminium) shutter including
chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead :
15.12.1 of area 3 sq. metres and below 100. 100.00 Each 367.20 36720.00 0.00
TOTAL SUB HEAD -11 685807.00 0.00
Digitally signed by ANUJ
Abstract of Cost (Civil ) 40 GULIA
ABSTRUCT OF COST
SH 01: LOOSE FURNITURE
ITEM NAME Description Size Unit Qty Rate Amount Reference Image
Providing and fixing in position of customised design ref. images and shop drawing as approved Working table with
Decorative Veneer as approved ( T1 ) including drawer unit of required size:
- Table top shall be made out of 36 mm thick ( 18mm+18mm) commercial ply wood of MR grade (Make: Century
Architect Ply / Durian /Archid ply /Greenlam Club) IS 303 : 1989 .
- The side panel / vertical support shall be made out of 24mm thick commercial ply wood of MR grade shall be supporting
below the working table top and front modesty shall be made out of 18mm thick commercial plywood of MR grade having
height of 710 mm shall be fixed at front side of table top.
- Table top, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 3.50 to 4.00 mm
thick natural veneer (Make : Archid ply/ Durian/ Century/ Duro) with hot pressed glue/ adhesive of approved quality.
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue/ adhesive of approved quality.
- The working or non-working edges shall be provided with veneer edge binding using with special hot melt glue at hot
- All necessary hardware/ fitting/S.S. hinges etc. of approved quality (Make: Ebco/Hettich/Hafele/Sumsung Irex).
- Natural Veneer to be use is Steam Beach/ English walnut or similar price as approved shade/ colour.
- All veneered to be sprayed with 03 coats of PU polish finished in desired shade using base material of
MRF/Jeevanjor/Sirca.
- Agency has to be adopt sound Interior Design practice while fabrication for stability and asthetically.
- The commercial ply wood/veneer/laminate shall be make of (Greenlam club/Century Architect ply /Durian/Archid ply) IS
- Wooden moulding require at skirting level to be covered both the sides panels and front modesty.
- Table shall have adequate provisions for the movement of electric/ data cables at desired levels. Keyboard runs on
telescopic channel for smooth operation
- For installation of table wooden dowels and minifix to use for additional support.
- Any additional member are support required for stability shall be provided where ever required as per instruction of
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower bolts/
handles etc . of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired with appproved SS Hardwares ( grade 316 ) and as per direction and satisfaction of
Engineer -in –Charge.
a) (Main Table ( Front )
b) Side Unit with Decorative Veneer as approved with 2 nos file drawer and 1 no box drawer
c) Storage/ Filing / Back unit (L)3000x (W)450x
Providing and fixing in position of customised design ref. images and shop drawing as approved Working table with
Decorative Veneer as approved ( T2 ) including drawer unit of required size:
- Table top shall be made out of 36 mm thick ( 18mm+18mm) commercial ply wood of MR grade(Make: Century Architect
Ply / Durian /Archid ply /Greenlam Club) IS 303 : 1989 .
- The side panel / vertical support shall be made out of 24mm thick commercial ply wood of MR grade shall be supporting
below the working table top and front modesty shall be made out of 18mm thick commercial plywood of MR grade having
height of 710 mm shall be fixed at front side of table top.
- Table top, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 3.50 to 4.00 mm
thick natural veneer (Make : Archid ply/ Durian/ Century/ Duro) with hot pressed glue/ adhesive of approved quality.
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue/ adhesive of approved quality.
- The working or non-working edges shall be provided with veneer edge binding using with special hot melt glue at hot
- All necessary hardware/ fitting/S.S. hinges etc. of approved quality (Make: Ebco/Hettich/Hafele/Sumsung Irex).
- Natural Veneer to be use is Steam Beach/ English walnut or similar price as approved shade/ colour.
- All veneered to be sprayed with 03 coats of PU polish finished in desired shade using base material of
MRF/Jeevanjor/Sirca.
- Agency has to be adopt sound Interior Design practice while fabrication for stability and asthetically.
- The commercial ply wood/veneer/laminate shall be make of (Greenlam club/Century Architect ply /Durian/Sumo/Archid
- Wooden moulding require at skirting level to be covered both the sides panels and front modesty.
- Table shall have adequate provisions for the movement of electric/ data cables at desired levels. Keyboard runs on
telescopic channel for smooth operation
- For installation of table wooden dowels and minifix to use for additional support.
- Any additional member are support required for stability shall be provided where ever required as per instruction of
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower bolts/
handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired with appproved SS Hardwares ( grade 316 ) and as per direction and satisfaction of
Engineer -in –Charge.
a) (Main Table ( Front )
Side Unit with Decorative Veneer as approved with 2 nos file drawer and 1 no box drawer
b) (L)2400x (W)600x (H)650 Digitally5 signed1,10,891.00
Storage/ Filing / Back unit
Providing and fixing in position of customised design ref. images and shop drawing as approved Working table with
Decorative Veneer as approved ( T3 ) including drawer unit of required size:
- Table top shall be made out of 36 mm thick ( 18mm+18mm) commercial ply wood of MR grade(Make: Century Architect
Ply / Durian /Archid ply /Greenlam Club) IS 303 : 1989 .
- The side panel / vertical support shall be made out of 24mm thick commercial ply wood of MR grade shall be supporting
below the working table top and front modesty shall be made out of 18mm thick commercial plywood of MR grade having
height of 710 mm shall be fixed at front side of table top.
- Table top, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 3.50 to 4.00 mm
thick natural veneer (Make : Archid ply/ Durian/ Century/ Duro) with hot pressed glue/ adhesive of approved quality.
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue/ adhesive of approved quality.
- The working or non-working edges shall be provided with veneer edge binding using with special hot melt glue at hot
- All necessary hardware/ fitting/S.S. hinges etc. of approved quality (Make: Ebco/Hettich/Hafele/Sumsung Irex).
- Natural Veneer to be use is Steam Beach/ English walnut or similar price as approved shade/ colour.
- All veneered to be sprayed with 03 coats of PU polish finished in desired shade using base material of
MRF/Jeevanjor/Sirca.
- Agency has to be adopt sound Interior Design practice while fabrication for stability and asthetically.
- The commercial ply wood/veneer/laminate shall be make of (Greenlam club/Century Architect ply /Durian/Sumo/Archid
- Wooden moulding require at skirting level to be covered both the sides panels and front modesty.
- Table shall have adequate provisions for the movement of electric/ data cables at desired levels. Keyboard runs on
telescopic channel for smooth operation
- For installation of table wooden dowels and minifix to use for additional support.
- Any additional member are support required for stability shall be provided where ever required as per instruction of
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower bolts/
handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired with appproved SS Hardwares ( grade 316 ) and as per direction and satisfaction of
Engineer -in –Charge.
a) (Main Table ( Front )
Side Unit with Decorative Veneer as approved with 2 nos file drawer and 1 no box drawer
Storage/ Filing / Back unit
Providing and fixing in position of customised design ref. images and shop drawing as approved Working table with
Decorative Veneer as approved ( T4 ) including drawer unit of required size:
- Table top shall be made out of 36 mm thick ( 18mm+18mm) commercial ply wood of MR grade(Make: Sumo / Century
Architect Ply / Durian /Archid ply /Greenlam Club) IS 303 : 1989 .
- The side panel / vertical support shall be made out of 24mm thick commercial ply wood of MR grade shall be supporting
below the working table top and front modesty shall be made out of 18mm thick commercial plywood of MR grade having
height of 710 mm shall be fixed at front side of table top.
- Table top, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 3.50 to 4.00 mm
thick natural veneer (Make : Archid ply/ Durian/ Century/ Duro) with hot pressed glue/ adhesive of approved quality.
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue/ adhesive of approved quality.
- The working or non-working edges shall be provided with veneer edge binding using with special hot melt glue at hot
- All necessary hardware/ fitting/S.S. hinges etc. of approved quality (Make: Ebco/Hettich/Hafele/Sumsung Irex).
- Natural Veneer to be use is Steam Beach/ English walnut or similar price as approved shade/ colour.
- All veneered to be sprayed with 03 coats of PU polish finished in desired shade using base material of
MRF/Jeevanjor/Sirca.
- Agency has to be adopt sound Interior Design practice while fabrication for stability and asthetically.
- The commercial ply wood/veneer/laminate shall be make of (Greenlam club/Century Architect ply /Durian/Sumo/Archid
- Wooden moulding require at skirting level to be covered both the sides panels and front modesty.
- Table shall have adequate provisions for the movement of electric/ data cables at desired levels. Keyboard runs on
telescopic channel for smooth operation
- For installation of table wooden dowels and minifix to use for additional support.
- Any additional member are support required for stability shall be provided where ever required as per instruction of
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower bolts/
handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired with appproved SS Hardwares ( grade 316 ) and as per direction and satisfaction of
Engineer -in –Charge.
a) (Main Table ( Front )
Side Unit with Decorative Veneer as approved with 2 nos file drawer and 1 no box drawer
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approved Working table with
decorative laminate as approved ( T5 ) including drawer unit of required size:
- Table top shall be made out of 36mm thick commercial ply wood of MR grade (Make: Sumo Architect Ply /Durian
/Archid ply/Greenlam Club) IS 303 : 1989 on both side of approved color and contained the thickness shall be 36mm
(12mm Plywood + 12mm baton between both the plywood + 12mm Plywood). For additional strength wooden framing
should be provided between both the plywood of table top total 06 numbers vertical baton size 12mm x 25mm x 900
height and 04 numbers horizontal baton 12mm x 25mm x 2100 length to be used.
- The side panel / vertical support shall be made out of 25mm thick commercial ply of MR grade (Make: Sumo /Century
Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 shall be supporting below the working table top and
front modesty shall be made out of 18mm thick commercial ply of MR grade (Make: Sumo /Century Architect Ply
/Durian /Archid ply /Greenlam Club) IS 303 : 1989 having height of 650 mm to 700 mm shall be fixed at front side of
- Table top surface, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 1.00 mm
5 E7 thick decorative / coloured high pressure laminated sheet (Make: Cedar Lam /Durian /Archid ply /IPL /Royal Touch)
with hot pressed glue including cost of glue/ adhesive of approved quality.
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. All necessary hardware/ fitting etc. of approved quality (Make:
Ebco/Hettich/Kitch/Sumsung Irex).
- Provision for metallic Keyboard runs on telescopic channel for smooth operation.
- Table shall have adequate provisions for the movement of electric/ data cables at desired levels.
- For installation of table wooden dowels and minifix to use for additional support.
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower
bolts/ handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired with appproved SS Hardwares ( grade 316 ) and as per direction and satisfaction of
Engineer -in –Charge.
(Main Table ( Front )
Side Unit with Decorative laminate as approved with 2 nos file drawer and 1 no box drawer
Providing and fixing in position of customised design ref. images and shop drawing as approveds Sliding Tile Base
Workstation ( T-6) including drawer unit as per sizes:
- Free standing partition height 1200mm and should be minimum of 55mm thick. Partition inner frame is 1.1mm thick
mild steel. Horizontal and vertical trims are made out of extruded aluminium of 1.0mm thick.
- All Panels/trims shall be powder coated with 50 microns. Aluminium trims are elegantly fixed with special fixtures in the
partition. The framework shall be fitted with 9mm thick pre laminated Particle tiles of approved shade.
- Partition shall have provision for pin up board with fabric/ white marker/ laminated of approved shade.
- Partition framework shall have adequate provisions for the movement of electric data cables at desired 2 levels; one at
skirting and another above / below the table top. Panel have cut-outs of required sizes for installing electric switch boards
( switch samples provided by client) there will be separate slots for passage of data and electrical wires. The frames
designed to easily handle CAT6 wire at entry points. The complete partitioning work shall be carried out as per the
approved drawing.
- Balancing Laminate pasted on below the top shall be thickness of 0.60mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
6 - Table top for workstation shall be made up of 25mm thick commercial ply of MR grade (Make: Sumo /Century Architect
E6 Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 including with 1mm thick decorative / coloured high pressure
laminated sheet (Make: Cedar Lam /Durian /Archid ply/Archid / IPL /Royal Touch) with hot pressed glue including cost of
glue/ adhesive of approved quality.
- Side panel shall be made out of 18/19mm thick commercial ply of MR grade (Make: Sumo/Century Architect Ply /Durian
/Archid /Greenlam Club) IS 303 : 1989 including with 1mm thick laminate (Make: Cedar Lam /Durian /Archid ply /IPL
Archid/ Royal Touch) IS 2046 : 1995 on both side matching with tabletop and contained the thickness shall be 18/19mm.
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using with
special hot melt glue at hot temperature. Metal Keyboard with telescopic channel for smooth operation.
- Metal CPU trolley with lockable castors for smooth operation on floor.
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower bolts/
handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired and direction of Engineer -in –Charge.
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approved, Reception counter /
table ( T115 ) as per given sizes:
- Reception counter / table shall be made out of 36mm thick commercial ply wood of MR grade (Make:Century
Architect Ply /Durian /Archid classic /Greenlam Club) IS 303 : 1989 on both side of approved color and contained the
thickness shall be 36mm (12mm Plywood + 12mm baton between both the plywood + 12mm Plywood) and cladded
with solid acrylic surface and PU /melamine polished veneer facia paste on marine ply and trim light below as per
design. Two drawers with lock and space for two pc, keyboard tray and CPU trolley will be provided. Space for
biometric and printer. Keyboard tray made of powder coated CRCA steel sheet with soft closing channels. CPU trolley
made of powder coated CRCA steel sheet with castor for smooth operation on floor. Complete table having knock
down system. Drawing unit pedestal having a combination of two drawers and one filling/ backing/ drawers bottom
/top shall be made of 18 mm thick marine ply with laminated and required size is (L)600 X (W)600 X (H)600 . For
additional strength wooden framing should be provided between both the plywood of table top total 05 numbers
vertical baton size 12mm x 25mm x 1050 height and 03 numbers horizontal baton 12mm x 25mm x 3000mm length to
7 MR - Carcase box/ under structure should be made of minimum 18/19 mm thick commercial ply wood of MR grade (Make:
Sumo/Century Architect Ply /Durian /Archid ply /Archid classic /Greenlam Club) IS 303 : 1989 modesty having height
of 650 mm to 700 mm shall be fixed at front side of table top. In the addition table height to be raised till 1050mm (H)x
300mm(D)x 3000(L)front side only.
-All Visible sides, top and edging will be cladded with 12mm thick solid acrylic surface milkey finished or as approved
colour / shade and as per detail drawing.
- Table having provision of two numbers pedestal with a combination of two drawers and One filling shall be made of
18 mm thick commercial ply of MR grade (Make: Sumo/Century Architect Ply /Durian /Archid ply /Archid/ Greenlam
Club) IS 303 : 1989 and pedestal backing/ drawers bottom shall be 8 mm thick ply of MR grade IS 303 : 1989.
- Balancing Laminate pasted below the table top, inner side of modesty/ both the side panel and pedestal inner/ outer
shall be thickness of 0.60 mm in gloss / matt finish with high density protective surface layer pasted with hot pressed
glue / adhesive of approved quality.
- The pedestal edges shall be provided with matching machine pressed 2mm thick PVC edging using with special hot
melt glue at hot temperature. All necessary hardware/ fitting etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower
bolts/ handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
Reception counter / table ( T15 ) (L)3000x(W)750x
b) Storage/ Filing / Back unit ( S15a)
Providing and fixing in position of customised design ref. images and shop drawing as approved,Curve Reception
counter / table ( T116 ) as per given sizes:
- Reception counter / table shall be made out of 36mm thick commercial ply wood of MR grade (Make:Century
Architect Ply /Durian /Archid classic /Greenlam Club) IS 303 : 1989 on both side of approved color and contained the
thickness shall be 36mm (12mm Plywood + 12mm baton between both the plywood + 12mm Plywood) and cladded
with solid acrylic surface and PU /melamine polished veneer facia paste on marine ply and trim light below as per
design. Two drawers with lock and space for two pc, keyboard tray and CPU trolley will be provided. Space for
biometric and printer. Keyboard tray made of powder coated CRCA steel sheet with soft closing channels. CPU trolley
made of powder coated CRCA steel sheet with castor for smooth operation on floor. Complete table having knock
down system. Drawing unit pedestal having a combination of two drawers and one filling/ backing/ drawers bottom
/top shall be made of 18 mm thick marine ply with laminated and required size is (L)600 X (W)600 X (H)600 . For
additional strength wooden framing should be provided between both the plywood of table top total 05 numbers
vertical baton size 12mm x 25mm x 1050 height and 03 numbers horizontal baton 12mm x 25mm x 3600mm Curve
length to be used.
8 MR - Carcase box/ under structure should be made of minimum 18/19 mm thick commercial ply wood of MR grade (Make:
Sumo/Century Architect Ply /Durian /Archid ply /Archid classic /Greenlam Club) IS 303 : 1989 modesty having height
of 650 mm to 700 mm shall be fixed at front side of table top. In the addition table height to be raised till 1050mm (H)x
300mm(D)x 3600(Curve length)front side only.
-All Visible sides, top and edging will be cladded with 12mm thick solid acrylic surface milkey finished or as approved
colour / shade and as per detail drawing.
- Table having provision of two numbers pedestal with a combination of two drawers and One filling shall be made of
18 mm thick commercial ply of MR grade (Make: Sumo/Century Architect Ply /Durian /Archid ply /Archid/ Greenlam
Club) IS 303 : 1989 and pedestal backing/ drawers bottom shall be 8 mm thick ply of MR grade IS 303 : 1989.
- Balancing Laminate pasted below the table top, inner side of modesty/ both the side panel and pedestal inner/ outer
shall be thickness of 0.60 mm in gloss / matt finish with high density protective surface layer pasted with hot pressed
glue / adhesive of approved quality.
- The pedestal edges shall be provided with matching machine pressed 2mm thick PVC edging using with special hot
melt glue at hot temperature. All necessary hardware/ fitting etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower
bolts/ handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
Reception counter / table ( T16 ) (L)3600x(W750x
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approveds Conference Table
( T10/T10a ) with Decorative Veneer as approved of required size:
- The conference table top shall be having depth and height for each seating 750mm, table top shall be made out of
40mm thick commercial ply of MR grade (Make: Sumo /Century Architect Ply /Durian /Archid ply /Greenlam Club) IS
303 : 1989 on both side of approved color and contained the thickness shall be 40mm (12mm Plywood + 16mm baton
between both the plywood + 12mm Plywood). For additional strength wooden framing should be provided between
both the plywood of table top total 06 numbers vertical baton size 16mm x 25mm x 750 long and 04 numbers
horizontal baton 16mm x 25mm x 1500 long to be used.
-450 mm high modesty panel and legs made of 18mm thick marine ply with polished veneer pasted on front side and
laminate on inner side, edges will be sealed with veneer. Legs with PVC shoes. Complete table having a knock down
system on mini fitting. Each module to have 1nos. metal brush flapper with metal tray made of CRCA steel for wire
management and electrical & data switch socket mounting provision.
- The side panel / vertical support shall be made out of 18mm thick commercial ply of MR grade (Make: Sumo
/Century Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 shall be supporting below the working table
top and front modesty shall be made out of 18mm thick commercial ply of MR grade (Make: Century Architect Ply
/Durian /Archid ply /Greenlam Club) IS 303 : 1989 having height of 650 mm to 700 mm shall be fixed at front side of
table top. Vertical support shall be giving after two seating of minimum of 1500mm intervals.
- Table top surface, both sides of vertical support/ side panel and both sides of modesty shall be pasted with 3.50 to
4.00 mm thick veneer (Make : Archid ply/ Durian/ Archid /Century/ Duro) with hot pressed glue/ adhesive of approved
- Balancing Laminate pasted below the table top shall be thickness of 0.60 mm in gloss / matt finish with high density (L)1500x(W)750x(H)750-24no
9 Confrence table protective surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality. +750X750X750*3 no sqm 60 27,382.00 16,42,920.00
- There is a provision of Openable raceways size 1500 (L) x200 (D) x200 (H) mm for operating with double end lock ( part size)
attached below the table top for all data and electric wiring flow should be made out of 18mm thick commercial ply of
MR grade (Make: Sumo/Century Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 including with
0.60mm thick laminate (Make: Cedar Lam /Durian /Archid ply /IPL /Royal Touch) IS 2046 : 1995 matching with
tabletop color.
- Raceway having cut outs of required sizes for installing electric switch boards ( switch samples provided by client)
there will be separate slots for passage of data and electrical wires. The frames designed to easily handle CAT6 wire
at entry points. Two numbers of powder coated MS tube size 50 x 50 x 1.2mm thick should be provided for electrical
& data cable flow.
- The working or non-working edges shall be provided with veneer edge binding using with special hot melt glue at hot
temperature. All necessary hardware/ fitting/ hinges etc. of approved quality (Make: Ebco/Hettich/Kitch/ Hafele).
- Veneer to be use is American Oak/ Steam Beach or similar price of make Archid ply/ Durian/ Century/ Duro.
- All veneered portion to be polished minimum four layered of PU coating with sprayed finish in desired shade using
- For installation of table wooden dowels and minifix to use for additional support.
- All Complete job as per direction of Engineer -in –Charge.
- For payment purpose top surface area/ plan area will be measured.
Providing and fixing in position of customised design ref. images and shop drawing as approveds Sliding Tile Base
Workstation ( T-7) including drawer unit as per sizes:
- Free standing partition height 1200mm and should be minimum of 55mm thick. Partition inner frame is 1.1mm thick
mild steel. Horizontal and vertical trims are made out of extruded aluminium of 1.0mm thick.
- All Panels/trims shall be powder coated with 50 microns. Aluminium trims are elegantly fixed with special fixtures in
the partition. The framework shall be fitted with 9mm thick pre laminated Particle tiles of approved shade.
- Partition shall have provision for pin up board with fabric/ white marker/ laminated of approved shade.
- Partition framework shall have adequate provisions for the movement of electric data cables at desired 2 levels; one
at skirting and another above / below the table top. Panel have cut-outs of required sizes for installing electric switch
boards ( switch samples provided by client) there will be separate slots for passage of data and electrical wires. The
frames designed to easily handle CAT6 wire at entry points. The complete partitioning work shall be carried out as per
the approved drawing.
- Balancing Laminate pasted on below the top shall be thickness of 0.60mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
10 E3-E5 - Table top for workstation shall be made up of 25mm thick commercial ply of MR grade (Make: Sumo /Century (L)1400x(W) 600x (H) 750 Each 120 43,523.00 52,22,760.00
Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 including with 1mm thick decorative / coloured high
pressure laminated sheet (Make: Cedar Lam /Durian /Archid ply/Archid / IPL /Royal Touch) with hot pressed glue
including cost of glue/ adhesive of approved quality.
- Side panel shall be made out of 18/19mm thick commercial ply of MR grade (Make: Sumo/Century Architect Ply
/Durian /Archid /Greenlam Club) IS 303 : 1989 including with 1mm thick laminate (Make: Cedar Lam /Durian /Archid
ply /IPL Archid/ Royal Touch) IS 2046 : 1995 on both side matching with tabletop and contained the thickness shall be
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. Metal Keyboard with telescopic channel for smooth operation.
- Metal CPU trolley with lockable castors for smooth operation on floor.
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower
bolts/ handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired and direction of Engineer -in –Charge. .
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approveds Sliding Tile Base
Workstation ( T-8) including drawer unit as per sizes:
- Free standing partition height 1200mm and should be minimum of 55mm thick. Partition inner frame is 1.1mm thick
mild steel. Horizontal and vertical trims are made out of extruded aluminium of 1.0mm thick.
- All Panels/trims shall be powder coated with 50 microns. Aluminium trims are elegantly fixed with special fixtures in
the partition. The framework shall be fitted with 9mm thick pre laminated Particle tiles of approved shade.
- Partition shall have provision for pin up board with fabric/ white marker/ laminated of approved shade.
