Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.3 LAccepted-AOC | L1 | Accepted-AOC being lowest | |
| 2 | L2₹7.4 L+₹82,515.62 (12.5%)Rejected-Finance | L2 | Rejected-Finance Highest amount quoted |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
3 Sept 2024, 6:00 pmClosed
AGE I UDAIPUR
ASST. GARRISON ENGINEER (I) EKLINGGARH CANTT, UDAIPUR (RAJ.) - 313001
COMPREHENSIVE REPAIRS/REPLACEMENT TO E AND M INSTALLATIONS, DG SETS AND AMF PANELS AND CONNECTED WORKS IN ARMY AREA AT UDAIPUR MIL STN
2024_MES_661472_1
8898/E8/AGE (I) UDAIPUR
Open Tender
Civil Works
Item Rate
180 days
ARMY AREA UDAIPUR
AS PER TENDER DOCUMENTS
5 documents required · 5 mandatory
₹500
AGE I UDAIPUR
₹16,000
17 Oct 2024
24 Jun 2024
6 Sept 2024
24 Jun 2024
3 Sept 2024
8 Jul 2024
Amount
Material and labour for complete servicing to DG Set 30KV - 01 Nos Make -Mahindra Powerol by pass filter assembly, lubricant oil filter assembly and air cleaner assembly. cleaning all the filter shell and replacing the fuel filter element etc,draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution including replacement of following spares complete all as specified and directed. Note:- (i) Spares except above as required shall be measured and paid separately. (ii) The unit rate quoted by the tenderer shall also includes overall inspection of DG Sets complete including tappet adjustment etc.
Supply only of Fuel Filter
Supply only of Lubricant oil filter
Supply only lubricant oil supply pipe
Air filter Element
Material and labour for complete servicing to DG Set 50 KV - 02 Nos Make -Cummins & Mahindra Powerol by pass filter assembly, lubricant oil filter assembly and air cleaner assembly. cleaning all the filter shell and replacing the fuel filter element etc,draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution including replacement of following spares complete all as specified and directed. Note:- (i) Spares except above as required shall be measured and paid separately. (ii) The unit rate quoted by the tenderer shall also includes overall inspection of DG Sets complete including tappet adjustment etc.
Supply only of Fuel Filter
Supply only of Lubricant oil filter
Supply only lubricant oil supply pipe
Air filter Element
Material and labour for complete servicing to DG Set 75 KV - 01 Nos Make - Mahindra Powerol by pass filter assembly, lubricant oil filter assembly and air cleaner assembly. cleaning all the filter shell and replacing the fuel filter element etc,draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution including replacement of following spares complete all as specified and directed. Note:- (i) Spares except above as required shall be measured and paid separately. (ii) The unit rate quoted by the tenderer shall also includes overall inspection of DG Sets complete including tappet adjustment etc.
Supply only of Fuel Filter
Supply only of Lubricant oil filter
Air filter Element
Supply only lubricant oil supply pipe
Material and labour for complete servicing to DG Set 100 KV - 01 Nos Make - Mahindra Powerol by pass filter assembly, lubricant oil filter assembly and air cleaner assembly. cleaning all the filter shell and replacing the fuel filter element etc,draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution including replacement of following spares complete all as specified and directed. Note:- (i) Spares except above as required shall be measured and paid separately. (ii) The unit rate quoted by the tenderer shall also includes overall inspection of DG Sets complete including tappet adjustment etc.
Supply only of Fuel Filter
Supply only of Lubricant oil filter
Air filter Element
Supply only lubricant oil supply pipe
Material and labour for taking out old U/S engine oil from DG Sets sumps, cleaning the sump throughly, supply & filling new engine oil complete of Make: Servo Super 20W40 of Indian Oil or Equivalent grade of Hindustan Petroleum as approved by GE, complete all as specified and directed
Material and labour for topping up of water coolant in radiator of DG Set ,complete all as specifoed and as directed.
Repair/Overhauling of dynamo/charging alternator including replacement carbon, brushes holder, spring commutator/slip ring assembly bearing regulator of any make , type and capacity complete all as specified and as directed
Supply and fixing in replacement of old U/S automatic voltage regulator suitable for DG Set of following rating of approved Make & model by the AGE(I), complete all as specified and as directed
Material and labour for replacement of old U/S fuel shutdown valve assembly complete testing including replacement of old unserviceable valves of any capacity DG Set, complete all as specified and as directed.