- Partition framework shall have adequate provisions for the movement of electric data cables at desired 2 levels; one
at skirting and another above / below the table top. Panel have cut-outs of required sizes for installing electric switch
boards ( switch samples provided by client) there will be separate slots for passage of data and electrical wires. The
frames designed to easily handle CAT6 wire at entry points. The complete partitioning work shall be carried out as per
the approved drawing.
- Balancing Laminate pasted on below the top shall be thickness of 0.60mm in gloss / matt finish with high density
protective surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
11 E2 & below - Table top for workstation shall be made up of 25mm thick commercial ply of MR grade (Make: Sumo /Century (L)1200x(W) 600x (H) 750 Each 89 41,346.00 36,79,794.00
Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 including with 1mm thick decorative / coloured high
pressure laminated sheet (Make: Cedar Lam /Durian /Archid ply/Archid / IPL /Royal Touch) with hot pressed glue
including cost of glue/ adhesive of approved quality.
- Side panel shall be made out of 18/19mm thick commercial ply of MR grade (Make: Sumo/Century Architect Ply
/Durian /Archid /Greenlam Club) IS 303 : 1989 including with 1mm thick laminate (Make: Cedar Lam /Durian /Archid
ply /IPL Archid/ Royal Touch) IS 2046 : 1995 on both side matching with tabletop and contained the thickness shall be
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. Metal Keyboard with telescopic channel for smooth operation.
- Metal CPU trolley with lockable castors for smooth operation on floor.
-All CRCA steel components / parts powder coated of 50-60 micron. All necessary hardware/ fitting/ hinges/ tower
bolts/ handles etc. of approved quality (Make: Ebco/Hettich/Kitch).
- All Complete job as desired and direction of Engineer -in –Charge. .
Providing and fixing in position of customised design ref. images and shop drawing as approved Meeting table (T- 9)
with decorative laminate as approved of required size:
- Table top shall be made out of 24mm thick commercial ply of MR grade (Make: Sumo /Century Architect Ply /Durian
/Archid ply /Greenlam Club) IS 303 : 1989
- The vertical support shall be made out of 18mm thick commercial ply of MR grade (Make: Sumo /Century Architect
Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 and modesty shall be made out of 18mm thick commercial ply of
MR grade (Make: Sumo /Century Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 having height of 650
mm to 700 mm shall be fixed at mid of table top.
- Table top surface shall be pasted with 1.00 mm thick decorative / coloured high pressure laminated sheet (Make:
Cedar Lam /Durian /Archid ply/ Archid /IPL /Royal Touch) with hot pressed glue including cost of glue/ adhesive of
approved quality.
- Balancing Laminate shall be pasted below the table top, both sides of vertical support/ side panel and both sides of
12 AUDITOR TABLE modesty shall be thickness of 0.60 mm thick decorative / coloured in gloss / matt finish with high density protective (3000X1500X750) *1 sqm 5 38,527.00 1,92,635.00
surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
- Raceway having cut outs of required sizes for installing electric switch boards ( switch samples provided by client)
there will be separate slots for passage of data and electrical wires. The frames designed to easily handle CAT6 wire
at entry points.
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. All necessary hardware/ fitting etc. of approved quality (Make:
Ebco/Hettich/Kitch/ Hafele)..
- For installation of table wooden dowels and minifix to use for additional support.
- All complete as desired and as per direction and satisfaction of Engineer-in-charge.
For payment purpose top surface area will be measured.
Providing and fixing in position of customised design ref. images and shop drawing as approved Dinning Table ( T 11)
with first class solid teak wood frame with 12mm thick beveled edge toughened glass top to be provided. PU Polishing –
General Holes and indentations on surface shall be filled with putty made of whiting and linseed oil. The pad shall be
13 DINING TABLE moistened with polish and rubbed hard on the surface applying the polish sparingly but uniformly and completely over the (L)900x(D) 900x(H)750 Each 5 29,183.00 1,45,915.00
entire surface. Another coat shall be applied in the same way after the first coat has dried sufficiently. Finishing coats
shall be sprayed on the surface in 2 coats or as required till the satisfied result, using PU/melamine polish of approved
make. All complete as per direction and satisfaction of Engineer-in-charge.
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approved Meeting table (T-
12) with decorative laminate as approved of required size:
- Table top shall be made out of 24mm thick commercial ply of MR grade (Make: Sumo /Century Architect Ply /Durian
/Archid ply /Greenlam Club) IS 303 : 1989
- The vertical support shall be made out of 18mm thick commercial ply of MR grade (Make: Sumo /Century Architect
Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 and modesty shall be made out of 18mm thick commercial ply of
MR grade (Make: Sumo /Century Architect Ply /Durian /Archid ply /Greenlam Club) IS 303 : 1989 having height of 650
mm to 700 mm shall be fixed at mid of table top.
- Table top surface shall be pasted with 1.00 mm thick decorative / coloured high pressure laminated sheet (Make:
Cedar Lam /Durian /Archid ply/ Archid /IPL /Royal Touch) with hot pressed glue including cost of glue/ adhesive of
approved quality.
- Balancing Laminate shall be pasted below the table top, both sides of vertical support/ side panel and both sides of
14 MEETING TABLE modesty shall be thickness of 0.60 mm thick decorative / coloured in gloss / matt finish with high density protective (2400X1200X750) *8 sqm 24 24,663.00 5,91,912.00
surface layer pasted with hot pressed glue including cost of glue/ adhesive of approved quality.
- Raceway having cut outs of required sizes for installing electric switch boards ( switch samples provided by client)
there will be separate slots for passage of data and electrical wires. The frames designed to easily handle CAT6 wire
at entry points.
- The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. All necessary hardware/ fitting etc. of approved quality (Make:
Ebco/Hettich/Kitch/ Hafele)..
- For installation of table wooden dowels and minifix to use for additional support.
- All complete as desired and as per direction and satisfaction of Engineer-in-charge.
For payment purpose top surface area will be measured.
Control Room Furniture/Operator Console
Workspace make New Modular Control Desk for Provision of 02 nos. 24'' Monitors made in " Dynamic XE "system.
1. Table-top:The material of the working surface shall be minimum 25 mm thick MDF with High-Pressure laminate.
Adequate space shall be provided on the desktop for writing area, to accommodate the operator workstation, mouse,
telephone console and other miscellaneous items. Proposed console shall not have any hazardous substances.
2.1 Made of heavy duty extruded vertical and horizontal aluminium profiles. The extrusions shall be duly powder
coated with 40+microns over all surfaces. All sheet metal parts shall be finished with a durable, black, electrostatic
powder coating. The structure shall allow easy assembly of shutters and gland plate in extremely rigid manner.
2.2 To allow future extension and expansion, a weld-free system shall be proposed. Interconnecting joints shall not be
The structure shall be rigid enough to withstand BIFMA X5.5 tests.The structure shall allow easy assembly of hinged
shutters, table top, side leg and gland plate in extremely rigid manner.
3. Modular removable PU nosing: The front edge of consoles is the component which comes in frequent contact of the
The soft polyurethane edge is meant to prevent injury (accidental impact) to operator during emergency and it also
reduces the contact stress. In case of damage to this edge the desk design shall permit quick & easy replacement
within half an hour without taking any shutdowns or removal of the tabletops. Audit certified design feature of modular
PU Edge: High-density poly-urethane moulded on industrial grade aluminium core to form 50mm deep tapered edge to
be installed on worktop. In case of damage or wear, the edge shall be mechanically replaceable within 30 minutes
without opening or removing the worktop.
4. Shutters: - The shutter tiles shall be made of minimum 1mm Thick MS sheet with Powder coated finish. The shutter
tile shall be class A fire rated as per ASTM e84 (from UL/Intertek) for surface burning characteristics.
5 Side Legs: - Extreme end side leg shall have sandwich construction made up of 18mm thick laminated MDF
boards/Alumina Tri-hydrate and acrylic resin material.The central portion of the side leg shall feature illuminated strip
SOC CONTROL on the periphery.The proposed console shall be Greenguard Gold certified.
6. Desktop Automation: - Hassle free ergonomic operations/adjustments and durability of the product, the console shall
have UL/Intertek audit certified feature on all mechanisms of console. The mechanisms shall be tested & certified for at
least 1000 time synchronous up-down movement of worktop, tilt adjustments, up-down and front-back movement of
monitor base w.r.t.worktop and all these mechanisms shall be operated by using single touch screen.
7 Desktop Lift Mechanism: - Adjustable (Height) Desks (sit-and-stand with step-less automatic height adjustment).
8. Touch Screen: - Programmable touch screen controls shall be provided for operator movements with 20 autosave
preset options related to desk movements/position. The preset shall be used to define the desk configuration.The
integrated illumination strip shall have RGB colors. The Illumination color shall be controlled by this touchscreen for
different scenario like blue for VIP visit, green for Normal Operations and red for emergency etc 9. Height Adjustable
Mechanisms for Monitor Base: - Height adjustable ±3” (±75mm) with respect to tabletop. Height shall be adjusted with
electrical drive. Monitors shall also have depth adjustment feature in horizontal plane up-to 100mm. Independent
electronic powered height adjustment of platform and workspace.
10. Monitor tilt variation with motorized height/tilt/depth adjustment: - Monitor screens tilt shall be adjusted with
electrical drive at desired angle, depth & curvilinear arrangement of screens depending on the operator's ease of
working. It shall be capable for mounting all type of LCD display with dimensions between 17” to 24” using suitable
adapter /additional base plate for complying VESA standards 75 x 75, 100 x 100. All the monitor screens shall have
synchronized tilting with 0 to 60ᵒ from vertical plane by single control, customisable.
All complete as desired and as per direction and satisfaction of Engineer-in-charge. For payment purpose top surface
area will be measured.
Digitally signed by ANUJ
Providing and Placing in position of Main Entrence Reception curve seven seater Sofa cum centre table (750 mm
dia) as per Reference image /photograph or equivqlent as approved. The contemporary customised design &
drawings sofa of Size : (L)600.0cm X (D)75.0cm X (H)75.0cm, seat height 46.0cm, seat depth 51.0cm and back
height 55.0cm, should be upholstered in premium leatherette, this sofa is sleek and comfortable. The wooden frame is
finished in a rich brown polish with split panel seating. The back and seat have medium to firm cushioning for better
posture. The Sofa stands on moulded pvc legs beautiful accents that are slightly curved on the front face of the sofa.
16 MR Each curve defines a seating space which provides for people to be seated comfortably. Finished in a luxurious Each 1 2,30,201.00 2,30,201.00
Leatherette, the sofa exudes a certain class. Seat of Sofa is layered with silicon fibre filling over high density foam.
The seat cushion is made of multi layered foam of density 32(+/-2kg /m3). The seating cushions have 2.75 & 1.75
inches of elastic webbing. The thread used is nylon bonded to provide lasting stitch strength. All complete as per
direction and satisfaction of Engineer-in-charge.
Providing and Placing in position of Three Seater Sofa ( S3) as per Reference image /photograph or equivqlent as
approved. The contemporary customised design & drawings sofa of Size : (L)180.0cm X (D)75.0cm X (H)85.0cm,
seat height 46.0cm, seat depth 51.0cm and back height 55.0cm, should be upholstered in premium leatherette, this
sofa is sleek and comfortable. The wooden frame is finished in a rich brown polish with split panel seating. The back
and seat have medium to firm cushioning for better posture. The Sofa stands on moulded pvc legs beautiful accents
that are slightly curved on the front face of the sofa. Each curve defines a seating space which provides for people to
be seated comfortably. Finished in a luxurious Leatherette, the sofa exudes a certain class. Seat of Sofa is layered
17 MR with silicon fibre filling over high density foam. The seat cushion is made of multi layered foam of density 32(+/-2kg Each 9 58,349.00 5,25,141.00
/m3). The seating cushions have 2.75 & 1.75 inches of elastic webbing. The thread used is nylon bonded to provide
lasting stitch strength. All complete as per direction and satisfaction of Engineer-in-charge.
Providing and Placing in position of Two Seater Sofa ( S2) as per Reference image /photograph or equivqlent as
approved. The contemporary customised design & drawings sofa of Size : (L)150.0cm X (D)75.0cm X (H)85.0cm,
seat height 46.0cm, seat depth 51.0cm and back height 55.0cm, should be upholstered in premium leatherette, this
sofa is sleek and comfortable. The wooden frame is finished in a rich brown polish with split panel seating. The back
and seat have medium to firm cushioning for better posture. The Sofa stands on moulded pvc legs beautiful accents
that are slightly curved on the front face of the sofa. Each curve defines a seating space which provides for people to
be seated comfortably. Finished in a luxurious Leatherette, the sofa exudes a certain class. Seat of Sofa is layered
18 MR with silicon fibre filling over high density foam. The seat cushion is made of multi layered foam of density 32(+/-2kg Each 6 38,893.00 2,33,358.00
/m3). The seating cushions have 2.75 & 1.75 inches of elastic webbing. The thread used is nylon bonded to provide
lasting stitch strength. All complete as per direction and satisfaction of Engineer-in-charge.
Providing and Placing in position of Single Seater Sofa ( S1) as per Reference image /photograph or equivqlent as
approved. The contemporary customised design & drawings sofa of Size : (L)75cm X (D75.0cm X (H)85.0cm, seat
height 46.0cm, seat depth 51.0cm and back height 55.0cm, should be upholstered in premium leatherette, this sofa is
sleek and comfortable. The wooden frame is finished in a rich brown polish with split panel seating. The back and seat
have medium to firm cushioning for better posture. The Sofa stands on moulded pvc legs beautiful accents that are
slightly curved on the front face of the sofa. Each curve defines a seating space which provides for people to be
19 MR seated comfortably. Finished in a luxurious Leatherette, the sofa exudes a certain class. Seat of Sofa is layered with Each 20 27,780.00 5,55,600.00
silicon fibre filling over high density foam. The seat cushion is made of multi layered foam of density 32(+/-2kg /m3).
The seating cushions have 2.75 & 1.75 inches of elastic webbing. The thread used is nylon bonded to provide lasting
stitch strength. All complete as per direction and satisfaction of Engineer-in-charge.
Providing and fixing in position of customised design ref. images and shop drawing as approved Center Table ( T13)
with first class solid teak wood frame with 12mm thick beveled edge toughened glass top to be provided. PU Polishing –
General Holes and indentations on surface shall be filled with putty made of whiting and linseed oil. The pad shall be
moistened with polish and rubbed hard on the surface applying the polish sparingly but uniformly and completely over the
entire surface. Another coat shall be applied in the same way after the first coat has dried sufficiently. Finishing coats
shall be sprayed on the surface in 2 coats or as required till the satisfied result, using PU/melamine polish of approved
make. All complete as per direction and satisfaction of Engineer-in-charge.
Providing and fixing in position of customised design ref. images and shop drawing as approved Side Table ( T14) with
first class solid teak wood frame with 12mm thick beveled edge toughened glass top to be provided. PU Polishing ,
General Holes and indentations on surface shall be filled with putty made of whiting and linseed oil. The pad shall be
moistened with polish and rubbed hard on the surface applying the polish sparingly but uniformly and completely over the
entire surface. Another coat shall be applied in the same way after the first coat has dried sufficiently. Finishing coats
VISITOR SIDE shall be sprayed on the surface in 2 coats or as required till the satisfied result, using PU /melamine polish of approved
TABLE make. All complete as per direction and satisfaction of Engineer-in-charge.
Digitally signed by ANUJ
Providing and fixing in position of customised design ref. images and shop drawing as approved Side Table ( T14a) with
first class solid teak wood frame with 12mm thick beveled edge toughened glass top to be provided. PU Polishing ,
General Holes and indentations on surface shall be filled with putty made of whiting and linseed oil. The pad shall be
moistened with polish and rubbed hard on the surface applying the polish sparingly but uniformly and completely over the (L)600x (D)
22 entire surface. Another coat shall be applied in the same way after the first coat has dried sufficiently. Finishing coats Each 17 29,125.00 4,95,125.00
TABLE 450x(H)450
shall be sprayed on the surface in 2 coats or as required till the satisfied result, using PU /melamine polish of approved
make. All complete as per direction and satisfaction of Engineer-in-charge.
Providing and fixing in position of customised Design & Drawing Storage unit ( ST1 ) with deorative laminate as
approved at all floors of Depth 600 mm of required size all complete as per direction and satisfaction of Engineer-in-
- Storage carcase and shutter shall be made of 18 mm thick commercial plywood of MR grade (Make: Sumo/Century
Architect Ply /Durian /Archid ply /Archid classic/Greenlam Club) IS 303 : 1989 and storage backing shall be 12 mm
thick commercial plywood of MR grade IS 303 : 1989. The gap between 2 shelves should be range from 400 mm as
per the direction of EIC.
- Storage top, sides and front facia shall be shall be pasted with 1.00 mm thick decorative / coloured high pressure
laminated sheet (Make: Cedar Lam /Durian /Archid ply /IPL/Archid /Royal Touch) with hot pressed glue including cost
of glue/ adhesive of approved quality
- Balancing Laminate pasted on storage below the top, back, inner area of storage shall be thickness of 0.60 mm in
gloss / matt finish with high density protective surface layer pasted with hot pressed glue including cost of glue/
STORAGE adhesive of approved quality. 1200X450X2100/
CABINET 01 - The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using 600x450x2100
with special hot melt glue at hot temperature. All necessary hardware/ fitting/ hinges etc. of approved quality (Make:
Ebco/Hettich/Kitch).
- Each shutter should be fixed with 2 / 3 numbers SS butt hinges,round shape multipurpose lock, SS tower bolt of 100
x 10mm, Magnetic double strip catcher. Shutter shall have 100 mm size SS fancy handles (one on each drawer) with
minimum of 6 thread necessary hardware/ fitting/ hinges etc. of approved quality(Make: Ebco/Hettich/Kitch/
Hafele/Sumsung Irex).
- Shelf should have metal stiffener complete end to end for extra load & two numbers heavy duty SS shelf pin on each
- For installation of storage wooden dowels and minifix to use for additional support.
- All complete as per direction and satisfaction of Engineer-in-charge.
- For payment purpose front surface will be measured..
Providing and fixing in position of customised Design & Drawing Storage unit ( ST1 ) with deorative laminate as
approved at all floors of Depth 600 mm of required size all complete as per direction and satisfaction of Engineer-in-
- Storage carcase and shutter shall be made of 18 mm thick commercial plywood of MR grade (Make: Sumo/Century
Architect Ply /Durian /Archid ply /Archid classic/Greenlam Club) IS 303 : 1989 and storage backing shall be 12 mm
thick commercial plywood of MR grade IS 303 : 1989. The gap between 2 shelves should be range from 400 mm as
per the direction of EIC.
- Storage top, sides and front facia shall be shall be pasted with 1.00 mm thick decorative / coloured high pressure
laminated sheet (Make: Cedar Lam /Durian /Archid ply /IPL/Archid /Royal Touch) with hot pressed glue including cost
of glue/ adhesive of approved quality
- Balancing Laminate pasted on storage below the top, back, inner area of storage shall be thickness of 0.60 mm in
gloss / matt finish with high density protective surface layer pasted with hot pressed glue including cost of glue/
STORAGE adhesive of approved quality.
CABINET 02 - The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. All necessary hardware/ fitting/ hinges etc. of approved quality (Make:
Ebco/Hettich/Kitch).
- Each shutter should be fixed with 2 / 3 numbers SS butt hinges,round shape multipurpose lock, SS tower bolt of 100
x 10mm, Magnetic double strip catcher. Shutter shall have 100 mm size SS fancy handles (one on each drawer) with
minimum of 6 thread necessary hardware/ fitting/ hinges etc. of approved quality(Make: Ebco/Hettich/Kitch/
Hafele/Sumsung Irex).
- Shelf should have metal stiffener complete end to end for extra load & two numbers heavy duty SS shelf pin on each
- For installation of storage wooden dowels and minifix to use for additional support.
- All complete as per direction and satisfaction of Engineer-in-charge.
- For payment purpose front surface will be measured..
Digitally signed by ANUJ
Providing and fixing in position of customised Design & Drawing Storage unit ( ST2 ) with deorative laminate as
approved at all floors of Depth 600 mm of required size all complete as per direction and satisfaction of Engineer-in-
- Storage carcase and shutter shall be made of 18 mm thick commercial plywood of MR grade (Make: Sumo/Century
Architect Ply /Durian /Archid ply /Archid classic/Greenlam Club) IS 303 : 1989 and storage backing shall be 12 mm
thick commercial plywood of MR grade IS 303 : 1989. The gap between 2 shelves should be range from 400 mm as
per the direction of EIC.
- Storage top, sides and front facia shall be shall be pasted with 1.00 mm thick decorative / coloured high pressure
laminated sheet (Make: Cedar Lam /Durian /Archid ply /IPL/Archid /Royal Touch) with hot pressed glue including cost
of glue/ adhesive of approved quality
- Balancing Laminate pasted on storage below the top, back, inner area of storage shall be thickness of 0.60 mm in
gloss / matt finish with high density protective surface layer pasted with hot pressed glue including cost of glue/
STORAGE adhesive of approved quality.
CABINET O2 - The working or non-working edges shall be provided with matching machine pressed 2mm thick PVC edging using
with special hot melt glue at hot temperature. All necessary hardware/ fitting/ hinges etc. of approved quality (Make:
Ebco/Hettich/Kitch).
- Each shutter should be fixed with 2 / 3 numbers SS butt hinges,round shape multipurpose lock, SS tower bolt of 100
x 10mm, Magnetic double strip catcher. Shutter shall have 100 mm size SS fancy handles (one on each drawer) with
minimum of 6 thread necessary hardware/ fitting/ hinges etc. of approved quality(Make: Ebco/Hettich/Kitch/
Hafele/Sumsung Irex).
- Shelf should have metal stiffener complete end to end for extra load & two numbers heavy duty SS shelf pin on each
- For installation of storage wooden dowels and minifix to use for additional support.
- All complete as per direction and satisfaction of Engineer-in-charge.
- For payment purpose front surface will be measured..
Providing & Placing in position of High back with leather upholstery chair ( C1 ) as per Reference image
/photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed
plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness
load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The
back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02
cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat
depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Providing & Placing in position of medium back with leather upholstery chair ( C1a ) as per Reference image
/photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed
plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness
load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The
back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02
cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
27 in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat Each 4 33,446 1,33,784.00
depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Digitally signed by ANUJ
Providing & Placing in position of High back with leather upholstery chair ( C2) as per Reference image
/photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed
plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness
load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The
back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02
cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
28 DIRECTOR CHAIR in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat Each 9 33,446 3,01,014.00
depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Providing & Placing in position of Medium back with leather upholstery chair ( C2a) as per Reference image
/photograph or equivqlent as approved. Chair seat shall be made up of 1.2+/-0.1cm hot pressed plywood upholstered
in mesh fabric and moulded with PU foam superior load capacity of over 135 kgs, Seat Size is 45.0 W cm x 47.0 D
cm. Chair having a back in one piece curved design shall be made of injection moulded plastic outer & inner
upholstered with breathable nylon mesh superior load capacity of over 135 kgs. The back size is 46.0 W cm x 58.0 H
cm. Chair breathable nylon mesh having with creative tree detailing on the back, so when you look at it from afar it
feels as if a tree is emerging from the roots to the branches and leaves on the top. The leaves add function to the
design height adjustable lumbar support for improving of seating capacity and lumbar support. The armrest top is
moulded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps and having the adjustment of forward/ backword feature for extra support and comfort. The
DIRECTOR armrest is scratch and whether resistant. The arm rests are fitted to the seat with a connecting strip assembly made of
29 5mm of HR steel. The adjustable tilting mechanism is designed with following features : 360° revolving type, front- Each 15 32,233 4,83,495.00
pivot for tilt with feet resting on ground and tilt tension adjustment can be operated in seating position, 5 position tilt
limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2 with synchro tilt mechanism. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm, shall be operated at 30kgs extension force and
lever should be attached right side between injection moulded plastic outer & inner of the seat frame. The pedestal is
high pressure die cast polished aluminium 65.0±0.5cm pitch centre dia. (75.0±1.0cm with castors). 5 nos. of twin
wheel castors are injection moulded in nylon having 6.0±0.1cm wheel diameter and assembled to pedestal. The
telescopic bellows is 3 piece telescopic type and injection moulded in black polyurethane. Complete as per direction of
Engineer -in –Charge.