Material and labour for replacement of old U/S bendix assembly of self starter of capacity 30 KVA to 200KVA DG Set complete all as specified and as directed
Supply and fixing in replacement of old U/S top solenoid suitable for DG Set of following rating of approved Make & model by the AGE(I), complete all as specified and as directed
Supply and fixing in repairs Electronic Controller in AMF Panel of DG Set capacity 30 KVA to 200 KVA and making all necessary connection and programming to make functional of DG Set
Material and labour for replacement of SMPS based ElectronicBattery Charger suitable for 12/24 Volts battery charging system complete as specified and as directed.
Supply and replacement of old unserviceable battery 12Volts 180 AH maintenance free suitable for DG Sets complete as specified and directed. Make-Amron,Exide,luminous
Supply and replacement of old unserviceable battery 12Volts 150 AH maintenance free suitable for DG Sets complete as specified and directed. Make-Amron,Exide,luminous
Supply and replacement of old unserviceable battery 12Volts 100 AH maintenance free suitable for DG Sets complete as specified and directed. Make-Amron,Exide,luminous
Material and labour for replacement of on load change over switch 4 pole, 415Volt, of capacity 63Amps, complete as specified and directed.
Material and labour for replacement of on load change over switch 4 pole, 415Volt, of capacity 100Amps, complete as specified and directed.
Cutting unaxious green growth and wild grass by manual labour or by machine at Water supply Installation Premises, around Pole, along the boundary Fencing, removing rubbish from the Site of Work and deposting where directed not exc. 100 Metre from the starting Point, complete all as specified and as directed. NOTE : The Item shall be operated 3 times in the entire period of the Contract and the measurement will be taken one time for payment
Material and labour for laying LT underground Cable, including takingdown existing u/s XLPE insulated, heavy duty armoured sheathed 1100 volts grade 95 Sq mm, 4core, with aluminium conductor, ISI marked as per IS : 7098(Part-1) complete with all as specified.
Material and labour for spreading, levelling in layers n exc. 25 cm thick and ramming of sand cushioning to PVC/ XLPE cables with tibba sand and punning to provide required cover to UG cables. Note :- For the purpose of payment only punned thickness will be measured
Supply and laying reinforced precast concrete cable cover, class LV, type 1 flat, 250mm x 150mm x 40mm.
Excavating in trenchs, n exc 1.5m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out soft/loose soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm soft/loose soil.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point
Disconnecting of electric main connections from the existing unserviceable motor control panel removing effected parts, cleaning complete to carryout various repair/replacement work and connecting up electically after repair work in and including providing new internal wiring within control panel board for connecting up of connector/relay/voltmeter with suitable size twisted type PVC insulated complete with bottle neck lugs/thimble and new nuts & bolts if required connection shall be properly bunched, tied and dressed, ferrule markred for proper identification and shall be wrapped with PVC spring type tube near the door hinges complete all as directed by Engr-in-charge
Supply and mixing of ferric Alum as and when required complete all as specified and directed
Supply and mixing of Bio-Nuts for healthy growth of bacteria in waste water treatment plants for B.O.D related treatments as and when required complete all as specified and directed Make : TES (Techno Economic Services) or equivalent
Supply and mixing of liquid chlorine in 50 ltrs containers (containers will be kept in custody of plant staffs and not return to contractor) as and when required complete all as specified and directed
Material and labour for opening of centrifugal pump capacity 15 HP by disconnecting from motor and pipe, strip opening the pump and replacement of unserviceable parts such as impeller, SS bushes, shaft sleeves, ball bearing, nut bolts, gland plate, gasket, water hose pipe, water seal etc and lathe work/turning, grinding etc on shaft and shaft key way as required including greasing/oiling and re-assembling at the same location with proper alignment with motor and testing complete all as specified and directed by Engineer-in-charge. Note : - (i) Major items like impeller, bearing, bush, gland plate, tyre coupling, coupling assembly shall be measured and paid for separately under respective items of BOQ as “Supply only”. (ii) Cost for transportaion to workshop and carry back to site after repair is inlcuded in the unit rate of item nothing extra shall be paid on this acount.
Material and labour for opening of centrifugal pump capacity 10 HP by disconnecting from motor and pipe, strip opening the pump and replacement of unserviceable parts such as impeller, SS bushes, shaft sleeves, ball bearing, nut bolts, gland plate, gasket, water hose pipe, water seal etc and lathe work/turning, grinding etc on shaft and shaft key way as required including greasing/oiling and re-assembling at the same location with proper alignment with motor and testing complete all as specified and directed by Engineer-in-charge. Note : - (i) Major items like impeller, bearing, bush, gland plate, tyre coupling, coupling assembly shall be measured and paid for separately under respective items of BOQ as “Supply only”. (ii) Cost for transportaion to workshop and carry back to site after repair is inlcuded in the unit rate of item nothing extra shall be paid on this acount.