Providing & Placing in position of High back with leatheritte upholstery chair ( C3 ) as per Reference image
/photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed
plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness
load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The
back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02
cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
30 E 7,8&9 CHAIR in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat Each 61 27,727 16,91,347.00
depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Digitally signed by ANUJ
Providing & Placing in position of Medium back with leatheritte upholstery chair ( C3a ) as per Reference image
/photograph or equivqlent as approved. Chair seat shall be made up of 1.2+/-0.1cm hot pressed plywood upholstered
in mesh fabric and moulded with PU foam superior load capacity of over 135 kgs, Seat Size is 45.0 W cm x 47.0 D
cm. Chair having a back in one piece curved design shall be made of injection moulded plastic outer & inner
upholstered with breathable nylon mesh superior load capacity of over 135 kgs. The back size is 46.0 W cm x 58.0 H
cm. Chair breathable nylon mesh having with creative tree detailing on the back, so when you look at it from afar it
feels as if a tree is emerging from the roots to the branches and leaves on the top. The leaves add function to the
design height adjustable lumbar support for improving of seating capacity and lumbar support. The armrest top is
moulded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps and having the adjustment of forward/ backword feature for extra support and comfort. The
armrest is scratch and whether resistant. The arm rests are fitted to the seat with a connecting strip assembly made of
E 7,8&9 VISITOR 5mm of HR steel. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-
CHAIR pivot for tilt with feet resting on ground and tilt tension adjustment can be operated in seating position, 5 position tilt
limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2 with synchro tilt mechanism. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm, shall be operated at 30kgs extension force and
lever should be attached right side between injection moulded plastic outer & inner of the seat frame. The pedestal is
high pressure die cast polished aluminium 65.0±0.5cm pitch centre dia. (75.0±1.0cm with castors). 5 nos. of twin
wheel castors are injection moulded in nylon having 6.0±0.1cm wheel diameter and assembled to pedestal. The
telescopic bellows is 3 piece telescopic type and injection moulded in black polyurethane. Complete as per direction of
Engineer -in –Charge.
Providing & Placing in position of Medium back with leatheritte upholstery chair ( C4 ) as per Reference image
/photograph or equivqlent as approved. Chair seat shall be made up of 1.2+/-0.1cm hot pressed plywood upholstered
in mesh fabric and moulded with PU foam superior load capacity of over 135 kgs, Seat Size is 45.0 W cm x 47.0 D
cm. Chair having a back in one piece curved design shall be made of injection moulded plastic outer & inner
upholstered with breathable nylon mesh superior load capacity of over 135 kgs. The back size is 46.0 W cm x 58.0 H
cm. Chair breathable nylon mesh having with creative tree detailing on the back, so when you look at it from afar it
feels as if a tree is emerging from the roots to the branches and leaves on the top. The leaves add function to the
design height adjustable lumbar support for improving of seating capacity and lumbar support. The armrest top is
moulded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps and having the adjustment of forward/ backword feature for extra support and comfort. The
E-6 CHAIR armrest is scratch and whether resistant. The arm rests are fitted to the seat with a connecting strip assembly made of
( work station) 5mm of HR steel. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-
pivot for tilt with feet resting on ground and tilt tension adjustment can be operated in seating position, 5 position tilt
limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2 with synchro tilt mechanism. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm, shall be operated at 30kgs extension force and
lever should be attached right side between injection moulded plastic outer & inner of the seat frame. The pedestal is
high pressure die cast polished aluminium 65.0±0.5cm pitch centre dia. (75.0±1.0cm with castors). 5 nos. of twin
wheel castors are injection moulded in nylon having 6.0±0.1cm wheel diameter and assembled to pedestal. The
telescopic bellows is 3 piece telescopic type and injection moulded in black polyurethane. Complete as per direction of
Engineer -in –Charge.
Providing & Placing in position of Medium back with leatheritte upholstery chair ( C5 ) as per Reference image
/photograph or equivqlent as approved. Chair seat shall be made up of 1.2+/-0.1cm hot pressed plywood upholstered
in mesh fabric and moulded with PU foam superior load capacity of over 135 kgs, Seat Size is 45.0 W cm x 47.0 D
cm. Chair having a back in one piece curved design shall be made of injection moulded plastic outer & inner
upholstered with breathable nylon mesh superior load capacity of over 135 kgs. The back size is 46.0 W cm x 58.0 H
cm. Chair breathable nylon mesh having with creative tree detailing on the back, so when you look at it from afar it
feels as if a tree is emerging from the roots to the branches and leaves on the top. The leaves add function to the
design height adjustable lumbar support for improving of seating capacity and lumbar support. The armrest top is
moulded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps and having the adjustment of forward/ backword feature for extra support and comfort. The
E-5,3,2, control armrest is scratch and whether resistant. The arm rests are fitted to the seat with a connecting strip assembly made of
room & below 5mm of HR steel. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-
CHAIR pivot for tilt with feet resting on ground and tilt tension adjustment can be operated in seating position, 5 position tilt
limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2 with synchro tilt mechanism. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm, shall be operated at 30kgs extension force and
lever should be attached right side between injection moulded plastic outer & inner of the seat frame. The pedestal is
high pressure die cast polished aluminium 65.0±0.5cm pitch centre dia. (75.0±1.0cm with castors). 5 nos. of twin
wheel castors are injection moulded in nylon having 6.0±0.1cm wheel diameter and assembled to pedestal. The
telescopic bellows is 3 piece telescopic type and injection moulded in black polyurethane. Complete as per direction of
Engineer -in –Charge.
Digitally signed by ANUJ
Providing & Placing in position of Medium back with leatheritte upholstery chair ( C6 ) as per Reference image
/photograph or equivqlent as approved. Chair seat shall be made up of 1.2+/-0.1cm hot pressed plywood upholstered
in mesh fabric and moulded with PU foam superior load capacity of over 135 kgs, Seat Size is 45.0 W cm x 47.0 D
cm. Chair having a back in one piece curved design shall be made of injection moulded plastic outer & inner
upholstered with breathable nylon mesh superior load capacity of over 135 kgs. The back size is 46.0 W cm x 58.0 H
cm. Chair breathable nylon mesh having with creative tree detailing on the back, so when you look at it from afar it
feels as if a tree is emerging from the roots to the branches and leaves on the top. The leaves add function to the
design height adjustable lumbar support for improving of seating capacity and lumbar support. The armrest top is
moulded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps and having the adjustment of forward/ backword feature for extra support and comfort. The
armrest is scratch and whether resistant. The arm rests are fitted to the seat with a connecting strip assembly made of
34 5mm of HR steel. The adjustable tilting mechanism is designed with following features : 360° revolving type, front- Each 3 25863.00 77,589.00
pivot for tilt with feet resting on ground and tilt tension adjustment can be operated in seating position, 5 position tilt
limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2 with synchro tilt mechanism. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm, shall be operated at 30kgs extension force and
lever should be attached right side between injection moulded plastic outer & inner of the seat frame. The pedestal is
high pressure die cast polished aluminium 65.0±0.5cm pitch centre dia. (75.0±1.0cm with castors). 5 nos. of twin
wheel castors are injection moulded in nylon having 6.0±0.1cm wheel diameter and assembled to pedestal. The
telescopic bellows is 3 piece telescopic type and injection moulded in black polyurethane. Complete as per direction of
Engineer -in –Charge.
Providing & Placing in position of Medium back with leatheritte upholstery chair ( Meeting Room ) as per
Reference image /photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm
hot pressed plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2
kg/m³, & hardness load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D
cm + 2 cm . The back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ±
0.03cm x 0.16 ± 0.02 cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest
top is molded from polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of
Ø3.81±0.03cm x 0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to
6.5±0.5 cm in 5 steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-
pivot for tilt with feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment
can be operated in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt
35 MEETING CHAIR Each 20 44269.00 8,85,380.00
ratio 1:2, Seat depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is
of 6.0±0.5cm. It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need.
The pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Providing & Placing in position of High back leather upholstery chair as per Reference image /photograph or
equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed plywood is
upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness load of
16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The back is
cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02 cm,
upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
BOARD ROOM/ feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
CONFERENCE in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat
ROOM CHAIR depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
PERSON It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Digitally signed by ANUJ
Providing & Placing in position of Medium back with leatheritte upholstery chair as per Reference image
/photograph or equivqlent as approved . The cushioned seat and back shall be made of 1.2+/-0.1cm hot pressed
plywood is upholstered with leather and moulded high resilience polyurethane foam of density 45±2 kg/m³, & hardness
load of 16±2 kgf as per IS:7888 for 25% compression. Seat Size is 47.0 W cm + 2cm W x 48.0 D cm + 2 cm . The
back is cushioned made of PU foam with insitu moulded M.S. ERW round tube of size 1.9 cm ± 0.03cm x 0.16 ± 0.02
cm, upholstered with leather. The back size is 48 W cm + 2 cm x 77 D cm + 2 cm . The armrest top is molded from
polyurethane and mounted on to a drop lift adjustable type tubular armrest support made of Ø3.81±0.03cm x
0.2±0.01cm thick M.S. ERW tube having chrome plated finish. The armrest is height adjustable up to 6.5±0.5 cm in 5
steps. The adjustable tilting mechanism is designed with following features : 360° revolving type, front-pivot for tilt with
BOARD ROOM/ feet resting on ground and continuous lumbar support ensuring more comfort, tilt tension adjustment can be operated
37 CONFERENCE in seating position, 5position tilt limiter giving option of variable tilt angle to the chair, Seat/back tilt ratio 1:2, Seat Each 96 59,997.00 57,59,712.00
ROOM CHAIR depth adjustment is integrated in the seat through a sliding mechanism. Seat depth adjustment range is of 6.0±0.5cm.
It can be adjusted in the range of 7.42±0.5 comfort the comfortable back support to suit individual need. The
pneumatic height adjustment has an adjustment stroke of 10.0±0.3cm. The pedestal is high pressure die cast
polished aluminium & fitted with 5 nos. of twin wheel castors. The pedestal is 65.0±0.5cm pitch centre dia.
(75.0±1.0cm with castors). 5 nos. of twin wheel castors are injection moulded in plastic having 6.0±0.1cm wheel
diameter and assembled to pedestal. All complete as per direction and satisfaction of Engineer-in-charge.
Café chair : Designed to hold straps & handbags, UNDERSTRUCTURE Powder Coated
UPHOLSTERY Bent Ply Mould Double
Side Re-Engineered Veneer. Well designed bushes to help correct
stackability and damping to shocks.
Providing and fixing in position of customised design & drawings ( factory made) Metal Storage Compactors of at
all floors to store box files, flat files, documents, etc in Push-Pull type unit with central locking system as per
drawings(variation if any with actual measurement at site will be taken). The movement of storage unit trolley is
achieved by “C” type handle of approved make with inbuilt security lock in drive wheels over rails which are installed
above floors by means of expansion type. Foundation bolts having in stoppers. The undercarriage is welded frame
made of HR sheet 3.15mm thick confirming to IS:10748 suitably fabricated to take the load based on configuration
and as per the manufacturer. Specifications: there are 4 adjustable shelves per body giving 5 loading levels and each
shelf designed to carry a UDL of 50kgs minimum. Optimizer height from floor is 2080mm (1980 body+65 under
39 carriage+35 channel system). The main body I/C shelves are made of 1mm thick CRCA steel conforming to IS:513 (L)915X(D) 915 X (H) 2080 Each 8 61,236.00 4,89,888.00
grade. The final finish consisting of epoxy polyester powder coat of approved colour and shade with a dry film
thickness of minimum 40 microns and anti-rust surface treatment as per the satisfaction of the engineer in-charge.
The complete compactor unit will be comprised of size(915x915x2080mm). the metal sheet to be used of tata sheet.
The locking arrangement of Key man or equivalent. The product should be from BIFMA/ ISO 9001-2008/ ISO 14001:
2004 certified company (photograph annexed is only for guidance). Complete as per direction and satisfaction of
engineer in-charge.
Digitally signed by ANUJ
BOQ FOR SOFT LANDSCAPE WORKS
S.No. Particulars Qty. unit Rate Amt. Particulars
1 Providing , laying and plantation at site i/c 800 each 1177.00 941600
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant as per direction of the officer-in-
Conocarpus trees 8'-10' ht
Conocarpus trees 8'-10' ht
2 Providing , laying and plantation at site i/c 1150 each 235.00 270250
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Chandni variegated 2' ht
Chandni variegated 2' ht
3 Providing , laying and plantation at site i/c 550 each 249.00 136950
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge ..
Hamelia patens 3' ht
Hamelia patens 3' ht
4 Providing , laying and plantation at site i/c 650 each 249.00 161850
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
5 Providing , laying and plantation at site i/c 250 each 249.00 62250
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge . .
Calliandra brush 4' ht
Calliandra brush 4' ht
6 Providing , laying and plantation at site i/c 2500 each 21.00 52500
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Wedelia trilobata ground cover
Wedelia trilobata ground cover
Digitally signed by ANUJ
7 Providing , laying and plantation at site i/c 200 each 277.00 55400
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Putranjiva 3' ht
Putranjiva 3' ht
8 Providing , laying and plantation at site i/c 300 each 277.00 83100
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Chandni single 3.5' ht
Chandni single 3.5' ht
9 Providing , laying and plantation at site i/c 600 each 83.00 49800
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Jade plant ground cover
Jade plant ground cover
10 Providing , laying and plantation at site i/c 30 each 4845.00 145350
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Ficus retusa topiary 6' -7' ht
Ficus retusa topiary 6' -7' ht
11 Providing , laying and plantation at site i/c 20 each 3461.00 69220
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Terminalia mantaly 10' -12'
Terminalia mantaly 10' -12'
12 Providing , laying and plantation at site i/c 5000 each 21.00 105000
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Red Irisine ground cover
Red Irisine ground cover
Digitally signed by ANUJ
13 Providing , laying and plantation at site i/c 100 each 166.00 16600
watering and removal of unserveiceable
material’s well developed fresh & healthy
Trees /Plant in 30 cm Earthen Pot/Plastic Pot
and as per direction of the officer-in-charge .
Oleander desi 3' ht
Oleander desi 3' ht
14 Providing and Displaying as per direction 4100 sqft sqft 118.00 263500
of the officer-in-charge .
Artificial grass
Artificial grass
15 Providing and Displaying as per direction 80 each 415.00 33200 Cattle manure (bag)
of the officer-in-charge . Cattle manure (bag)
Notes : all above rates are inclusive of
Ecxcavation, filling of good earth of pits for
respective plants , Supplying and stacking of
good earth at site including royalty all lead
complete (earth measured in stacks will be
reduced by 20% for payment).
Supplying ,stacking ,mixing,spreading sludge/
well decayed cattle manure inclusive required
fretilisers etc at site including royalty complete
job all lead (sludge measured in stacks will be
reduced by 8% for payment).
Complete maintenance ( 2 years ) of the entire
garden features having as per yard stick in the
garden area i.e. lawn, trees, shrubs, edge,
flower beds, foliages,creepers etc. including
hoeing,weeding pruning replacement of plants,
gap filling, watering, mowing of lawn, grass
cutting by lawn mover and brush cutter,
removal of garden waste, applying insecticide,
pesticide &fertilizers(whenever required) top
dressing of lawn with good earth and menure
and maintenance of other garden related works
as directed by office-in-charge .
Payment terms : 70% of the rates shall be paid
after plantation and 30% shall be paid 2 years
maintence period.
Digitally signed by ANUJ
PROJECT: GRID INDIA
PACKAGE :- PLUMBING WORKS
S.NO DESCRIPTION Total Amount
S.NO DESCRIPTION Total Amount
DSR 2023 Amount NS Amount
1 SANITARY FIXTURE 1,81,690 29,64,378
3 INTERNAL WATER SUPPLY 7,18,185 5,84,621
Cost Index on DSR 2022 @3% (on base of PAR 2023) per CPWD OM DG/Cost
5 GRAND TOTAL DSR + NSR 69,32,336.14
5 GRAND TOTAL DSR + NSR 69,32,336.14
Digitally signed by ANUJ
PROJECT: GRID INDIA
PACKAGE :- PLUMBING
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
SANITARY FIXTURE DSR
Providing, fixing, testing and commissioning of white vitreous China
wall mounting Wall mounted W.C with concealed cistern European
water closet with C.P. bolts, nuts, C.I. chair (painted with two coats of
enamel paint over a coat of primer) or other hanging arrangements,
bakelite / poly propylene seat & cover with C.P. hinges & rubber buffers,
C.P. brass screw, washer with all accessories. Including cutting & making
good the walls, floors, slab wherever required .
Providing and fixing Health Faucet ABS with double lock 1.0 m long 8mm
2 dia and SS flexible hose and wall hook including CP flange. 15mm dia. 54 No. 1443 77,922 MR -2
Providing and Fixing 2 Nos. support arms and backrest to mounted on the
3 track (vertically and laterally) for handicap toilet complete as required. 4 No. 1720 6,880 MR -3
Providing, fixing, testing & commissioning of C.P. brass Sensor tap.
Supply, installation , testing & commissioning first quality white vitreous
china half padestal washbasins, 32 mm CP brass waste ( full threaded)
and CP brass cast bottle trap and pipe to wall with CP brass flange and
rubber adopter for waste connection complete including filling gap
between counter and wash basin with approved type poly sulphide
sealant, cutting and making good the walls wherever required as per
manufacturer recommendation. ( for handicapt toilet)
Providing and fixing stainless steel A ISI 304 (18/8) Kitchen sink as per
IS : 13983 with CI bracket and stainless steel plug 40 mm including
painting of fittings and brackets ,cutting and making good the walls
wherever required:
Kitchen sink with drain board - 17.10.1
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Providing and fixing CP Brass Single lever telephonic wall mixer of quality
8 & make as approved by Engineer in charge. (a) 15 mm nominal dia 3 No. 6940.75 6753.3498 20,260 17.22B (DSR- 2023)
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality
& make and as per the direction of Engineer-in-charge.
Providing and fixing uplasticized connection pipe with brass union:
Providing and fixing CP BRASS towel ring complete with brackets fixed
12 to wooden cleats with CP brass screws with concealed fittings 56 No. 1227 - 68,712 MR - 6
arrangement of approved quality and colour
Providing and fixing CP Brass soap Dish Holder.
Providing and fixing C.P. brass angle valve for basin mixer and geyser
points of approved quality conforming to IS:8931
15 Providing and fixing toilet paper holder : 0 - 17.34 (DSR- 2023)
Fixing of horizontal/vertical storage type water heater of approved shade
with copper container with multi-function safety valve for high pressure
operation without additional pressure reducing valve, glass wool
16 insulation, stove enamelled M.S jacket, thermostatically controlled inner - MR - 8
heater with pilot neon lamps, angle valve on inlet connection, 15mm dia
C.P flexible connection pipe in inlet & outlet suitable for working pressure
of 5 kg/sqcm complete as required.
16.1 Capacity: 6 litres 3 No. 10311 - 30,933
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Providing and fixing white vitreous china battery based infrared sensor
operated urinal of approx. size 610 x 390 x 370 mm having pre & post
flushing with water (250 ml & 500 ml consumption), having water inlet
from back side, including fixing to wall with suitable brackets all as per
manufacturers specification and direction of Engineer-in-charge.
Providing and fixing solid state, no touch operting, fully hygienic hand
drier of approved shade with single blower, with time delay, summer &
18 winter control, music while drying, volume ON/OFF controls including 8 No. 11711 - 93,688 MR - 10
providing necessary brackets, cable from drier to Plug, Plug top key and
lock etc, complete as required.
19 Providing and fixing Coat Hook. 54 No. 686 - 37,027 MR - 11
20 Providing and fixing soil, waste and vent pipes :
Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989.
Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989.
Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989.
Providing and fixing on wall face uplasticised Rigid PVC rain water pipes
conforming to IS 13592 Type A including jointing with steel ring
conforming to IS 5382 leaving 10 mm gap for thermal expansion (i) single
socketed pipes and fitting as required.
Providing and fixing to the inlet mouth of rain water pipe cast iron grating
15 cm diameter and weighing not less than 440 grams.
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Providing and fixing M.S. stays and clamps for sand cast iron/
centrifugally cast (spun) iron pipes of diameter :
Providing and fixing bend of required degree with access door, insertion
rubber washer 3 mm thick, bolts and nuts complete.
25 Providing and fixing plain bend of required degree. 0.0 - -
25.1 Sand cast iron S&S as per IS : 3989 150 No. 570.05 554.7 83,199
25.3 Sand cast iron S&S as per IS - 3989 35 No. 629 - 22,005 MR - 16
Providing and fixing single equal plain junction of required degree with
26 access door, insertion rubber washer 3 mm thick, bolts and nuts - - MR - 17
26.1 Sand cast iron S&S as per IS - 3989 50 No. 1244 - 62,202 A
26.2 Sand cast iron S&S as per IS - 3989 25 No. 164 - 4,090 B
27 Providing and fixing single equal plain junction of required degree : - -
28.0 Providing and fixing single unequal plain junction of required degree : 0.0 - -
29.00 Providing and fixing terminal guard: 0.0 - -
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Providing & fixing of drip sealant for the cast iron pipe jointing as per
30.1 75mm diameter 50 No. 15 - 750 A
Providing and fixing trap of self cleansing design with screwed down or
31 hinged grating with or without vent arm complete, including cost of cutting - -
and making good the walls and floors :
100 mm inlet and 100 mm outlet - -
Providing and fixing G.I. Pipes ( Confirming IS 1239 class - B)complete
with G.I. fittings and clamps, i/c making good the walls etc. concealed
pipe, including painting with anti corrosive bitumastic paint, cutting
chases and making good the wall :
32.1 32 mm dia. nominal bore 100 Metre 837 - 83,323 A
32.1 40 mm dia. nominal bore 22 Metre 1002 - 22,044 B
32.2 50 mm dia. nominal bore 26 Metre 1279 - 33,766 C
Providing and fixing G.I. inlet hopper with two or three inlets fittings to
receive waste pipes from fixtures waste. The hopper shall be fabricated
from 100 mm dia upto 800 mm long G.I. heavy class pipe and welded G.I.
sockets, fixed to C.I. trap with drip seal joint and support through
galvanized steel support from slab or set in cement concrete mix 1:2:4
complete as required. The hopper shall be hot dip galvanized after
fabrication and fixed to CI trap / pipe with drip seal joint.
Providing & fixing G.I. waste with reducing elbow & nipple cutting chases,
34 the floor / slab, repairs complete as required and connection to GI / CI - - MR - 21
Providing & fixing 100 mm diameter Cast Iron Clean out plug for soil,
waste pipes conforming to IS 3989.
INTERNAL WATER SUPPLY
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c
36 cutting and making good the walls etc. - - DSR -2023 -18.10
Internal work - Exposed on wall and terrace
36.1 20 mm dia nominal bore 6 Metre 437.6 425.8 2,342 DSR -2023 -18.10.2
36.2 25mm dia nominal bore 39 Metre 552 536.8 20,667 DSR -2023 -18.10.3
36.3 32mm dia nominal bore 121 Metre 667 649.0 78,528 DSR -2023 -18.10.4
36.4 40 mm dia nominal bore 64 Metre 811 789.1 50,345 DSR -2023 -18.10.5
36.6 65 mm dia nominal bore 56 Metre 1021 - 57,278 MR -23
Domestic and Flushing water supply-Providing and fixing Chlorinated
Polyvinyl Chloride (CPVC - SDR 11) pipes, having thermal stability for hot
& cold water supply, including all CPVC plain & brass threaded fittings,
37 including fixing the pipe with clamps at 1.00 m spacing. This includes - - DSR -2023-18.8
jointing of pipes & fittings with one step CPVC solvent cement and testing
of joints complete as per direction of Engineer in Charge.
(Concealed Work) - -
37.1 15 mm dia nominal bore 83 Metre 498 484.4 39,960 DSR -2023 -18.8.1
37.4 32 mm dia nominal bore 63 Metre 739 719.3 45,103 DSR -2023 -18.8.4
37.5 40 mm dia nominal bore 25 Metre 1055 - 26,692 MR -24
Providing and fixing nitrile rubber insulation and proprietary polyshield
outer mechanical protection ON nitrile rubber insulation comprising of
wrapping with poly glass tape helically wound and subsequently applying
2 coats of polyshield material (resin & hardener) as per manufacturers
specification and approved by Project Manager / Consultants.
38.1 20 mm dia. nominal bore 10 Metre 210 - 2,079 A
Providing & fixing full way lever operated Brass ball valve of brass body
with stainless steel ball conforming to IS 778 with threaded / flanged joints
(PN 16) complete with nuts, bolts, gaskets, washers and fixing to
supports etc.(PN 16)
39.1 20 mm nominal bore 18 No. 673 - 12,114 A
39.2 25 mm nominal bore 7 No. 775 - 5,425 B
39.3 32 mm nominal bore. 5 No. 1324 - 6,620 C
39.4 40 mm nominal bore 5 No. 1857 - 9,285 D
39.5 50 mm nominal bore 1 No. 2711 - 2,711 E
Digitally signed by ANUJ
REF DSR-2023/ NON DSR REFERENCE
DSR Rate Total Amount
DSR Rate Total Amount
S.No. Description Qty. Unit Rate (Rs.) @0.973
Supply, Installation, Testing and Commissioning of compact packaged type skid
mounted, self contained variable frequency drive hydropneumatic system
complete as per following technical specification complete as required:-
(i) In- line vertical multistage centrifugal clear water pump set with SS-304
casing, SS-304 impeller with SS-316 shaft ,CI base with CED coating complete
directly coupled with TEFC induction motor of class "F" insulation & efficiency - -
class IE-2, 2900rpm, suitable for opertion on 415 Volts ±10%, 3 phase, 50 Hz
A.C. supply complete.
(ii) The entire system shall be mounted on a common base frame i/c common
suction and common delivery of G.I heavy class pipe headers with flanges,
interconnecting piping with all required Conrol Valves, Non-return valves,
pressure guage with isolation cock etc. and all requried accessories.
(iii) Pressure vessel of non corrosive FRP composite construction lined with
NSF and/or FDA listed material, like high density polyethylene with fully
replaceable polyurethane. Air cell burst pressure of minimum of 3 times the
vessel operating pressure and prototype cycle tested for 80,000 cycles with - -
charging connections to dischage pipe line with necessary flanges, gaskets,
isolating valve, nuts/ bolts etc. with suitable foundation boits & other
accessories, complete.
(iv) Panel mounted microprocessor multi pump contoller with large graphical
display and Flying variable frequency drive (VFD) mounted inside a panel
complete with pressure sensor transmitter. The graphical display capable to
show number of pumps running & also communicate with other controllers
following with open protocol through RS485 port. System should be capable to - -
compensate for frictional losses at lower flows. All alarms should be displayed in
the controller. The panel should also have provision for manual / automatic
alternate (cyclic) operation of pumps, ON/OFF switch, complete.
(v) Necessary foundationing bolts, vibration elimination pads and other
accessories complete as required.
Duty of each pump suitable for:- - -
No. of Pumps : 2nos. (1 W + 1 S) - -
Capacity : 0.5LPS - -
Head : 30 Meters - -
40.1 Air Vessel : 1 Nos of Min. 60 Liters Cap. 1 Set 462417 - 4,62,417 MR -27
Digitally signed by ANUJ
SUMMARY (Electrical Works)
SCHEDULE OF QUANTITIES, ELECTRICAL WORKS
GRID INDIA, AYURVIGYAN NAGAR, NEW DELHI
Sl. No. SUB HEADS DSR 2022 AMOUNT Non DSR AMOUNT
A HT CABLE & TERMINATION 2,29,328.29 5,06,272.00
B HT PANEL & CSS WORKS 0.00 1,28,58,122.00
C LT PANELS & DISTRIBUTION BOARDS 8,87,238.79 1,07,21,885.00
D MV CABLES, CABLE JOINTING & END TERMINATIONS 40,728.64 1,10,27,189.00
E CABLE TRAYS WORKS 11,41,543.70 1,80,600.00
G CIRCUIT CUM POINT WIRING (With MS CONDUITING) 0.00 62,40,212.00
H CONDUITING & RACEWAYS FOR VOICE/ DATA (N/W) & TV SYSTEM 9,17,601.32 18,89,812.91
I EARTHING SYSTEM 35,00,182.61 3,13,490.00
K INTERNAL LIGHT FIXTURES AND FANS 0.00 1,11,44,530.00
L LIGHTING MANEGMENT SYSTEM 0.00 49,74,197.00
M BUS DUCTS - COMPACT SANDWITCH TYPE 0.00 1,64,51,840.00
N FIRE DETECTION AND ALARM SYSTEM - ANALOG ADDRESSABLE SYSTEM 62,46,921.36 15,17,858.00
O CLEAN AGENT BASED FIRE SUPPRESSION SYSTEM 0.00 54,80,338.00
P VERY EARLY SMOKE DETECTION & ALARM SYSTEM 0.00 5,86,246.00
R EV CHARGER 0.00 26,84,388.00
S PARKING MANAGEMENT 0.00 1,64,800.00
Less Cost Index on DSR 2022 @2.73% (On base of PAR 2021) as per CPWD
OM DG/Cost Index/06 dated 13.05.2022 (110 to 107) -3,53,960.77
Cost Index on DSR 2022 @3% (on base of PAR 2023) per CPWD OM
DG/Cost Index/10 dated 11.09.2024 1,29,89,984.09
GRAND TOTAL 12,42,56,918.00
GRAND TOTAL 12,42,56,918.00
Digitally signed by ANUJ
SCHEDULE OF QUANTITIES, ELECTRICAL WORKS
GRID INDIA, AYURVIGYAN NAGAR, NEW DELHI
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
A HT CABLE & TERMINATION
1.1 Supply of following size of 11kV (Un earthed) grade, multicore stranded
aluminium conductor, XLPE insulated & PVC sheathed armoured power
cable conforming to IS: 7098 (Part-II) 2011 with upto date ammendments
complete as required and as per specification encolsed.
2 HT CABLES END TERMINATION
supplying and making indoor cable end termination with heat shrinkable
jointing kit complete with all accessories including lugs suitable for following
size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
Supplying and making outdoor cable end termination with heat shrinkable
jointing kit complete with all accessories including lugs suitable for following
size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required
3 HT CABLES LAYING
3.1 Laying of one number XLPE power cable of 11kV grade of following size
direct in ground including excavation, sand cushioning, protective covering
and refilling the trench etc as required. 8.1
3.2 Laying of one number additional XLPE power cable of 11kV grade of
following size direct in ground in the same trench in one tier horizontal
formation including excavation, sand cushioning, protective covering and
refilling the trench etc as required. 8.2
3.3 Laying of one number XLPE power cable of 11kV grade of following size in
the existing RCC/ HUME/ METAL pipe as required. 8.3
3.4 HDPE PIPES
3.4.1 Supplying and laying of following size DWC HDPE pipe ISI marked along
with all accessories like socket, bend, couplersetc. conforming to IS: 14930,
Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm
below ground level) including excavation and refilling the trench but
excluding sand cushioning and protective covering etc., complete as
required. 14.16
4 Constructing water tight brick masonry manhole with 75 class designation
bricks in cement mortar 1:4 (1 cement: 4 coarse sand), R.C.C. top slab with
1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm
nominal size). Foundation concrete 150 mm thick 1:4:8 mix (1 cement: 4
coarse sand: 8 graded stone aggregate 40 mm nominal size), inside and
outside plastering 12 mm thick with cement plaster 1:3 (1 cement: 3 coarse
sand) finished with a floating coat of neat cement and making channels and
benching in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) finished with a floating coat of neat
cement complete as per standard design, complete with DI cover Heavy
duty of adequate size as per standard design and approved drawings. (Price
shall include the, cost of excavation, back filling, disposal of surplus earth,
dewatering & water proofing of manholes as directed at site & other
associated civil works).
4.1 Inside size 1000mm x 1000mm x 1100mm deep. Nos. 8 1,394 0.00 11152.00 EL. MR-2
Total Carried to Summary 2,29,328.29 5,06,272.00
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
B HT PANEL & CSS WORKS
1.0 11kV HT PANEL BOARD (ONE BREAKER)
(Earlier 1 No. Incomers + 4 Nos. Out goings HT Panel will convert to
Two Incomer + 1 No. Bus Coupler + 3 Nos. Outgoing after adding 1 No.
New VCB Breaker.) - -
Design, manufacture, supply, installation, testing and commissioning of 800
Amps., 11kV, 18.4kA breaking capacity (350 MVA) VCB panel board
fabricated out of 2mm sheet steel, dust tight, vermin proof, totally enclosed
and fully interlocked, IP-4X protection, cubical type, floor mounting,
extensible on both sides, suitable for indoor operation at 11kV, 3 phase, 50
Hz, AC supply complete with rack in - rack out mechanisms, switches, plugs
& sockets and all required accessories, cable termation box at back with
TOP cable entry for cable size upto 3 core 400 sqmm. armoured cable for
each section, internal copper wiring, earth terminals, painting etc. as
required, as per specifications & SLD with the following equipped switch
gears and accessories complete in aal respect.
a) INCOMER - 1 NO. - -
Each feeder shall consist of : - -
i) 800 Amps., 11kV horizontal draw out type VCB with motorized spring
charge mechanism and required safty switchgears complete. - -
ii) 11kV/ 110 volt PT of class 38/1 accurancy & 100 VA burden. - -
iii) Set of dual core dual ratio CTs of 300/ 150/5/5 Amps. of 15 VA burden &
accurancy class 1.0 for metering and class 5 P 10 for protection.
iv) 96mm x 96mm type 800 Amp Digital Type ammeter with inbuilt ASS - -
v) 96mm x 96mm type Digital Type Voltmeter protected by HRC fuses/ MCBs
with inbuilt VSS - -
vi) Digital tri-vector Meter (Smart Controller) having 30 days memory Class-1.0
with MDI & RS 485 port. - -
vii) Frequency meter - -
viii) Micro processor based feeder protection numerical relay with adjustable
O/L, E/F and short circuit protection with communication port. (O/L Setting
50-200% and E/F setting 20-80%) - -
ix) Set of LED indication lamp protected by MCB for RYB Phases, trip, ON &
OFF, spring charge, auto trip/ trip healthy of breaker complete. - -
x) Master trip & trip circuit supervision relay, Antipumping Relay, complete.
xi) Limit switch for tests & service position, circuit breaker control switch
xii) Trip coil operation at 24 Volts DC through battery bank - -
xiii) Phase Sequence Relay-2 Nos. (1 No. in new incomer + 1 No. in old
incomer.) - -
11kV MAIN HT PANEL BOARD (ONE BREAKER AND CHANGE IN
EXISTING HT PANEL AS ABOVE DETAILS) Job. 1 12,95,682 - 12,95,682 EL. MR-3
2.0 COMPACT SUBSTATION (WITH DRY TYPE TRANSFORMER, WITH
Indoor type Package Substation with facility for internal lighting,
earthing, padlocks etc. Connection between RMU & Transformer will
be by 3Nos. 1C x 95 Sqmm. Aluminium conductor XLPE cable and
connections from Transformer to LT ACB will be by Aluminium bus
bar connections. Cable termination kits for RMU shall be in the
scope of supply (within the enclosure).
Package Substation will have the following equipments: - -
a. HT SIDE - -
3 Way Non Extensible Unit with 2 Nos. Isolators as Incomer and 1
No. Circuit Breaker as Outgoing to Transformer : 1 No. - -
3 Way, 11kV, 630A, 21kA/ 3 Sec, indoor non extensible free
standing metal clad SF6 insulated ring main unit type comprising of
two numbers manual operated 630A fault making/ load breaking
switch and one number motorised operated tee-off SF-6 insulated
vacuum circuit breaker complete with all accessories as listed below:
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
i. IDMT RELAY-Self Powered, Microprocessor based numerical 3 Nos.
O/C+1 No. E/F (with inbuilt tripping mechanism-mytop or equivalent)
with LCD display-ON/OFF/Trip. - -
ii. Dual core CT’s for protection & metering, cast resin type and of
suitable ratio & burden, (Class-1 for metering & class 5P10 for
protection). - -
iii. Cast Resin PT's of 11000V/ √3/ 110V/ √3 ratio of Class-1 accuracy &
of suitable burden with HV fuse on primary side & MCB/ MPCB on
secondary side. - -
iv. The Ring Switches and Tee-Off Circuit Breaker are provided with
Integrated Earthing Switches with Making Capacity. - -
v. Live cable indicator for ring switches. - -
vi. Shunt trip coil rated for 24V DC - -
vii. SF6 Gas pressure indicator. - -
viii. Padlocking facility. - -
ix. Mechanical indications for breaker ON/ OFF/ TRIP - -
x. Communicable type multifunction meter with MDI (A, V, Hz, kW,
kWH, kVA, kVAH, kVAR, kVARH) - -
xi. Ammeter with selector switch. - -
xii. Voltmeter with selector switch. - -
xiii. Line Voltage presence indicator. - -
xiv. Transformer Auxiliary Relay with alarm & trip contacts for: - -
a. Winding temperature - -
b. Oil Temperature - -
c. Bucholz - -
xv. Emergency 'OFF' Push buttons - -
xvi. Manual ON/ OFF Push buttons - -
xvii. 12 Windows annunciator. (Hooter@ Remote location i.e. inside LT
Panel room) with necessary cabling. - -
xviii. Trip circuit healthy indication - -
xix. 230V AC/ 24V DC Power Pack of suitable capacity - -
xx. LED based bulk head light fixture with limit switch in the HT
Compartment. - -
b. TRANSFORMER - -
11kV/ 433V, 500kVA three phase, Dyn11, tapping +15% to -15% in
steps of 2.5% On Load Tap Changer (OLTC), CU/ CU Winding Dry
Type (Cast Resin) Transformer with standard accessories: 1 No.
Transformers No Load & Load Losses shall be as per Latest ECBC
norms or Less. - -
Door interlock to trip HT breaker on opening of transformer
compartment door (only in transformer's with off circuit tap changer).
c. LT SIDE - -
1 No. 4pole 800A/ 50kA manually operated fixed type ACB with
microprocessor based O/L, S/C & E/F releases. Ics = Icu for the
Note: LT side metering shall include: 1set of LT cast resin CT's, PT’s &
Communicable type VAF meter, LED TYPE R Y B indication lamps,
ON/ OFF/ Trip indication lamps, control MCB's/ MPCB’s of required
fault withstand and control wiring etc. at the LT side incomer breaker.
LED based bulk head light fixture with limit switch in the LT
Compartment. - -
CT chamber with double wound single phase, 3 nos., cast resin
CT's, 10VA burden or more as required with core-1 for metering
(Class 0.5 accuracy) and core-2 for protection (Class 5P15
accuracy) and of 30/15/5A ratio. = 3 Nos. - -
Packaged Substation as described above. Set 1 52,84,888 - 52,84,888 EL. MR-4
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
3.0 TRANSFORMER - -
Supply, installation, testing and commissioning of Cast Resin Dry
Type, 11/ 0.433kV, 3 phase, 50 Hz, DYn -11, vector group copper
wound, (with OLTC & RTCC) Class F insulation associated with
winding temperature indicator/ controller actuated by means of
resistance temperature detector embedded in LV winding, indoor
type transformer with approximately impedence as per IS (6.25%)
tapping for ON load operation on HV side in steps of 1.25% for + 5%
to - 15% having cable end boxes on HV side suitable for 3 core x
240 Sq.mm XLPE cable (TOP Entry) of 11kV grade and 4000/ 2000/
1200 Amp Sandwich Type Bus Duct for use on 3 phase 4 wire 415
V, 50Hz A.C. supply with metal clad enclosure having IP-33 on LV
side including supplying and laying of copper conductor multicore
control cable from transformer to HT breaker for safety tripping
suitably mounted on MS channel including supplying and grouting of
suitable MS channels with all accessories and conforming to
IS:11171: 1985 with uptodate ammendments & as per technical
specifications complete in all respect.
2000kVA Transformer Set 1 62,77,552 - 62,77,552 EL. MR-5
Total Carried to Summary - 1,28,58,122
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
C LT PANELS & DISTRIBUTION BOARDS
1 LT PANELS - -
Design, manufacture, assembly, wiring, testing at works and supply to
site of following panels/ distribution boards/ switch boards. The
boards shall be designed and fabricated as per general specifications,
technical details, specifications and notes as part of this tender/ BOQ
and relevant BIS codes. - -
Also, refer to General Notes and Specifications for Panels/ Boards
The Main LT Panel and all other ACB incomer panel will be Totally
Type tested. - -
GENERAL NOTES FOR MCCB's: - -
a. MCCB's shall be of 3P or 4P as called for in the BOQ. - -
b. Ics = Icu = 100% for the breakers. - -
c. If nothing is specified in the BOQ, MCCB's upto 250A shall be only with
magnetic release for motor duty and shall be with thermal magnetic release
upto 250A for non motor duty and above 250A shall be with microprocessor
based releases - motor duty/ non motor duty as the case may be. - -
d. MCCB's shall be with extended rotary handle. - -
e. For UPS output panels, MCCB's shall be of 3Pole with 2N, neutral links
(twice rated neutral link). - -
f. Exact rating (Amps), Poles, Type/ Duty, Short circuit rating of MCCB is to be
selected by the contractor as per load, fault and requirement and also
approval taken. - -
GENERAL NOTES FOR TRANSIENT VOLTAGE SURGE SUPPRESSOR
a. Transient Voltage Surge Suppressors (TVSS) shall be mounted out side the
panel/ switch board in a sheet steel enclosure. - -
b. It shall be suitable for handling required (specified) surge handling capacity,
shall be 10 modes protection with noise filters. (EMI & RFI) and with inbuilt
back up fuse protection. - -
c. Surge suppressor shall be complete with isolating/ protective device in the
form of MCB/ MCCB of kA rating (breaking capacity) as of switch board.
1.0 All Switchgear selections shall be as per manufacturer's recommendation.
2.0 Contractor to submit manufacturer's selection charts for approval. - -
3.0 Only one make of switchgear to be used in a board/ panel. - -
4.0 Incomer switchgear, bus bars, supports and outgoing switchgear shall be of
same fault level withstand capacity as mentioned for the panel. - -
1.1 NEW SECTION OF MAIN LT PANEL - -
(This new section will connect with Existing Main LT Panel) - -
IP Rating : IP 42 - -
i) Bus Coupler : - -
One (1) Nos. 2500A, 50kA Four pole, EDO ACB, with ON/ OFF indication
lamp and TNC control switch, Under Voltage & shunt trip release, anti
pumping protection etc. complete as required. - -
ii) Incomers : Transformer Incomer (2000 kVA) - -
1 Nos., 3200A, 50kA, 4P, EDO, ACB with: - -
a) 230V, AC spring charging motor - -
b) 230V, AC closing coil - -
c) 24V, DC shunt trip coil - -
d) 4 NO + 4NC Aux. contacts - -
e) In built trip LED's - -
f) Breaker control switch - -
Each Transformer supply breaker shall be provided with the following: - -
Protection: - -
a) In built micro processor based releases (O/C, S/C & E/F). - -
b) Phase Sequence Relay-2 Nos. (1 No. in new incomer + 1 No. in old
incomer.) - -
Metering & Indications: - -
a) R, Y, B LED indications (110V) - -
b) ON, OFF, TRIP LED indications (24V DC) - -
c) Trip circuit healthy indications (24V DC) - -
d) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
e) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - -
f) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - -
g) 3 Nos. Cast resin Class 1 CT's of adequate burden & ratio for automatic
power factor capacitor relay. - -
iii) Bus Bars : - -
3600A, TPN, Aluminium bus bars of electrolytic grade with Heat shrinkable
sleeves 50kA - 1 set. - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
iv) Outgoings : - -
a) One (1) No. 1000A, 50kA, TP MDO ACB with Microprocessor based release
for short circuit, over current protection. - -
b) One (1) No. 630A, 50kA, FP MDO ACB with Microprocessor based release
for short circuit, over current protection. - -
c) Six (6) Nos. 400A, 50kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - -
1) All out going feeders will be provided with MFM with RS 485 connectivity,
CTs of suitable range and ON/ OFF indicating lamps. - -
2) Incoming and Out going feeders will be with Sandwiched Bus Trunking
and UG Cables as per Schematics. - -
3) PLC based interlocking will be provided in all incomings and bus-couplers
after coordination with existing interlocking scheme. - -
4) All outgoing feeder fed to EV charger panel will trip, on DG power supply.
v) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
NEW SECTION OF MAIN LT PANEL as described above. Set 1 24,96,485 - 24,96,485.00 EL. MR-6
1.2 CAPACITOR (APFC) Panel, 500 kVAR - -
i) Bus Bars : - -
1200 amps TP Al. Bus Bars 50kA fault level with coloured heat Shrinkable
insulated sleeves. - 1 set - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
ii) Outgoings : - -
3 Phase Intelligent Power factor correction relay with inbuilt metering
features like: - -
12 Steps Relay - -
Total Current - -
Power Factor - -
Current of each bank - -
1 No. Off delay timer for manual operation - -
a. 1 No. 100 kVAR Sets, each comprising : - -
1 No. TP, MCCB of capacitor duty 50kA for 100kVAR Bank alongwith:
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 100kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
100kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
b. 5 Nos. 50 kVAR Sets, each comprising : - -
1 No. TP, MCCB of capacitor duty 50kA for 50kVAR Bank alongwith: - -
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 50kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
50kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
c. 6 Nos. 25 kVAR Sets, each comprising : - -
1 No. TP, MCCB of capacitor duty 50kA for 25kVAR Bank alongwith: - -
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 25kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
25kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
In case of capacitor banks with de-tuned reactor, the operating voltage
for capacitors shall be 525V minimum. - -
iii) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
APFC Panel, 500 kVAR as described above. Set 1 14,65,392 - 14,65,392.00 EL. MR-7
1.3 UPS INPUT PANEL - -
i) Incomer - -
a) Two (2) Nos. 400A, 35kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - -
1 No. 400A, 4P, ATS with manual bypass only and simultanous switching of
all poles as per IEC 60947-6-1 and on load isolation as per IEC 60947-3.
Each incomer having following details - -
Metering & Indications: - -
a) R, Y, B LED indications (110V) - -
b) ON, OFF, TRIP LED indications (24V DC) - -
c) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
d) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - -
e) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - -
ii) Busbar : - -
630A, 35kA TP+N AL. Busbar insulated with heat shrinkable sleeves and
shall be colour coded. The neutral busbar shall be 100% rated. - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
iii) Outgoings : - -
a) Two (2) Nos. 250A, 35 kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - -
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
iv) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
UPS INPUT PANEL as described above. Set 2 5,34,098 - 10,68,196.00 EL. MR-8
1.4 UPS OUTPUT PANEL - -
i) Incomer - -
a) Two (2) Nos. 250A, 25kA, 3P+2N MCCB with Microprocessor based
release for short circuit, over current protection. - -
(Both the incomer will work as parallel as both UPS will run as parallel
Each incomer having following details - -
Metering & Indications: - -
a) R, Y, B LED indications (110V) - -
b) ON, OFF, TRIP LED indications (24V DC) - -
c) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
d) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - -
e) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - -
f) Phase Sequence Relay - -
ii) Bus Coupler : - -
One (1) Nos. 250A, 25kA, 3P+2N MCCB with Microprocessor based
release for short circuit, over current protection. - -
iii) Busbar : - -
400A, 25kA TP+N Cu. Busbar insulated with heat shrinkable sleeves and
shall be colour coded. The neutral busbar shall be 100% rated. - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
iv) Outgoings : - -
a) Six (6) Nos. 160A, 25 kA, 4P MCCB with thermal magnetic release for short
circuit, over current protection. - -
b) Three (3) Nos. 100A, 25 kA, 4P MCCB with thermal magnetic release for
short circuit, over current protection. - -
c) Six (6) Nos. 63A, 25 kA, 4P MCCB with thermal magnetic release for short
circuit, over current protection. - -
v) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
UPS OUTPUT PANEL as described above. Set 2 5,53,431 - 11,06,862.00 EL. MR-9
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
1.5 PAC PANEL (SERVER ROOM) - -
i) Incomer - -
a) Two (2) Nos. 250A, 25kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - -
1 No. 250A, 4P, ATS with manual bypass only and simultanous switching of
all poles as per IEC 60947-6-1 and on load isolation as per IEC 60947-3.
Each incomer having following details - -
Metering & Indications: - -
a) R, Y, B LED indications (110V) - -
b) ON, OFF, TRIP LED indications (24V DC) - -
c) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
d) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - -
e) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - -
ii) Busbar : - -
400A, 25kA TPN Al. Busbar insulated with heat shrinkable sleeves and shall
be colour coded. The neutral busbar shall be 100% rated. - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
iii) Outgoings : - -
a) Eight (8) Nos. 63A, 10 kA, 4P MCB. - -
iv) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
PAC PANEL (SERVER ROOM) as described above. Set 1 3,50,458 - 3,50,458.00 EL. MR-10
2 MAIN LT PANEL - EV CHARGER - -
IP Rating : IP 42 - -
i) Incomers : Transformer Incomer (500 kVA) - -
1 Nos., 800A, 50kA, 4P, EDO, ACB with: - -
a) 230V, AC spring charging motor - -
b) 230V, AC closing coil - -
c) 24V, DC shunt trip coil - -
d) 4 NO + 4NC Aux. contacts - -
e) In built trip LED's - -
f) Breaker control switch - -
Each Transformer supply breaker shall be provided with the following: - -
Protection: - -
a) In built micro processor based releases (O/C, S/C & E/F). - -
b) Phase Sequence Relay - -
Metering & Indications: - -
a) R, Y, B LED indications (110V) - -
b) ON, OFF, TRIP LED indications (24V DC) - -
c) Trip circuit healthy indications (24V DC) - -
d) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
e) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - -
f) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - -
g) 3 Nos. Cast resin Class 1 CT's of adequate burden & ratio for automatic
power factor capacitor relay. - -
ii) Bus Bars : - -
1000A, TPN, Aluminium bus bars of electrolytic grade with Heat shrinkable
sleeves 50kA - 1 set. - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
iii) Outgoings : - -
a) One (1) No. 1000 A, 50 kA, TP MDO ACB with Microprocessor based
release for short circuit, over current protection. - -
b) One (1) No. 630 A, 50 kA, FP MDO ACB with Microprocessor based
release for short circuit, over current protection. - -
Digitally signed by ANUJ
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
c) Six (6) Nos. 400 A, 50 kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - -
1) All out going feeders will be provided with MFM with RS 485 connectivity,
CTs of suitable range and ON/ OFF indicating lamps. - -
2) Incoming and Out going feeders will be with Sandwiched Bus Trunking
and UG Cables as per Schematics. - -
3) All outgoing feeder fed to EV charger panel will trip, on DG power supply.
v) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
MAIN LT PANEL - EV CHARGER as described above. Set 1 15,52,655 - 15,52,655.00 EL. MR-11
2.1 CAPACITOR (APFC) Panel, 150 kVAR - -
i) Bus Bars : - -
630 amps TP Al. Bus Bars 35kA fault level with coloured heat Shrinkable
insulated sleeves. - 1 set - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - -
ii) Outgoings : - -
3 Phase Intelligent Power factor correction relay with inbuilt metering
features like: - -
8 Steps Relay - -
Total Current - -
Power Factor - -
Current of each bank - -
1 No. Off delay timer for manual operation - -
a. 4 Nos. 25 kVAR Sets, each comprising : - -
1 No. TP, MCCB of capacitor duty 35kA for 25kVAR Bank alongwith: - -
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 25kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
25kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
b. 2 Nos. 20 kVAR Sets, each comprising : - -
1 No. TP, MCCB of capacitor duty 35kA for 20kVAR Bank alongwith: - -
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 20kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
20kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
c. 1 No. 10 kVAR Set, each comprising : - -
1 No. TP, MCCB of capacitor duty 35kA for 10kVAR Bank alongwith: - -
3P capacitor duty contactor with 2NO + 2NC auxiliary contacts for 10kVAR
capacitor - -
A/M Selector switch - -
Illuminated ON/ OFF Push buttons - -
10kVAR Capacitor bank, MPP (Heavy duty) with 7% copper detuned
In case of capacitor banks with de-tuned reactor, the operating voltage
for capacitors shall be 525V minimum. - -
iii) AUTOMATIC FIRE DETECTION SUPPRESSION SYSTEM - -
Design, Supply, fixing, testing and commissioning of automatic linear
pneumatic tube Detection NOVEC1230/ FK-5-1-12 Clean agent System for
the above electrical panel (Linear Pnuematic Heat Detection tube (UL listed)
Panel Protection System), consisting of suitable capacity Novec 1230 (as
per NFPA 2001), Direct Low Pressure (DLP) Assembly with automatic
valve, push in connector for tube, Novec 1230 (UL listed) Clean agent,
mounting bracket, End of Line adopter and low pressure switch for
monitoring system activation, Linear Pneumatic Heat detection tube with
necessary supports and microprocessor based indication cum Control Unit
for controlling the system, complete with pressure switches, buzzers and
electronic hooters, including UL listed seamless cylinder, all necessary
accessories and electrical wiring to make the entire system functional
complete as required.
APFC Panel, 150 kVAR as described above. Set 1 5,83,435 - 5,83,435.00 EL. MR-12
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
2.2 TYPICAL UPS FLOOR PANEL - - -
i) Incomer - - -
a) Two (2) Nos. 63A, 25kA, 4P MCCB with Microprocessor based release for
short circuit, over current protection. - - -
1 No. 63A, 4P, ATS with manual bypass only and simultanous switching of
all poles as per IEC 60947-6-1 and on load isolation as per IEC 60947-3.
(Both the incomer will work as parallel as both UPS will run as parallel
Each incomer having following details - - -
Metering & Indications: - - -
a) R, Y, B LED indications (110V) - - -
b) ON, OFF, TRIP LED indications (24V DC) - - -
c) 415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
d) 3 Nos. cast resin class 1 metering CT's of adequate burden & ratio. - - -
e) MFM meter (with RS 485 port) with following parameter: A,V, PF, Hz, kW,
kWH, kVA, kVAR, kVARH. (110V AC) - - -
ii) Busbar : - - -
100A, 10kA TP+N Al. Busbar insulated with heat shrinkable sleeves and
shall be colour coded. The neutral busbar shall be 100% rated. - - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. (Bus PT's for metering of outgoing feeders) This
metering PT shall be of Class-1 accuracy. - - -
iii) Outgoings : - - -
a) Six (6) Nos. 40A, 10 kA, 4P MCB. - - -
TYPICAL UPS FLOOR PANEL as described above. Set 4 2,13,912 - 8,55,648.00 EL. MR-12A
3 MCCB, MCB & DB's (DISTRIBUTION BOARDS) - -
GENERAL NOTES FOR MCB's & DB's: - -
The MCB Distribution Boards shall be provided as under. - -
1) The DBs shall be separate for light load and power load, separate for
three phase load and single phase load, sepertae for UPS supply and
normal supply. - -
2) For light DBs, each circuit shall have not more than 800 Watt connected
load or not more than 15 points which ever is less. - -
3) All power points shall be wired in independent circuits. - -
4) At least 20 % extra circuits with MCB shall be left in every DB. - -
5) DP RCCB 30/ 100 mA shall be provided in out going phase. - -
6) MCB ratings shall be selected as per load requirement. - -
7) All DBs shall be installed in Electrical Rooms/ Locations as shown in the
drawings. - -
8) All three phase DBs shall be with per phase isolation for providning DP
Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240V, on surface/ recess, complete with tinned copper
3.1 bus bar, neutral bus bar, earth bar, din bar, interconnections, powder
painted including earthing etc. as required. (But without MCB/ RCCB/
Isolator) - - 2.3
Supplying and fixing following way, horizontal type three pole and neutral,
sheet steel, MCB distribution board, 415V, on surface/ recess, complete
3.2 with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But
without MCB/ RCCB/ Isolator) - - 2.4
Supplying and fixing of following ways surface/ recess mounting, vertical
type, 415V, TPN MCCB distribution board of sheet steel, dust protected,
duly powder painted, inclusive of 200A, tinned copper bus bar, common
neutral link, earth bar, din bar for mounting MCCBs (but without MCCBs and
incomer) as required. (Note: Vertical type MCCB TPDB is normally used
where 3 phase outlets are required.) - - 2.5
Supplying and fixing 5A to 32A rating, 240/ 415V, 10 kA, “C” curve,
miniature circuit breaker suitable for inductive load of following poles in the
existing MCB DB complete with connections, testing and commissioning etc.
as required. - - 2.10
Supplying and fixing single pole blanking plate in the existing MCB DB
complete etc. as required. No. 146 14 2,018.14 - 2.11
Supplying and fixing following rating, four pole, 415V, 'C' curve MCB 10kA in
3.6 the existing MCB DB complete with connections, testing and commissioning
etc. as required. - -
Supplying and fixing following rating, double pole, (single phase and neutral),
240V, residual current circuit breaker (RCCB), having a sensitivity current 30
mA in the existing MCB DB complete with connections, testing and
commissioning etc. as required. - - 2.14
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supplying and fixing following rating, four pole, (three phase and neutral),
415V, residual current circuit breaker (RCCB), having a sensitivity current 30
mA in the existing MCB DB complete with connections, testing and
commissioning etc. as required. - - 2.23
3.9.3 For 12 way, Double door SPN MCBDB No. 2 861 1,722.55 - 2.23.3
Supplying and fixing Cable End Box (Loose wire box) (IP 43) suitable for
following triple pole and neutral, sheet steel, MCB distribution board, 415V,
on surface/ recess, complete with testing and commissioning etc. as
required. - - 2.24
3.10.3 For 8 way, Double door TPN MCBDB No. 20 1,425 28,496.44 - 2.24.3
Supplying and fixing following rating, 240 volts, double pole,"C" curve,
residual current break over (RCBO) suitable for inductive load of following
capacities in the existing MCB DB complete with connections, testing and
commissioning etc. as required. - -
Supplying and fixing following way, horizontal type three pole and neutral,
sheet steel, MCB distribution board, 415V, on surface/ recess, complete
3.13 with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But
without MCB/RCCB/Isolator) - - -
Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole
and neutral, sheet steel, Vertical MCB distribution board, 415Volts, on
surface/ recess, complete with testing and commissioning etc. as required.
Supplying and fixing 240/ 415V, 10 kA, “C” curve, miniature circuit breaker
suitable for inductive load of following poles in the existing MCB DB
complete with connections, testing and commissioning etc. as required.
3.16 PDU-1 & 2 for ELV Racks - -
1 No. 63A, 10kA, TP+2N MCB. - -
with medium level surge protection i.e. MOV type surge protection device on
each phase & neutral. MOV shall have a max. current discharge not less
than 40kA & residual voltage not more than 1.2kV & shall be connected in
parallel to equipment - -
Incomer Metering & Indication: - -
415V/ √3/ 110V/ √3 PT's, Cast Resin type, 3 Phase for metering &
indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of
the panel on the primary side of PT & suitable rated 6A, TP MCB on the
secondary side of PT. This metering PT shall be of Class-1 accuracy.
R,Y,B phase indication lamps (110V) LED Type - -
ON' & Trip indication lamps (110V) LED Type - -
Cast resin metering CT's for each phase of class-1 accuracy & of suitable
burden & ratio - -
1 No. Digital MFM Meter (110V) (With RS 485 Port) - -
100A, TP+2N copper bus bars with heat shrinkable insulated coloured
coded sleeves. - -
Dedicated Earth Link - -
Dedicated earthing link on insulated supports for 3rd pin of sockets to be
provided in addition to body earthing. - -
Outgoings - -
9 Nos. 16A/ 20A/ 32A DP MCB's - -
PDU-1 & 2 as described above. Set 4 1,79,726 - 7,18,904.00 EL. MR-20
TOTAL CARRIED OVER TO SUMMARY 8,87,238.79 1,07,21,885.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
D MV CABLES, CABLE JOINTING & END TERMINATIONS
Supply & Laying, loading, transportation unloading at site, storages at site,
shifting from storage place to site of following sizes of 1.1kV grade XLPE
1.0 insulated, Extruded PVC inner sheathed & overall FR-LSH PVC outer
sheathed, Aluminium conductor, Armoured cables as per IS:7098 Part-I or
amended upto date and as per specifications. - -
2.0 CABLE TERMINATION (IS:7098 Part-I) - -
Supplying and making end termination with double brass compression gland
and aluminium lugs for following size of PVC insulated and PVC sheathed/
XLPE aluminium conductor cable of 1.1kV grade as required.
SUPPLY & LAYING OF CABLES - XLPE INSULATED, FR-LSH PVC
3.0 SHEATHED COPPER CONDUCTOR ARMOURED CABLES (IS:7098 Part-
Supply of following sizes of 1.1kV grade XLPE insulated, Extruded FR-LSH
PVC inner sheath Type ST-2, FR-LSH PVC outer sheath Type ST-2,
stranded Copper conductor, Armoured cables as per IS:7098 Part-I.
a. 4C x 4 sq.mm.Cu. Ar. XLPE cable Metre 1 354 354.00 EL. MR-31
b. 4C x 6 sq.mm.Cu. Ar. XLPE cable Metre 1 501 501.00 EL. MR-32
c. 4C x 10 sq.mm.Cu. Ar. XLPE cable Metre 520 820 4,26,400.00 EL. MR-33
d. 4C x 16 sq.mm.Cu. Ar. XLPE cable Metre 208 1,201 2,49,808.00 EL. MR-34
e. 4C x 150 sq.mm.Cu. Ar. XLPE cable Metre 576 11,357 65,41,632.00 EL. MR-35
f. 1C x 25 sq.mm.Cu. Ar. XLPE cable Metre 1 587 587.00 EL. MR-36
g. 1C x 50 sq.mm.Cu. Ar. XLPE cable Metre 1 1,111 1,111.00 EL. MR-37
h. 1C x 150 sq.mm.Cu. Ar. XLPE cable Metre 576 3,216 18,52,416.00 EL. MR-38
For Input cables to UPS from UPS input panel & output cable from
UPS to UPS out panel. - -
4.0 SUPPLY OF FIRE SURVIVAL CABLES: COPPER CONDUCTOR - -
Supply & Laying of Fire Survival armoured cables of 600/ 1000V rated with
Copper circular conductor having glass mica fire barrier tape covered by an
extruded layer of High module Ethylene Propylene Rubber (HEPR)
insulation and LSZH inner & outer sheath. Generally as per IS: 17505, BS
7846, IEC-60502-1 & BS-8519 (latest edition). Should retain circuit integrity
as per BS 8491:2008 (120 mins) for cables having overall dia of 20mm and
above. Cables with overall dia below 20 mm should retain circuit integrity as
per BS 8434-2. 3rd Party inspection required prior to despatch of every lot.
b. 4 x 4 sq. mm Metre 1 538 538.00 EL. MR-40
5.0 CABLE TERMINATION (IS:7098 Part-I) - -
Cable end Termination of following sizes 1.1kV grade XLPE insulated,
Extruded HR PVC inner sheath Type ST-2, FR-LSH PVC outer sheath Type
ST-2, stranded Copper conductor, Armoured cables as per IS:7098 Part-I
including cost of tinned copper, heavy duty crimpping lugs, double
compression glands, insulation tape and all necessary material to complete
the termination. -
a. 1C x 50 sq.mm.Cu. Ar. XLPE cable Nos. 1 496 496.00 EL. MR-49
b. 1C x 150 sq.mm.Cu. Ar. XLPE cable Nos. 72 769 55,368.00 EL. MR-50
c. 1C x 25 sq.mm.Cu. Ar. XLPE cable Nos. 1 454 454.00 EL. MR-51
d. 4C x 4 sq.mm.Cu. Ar. XLPE cable Nos. 1 384 384.00 EL. MR-52
e. 4C x 6 sq.mm.Cu. Ar. XLPE cable Nos. 1 384 384.00 EL. MR-53
f. 4C x 10 sq.mm.Cu. Ar. XLPE cable Nos. 40 384 15,360.00 EL. MR-54
g. 4C x 16 sq.mm.Cu. Ar. XLPE cable Nos. 16 384 6,144.00 EL. MR-55
h. 4C x 25 sq.mm.Cu. Ar. XLPE cable Nos. 1 496 496.00 EL. MR-56
i. 4C x 35 sq.mm.Cu. Ar. XLPE cable Nos. 1 496 496.00 EL. MR-57
j. 4C x 50 sq.mm.Cu. Ar. XLPE cable Nos. 1 769 769.00 EL. MR-58
k. 4C x 70 sq.mm.Cu. Ar. XLPE cable Nos. 1 769 769.00 EL. MR-59
l. 4C x 120 sq.mm.Cu. Ar. XLPE cable Nos. 1 909 909.00 EL. MR-60
m. 4C x 240 sq.mm.Cu. Ar. XLPE cable Nos. 1 1,049 1,049.00 EL. MR-61
n. 4C x 150 sq.mm.Cu. Ar. XLPE cable Nos. 16 909 14,544.00 EL. MR-62
6.0 SUPPLY & LAYING OF CONTROL CABLING
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supply, laying, testing and commissioning of the following sizes of 1.1 KV
grade XLPE insulated, Extruded FR-LSH PVC inner sheath Type ST-2,
FR-LSH PVC outer sheath Type ST-2, stranded Copper conductor,
Armoured control cable in the existing pipes, channels, trays etc.
complete as required and as per specifications as per IS: 7098 Part-I.
a. From Main LT Panel (from each transformer ACB) to respective capacitor
panel for APFC relay for CT sensing:
b. From Main LT Panel to DG Power Panel for Control & Feed back:
c. For DG Set Battery Charging:
i. From DG Set Battery charger section (of respective DG set) in DG Power
Panel to Main LT Panel:
ii. From Main LT Panel (battery charger section) to batteries of respective DG
d. From HT Panel to transformer's primary winding CT's sensing (for respective
e. From Transformer Marchalling Box to HT Panel (for winding temperature, oil
temperature & buchloz)
Cable & Pipe Sealing arrangement to stop waterpenetration/ Fire
Supply and installation of FU-FZ/ BKD sleeves and seals for sealing of
Cable & pipe openings through retaining as well as partition wall (such as
core cut, sleeves and cutout) to stop water and fire penetration. The Seal
must be circular type and shall be tested for rat bite with (Protective rate
0.7), termite proof (Decay Level 1) & age tested at 200° for 24Hrs, Sound
insulation up to 54dB from recognized testing institutes. The seal must have
Fire protection from recognized testing institutes as per National &
international standards. The seal must have been tested for RADON gas
tightness with 95% Efficiency, Salt Spray test certification/ report of 28days
for all metal parts of the seal. The seal made of SS 304 grade pressure
plate, nut, bolts & EPDM rubber (halogen free) & low-smoke index rubber &
must have rubber Shore hardness A 55±5°. Tightness according to FHRK
test regulations OR equivalent National & international standards from
recognized testing institutes like Lloyd’s register/ LGA/ SGS etc.
Technical Details:
Sleeve: FUFZ -Fibre reinforced concrete -Asbestos free.
Dimensions: Seal width: 40 mm Wall Thickness: 200mm-300mm
Load case: Pressing Water
Tightness: Gastight and watertight
Approval/ Test report by LGA: Water tight pressure test for upto 5 bar
Material: EPDM (55+-5 Shore A), V2A (EN 1.4301/ AISI 304).
a. Upto 100mm dia Each 5 28,522 1,42,610.00 EL. MR-69
TOTAL CARRIED OVER TO SUMMARY 40,728.64 1,10,27,189.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
E CABLE TRAYS WORKS
1 PERFORATED CABLE TRAY - -
Hot Dipped Galvanized Iron Cable Tray - -
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray (galvanisation thickness not less than 50 microns) with
perforation not more than 17.5%, in convenient sections, joined with
connectors, suspended from the ceiling with G.I. suspenders including G.I.
bolts & nuts, etc. as required. - - 4.6
1.1 100 mm width X 50 mm depth X 1.6 mm thickness RM 110 711 78,248.25 - '4.6.1
1.2 150 mm width X 50 mm depth X 1.6 mm thickness RM 120 761 91,358.74 - '4.6.2
1.3 225 mm width X 50 mm depth X 1.6 mm thickness RM 80 952 76,132.28 - '4.6.3
1.4 300 mm width X 50 mm depth X 1.6 mm thickness RM 115 1,024 1,17,755.16 - '4.6.4
1.5 450 mm width X 50 mm depth X 1.6 mm thickness RM 150 1,409 2,11,330.88 - '4.6.6
1.6 600 mm width X 75 mm depth X 2.0 mm thickness RM 95 2,079 1,97,481.39 - 4.6.14
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray “bends” (galvanisation not less than 50 microns)
2 withperforation not more than 17.5%, in convenient sections, joined with
connectors, suspended from the ceiling with G.I. suspenders including G.I.
bolts & nuts, etc. as required - - 4.7
2.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 14 1,232 16,945.01 - 4.7.1
2.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 15 1,350 20,255.87 - 4.7.2
2.3 225 mm width X 50 mm depth X 1.6 mm thickness Each 10 1,801 18,012.30 - 4.7.3
2.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 14 1,969 28,307.70 - 4.7.4
2.5 450 mm width X 50 mm depth X 1.6 mm thickness Each 19 2,853 53,490.64 - 4.7.6
2.6 600 mm width X 75 mm depth X 2.0 mm thickness Each 12 4,392 52,160.85 - 4.7.14
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray “Tee” (galvanisation not less than 50 microns) with
3 perforation not more than 17.5%, in convenient sections, joined with
connectors, suspended from the ceiling with G.I. suspenders including G.I.
bolts & nuts, etc. as required. - - 4.8
3.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 4 1,411 6,208.40 - 4.8.1
3.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 5 1,471 7,058.61 - 4.8.2
3.3 225 mm width X 50 mm depth X 1.6 mm thickness Each 3 2,092 6,692.84 - 4.8.3
3.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 5 2,292 10,545.38 - 4.8.4
3.5 450 mm width X 50 mm depth X 1.6 mm thickness Each 6 2,277 13,659.15 - 4.8.6
3.6 600 mm width X 75 mm depth X 2.0 mm thickness Each 4 5,160 19,608.74 - 4.8.14
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray “Cross member” (galvanisation not less than 50 microns) with
4 perforation not more than 17.5%, in convenient sections, joined with
connectors, suspended from the ceiling with G.I. suspenders including G.I.
bolts & nuts, etc. as required. - - 4.9
4.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 4 1,411 6,208.40 - 4.9.1
4.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 5 1,471 7,058.61 - 4.9.2
4.3 225 mm width X 50 mm depth X 1.6 mm thickness Each 3 2,113 6,760.89 - 4.9.3
4.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 5 2,516 11,572.53 - 4.9.4
4.5 450 mm width X 50 mm depth X 1.6 mm thickness Each 6 3,795 22,769.51 - 4.9.6
4.6 600 mm width X 75 mm depth X 2.0 mm thickness Each 4 5,163 19,620.86 - 4.9.14
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray “Reducer” (galvanisation not less than 50 microns) with
5 perforation not more than 17.5%, in convenient sections, joined with
connectors, suspended from the ceiling with G.I. suspenders including G.I.
bolts & nuts, etc. as required - - 4.10
5.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 2 1,760 3,871.48 - 4.10.1
5.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 2 2,043 4,902.24 - 4.10.2
5.3 225 mm width X 50 mm depth X 1.6 mm thickness Each 2 2,574 4,118.80 - 4.10.3
5.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 2 3,002 6,903.90 - 4.10.4
5.5 450 mm width X 50 mm depth X 1.6 mm thickness Each 3 3,957 11,869.62 - 4.10.6
5.6 600 mm width X 75 mm depth X 2.0 mm thickness Each 2 5,597 10,634.70 - 4.10.14
6 LADDER TYPE CABLE TRAY - -
Supply, fabrication and installation of Hot dip galvanised factory built G.I
ladder type cable trays complete with all bends, tees, elbows, reducers,
supports & fixing arrangement etc. of various widths in single tier/ two tier/
three tier/ five tier fashion either on one side of the wall or on two sides of
the wall or at ceiling/ wall/ floor. (All bends & tee shall be of factory built of
same make as that of tray). Cable tray supports are supposed to be
included in the rate of the trays. Nothing extra to be paid for cable tray
supports. Cable trays and supports shall be as per specifications. Cable tray
supports shall also be Hot dip galvanised.