Material and labour for opening of centrifugal pump capacity 7.5 HP by disconnecting from motor and pipe, strip opening the pump and replacement of unserviceable parts such as impeller, SS bushes, shaft sleeves, ball bearing, nut bolts, gland plate, gasket, water hose pipe, water seal etc and lathe work/turning, grinding etc on shaft and shaft key way as required including greasing/oiling and re-assembling at the same location with proper alignment with motor and testing complete all as specified and directed by Engineer-in-charge. Note : - (i) Major items like impeller, bearing, bush, gland plate, tyre coupling, coupling assembly shall be measured and paid for separately under respective items of BOQ as “Supply only”. (ii) Cost for transportaion to workshop and carry back to site after repair is inlcuded in the unit rate of item nothing extra shall be paid on this acount.
Supply only ball bearing suitable for centrifugal Pump Set assembled with 10 HP motor complete all as specified and directed by Engineer-in-charge.
Supply only ball bearing suitable for centrifugal Pump Set assembled with 7.5 HP motor complete all as specified and directed by Engineer-in-charge.
Supply only coupling assembly for flexible rubber tyre suitable for centrifugal pump Set assembled with 15/10/7.5 HP motor complete all as specified & as directed by Engineer-in-charge.
Material and labour for rewinding of Electric motor of 15 HP, three phase, 415 volts, AC, with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and making proper electrical connection after taking out old brunt out motor complete all as specified and directed by Engineer-in-charge. Note : Transportation of motor to contractor's workshop is included in the unit rate of items and nothing extra shall be paid on this account.
Material and labour for rewinding of electric motor of 10 HP, three phase, 415 volts, AC, with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and making proper electrical connection after taking out old brunt out motor complete all as specified and directed by Engineer-in-charge. Note : Transportation of motor to contractor's workshop is included in the unit rate of items and nothing extra shall be paid on this account.
Material and labour for rewinding of electric motor of 7.5 HP, three phase, 415 volts, AC, with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and making proper electrical connection after taking out old brunt out motor complete all as specified and directed by Engineer-in-charge. Note : Transportation of motor to contractor's workshop is included in the unit rate of items and nothing extra shall be paid on this account.
Material and labour for rewinding of electric motor of 1.5 HP, three phase, 415 volts, AC, with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and making proper electrical connection after taking out old brunt out motor complete all as specified and directed by Engineer-in-charge. Note : Transportation of motor to contractor's workshop is included in the unit rate of items and nothing extra shall be paid on this account.
Material and labour for rewinding of electric motor of 0.5HP, three phase, 415 volts, AC, with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and making proper electrical connection after taking out old brunt out motor complete all as specified and directed by Engineer-in-charge. Note : Transportation of motor to contractor's workshop is included in the unit rate of items and nothing extra shall be paid on this account.
Supply and fixing in replacement of power contactor, AC3 rating, 32 Amps, 3 Pole, AC control with Auxiliary contacts 2 NO + 2NC, suitable for coil voltage 110 V, 220, 240 & 415 volts, 50 Hz complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of power contactor, AC3 rating, 12 Amps, 3 Pole, AC control with Auxiliary contacts 2 NO + 2NC, suitable for coil voltage 110 V, 220, 240 & 415 volts, 50 Hz complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of thermal over load relay adjustment range 23-32 amps with all electrical wiring complete all as specified & as directed by Engineer-in-charge.
All as per item No 43 here-in-above but adjustment range 9-13 / 7-10 / 5.5-8 / 4-6 / 2.5-4 Amps
Supply only in replacement of electronic timer 0 to 30 second for star - delta changeover, DIN mounting complete all as specified & as directed by Engineer-in-charge.
Supply only in replacement of 3 phase preventor (SPP) with auto reSet, 415 Volts AC complete all as specified & as directed by Engineer-in-charge.
Supply only in replacement of push button, ON/OFF, Red/Green complete all as specified & as directed by Engineer-in-charge.
Material and labour for servicing of Air blower of Make : Usha, speed 1510 RPM with 20 HP motor by greasing, oiling and draining out of old oil and charging of new oil after replacement of unserviceable items (Suction filter, Set of seal and O ring, bearing, piston rings, bush, retainer, pressure guage, gasket, nut, bolts & washer)and any other items required for smooth functioning of blowers complete all as specified and directed by Engineer-in-charge.