6.1 750mm wide tray Metre 100 1,317 1,31,700.00 EL. MR-72
6.3 1000mm wide tray Metre 10 2,289 22,890.00 EL. MR-74
6.4 1250mm wide tray Metre 10 2,601 26,010.00 EL. MR-75
Contractor to ensure that cable trays and their supports are strong enough
to take care of the loads of the cables without sagging and the supporting
arrangement shall be safe enough to withstand earthquake situations as per
Note sesimic conditions prevailing at site. Contractor to improve upon
specifications of trays and supports as specified in the specifications and
BOQ, if it is felt necessary for the safety and with the approval of owner/
TOTAL CARRIED OVER TO SUMMARY 11,41,543.70 1,80,600.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
1 UPS Set - -
a. Supplying, installation, testing and commissioning of micro processor/ DSP
controlled of 120kVA/ kW Modular UPS in parallel redundant configuration.
Each 125kVA UPS (N+1) configuration, should be comprising of hot
swappable power modules and hot scalable to 200kVA or higher within the
same chassis. Power modules of 20kW, 25kW or 30kW may be selected by
OEM depending upon their respective designs to arrive at the desired rating.
Each Power Module shall be built using IGBT based rectifier to achieve
input THDI < 3% @ 100% Load and input power factor of greater than 0.99
and IGBT based inverter to achieve output THDV ≤ 1% @ 100% linear load.
True Online Double Conversion UPS using PWM IGBT technology, 3 Phase
input and 3 phase 400V output UPS system; and each comprising of the
b. Inbuilt/ External Input phase reversal correction to be provided. (The system
should run in mains operation inspite of phase sequence reversal and
should not switch to battery mode.) - -
c. Fully rated, unity power factor designed hot scalable and hot-swappable
Rectifier, charger, Inverter unit Integrated in each Power module. Power
modules to be integrated inside a single frame and it should be possible to
add or replace power modules without switching the load to bypass source
and without switching off the UPS. - -
d. 100% rated Inbuilt static bypass module at the bypass line. The Static
Bypass Module should be rated equivalent to the total power rating of the
chassis i.e 200kVA or higher. - -
UPS Efficiency shall be > 95% from 25% to 100% Load (w/o isolation
transformer losses). UPS System shall have automatic software algorithm to
switch off unwanted/extra power modules in low load condition to improve
the efficiency to 95% even at lower loads less than 25%. In event of load
increase the power modules should automatically switch ON and start taking
load seamlessly.
LCD Touch Screen Display indicating all important parameters. To improve
the UPS Security over LAN/ WAN the SNMP card provided with UPS shall
be having Cybersecurity enhancements for UL 2900-2 certification, including
stronger encryption, configurable password policy. The card shall work on
GIGABIT Speed and should support all major protocols. UPS shall be
provided with Temperature Humidity Sensors to monitor Temperature and
Humidity over LAN through SNMP card Software.
UPS shall be provided with Dust Filters, Snmp & Modbus Communication
Port, Touch Screen Display, Input Isolator, output Isolator, Bypass Isolator
and MBS Switch.
Offered Model of UPS System shall be Type Tested from a Third Party
NABL accredited Lab for IEC 62040-3 Standard and detailed type test report
shall be provided.
Top Covered Battery Rack, Battery Interlinks, Battery MCCB, Battery MCCb
Enclosure, Battery to UPS DC canle, Battery Terminal Caps for extra safety,
parallel card & Kit shall be provided by UPS Vendor only.
External Isolation Transformer (as per suitable UPS size) at Input of UPS, K-
1 Type, H Insulation Class, Air Cooled, Indoor Type, with Inbuilt Input MCCB
for overcurrent protection. A separate isolation transformer should be
provided with each UPS Rack of min. 10% higher rating and capacity.
Each Modular UPS to be offered with Lithium ion batteries to have minimum
specification as per below
The UPS battery shall be sized for 15 minutes on each UPS using UL1642,
UL1973, UL 991, UL 1998 and mandatory Ul9540a, At Cell Level, Module
Level and rack level for complete fire propagation certificate Lithium ion
battery backup at 0.8 power factor at 120kVA load considering 85% DOD or
15% Ageing Margin in battery calculation.
1-Type of Battery: Lithium Ion Battery with LMO-NCM chemistry
2-Cycle life (@25℃,1C/1C,100%DOD) shall be ≥ 2500 Cycles
3-Each battery cabinet shall feature a DC rated circuit breaker for control
and protection. The circuit breaker within the battery cabinet shall only
provide protection to the battery string within that battery cabinet.
i.Over/ Under Voltage
ii.Over/ Low temperature
iii.Over Current
iv.Short Circuit
5-Inbuilt Rack based Battery Monitoring System: Monitor + Control along
with balance charging. Individual Module Level, Rack Level & System Level
shall be provided with each UPS with LIB system. The BMS shall provide
SOC (State of Charge), SOH (State of Health), Voltage and Temperature for
each Cell and Module within the LIB rack. The PC based external BMS is
not acceptable .
6-Lithium-ion batteries should be supplied according to the OEM standard
model, complete with a Battery Management System (BMS) and rack
provided by the OEM of the lithium-ion batteries. This ensures the highest
quality and maintains all applicable safety certifications at the rack level. The
quoted model should also be listed on the global OEM website or available
on the UPS OEM website.
120 kW/ kVA (N+1) Modular UPS as described above Set 2 57,35,386 1,14,70,772.00 EL. MR-76
UPS System will be with Standard Warranty of 3 years and Lithium Ion
Batteries will be with 3 years standard and 10 years performance
warranty. Comprehensive AMC for 120 kW/ kVA (N+1) Modular UPS
(Both the UPS will be in parallel mode)
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supplying, installation, testing and commissioning of micro processor/ DSP
controlled of 120kVA/ kW Modular UPS in parallel redundant configuration.
Each 125kVA UPS (N+1) configuration, should be comprising of hot
swappable power modules and hot scalable to 200kVA or higher within the
same chassis. Power modules of 20kW, 25kW or 30kW may be selected by
OEM depending upon their respective designs to arrive at the desired rating.
Each Power Module shall be built using IGBT based rectifier to achieve
input THDI < 3% @ 100% Load and input power factor of greater than 0.99
and IGBT based inverter to achieve output THDV ≤ 1% @ 100% linear load.
True Online Double Conversion UPS using PWM IGBT technology, 3 Phase
input and 3 phase 400V output UPS system; and each comprising of the
Inbuilt/ External Input phase reversal correction to be provided. (The system
should run in mains operation inspite of phase sequence reversal and
should not switch to battery mode.)
Fully rated, unity power factor designed hot scalable and hot-swappable
Rectifier, charger, Inverter unit Integrated in each Power module. Power
modules to be integrated inside a single frame and it should be possible to
add or replace power modules without switching the load to bypass source
and without switching off the UPS.
100% rated Inbuilt static bypass module at the bypass line. The Static
Bypass Module should be rated equivalent to the total power rating of the
chassis i.e 200kVA or higher.
100% rated Maintenance Bypass Switch for the complete isolation of UPS
from incoming source and load while ensuring continuous operation of the
load during maintenance with make before break transfer arrangement.
UPS Efficiency shall be > 95% from 25% to 100% Load (w/o isolation
transformer losses). UPS System shall have automatic software algorithm to
switch off unwanted/extra power modules in low load condition to improve
the efficiency to 95% even at lower loads less than 25%. In event of load
increase the power modules should automatically switch ON and start taking
load seamlessly.
LCD Touch Screen Display indicating all important parameters. To improve
the UPS Security over LAN/ WAN the SNMP card provided with UPS shall
be having Cybersecurity enhancements for UL 2900-2 certification, including
stronger encryption, configurable password policy. The card shall work on
GIGABIT Speed and should support all major protocols. UPS shall be
provided with Temperature Humidity Sensors to monitor Temperature and
Humidity over LAN through SNMP card Software.
UPS shall be provided with Dust Filters, Snmp & Modbus Communication
Port, Touch Screen Display, Input Isolator, output Isolator, Bypass Isolator
and MBS Switch.
Offered Model of UPS System shall be Type Tested from a Third Party
NABL accredited Lab for IEC 62040-3 Standard and detailed type test report
shall be provided.
Top Covered Battery Rack, Battery Interlinks, Battery MCCB, Battery MCCb
Enclosure, Battery to UPS DC canle, Battery Terminal Caps for extra safety,
parallel card & Kit shall be provided by UPS Vendor only.
External Isolation Transformer (as per suitable UPS size) at Input of UPS, K-
1 Type, H Insulation Class, Air Cooled, Indoor Type, with Inbuilt Input MCCB
for overcurrent protection. A separate isolation transformer should be
provided with each UPS Rack of min. 10% higher rating and capacity.
Each Modular UPS to be offered with Lithium ion batteries to have minimum
specification as per below
The UPS battery shall be sized for 15 minutes on each UPS using UL1642,
UL1973, UL 991, UL 1998 and mandatory Ul9540a, At Cell Level, Module
Level and rack level for complete fire propagation certificate Lithium ion
battery backup at 0.8 power factor at 120kVA load considering 85% DOD or
15% Ageing Margin in battery calculation.
1-Type of Battery: Lithium Ion Battery with LMO-NCM chemistry
2-Cycle life (@25℃,1C/1C,100%DOD) shall be ≥ 2500 Cycles
3-Each battery cabinet shall feature a DC rated circuit breaker for control
and protection. The circuit breaker within the battery cabinet shall only
provide protection to the battery string within that battery cabinet.
i.Over/ Under Voltage
ii.Over/ Low temperature
iii.Over Current
iv.Short Circuit
5-Inbuilt Rack based Battery Monitoring System: Monitor + Control along
with balance charging. Individual Module Level, Rack Level & System Level
shall be provided with each UPS with LIB system. The BMS shall provide
SOC (State of Charge), SOH (State of Health), Voltage and Temperature for
each Cell and Module within the LIB rack. The PC based external BMS is
not acceptable .
6-Lithium-ion batteries should be supplied according to the OEM standard
model, complete with a Battery Management System (BMS) and rack
provided by the OEM of the lithium-ion batteries. This ensures the highest
quality and maintains all applicable safety certifications at the rack level. The
quoted model should also be listed on the global OEM website or available
on the UPS OEM website.
120 kW/ kVA (N+1) Modular UPS as described above Set 2 57,35,386 1,14,70,772.00 EL. MR-77
UPS System will be with Standard Warranty of 3 years and Lithium Ion
Batteries will be with 3 years standard and 10 years performance
warranty. Comprehensive AMC for 120 kW/ kVA (N+1) Modular UPS
(Both the UPS will be in parallel mode)
TOTAL CARRIED TO SUMMARY 2,29,41,544.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
CIRCUIT CUM POINT WIRING (With MS CONDUITING)
1 All wiring shall be of 1100 volts grade.
2 All wiring shall be HR FRLS PVC insulated unsheathed, flexible, copper
conductor, single or multi core as called for.
3 Earth wiring shall also be HR FRLS PVC insulated unsheathed, flexible,
copper conductor, single core as called for.
4 Size of earth wire shall be the same as of the phase conductor or as
specified otherwise.
5 All Switches & Sockets shall be of modular design complete with modular
plate and suitable sized GI/ moulded boxes as called for and shall be
suitable upto 250V, AC supply.
6 The recessed Switches and Socket outlet boxes shall be of 1 MM thick pre-
galvanized sheet and of the same make/ manufacturer as of the switches
and sockets. Local make boxes are not to be used.
7 The surface mounted Switches & Sockets outlet boxes shall be moulded
and of the same make/ manufacturer as of the Switches & Sockets.
8 PVC Conduits shall be of FRLS type and shall be of minimum wall
thickness of 2mm. (Rigid Heavy duty Conduit) unless otherwise specified.
Company specified adhesive to be used for joining/ fixing of PVC conduits
9 GI and MS Conduits shall be of min. 16G thickness. Metallic conduit work
shall be complete with proper threads, check nuts/ lock nuts etc.
10 Flexible conduits, where ever required, shall be of heavy duty and complete
11 Minimum diameter of the conduit to be used shall be 25mm. Conduit less
than 25mm dia is not to be used unless otherwise specified.
12 Conduiting may be concealed or surface mounted (Exposed) as the case
a Circuit cum point wiring for light points, ceiling fan points & exhaust fan
points, 6A raw light plug sockets, 16A raw power Sockets, Raw Metal clad
and Raw moulded socket outlets shall include:
b Circuit Wiring (Phase & Neutral) of required length from DB/ board to switch.
c Point Wiring (Phase & Neutral) of required length from switch board to point.
d Insulated Green Colour earth wire for earthing of light fixture, switch and
socket outlet box and 3rd pin of socket. Each circuit will have a separate
earth wire from the DB.
e Conduits, bends, junction boxes, pull boxes and GI pull wire as required.
f Switch/ Switches/ socket outlets/ eletronic fan regulator/ dimmer with GI
outlet boxes/ moulded outlet boxes of suitable sizes, heavy duty 'MS'
hexogonal hook box with hook for ceiling fans.
13 All hard ware and civil work etc.
a Circuit cum point wiring for UPS points shall include:
b Circuit Wiring (Phase & Neutral) of required length.
c Point Wiring (Phase & Neutral) of required length.
d Insulated green colour earth wire for socket outlet box and furniture and a
separate green colour earth wire with yellow band for 3rd pin of the socket
outlet. Each circuit will have separate earth wires for 3rd pin earthing and
box/ furniture earthing from the DB.
e Conduits, bends, junction boxes, pull boxes and GI pull wire as required.
f Switch/ Switches/ socket outlets with GI/ moulded outlet boxes of suitable
sizes as called for.
14 All hard ware and civil work etc.
16 Wiring terminations shall be made using proper sized thimbles/ lugs.
15 All circuit & point wiring shall be colour coded & shall have ferruling on either
end for circuit identification.
16 The rates shall include material & labour for necessary length of circuit and
point wiring, earth wiring, rigid and flexible conduiting, bends, junction boxes,
pull boxes, screws, washers, check nuts, couplers, saddles, hangers
supports, GI pull wire, civil work comprising chipping, cutting chases, fixing
conduits & making good or surface clamping of conduit work as the case
may be, modular switches, socket outlets, Electronic fan regulators surface
or recessed outlet boxes as the case may be, ceiling rose, rigid and flexible
conduit (PVC/ GI/ MS) as may be required, connectors and terminal blocks
of proper rating etc. & sleeves etc. including lugs/ thimbles for
terminations. Fan points wiring shall include switch as well as electronic
speed regulator and fan hook box with fan hook.Wiring shall include
conduiting and wiring (Phase, Neutral, Earth) of light points/ fan points/ UPS
and raw sockets outlets of required length from the distribution board via
switch to the point.
Cost of circuit cum point wiring shall include everything and all items and
accessories to make the job complete in all respects.
a Important Notes:
b For FCU's, 6A Switched socket outlet to be used near FCU's.
c For Indoor Units of VRV System, 6A or 16A switched socket outlets to be
used depending upon the load.
d For 1 Phase window AC Units, moulded socket outlets to be used.
e For 1 Phase & 3 Phase Split Units, moulded socket outlets to be used
(weather proof). Wiring and conduiting upto outdoor unit to be considered in
the point rate.
f For 1 Phase & 3 Phase Inline Exhaust/ Fresh Air Fans, moulded socket
outlets to be used.
g For 1 Phase & 3 Phase Ceiling hung AHU's, moulded sockets to he used.
1.0 For Light Points, Ceiling Fan Points, Exhaust Fan Points & 6A Socket
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
i) For switch Controlled light points.
ii) For switch Controlled Ceiling Fan points.
iii) For switch Controlled Exhaust Fan points.
iv) For 6A switched socket outlets.
v) For MCB Controlled Light points.
vi) Wiring with 2x1.5 sqmm + 1x1.5 sqmm (earth wire).
vii) Wiring of required length from DB to point via switch for switch controlled
viii) Wiring of required length from DB or Dimmer Panel to point for MCB
controlled points.
ix) Wiring of required length from DB to point via power pack for occupancy
sensor as MCB controlled points.
x) Wiring of required length from DB to point via scene selector as MCB
controlled points.
xi) Modular switch for light points
xii) Modular switch and electronic fan regulator for Ceiling Fan points/ electronic
fan regulator, if specifically called for in the BOQ.
xiii) Modular switch for Exhaust Fan point and modular unswitched socket near
xiv) Modular 6A, 3 pin switched socket outlets.
xv) Suitable sizes of GI outlet boxes.
xvi) MS conduiting of required length complete with bends, junction boxes and
xvii) Surface or recessed conduiting including civil work like chase cutting and
making good as required (as the case may be).
1.1 Switch Control Light points wiring: (Refer tender drawings)
• Circuit wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth)
• Point wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth)
• in 25mm dia conduit:
i. Primary (First) light point controlled by a switch. Nos. 15 2,833 - 42,495.00 EL. MR-78
ii. Secondary (Loop) light point looped to first point and so on. Nos. 25 1,380 - 34,500.00 EL. MR-79
1.2 MCB Control Light points wiring: (Refer tender drawings)
• Circuit wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth)
• Point wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth)
• in 25mm dia conduit:
i. Primary (First) light point controlled by a MCB in the DB. Nos. 60 3,022 - 1,81,320.00 EL. MR-80
ii. Secondary (Loop) light point looped to first point and so on. Nos. 80 1,235 - 98,800.00 EL. MR-81
Note: MCB cost not to be included here.
1.3 Wiring of light points Lighting DB and dimmable balast connection to
dali controler, lighting control through local keypad without Local
switches (all wiring going to DB/ Dimmer controller) MCB controlled
wiring. (Refer tender drawings)
Wiring for MCB light controlled points
a • Circuit wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth)
• Point wiring with 2 x 1.5mm2 + 1 x 1.5mm2 (Earth) and including with
1x1.5 Sq.mm control wiring from dimmable balast connection to dali
• in 25mm dia conduit:
i. Primary (First) Point (wiring from MCB DB to first point) Nos. 475 2,688 - 12,76,800.00 EL. MR-82
ii. Secondary (Loop) Point (light looped to first point & so on): Nos. 1070 1,126 - 12,04,820.00 EL. MR-83
Note: Occupany sensors, day light sensors, Dalli Dimmers, wall touch
panels are excluded from here (shall be covered separatelly in light
controls & automation). All control wiring for dimmable ballasts is
excluded from here.
1.4 Ceiling Fan Point:
Ceiling Fan point controlled by a switch and an electronic regulator. Nos. 5 1,569 - 7,845.00 EL. MR-84
1.5 6A, 3 Pin Switched Socket Outlet Point Nos. 50 1,671 - 83,550.00 EL. MR-85
1.6 6A, 3 pin, Round pin, Shuttered UPS switched/ unswitched socket
outlet wiring for AHU room fire dampers/ for VAV boxes:
i. For AHU room fire dampers:
Wiring for a 6A, 3 pin, Round Pin, unswitched UPS socket outlet but in
surface mounted plastic boxes with 2 x 2.5mm2 + 1 x 2.5mm2 (Earth) in
25mm dia conduit. Nos. 50 1,772 - 88,600.00 EL. MR-86
Note: a. One independent circuit for all 6A unswitched socket outlets for fire
dampers in one AHU room
b. Max. 10 VAV box 6A socket on one circuit.
1.7 Wiring for work station UPS socket outlets : First point
a. First point Wiring with 4Cx2.5mm², 450/ 750V grade, PVC Insulated, FR-
LSH PVC sheathed, flexible copper conductor, multi core, flexible
cable (Phase, Neutral, IG, G) for a First set of UPS socket outlets on
the work stations/ table/ counter. Wiring partly in conduits & mainly in
raceway. Raceways to be accounted for separately but conduiting is
included here. (Conduit only from raceway to first point).
i. A set of 3 x 6A socket outlets (as approved by consultant) controlled by a
ii. A set of 2 x 6A socket outlets (as approved by consultant) controlled by a
b. Wiring for work station UPS socket outlets : Loop Point
Loop point wiring with 4Cx2.5mm², 450/ 750V grade, PVC Insulated, FR-
LSH PVC sheathed, flexible copper conductor, multi core, flexible
cable (Phase, Neutral, IG, G) for a next set of UPS socket outlets on
the next work stations/ tables/ counters. (Wiring to run in furniture
i. A set of 3 x 6A socket outlets (as approved by consultant) controlled by a
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
ii. A set of 2 x 6A socket outlets (as approved by consultant) controlled by a
Note: Maximum 4 Nos. workstation on a UPS circuit.
1.8 WIRING FOR POP-UP BOXES
Providing and fixing aluminum construction, factory fabricated pop-up boxes
for meeting rooms/ cabins table etc:
i. 10 module Pop-up Box complete with 3 x 6A, 3pin switched socket outlets
and 4 nos. N/W nodes with company's factory fabricated moulded outlet box
as may be required. (Pop up boxes with sockets are considered in AV
package, only installation & coordination to be considered here.)
ii. 7 module Pop-up Box complete with 2 x 6A, 3pin switched socket outlets
and 3 nos. N/W nodes with company's factory fabricated moulded outlet box
as may be required. (Pop up boxes with sockets are considered in AV
package, only installation & coordination to be considered here.)
iii. 3 module Pop-up box complete with 1 x 6A, 3 pin switched socket outlet
with company's factory fabricated moulded outlet box as may be required.
(Pop up boxes with sockets are considered in AV package, only
installation & coordination to be considered here.)
iv. 3 module Pop-up box complete with 3 nos. N/W nodes and with company's
factory fabricated moulded outlet box as may be required. (Pop up boxes
with sockets are considered in AV package, only installation &
coordination to be considered here.) No. 1 654 654.00 EL. MR-94
b WIRING FOR POP-UP BOXES
i. Wiring in existing raceways including termination for pop-up boxes:
4C x 2.5mm2 450/750V grade, PVC Insulated, FR-LSH PVC sheathed,
flexible copper conductor, multi core, flexible cable (Phase, Neutral, IG, PE)
partly in existing raceways & partly in conduits. RM 1110 269 - 2,98,590.00 EL. MR-95
(Cost of raceways not to be included here but including necessary
conduiting if required so). Conduiting from raceway to Pop-up box.
1.9 For 16A, 6Pin Power Switched Socket Outlets:
i) Wiring with 2x4 sqmm + 1x2.5 sqmm (Earth wire) for ONE SOCKET
OUTLET ON ONE CIRCUIT.
ii) Wiring with 2x6 sqmm + 1x4 sqmm (Earth wire) for first socket outlet and
2x4sqmm + 1x2.5 sqmm (Earth wire) for second socket outlet (TWO
SOCKET OUTLETS ON ONE CIRCUIT).
iii) Wiring of required length from DB to Switched Socket outlet.
iv) Modular Switched Socket outlet and plate.
v) Suitable size of GI outlet box.
vi) MS conduiting of required length complete with bends, junction boxes and
vii) Surface or recessed conduiting including civil work like chase cutting and
making good as required (as the case may be).
1.9.1 Wiring for one 6/16Amp socket outlet (6/16A) on one circuit. Wiring with
1.9.2 Wiring for two 6/16Amp Socket Outlets (6/16A) on one Circuit. First point
with 2x6 sq.mm + 1x4 Sq.mm (E) and loop point with 2x4 Sq.mm + 1x2.5
1.10 For Moulded Socket outlet, wiring for 16A/ 3Pin/ 240V, 20A/ 3Pin/ 240V
for 1Phase power equipment, Window/ Split AC Units and
Miscellaneous multipurpose/ convenience power outlets:
i) Wiring of required length from DB to Socket outlet.
ii) Socket outlet and suitable rating of DP/ FP, 30mA RCBO with suitable outlet
box and suitable plug top.
iii) Weather proof socket outlet in case of outdoor installation.
iv) MS conduiting of required length complete with bends, junction boxes and
v) Surface or recessed conduiting including civil work like chase cutting and
making good as required (as the case may be).
1.10.1 Wiring for 20A/ 3Pin/ 240V/ 1Phase moulded socket outlet (indoor type)
with 2x6 sq.mm + 1x4 sq.mm (E) Nos. 8 6,857 - 54,856.00 EL. MR-98
1.10.2 Wiring for 16A/ 3Pin/ 240V/ 1Phase moulded socket outlet (indoor type)
1.10.3 Wiring for 16A/ 3Pin/ 240V/ 1Phase moulded socket outlet (outdoor type)
2 WIRING FOR IT RACKS ETC. AT COMMUNICATION ROOM
2.1 With Metal Enclosure and Plastic Plug & Socket
2.1.1 Wiring for IT Racks
a. Providing & Fixing of 16A Socket outlets with plug top & Wiring with 4
sq.mm. (for upto 2kW Rack):
16A, 1 Phase, 230V, 3 Pin, round pin, plastic socket out let with plastic
angled plug top in CRCA sheet steel powder coated metallic enclosure with
16A DP MCB, 10kA, ‘D’ Curve. Socket & plug top with IP 44 rating &
metal enclosure IP30. Nos. 20 10,344 - 2,06,880.00 EL. MR-101
b. Supply & Laying of wiring in existing raceways/ on existing cable trays:
4C x 4 Sq.mm 450/ 750 Volts grade PVC insulated FR-LSH PVC sheathed
flexible copper conductor cable including termination at both end (P,N,G, IG)
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
3.0. U-PVC Trunking in Server Room for IT Cabling:
Supply & Fixing of U-PVC trunking with top cover, end caps angles, bends,
joints, junction boxes, separators, couplers and clips etc. as may be
required and as approved by Architect/ Consultants:
4.0. RACK BODY EARTHING:
Supply and laying including terminations of FR LSH PVC insulated,
unsheathed, 450/ 750 Volts grade stranded copper conductor single core
wire for rack body earthing along with thimbles, running under false floor/ or
on OH tray, from one rack to another rack:
i. 6 sq mm Single Core Wire RM 1000 138 - 1,38,000.00 EL. MR-105
TOTAL CARRIED OVER TO SUMMARY - 62,40,212.00
H CONDUITING & RACEWAYS FOR VOICE/ DATA (N/W) & TV SYSTEM
Supply, installation, testing and commissioning of all conduiting for
telephone system including providing and fixing:
ii. All necessary specials and fittings, brass bushes etc.
iii. Approved cover plates for inspection, junction and outlet boxes.
iv. 2mm thick outlet boxes and junction boxes.
v. All fixing accessories such as clips, nails, screws etc.
vi. Providing and fixing approved saddles, hooks and grouting the same as
required, in the case of all exposed conduit work.
vii. Embedding conduits and accessories in wall, floors etc. during construction
and/ or cutting chases and making good as approved.
viii. Providing 14 SWG GI pull wire in all conduit work.
Repainting of MS conduit, outlet boxes and junction boxes when ever
a. Important Notes:-
b. Contractor to get the samples of floor and ceiling raceways to be approved
from the Architect/ Project Manager/ Consultant/ Client before supply &
c. Depth of the floor raceway is to be decided by the contractor after checking/
examining screed depth available at site. For this purpose chipping to be
carried out at various places on the floor/ floors to carefully assess the
depth/ floor margin available. Final approval is to be obtained from the
Architect/ Project Manager/ Client before ordering/ fabricating raceway. The
sizes & depths of raceways given in the BOQ are only tentative & indicative.
d. Contractor is also supposed to check and confirm the adequacy of raceway
sizes by calculating the exact number of electrical circuit wires & N/W wires
for respective Electrical & N/W raceways.
e. Electrical & N/W raceways to be run separated by a gap of not less than
f. 'N/W' stands for Networking cables.
1N/ 2N/ 3N/ 4N stands for One node/ Two nodes/ Three nodes & Four
nodes respectively of voice & data face plates/ wires.
1 CONDUITING FOR VOICE/ DATA & TV OUTLETS:
a. Supplying and fixing of following sizes of steel conduit along with
accessories in surface (on surface of wall/ slab, metal decking/ trusses etc
as per site conditions with suitable fixing arrangment)/ recess including
painting in case of surface conduit, or cutting the wall and making good the
same in case of recessed conduit as required.
b. Supplying and fixing of following sizes of medium class PVC conduit along
with accessories in surface/ recess including cutting the wall and making
good the same in case of recessed conduit as required. 1.21
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
2 GI OUTLET BOXES FOR VOICE/ DATA FACE PLATES:
Providing & Fixing of factory fabricated 1 MM thick pre-galvanized sheet
boxes for IN/ 2N/ 3N/ 4N Voice/ Data (N/W) face plates. No. 385 180 - 69,300.00 EL. MR-106
3 TV CORD OUTLET
Supply, Fixing, Connecting including testing & commissioning of TV Co-axial
cable moduler socket outlet with moduler plate and 1 MM thick pre-
galvanized sheet boxes. No. 5 651 - 3,255.00 EL. MR-107
4 TV CO-AXIAL CABLE
Supply & laying of RG-6 Co-axial TV signal cable in existing conduits. RM 200 73 - 14,600.00 EL. MR-108
a IN FLOOR/ SCREED RACEWAY
Supply & Fixing of factory fabricated pre-galvanised sheet steel raceway in
2mm thickness for bottom & sides and 2mm/ 3mm thick top cover as
called for in the BOQ below, including necessary civil work such as chase
cutting in screed, fixing/ jamming the raceway, aligning & leveling and
finishing with sand cement plaster & chicken wire mesh:
ii. 150mm x 40mm (2mm top cover) RM 120 743 - 89,160.00 EL. MR-110
iii. 225mm x 40mm (3mm top cover) RM 55 1,218 - 66,990.00 EL. MR-111
b. RACEWAY FLOOR JUNCTION BOXES (IN SCREED)
Providing & Fixing of GI sheet steel 4 WAY junction boxes with top cover to
suite the raceway fixing & necessary civil work such as floor chipping,
jamming of junction box and repair of floor.
for 40mm depth raceway
i. 150mm x 150mm x 50mm (For 100mm wide raceway) Nos. 156 432 - 67,268.57 EL. MR-114
ii. 200mm x 200mm x 50mm (For 150mm wide raceway) Nos. 34 576 - 19,748.57 EL. MR-115
iii. 250mm x 250mm x 50mm (For 200mm wide raceway) Nos. 55 720 - 39,600.00 EL. MR-116
iv. 300mm x 300mm x 50mm (For 250mm wide raceway) Nos. 25 864 - 21,600.00 EL. MR-117
v. 400mm x 400mm x 50mm (For 300mm wide raceway) Nos. 34 1,152 - 38,990.77 EL. MR-118
c. CEILING RACEWAY
Supply and Fixing GI openable bottom cover junction boxes made from
2mm thick pre-galvanized sheets for top, bottom and sides and
complete with 2mm thick bottom cover complete with rubber gasketing.
The junction box shall be suitable to accommodate GI raceways specified
above. Necessary civil work to support/ clamp from RCC slab need to be
included here too. Raceways shall be complete with junction boxes of
required size & required quantity to be included in the cost of the raceways:
TOTAL CARRIED OVER TO SUMMARY 9,17,601.32 18,89,812.91
I EARTHING SYSTEM
The rates for earthing items include:
i. All fixing accessories such as brass, saddles, brass screws, rawl plugs etc.
ii. Jointing by riveting and brazing after tinning.
iii. Cutting chases, holes and making good the same wherever required.
iv. Effecting adequate and proper interconnections.
v. Use of copper thimbles.
vi. Excavation of earth, refilling, watering and ramming and making good as
approved in all kinds of soil.
vii. Earthing shall be as per IS: 3043-1987.
viii. Carrying out earth resistance tests and proving adequacy of earthing system
or improving the same by increasing the earth pits than mentioned in the
BOQ. Resistance of the earthing system shall be less than 1 ohm.
Contractor shall be responsible for suitability of the earthing system.
1 GI EARTHING- TAPE/ WIRES
Providing and fixing 25mm x 5mm copper strip in 40mm dia G.I. pipe from
1.1 earth electrode including connection with brass nut, bolt, spring, washer
excavation and re-filling etc. as required. RM 690 1,649 11,37,933.03 - 5.10
Providing and fixing 25mm x 5 mm G.I. strip in 40mm dia G.I. pipe from
1.2 earth electrode including connection with G.I. nut, bolt, spring, washer
excavation and re-filling etc. as required. RM 500 751 3,75,344.90 - 5.11
Providing and fixing 25mm x 5mm copper strip on surface or in recess for
connections etc. as required. RM 50 1,236 61,777.73 - 5.14
Providing and fixing 25mm x 5mm G.I. strip on surface or in recess for
connections etc. as required. RM 50 259 12,972.26 - 5.15
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop
earthing as required. RM 600 74 44,658.60 - 5.16
Providing and fixing earth bus of 50mm x 5mm copper strip on surface for
connections etc. as required. RM 660 2,247 14,82,856.91 - 5.20
Providing and fixing earth bus of 50mm x 5mm G.I. strip on surface for
connections etc. as required. RM 760 478 3,63,648.60 - 5.20
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Providing and fixing 4.00 mm dia copper wire on surface or in recess for
loop earthing as required. RM 50 165 8,240.58 - 5.17
2 CHEMICAL EARTHING - EARTH PIT
Supply, installation, testing and commissioning of Maintenance Free
Earthing System consisting of 1 Nos. CPRI tested 'UL' Listed copper
bonded carbon steel core electrode of 25 mm dia each with a minimum
coating thickness of 250 microns and length of 3 meters. 25 kgs/ Electrode
or more as required of earth enhancing compound needs to be considered
to fill the 100mm augered hole surrounding to the electrode. The rate shall
include excavation of earth, filling with back fill compound and earth pit
marking. The Complete installation shall be as per technical specifications.
Earth Pit shall essentially consist of:
a. UL Listed 25 mm dia. Copper bonded carbon steel core Electrode tested
according to IEC 62561-2.
b. SS Universal Clamp of Size 175X50X3 mm for Connection Terminal.
c. Earth enhancing compound (OEC) tested as per IEC 62561-7 (miminum
25 kg or more as per requirement).
d. Poly Propiline Heavy duty Pit cover.
Providing, fixing of heat shrinkanle black colour PVC sleeves for neutral/
dedicated earthing complete as required. RM 150 85 85 12,750.00 12,750.00 EL. MR-125
1. Contractor shall be responsible for obtaining earth-pit resistance results
as per IS codes.
2. Depth of earth pits to be decided accordingly to achieve desired results of
less than 1 ohm.
3. The quantities of each pits given in the schedule of quantities are
tentative. Earthing sytsem's restance to be achieved shall have be less than
4. Contracto to kake additional parallel earth pits, if the earth restance
comes more than 1 ohm to bring it doen to 1 ohm or less.
5. Or Contractor need to make earthing mat to achieve earthing system 's
resistance less than 1 ohm.
TOTAL CARRIED OVER TO SUMMARY 35,00,182.61 3,13,490.00
Providing and fixing M.V. danger notice plate of 200 mm x 150 mm, made of
mild steel, at least 2 mm thick, and vitreous enameled white on both sides,
1.0 and with inscription in single red Colour on front side as required as per
specifications of this tender and directions of Engineer-in-Charge.
Providing and fixing H.T. danger notice plate of 250 mm x 200 mm, made of
mild steel, at least 2 mm thick, and vitreous enameled white on both sides,
2.0 and with inscription in single red Colour on front side as required as per
specifications of this tender and directions of Engineer-in-Charge.
Supply and fixing wooden framed covered with glass shock treatment chart
printed on cloth in English, Hindi & Local language. Job 5 801 - 4,005.00 EL. MR-126
Supply and fixing suitable size wooden framed covered with glass for Main
4.0 Panel SLD in electrical room as per IE rules fixed to wall as required.
Supply, installation, testing and commissioning of Standard First aid box
complete with all accessories as required. Each 5 2,160 - 10,800.00 EL. MR-128
Portable 5 kg. dry type fire extinguisher suitable for electrical fire and as
recommended by the tariff advisory committee. Each 7 5,941 - 41,587.00 EL. MR-129
Supply and fixing of tool kit with all standard tools such as screw driver,
spaner etc as required. Each 5 10,485 - 52,425.00 EL. MR-130
Supply and Installation of Elastomer mat 1000 mm. wide, 2mm thick, for
upto 3.3kV grade as per Latest BIS Codes (IS: 15652/ 2006). (Vendor to
check the thickness of the mat as per latest IS code & Quoe accordingly
and also mention the thickness provided). RM 10 2,796 - 27,960.00 EL. MR-131
Supply and fixing of fire retardant electrically insulated synthetic mat of class
C, 3.0 mm thick suitable for 11kV AC grade system meeting requirements of
IS 15652:2006 tested for breakdown strength, tensile/ elongation, aging
properties, insulation resistance, effect to acid, alkaline, diesel, transformer
oil & leakage current test, fire test etc. having minimum width of 1000 mm ±
20 mm along with all allied materials such as Pu-resin, Chemi bound, special
PVC adhesive, liquid primer etc. in what so ever quantity required to
complete the job as per site conditions and as per instructions from
Engineer-in-Charge.
Supplying and laying of following size DWC HDPE pipe ISI marked along
with all accessories like socket, bend, couplersetc. conforming to IS: 14930,
Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm
below ground level) including excavation and refilling the trench but
excluding sand cushioning and protective covering etc., complete as
a. 120 mm dia (OD-120 mm & ID-103 mm nominal) Meter 40 2,307 - 92,280.00 EL. MR-133
TOTAL CARRIED OVER TO SUMMARY 2,051.11 2,51,937.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
K INTERNAL LIGHT FIXTURES AND FANS
a) Service Life of the fixture including driver/ control gear should be minimum
50000hrs @L70B10 Lumen maintenance
b) The housing of the indoor fixtures should be extruded aluminium/ CRCA.
c) The IP category should be as per specification of items or higher for indoor
applications as per application area.
d) The Surge Protection to be provided conforming to relevant IS standards/
IEC 61643-II Class-2 & EN 61643-II Type-2.
e) The Power factor should be 0.95 or higher.
f) The manufacturer’s name/ logo should be engraved/ embossed on the
housing/ body or Name/ Logo on aluminium plate labels or Name/ logo
printed on housing/ body.
g) The warranty period on complete luminaire including driver/ control gear,
LED, all accessories should be 5 years from the actual date of completion of
h) Color of powder coating shall be decided at the time of execution. It should
be possible to powder coat the fixture in any RAL shade.
i) The light fixtures and driver shall be BIS certified. The manufacturer shall
submit BIS certificates with respective R codes for each fitting and driver for
approval before execution.
j) Luminaire manufacture shall provide LM79 report from NABL accredited lab
& LM80 report issued by LED manufacturer alongwith technical data sheets
of each fitting for approval before execution.
k) Before dispatch of approved light fixtures, third party test shall be carried out
by NABL accredited lab and the test reports shall be submitted.
l) Before execution, the contractor should get light level calculations from the
supplier after selection of fixtures.
m) The light fixtures shall be selected as per Reflected Ceiling Plan.
Supply, installation, testing and commissioning of recessed type LED
downlight with maximum system wattage 9W and minimum system lumen
810lm available with coloured trim of various shade i.e rose gold/ black/
gold. CCT=4000K (SDCM<3), CRI>80. Housing made of pressure die cast
Aluminium. Specialy design optics made of aluminum reflector with beam
1 angle 60 deg. The luminaire shall have a rated system lifetime of 50,000
burning hours at L70. The luminaire shall meet IP20 rating with THD<10%
and PF > 0.9. Operating voltage 220-240V, 50/60 Hz. Fixture & Driver
should be BIS compliant. Including 3 core 1.5 sq.mm FRLS PVC insulated
and PVC sheathed copper conductor cable and earthing etc. Up to suitable
point complete as required.
Supply, installation, testing and commissioning of DALI dimmable recessed
type LED downlight with maximum system wattage 9W and minimum
system lumen 810lm available with coloured trim of various shade i.e rose
gold/black/gold. CCT=4000K (SDCM<3), CRI>80. Housing made of pressure
die cast Aluminium. Specialy design optics made of aluminum reflector with
beam angle 60 deg. The luminaire shall have a rated system lifetime of
2 50,000 burning hours at L70. The luminaire shall meet IP20 rating with
THD<10% and PF > 0.9. Operating voltage 220-240V, 50/60 Hz. Fixture &
Driver should be BIS compliant. Including 3 core 1.5 sq.mm FRLS PVC
insulated and PVC sheathed copper conductor cable and earthing etc. Up
to suitable point complete as required.
Supply, installation, testing and commissioning of DALI dimmable recessed
type LED downlight with maximum system wattage 12W and minimum
system lumen 960lm available with coloured trim of various shade i.e rose
gold/black/gold. CCT=4000K (SDCM<3), CRI>80. Housing made of pressure
die cast Aluminium. Specialy design optics made of aluminum reflector with
beam angle 60 deg. The luminaire shall have a rated system lifetime of
3 50,000 burning hours at L70. The luminaire shall meet IP20 rating with
THD<10% and PF > 0.9. Operating voltage 220-240V , 50/60 Hz .Fixture &
Driver should be BIS compliant.Including 3 core 1.5 sq.mm FRLS PVC
insulated and PVC sheathed copper conductor cable and earthing etc. Up
to suitable point complete as required.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supply, installation, testing and commissioning of 30W DALI dimmable
Recess mounted LED 2'x2' luminaire delivering an initial system lumen of
4500 lumens & the luminaire shall be with system efficacy ≥ 150lm/W.
Housing: CRCA white powder coated white, Optics: HET diffuser, IP20
Protection. The operating CCT shall be 4000K with CRI of ≥80, SDCM<3. The
luminaire shall be BIS Registered with isolated type electronic driver in
4 polycarbonate/ metal enclosure with input voltage range of 150 to 270V,
THD ≤ 10% & PF ≥ 0.95, 50,000 Hrs LED Life with L70B0 Criteria. The LED
Driver shall be of same make and made in India for ease of repair and
service. The LED shall be SMD type. Luminaire shall have minimum surge
protection of 4KV. The luminaire shall be with following certifications:
LM79 & LM80 issued by LED manufacture along with Photo Biological
Safety Standard.
Supply, installation, testing and commissioning of 2ft length, 10W LED
Mirror luminaire wall mounted delivering minimum system lumen of 1000
lumens & the luminaire shall be with system efficacy 100 lm/W. The
luminaire Housing shall be made of extruded aluminium & the diffuser shall
be of PMMA/PC. The operating CCT shall be 4000K with CRI of ≥80,
SDCM<5. The luminaire shall be with BIS Registered electronic driver with
input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95. LED Life with
L70 Criteria should be 50,000 hours. IP20 protection. The LED Driver shall
be easily available in India for repair and service. The LED shall be SMD
type. Luminaire shall have minimum surge protection of 2.5KV. The
luminaire shall be with following certifications: LM79 & LM80 issued by
LED manufacture along with Photo Biological Safety Standard.
Supply, installation, testing and commissioning of 32 Watt 4 feet Surface/
Suspended/ Wall Mounted IP40 LED Batten with minimum luminaire
system efficacy of 125 lm/w having a color temperature of 4000K and
housing should made up of Aluminium Anodized Extruded with high
efficiency Polycarbonate diffuser with intergrated isolated constant current
driver, LEDs used are SMD, Life of LED 50000 burning Hrs. @L70 Lumen
6 maintenance, CCT 5700K, CRI≥80, PF≥0.95 & THD<10%, an operating
Voltage Range of 150 - 270 VAC. Minimum Internal Surge Protection 3KV.
The fixture design should comply driver leakage current as per as per IEC
60598 along with BIS certification for LED Driver & Luminaire. Luminaire
manufacture shall provide LM79 report from NABL accredited lab.
Supply, installation, testing and commissioning of DALI dimmable IP20
linear suspended standalone/ continuous fitting made of extruded
aluminium housing with white powder coating and is should have
Microstructured antiglare optical lens. Fixture should have minimum
efficacy at System level (Not Chip Level) >120lumens/ watt(SDCM<3) and a
minimum system lumen output of 2400 (downlight) lumens and maximum
system wattage of 20W and Beam angle 60-65deg, sheilding angle should
be greater than 65deg. Fixture should have office complaince i.e UGR<16.
Luminaire should have Life of 50000hrs@L70B0 Lumen maintenance at
7 45deg C ambient temperature, CCT up to 4000K, IK02, CRI >80, PF >0.95,
THD<10% at full load, EMC/EMI compliance and an operating Voltage
Range of 150 - 270V AC & Internal Surge Protection 3kV. The fixture should
comply with the parameters as per IS10322. Manufacturer shall have
inhouse lab approved by NABL or ministry of science of govt of India. LM 79
and LM80 reports need to be submitted from a NABL/UL accredited lab to
verify above parameters. Including 3 core 1.5 sq.mm.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supply, installation, testing and commissioning of DALI dimmable and
tunnable Suspened LED stretch fabric Luminaire of dimension
4800mmX1800mm(±5%), with extruded aluminum housing delivering upto
3890lumen/sq m and it draws 55W/sq m maximum from standard 220-
240V AC supply. Fixture offers excellent light output, long source life, high
CRI, and energy efficiency, in a beautiful, clean plane of light. Industry-best
quality of 80+ CRI and color consistency within a 3-step MacAdam ellipse
provides a glare-free direct view luminaire, and abundant, uniform daylight
illumination evenly lit across the entire task surface. The diffuser shall be
Special translucent stretch fabric having good resistance properties -Flame
8 retardant, Anti-bacterial, Anti-Fungal and Anti-Static, Impermeable to
Water and steam for uniform and optimum light distribution. Fixture
should have IP20, CCT 4000k, PF ≥ 0.95, THD<=10%, CRI 80 and drive should
have Surge Protection upto 2KV and must be compatible with DALI 2.0 for
both tunning and dimmable option. The LED Driver shall be easily available
in India for repair and service. The luminaire shall be with following
certifications: LM79 & LM80 issued by LED manufacture along with Photo
Biological Safety Standard.
Supply, installation, testing and commissioning of DALI dimmable and
tunnable Suspened LED stretch fabric Luminaire of dimension
7800mmX1800mm(±5%), with extruded aluminum housing delivering upto
3890lumen/sq m and it draws 55W/sq m maximum from standard 220-
240V AC supply. Fixture offers excellent light output, long source life, high
CRI, and energy efficiency, in a beautiful, clean plane of light. Industry-best
quality of 80+ CRI and color consistency within a 3-step MacAdam ellipse
provides a glare-free direct view luminaire and abundant, uniform daylight
illumination evenly lit across the entire task surface. The diffuser shall be
Special translucent stretch fabric having good resistance properties -Flame
9 retardant, Anti-bacterial, Anti-Fungal and Anti-Static, Impermeable to
Water and steam for uniform and optimum light distribution. Fixture
should have IP20, CCT Range – 4000k, PF ≥ 0.95, THD<=10%, CRI 80 and
drive should have Surge Protection upto 2KV and must be compatible with
DALI 2.0 for both tunning and dimmable option. The LED Driver shall be
easily available in India for repair and service. The luminaire shall be with
following certifications: LM79 & LM80 issued by LED manufacture along
with Photo Biological Safety Standard.
Supply, installation, testing and commissioning of 5mtr IP20 flexible LED
strip light made of Polymide double sided PCB, Strip should have minimum
efficacy at System level >=70lumens/ watt with nominal system lumens
10 700lm/mtr, Life of LED strip: 35000 burning Hrs. @ (ta 45 C) @L70 Lumen
maintenance, CCT of 3000K, CRI Ra >=80, an operating Voltage Range of
100 - 300 VAC, and surge protection of 3kV.
Supply, installation, testing and commissioning of DALI dimmable 40W High
efficient deep recess mounted COB LED downlighter delivering an initial
system lumen of 4000 lumens with system efficacy ≥ 100lm/W. Die cast
aluminium housing with UGR<15. High efficiency reflector optics, 60 deg
beam optics, effiective thermal management using aluminium casting.
11 CRI>80, CCT - 4000K, 50,000 hrs@ L70 life. IP20, Driver efficiency≥85%,
PF≥0.95, Surge protection - 3kV with High and Low Input Voltage Cutoff
protection, driver shall be suitable for voltage range 160-280V AC. Cutout
Dia-ø110mm. The LED Driver shall be easily avaiable in India for repair and
service. The luminaire shall be with following certifications: LM79 & LM80
issued by LED manufacture along with Photo Biological Safety Standard.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supply, installation, testing and commissioning of 20W Suspended Acoustic
Mute light fixture of 1200mm length linear profile. The light fixture should
be impeccably integrated with Acoustic material which enhances the
product Aesthetic looks. The Acoustic PET board material should be made
of High quality Acoustic polyester fibre with Hybrid technology. The Hybrid
technology utilizes deep airspaces and multiple layers construction which in
combinations of Acoustic material+Soft polyester+PET Board which insures
Higher NRC Value of 0.85-0.9 and greater SAC Sound absorption coefficient.
Hybrid deep airspaces technology insures the up to 40-50% Average
decrement in reverberation time (RT60). All the acoustic materials must be
tested in third Party Acoustic Labs preferably in ARAI to insure the quality
of product. The PET board should be made of 100% recyclable/ sustainable
material. Acoustic body should be light weight for easy and effective
12 installation and should be having fire Retardant property & should comply
to Fire Classification: B s1, d0 as per EN 13501. The Acoustic materials
should be high resistance to humidity and moisture. The product should be
Non VOC compliant and should be having Anti-fungal properties. The
Acoustic material should be also available for customization as per
customer demand in Different customization options in shape, size,
formation and RAL shades. The luminaire integrated with the acoustic
material should be having system output ranges from ≥2000 lm with
collimeter lens having UGR<6. Luminaire shall have Optical Grade High
Efficiency Translucent PC diffuser. The LED used inside the light fixture
should be LM 80-08 compliant, ANSI rated LEDs from reputed makes such
as Nichia, Japan/ Cree, USA/ Bridgelux, USA/ Lumiled USA/ Citizen Japan
should be provided. Luminaire shall use multiple LEDs of less than 0.5W
Class for better diffusion and heat management. The LEDs shall be driven
on optimal point for higher reliability & performance. The LED shall be
Supply, installation, testing and commissioning of DALI dimmable IP20
suspended cylindrical LED Downlighter made of extruded aluminum
Housing and LED Used shall be COB type and fixture should have minimum
efficacy at System level (Not Chip Level) >=80lumens/ watt with Minimum
system Lumens 1600 with maximum system wattage of 20W. Fixture
should have office compliance i.e UGR<10. Life of fixture (Including Driver):
50000 burning Hrs. @ L70 Lumen maintenance, CCT of 4000K (SDCM<3),
13 CRI >80, PF >0.95, Min working temp range - 0°C < Ta < 45°C, and operating
Voltage Range of 140 - 240 VAC. it should has a Minimum Internal Surge
Protection of 3KV, THD<10%. The fixture design should comply with EMC/
EMI compliance along with BIS certification for LED Driver & Luminaire.
Luminaire manufacture shall provide LM79report from NABL accredited lab
& LM80 report issued by LED manufacturer. Including 3 core 1.5 sq.mm
FRLS PVC insulated and PVC sheathed copper conductor cable and earthing
etc. Up to suitable point complete as required.
Supply, installation, testing and commissioning of decorative sphere with
Supply, installation, testing and commissioning of decorative Semi spherical
luminaire made of jute with E27 lamp holder. No. 3 9,301 - 27,903.00 EL. MR-148
Supply, installation, testing and commissioning of decorative dome
luminaire made of spun aluminium with E27 lamp holder. No. 3 6,094 - 18,282.00 EL. MR-149
Supply, installation, testing and commissioning of IP20 Aluminium body
power supply 24V output. Power consumption- 90W (±10%)driver featuring
the constant power mode. Power supply should operate from 140~300VAC
and offers models with different rated current ranging between <3.0A at
full load. High efficiency up to 75%, with the fanless design, must be able to
operate at -0°C ~+45°C case temperature under free air convection.
Output Parameters:
i. Line Regulation: ±5%
ii. Load regulation: ±5%
iii. Output current tolerance: ±5%
iv. Output voltage ripple: <3%
Driver Protection:
i. Input voltage protection: Cut-off Voltage: >300Vac ± 15V, Cut-in Voltage:
ii. Output short circuit protection: Auto recovery - Hiccup mode
iii. Output open circuit: Available
iv. Ouput overload: Auto recovery - Hiccup mode
v. Over temperature: Shutdown & Auto recovery
vi. Isolation b/w input & output: Withstand 1.5kV for 1Minute
vii. Insulation resistance : Between L & N to DC output:>10MΩ (To be
measured with test voltage of 500VDC)
viii. Surge in DM: 3kV
Driver should have EN 61000-4-5 approval for surge voltage protection & IS
15885-2-13 for BIS approval.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
TOTAL CARRIED OVER TO SUMMARY - 1,11,44,530.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
L LIGHTING MANEGMENT SYSTEM
Wireless IoT System having BLE 5.2 AES 128 Bit encyption based 4 child
DALI controller, operates on 90-277 VAC, 65mA, 50Hz, following DALI 2.0
protocol. It must have auxillary power output of 12VDC & 100mA to power
sensor devices & 8mA current connected to 4 DALI drivers, 0 - 100%
dimming, device to device range 45m. Controller must individually control
standard DALI or Tunable DALI Drivers independantly or combination of
both. Operating temperature -20 to 50 deg celsius, surge protection 4kV.
System shall support easy commissioning and configuration via Mobile
Application along with user and site management features. Optional Cloud
Application must be available for control and monitoring of the devices along
with analytics reports. Mobile Application shall have features of individual &
group control for On/ off/ dimming/ colour tuneing/ Scene Control/ Animation
etc. Device must have security key for commissioning and replacement for
Wireless IoT System having BLE 5.2 AES 128 Bit encyption based 32 child
DALI controller and analog 2 channel (0-10V) output, operates on 100-277
VAC, 10-30mA, 50Hz, DALI 2.0 protocol. Sensor input of 0-3V DC & 1mA.
For analog dimming, It provides output voltage of 0-10V DC +/- 0.2V and
15mA per channel. For DALI output, it provides 12-20V DC and 160mA max
for 32 DALI devices. An auxillary power output of 3.3VDC and 30mA. 0 -
100% dimming, device to device range 45m. Controller must control
individually control standard DALI or Tunable DALI Drivers independantly or
2 combination of both. Operating temperature -20 to 50 deg celsius, surge
protection 3kV. System shall support easy commissioning and configuration
via Mobile Application along with user and site management features.
Optional Cloud Application must be available for control and monitoring of
the devices along with analytics reports. Mobile Application shall have
features of individual & group control for On/off/dimming/ colour tuneing/
Scene Control/ Animation etc. Device must have security key for
commissioning and replacement for future.
BLE 5.2 AES 128 Bit encyption based, AC Powered Wireless PIR Motion &
Light Sensor (0-2000 lux). Operates on input voltage of 90-277V AC with
input current of 9mA at 230VAC and 15mA at 90VAC, 50Hz. Ceiling
mounted with maximum height of 4m and maximum detection range of 14m
dia at 4m mounting height. Device to device range 45m, operating
temperature 0 to 80 deg celsius, surge rating 4kV. System shall support
easy commissioning and configuration via Mobile Application along with user
and site management features. Optional Cloud Application must be available
for control and monitoring of the devices along with analytics reports. Mobile
Application shall have features of commissioning of the sensors along with
setting step dim function, sensitivity levels and time day options. Device
must have security key for commissioning and replacement for future.
Device must have security key for commissioning and replacement for
BLE 5.2 AES 128 Bit encyption based wireless battery powered 5-button
wall switch that controls ON/ OFF, intensity and CCT of an individual or
group of luminaires. Operates on 3V DC input voltage in an ambient
temperature of 0 to 50 deg celsius and device to device range 45m. System
shall support easy commissioning and configuration via Mobile Application
along with user and site management features. Optional Cloud Application
must be available for control and monitoring of the devices along with
analytics reports. Nos. 76 9,676 - 7,35,376.00 EL. MR-154
BLE 5.2 AES 128 Bit encyption based wireless battery powered 8-button
wall switch that controls ON/ OFF, intensity and CCT of an individual or
group of luminaires. Operates on 3V DC input voltage in an ambient
temperature of 0 to 50 deg celsius and device to device range 45m. System
shall support easy commissioning and configuration via Mobile Application
along with user and site management features. Optional Cloud Application
must be available for control and monitoring of the devices along with
analytics reports. Nos. 2 20,593 - 41,186.00 EL. MR-155
WiFi and BLE 5.2 AES 128 Bit encyption Gateway with Ethernet and built-in
Real Time Clock for cloud connectivity and scheduling. It is powered by 5V,
2A Mini USB/ DC Adaptor and has 1 ethernet port with 10/100 Mbps data
transmission rate. RTC is battery powered with 3V DC. Device to device
range 30m X 30m, operating ambient temperature of -20 to 55 deg celsius.
System shall support easy commissioning and configuration via Mobile
Application along with user and site management features. Optional Cloud
Application must be available for control and monitoring of the devices along
with analytics reports. Device must have security key for commissioning and
replacement for future.
EDGE Gateway for facilitating 2 way data flow between BLE mesh networks
and BMS, it operates on 5VDC and 3A input current. Multiple gateways to
BMS connectivity through 2.4 and 5GHz Wi-Fi bands or ethernet. Ambient
7 operating temperature of 0 to 50 deg celsius. System shall support easy
commissioning and configuration via Mobile Application along with user and
site management features. Optional Cloud Application must be available for
control and monitoring of the devices along with analytics reports.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Provides all features of commissioning, configuration, control and
automation as in Wipro iOL mobile app. Additionally, measures, tracks and
reports real time energy usage for every floor, zone, group and device; gives
data on occupancy patterns by heat maps; emergency monitoring, space
and energy management, asset tracking, multi-tier data security, data
encryption, authenticated user access, on premise and remote access.
Supply of PIR sensor with a built-in switch. It will switch off the lights in a
room or area when it is vacated and thus save energy. Occuswitch can
switch any load up to 10A and control an office area of around 20 sq.m. for
9 small movements (e.g. desk work) and arround 50 sq.m. for large
movements (e.g. walking). Its smart daylight sensing technology offers
additional saving through daylight override and daylight switching. Detection
dia Ø8m from 4m mounting ht. Nos. 18 2,170 - 39,060.00 EL. MR-159
10 BMS points integration Nos. 1241 386 - 4,79,026.00 EL. MR-160
TOTAL CARRIED OVER TO SUMMARY - 49,74,197.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
M BUS DUCTS - COMPACT SANDWITCH TYPE
1 From 2000kVA Transformer to Main LT Panel-2 & APFC Panel :
Note: Design, Manufacture, Supply, Installation, Testing and Commissioning of
Sandwich Busway 1100 volts system Busduct with cooling Fins, 4bar - 3P &
1N, Aluminum conductor, Class 'F' Insulation, with aluminium body/
enclosure acting as earth, as per specifications, suitable for 3ph 4wire
50HZ, of short circuit fault withstand capacity for 1 Sec as specified below.
The Busway shall have a system of single bolt double head section jointing
system. The bus duct suspension system shall be complete with steel rods,
GI angle supports and dash fasteners etc. at required intervals for safe
installation of bus ducts. Supporting system shall be fail proof even in earth
quake situations, as per Sesmic requirement at site.
100% sized Neutral as of phase current.
1.1 3200Amp 50kA, 4P, Indoors in utility block - IP-55, ALUMINUM
a. Straight run Horizontal as well as Vertical RM 65 38,900 - 25,28,500.00 EL. MR-161
b. Vertical bends Each 4 17,508 - 70,032.00 EL. MR-162
c. Horizontal bends Each 4 17,508 - 70,032.00 EL. MR-163
e. End Flange flexible connector at LT Panel Each 2 89,307 - 1,78,614.00 EL. MR-165
1.2 1000Amp 50kA, 4P, Indoors in utility block - IP-55, ALUMINUM
a. Straight run Horizontal as well as Vertical RM 15 15,179 - 2,27,685.00 EL. MR-166
b. Vertical bends Each 2 6,848 - 13,696.00 EL. MR-167
c. Horizontal bends Each 2 6,848 - 13,696.00 EL. MR-168
e. End Flange flexible connector at LT Panel Each 2 36,852 - 73,704.00 EL. MR-170
2 From CSS to Main LT Panel-3:
Note: Design, Manufacture, Supply, Installation, Testing and Commissioning of
Sandwich Busway 1100 volts system Busduct with cooling Fins, 4bar - 3P &
1N, Aluminum conductor, Class 'F' Insulation, with aluminium body/
enclosure acting as earth, as per specifications, suitable for 3ph 4wire
50HZ, of short circuit fault withstand capacity for 1 Sec as specified below.
The Busway shall have a system of single bolt double head section jointing
system. The bus duct suspension system shall be complete with steel rods,
GI angle supports and dash fasteners etc. at required intervals for safe
installation of bus ducts. Supporting system shall be fail proof even in earth
quake situations, as per Sesmic requirement at site.
100% sized Neutral as of phase current.
2.1 800Amp 50kA, 4P, Indoors in utility block - IP 55, ALUMINUM
a. Straight run Horizontal as well as Vertical RM 70 13,908 - 9,73,560.00 EL. MR-171
b. Vertical bends Each 2 6,283 - 12,566.00 EL. MR-172
c. Horizontal bends Each 2 6,283 - 12,566.00 EL. MR-173
e. End Flange flexible connector at LT Panel Each 2 30,569 - 61,138.00 EL. MR-175
3 160A Busduct System for Server Rack
3.1 160A Busway Section, 4P- 3 mtr Nos 24 1,09,305 - 26,23,320.00 EL. MR-176
3.2 160A Busway Section, 4P- 2 mtr Nos 8 84,829 - 6,78,632.00 EL. MR-177
3.3 160A End Feed Unit, 4P, Standard lugs, Standard box, Standard unit. Nos 4 1,21,749 - 4,86,996.00 EL. MR-178
3.4 160A End Feed Unit, 4P, Standard lugs, Standard box, Reverse unit. Nos 4 1,21,749 - 4,86,996.00 EL. MR-179
3.8 Closure strip, 3 mtr per length Each 29 15,353 - 4,45,237.00 EL. MR-183
3.9 Installation Tool. Nos 2 37,441 - 74,882.00 EL. MR-184
3.10 E93 Plugin Box with Single phase circuit having 1 No 32A Single phase IEC
60309 Angle receptacle controlled with 1 No 32A Single pole circuit breaker.
For 41 Racks. (Dual Source) Nos 82 76,498 - 62,72,836.00 EL. MR-185
TOTAL CARRIED OVER TO SUMMARY - 1,64,51,840.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
N FIRE DETECTION AND ALARM SYSTEM - ANALOG ADDRESSABLE
Design, Supply, installation, testing & commissioning of Fire Detection &
Alarm system as per local fire norms & NBC/ NFPA Codes:
Supplying, installation, testing and commissioning of micro processor based
intelligent addressable main fire alarm panel, central processing unit with the
following loop modules and capable of supporting not less than 240 devices
(including detectors) and minimum 120 detectors per loop and loop length
up to 2 km, network communication card, minimum 320 character graphics/
LCD display with touch screen or other keypad and minimum 4000 events
history log in the non volatile memory (EPROM), power supply unit (230 ±
5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries
with automatic charger. The panel shall have facility to connect printer to
printout log and facility to have seamless integration with analog/ digital
voice evacuation system (which is part of the schedule of work under SH:
PA System) and shall be complete with all accessories. The panel shall be
compatible for IBMS system with open protocol BACnet/ Modbus over IP
complete as per specifications.
Supplying, installation, testing & commissioning of intelligent analog
4.0 addressable photothermal detector (Multi Criteria) complete with mounting 453
base complete as required. Each 3,039 13,76,626.86 - 17.2.4
Supplying, installation, testing & commissioning of response indicator on
5.0 surface/ recessed MS Box having two LED, metallic cover complete with all 193
connections etc as required. Each 293 56,639.86 - 17.2.5
Supplying, installation, testing & commisssioning of intelligent addressable
programmable sounder complete as required. Each 2,819 5,637.62 - 17.2.6
Supplying, installation, testing & commissioning of fault isolator complete
with base as required. Each 3,477 89,845.45 - 17.2.7
Supplying, installation, testing & commissioning of intelligent interface unit
BACnet/ Modbus protocol i.e. supplying communication links between
building management system and fire alarm control panel complete as
Supplying, installation, testing & commissioning of ceiling/ wall mounted loud
19.0 speaker, 3/1.5 Watt in ABS enclosure complete as required. 211
Supply, installing, testing and commissioning of Integrated 8 channel (FOR
8 DIFFERENT TYPE OF MESSAGES TO GET RELAYED
SIMULTANEOUSLY) Digital Voice Evacuation and 2 way
Communication Fire Fighters System capable to supervise all the
21.0 speaker circuits, with required number of zone control as given below and
accessories required to complete the system. The equipment shall be of
same make as panel.
DVC shall offer minimum one fire man's telephone circuit & one speaker's
circuit. DVC shall be with in-built digital microphone, fire man's
telephone hand set & PA Zone control
Notes: Networkable DVC with in-built features like:
b. In-built 'PA' Microphone
c. In-built Fire Main's telephone hand set for 2 way communications.
d. 'Aux'/ IPAD/ EPABX Input ports for music
e. Facility to control all PA zones
f. Facility to relay pre-corded massages
DVC to give out one Fire Man's telephone riser & 32 Nos. Digital Amplifiers
DVC with 24 zone control
22.0 DIGITAL AMPLIFIERS
Supply, installing, testing and commissioning of Addressable & fully
supervised DIGITAL AMPLIFIERS with minimum Wattage as given
below with 70.7 VRMS. The Digital Amplifiers shall have inbuilt minimum of
4 Speakers Zone Circuits and minimum 1 Fire Fighters communication.
The Amplifiers shall be stand alone with its own battery backup incase of
Main fire Alarm panel/ Digital Voice Panel failure and the Digital Amplifiers
shall still be in position to carry out Voice Evacuation.
a. Amplifier shall sit on Amplifier loop - -
b. Amplifier shall have minimum in-built four PA speaker zones - -
c. Amplifier shall have a fire man's telephone riser - -
d. Amplifier shall support 2 way communication for fire man - -
e. Telephone hand set for 2 way communication to be ordered
seperately as may be required. - -
23.0 WIRES & CONDUITS:
Supplying & laying of 2x1.5 sqmm fire survival armoured cable including
termination, 600/ 1000V rated with annealed copper conductor having glass
mica fire barrier tape covered by an extruded layer of Cross Linkable
Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel
wire armouring & LSZH outer sheath complete as required.
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
Supplying and drawing of cable Fire Retardant PVC insulated copper
conductor cable in the existing surface/ recessed steel conduit of following
pairs, cores and size including connections and interconnections etc. as
required. - - 17.5.3
23.2.1 Speaker cable Two pair, 2-core, 1.5 sqmm RM 2110 95 1,99,677.11 - 17.5.3.2
Supplying and fixing of following sizes of steel conduit along with
accessories in surface/ recess including painting in case of surface conduit,
or cutting the wall and making good the same in case of recessed conduit
as required. - - 1.20
Supplying and fixing 25 mm dia MS flexible pipe along with all ancillaries and
accessories like coupler etc. as required. 56 96,592.30 - 17.5.4
TOTAL CARRIED OVER TO SUMMARY 62,46,921.36 15,17,858.00
Digitally signed by Page
SL. NO. ITEM DESCRIPTIONS UNIT QTY. DSR RATE Non DSR RATE DSR AMOUNT Non DSR Ref. DSR
@1.0633 (Rs.) (Rs.) AMOUNT 2022/ MR
O CLEAN AGENT BASED FIRE SUPPRESSION SYSTEM
Supply, Installation, testing & commissioning of Gas Suppression system
consisting UL Listed/ CCOE approved high pressure seamless BIS 7285
approved Cylinders, UL/ FM approved NOVEC 1230/ FK-5-1-12 clean agent
gas with UL/ FM listed valve assembly and electric solinoid switch. The
system also to be fitted with low pressure supervisory switch for monitoring
cylinder pressure gauge with safety burst disc safety cap, elbow and other
accessories, mounting bracket, container straps, NRV, Pressure operated
control head which shall allow for pressure actuation of gas mounted,
manually operated actuator to actuate the gas flooding process with the help
of a lever, flexible rubber hose with wire bralded enforcment to route the gas
from the storage cyinder to the discharge piping, to be connected to the
discharge outlet of gas cylinder valve & to be terminated at the system
piping or discharge manifold, Flexible actuation hose complete as required.
Discharge nozzle, 180/ 360 degree. Designated to provide proper flow rate
& distribution NOVEC 1230/ FK-5-1-12 gas to flood the hazard area as per
latest NFPA 2001. Piping ASTM grade A 106 schedule 40 with fittings &
supports and Gas Release Panel compatible to Fire Alarm System. An
undertaking from manufacturer must be submitted with the tender to comply
Gas Quantity would be as per the volume of the room. CLEAN AGENT
(NOVEC 1230/ FK-5-1-12) shall be UL/ FM Listed with Zero Ozone
Depletion Potential (ODP). The gas used should be colourless and have
citrus like odour.
Note: The Cylinder, Volume of Gas, Nos. of Nozzles, piping design and
pressure calculations using manufacturer design software for a given
dimension of room duly approved by manufacturer (OEM) shall be
submitted prior to starting of the works. The Hydraulic Flow
Calculation Software must be UL/ FM approved.
The system described above is to be provided for the following room(s):
1.1.3 COMMUNICATION ROOM - 3000mm x 5400mm x 3200mm (LxWxH)
1.1.4 COMMUNICATION ROOM - 3000mm x 2600mm x 3200mm (LxWxH)
TOTAL CARRIED OVER TO SUMMARY - 54,80,338.00
P VERY EARLY SMOKE DETECTION & ALARM SYSTEM
Supply, lnstallation, Testing and commissioning of UL/ EN listed (Latest
Version) Single channel - BLUE LED Based Aspiration Detection Unit with
sensitivity ranging from 0.0015 - 20% obs/m along with 8 Relay Outputs, 3
Stage Filtration with TCP/ IP network Capability as required. [For Server
Room - 9200mm x 15800mm x 3000mm (LxWxH)].
TOTAL CARRIED OVER TO SUMMARY 5,86,246.00
Digitally signed by Page
aoc.pdf
Download all tender documents and submit your bid