Supply only air filter for blower assembled with 20 HP motor as per existing make and model complete all as specified and directed by Engineer-in-charge.
Supply only Gear oil for air blower (Castrol Hypoy 90EP / HP EP90)complete all as specified & as directed by Engineer-in-charge.
Material and labour for taking out spindle, nut and gate assembly from sluice valve of size 150 /250 mm bore and replacement of bronze nut with internal threading, welding work, finishing work gland packing, rubber gasket as required to make smooth funtioning and refixing in the same position, complete all as specified and directed by Engineer-in-Charge. Note :- Excavation & earthwork including dewatering etc required for the Job is deemed to be included in the rate quoted.
Supply and fixing in replacement of chemical dosing injector unit capacity 10 litre/hr with digital display and adjustable dosing capacity knob with pvc suction pipe and outlet pipe complete all as specified and directed by Engineer-in-charge.
Supply and fixing mild steel framed work such as grills, gratings, etc., with ends of bars shouldered and/or riveted, or forged into spikes, framed guard bars, barred iron doors, ladders, framed balusters, walk ways, railings, cooler stand, framework of water tanks and similar works of quality Fe 290 (Gde E-165) etc complete all as specified and directed by Engineer-in-charge.
Lifting/ lowering of non clog sewage submersible pump / monoblock pump Set of the capacity 3.0,10 HP from the sewage pump houses & STP PLANT Lifting : Disconnection of outgoing delivery mains and eletrical connection from the panel and lifting of unserviceable non clog sewage submersible pump Set of any depth alongwith column pipe, SWR rope including existing submersible cable and check the unserviceability,remove the sludge/ poly bags/ cement bags/any solid items from inside the pump bowel/impellor and make good working condition with all safetyes etc complete all as directed. Lowering :- Lowering the non clog sewage submersible pump after making operational condition alongwith column pipe, SWR rope including existing submersible cable and all respective items here-in- above lifting and installation of pump motor in its original position, connections the as well as delivery main including electrical connectiion of both end i.e. with starter and motor terminals. Note :- Note :- (a) Rate quoted against items deemed to be included for lifting /lowering. delay may be penalised Rs: 1000/- per/hour.
Material and Labour for repairing and servicing /cleaning complete of submersible pump Set of the capacity 3.0,10.0 HP with replacement of worn out /unserviceable parts and reassembling the same after complete repair with accessories such as nut, bolts, washers etc. Installation with proper alignment including testing, commissioning complete to the entire satisfaction of Engr-in-charge. Note:- All spare parts as required for repair/overhauling shall be measured and paid separately under relevant item of Schedule 'A' and the spares should be suitable to as per above refered model No & make of KSB.
(i) Cutting and taking out existing burnt out/unserviceable copper winding from the stator unit of non clog sewage submersible pump Set Cleaning of slots and complete stator unit with using carbon tetra chloride (CTC Solution). Material and labour for rewinding the motor with 'F' class super enamelled copper wire of existing size/gauge including providing bi-metallic thermal overload protection and all necessary insulating materials such as varnish, insulating paper, sleev etc for the following capacity of 10.00 HP motor.
All as per item No.55 but capacity of 3 HP Motor
Bearing suitable to above make pump & motor
Oil seal
Impeller wear ring
Bearing sleeve
Cable duct
Colling oil for Motor (ISO VG 68)
Taking out old leakage/unserviceable butterfly valves of size 50,80 & 100 mm from various location in Sewage Treatment plant, Sewage pump houses and swimming pool complete all as directed by EIC.
Supplied and installed butterfly valve with standard case flaged type of make: Normax/auma/honeywell , confirming to IS-13095 complete of the following sizes: (a) 50 mm dia
Butterfly valve size 80 mm.
Butterfly valve size 100mm.
Material and labour for taking down existing old unserviceable cable of any size and Supply laying flexible flat PVC insulated PVC sheathed copper couductor stranded submersible cable,1100 volts grade (a) 4 Sqmm 3 core including jointing material and connection work. Make : Polycab/Finolex/Havells.
(b) All as per above item No.19 but 6 Sqmm 3 core
Supply only Bearing Grease in 1 Kg Packing
Supply and replace Digital voltage meter suitabel for 3 phase AC in MA panel at STP of suitable size required at site
Supply and fixing stainless steel short heavy duty chain in sewage sump motors placement in sump house locations and sewage pump at STP
Testing of STP water for TDS . BOD ,COD, PH , DO, Coliform at receving inlet, secondary treatment and tertiary treatment from any recognised LAB.
M/s K R and Sons (BID ID -3076426)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .