| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.7 LAccepted-AOC FLAT NO 151 BLOCK NO 1 DIAMOND SQUARE CGHS LTD PLOT NO 13A SECTOR 6 DWARKA NEW DELHI 110075 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110075 | L1 | Accepted-AOC AOC Awarded | |
| 2 | L2₹19.4 L+₹3.1 L (18.9%)Rejected-AOC | L2 | Rejected-AOC Rejected | |
| 3 | L3₹19.8 L+₹3.4 L (21.0%)Rejected-AOC H 13 GEETANJALI PARK WEST SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L3 | Rejected-AOC Rejected | |
| 4 | L4₹25.0 L+₹8.7 L (53.4%)Rejected-AOC | L4 | Rejected-AOC Rejected |
Tender Value
Refer Docs
EMD Value
₹77,000
Closing Date
19 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (P) AF Gurgaon
GE (P) AF Gurgson near Atul Kataria Chowk Gurgaon
CA NO GE (P) AF/GUR-68/2020-21 REPAIR MAINT OF EXTERNAL E/M SERVICES AND OTHER CONNECTED WORKS AT 27 ED AND 31 MCU AF STN PALAM UNDER GE (P) AF GURGAON
2020_MES_396905_1
GE(P)AF/GUR-68/2020-21
Open Tender
Miscellaneous Works
Item Rate
272 days
GE (P) AF Gurgaon
All as per NIT
10 documents required · 10 mandatory
₹500
GE (P) AF Gurgaon
₹77,000
Yes
26 Dec 2020
20 Nov 2020
21 Dec 2020
21 Nov 2020
19 Dec 2020
5 Dec 2020
60 days
Amount
Excavation in trenches in soft/loose soil not exceeding 1.50 Mtrs wide and not exc. 1.5 Mtr deep and getting out for taking out/laying cable, poles &stay etc complete all as specified and as directed by Engr-in-Charge.
Demoliton of Concrete of any description and in any position not otherwise specifically provided complete all as specified and as directed by Engineer-in-charge.
Returning, filling in including spreading leveling, watering and well ramming in layers not exc 25 cm thick after the cable have been laid tested complete all as specified and as directed by Engineer-in-Charge.
Removal of excavated surplus soil to a distance not exc. 50 Mtrs and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and as directed by Engr-in-charge.
M&L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable and punned down to 18cm, complete all as specified and as directed by Engr-in-charge.
M&L for brick laid in trenches for cable protection of burnt clay sub class ‘B’ complete laid dry flat, complete all as specified and as directed by Engr-in-charge.
Laying old serviceable bricks (retrieved under item 01 of Sch ‘A’, complete all as specified and as directed by Engr-in-charge.
M&L for PCC 1:2:4 type B1 using 20mm grade stone aggregate as in copping of electric pole, solar platform or making good of disturbed surface complete all as specified and as directed by Engineer-in-charge.
M&L complete for driling hole hard standing / road for laying of pipe for protection of cable etc by means of manual booklet and without disturbing the top surface or cutting and making good the disturbed surface to the existing if any complete all as specified and directed by Engineer-in-charge. GI pipe shall be measured and paid sepretely.
Supply and lay or fixing or passing through pipe cable XLPE (FRLS) with aluminium conductor with heavy duty stranded,1100 volts size of 16 Sqmm 2 Core including taking out old U/S cable complete all as specified and as directed. Note :- XLPE insulated pvc sheathing (heavy duty) armoured cable with aluminium conductor for working pressure up to and including 1100 volts to IS -7098 (Part-I) for pvc insulated cables with following :- (a) Cable shall have fire retardate low smoke (FRLS) compound added to it in the inner sheathing and out sheathing as per IEC 754 (part-I) IEC-60332 part-2 IFEE 383 ASTM 2x43 and ASTM 2X63 flame retardate compound (PR) as per EIC specification. (b) Inner sheathing shall be of extruded PVC. (c)Heat resisting PVC shall also be added to extruded inner and outer sheathing. (d) Cable shall also be supplied with sequences hal marking at every meter as the outer sheathing. (e) ultra violet radiation resistances compounded comprising ton ASTMG-53. (f) anti rodent and antitermite compound added. (g) pvc compounds of various grades as IS-5831. (h) compaction conductors shall be shaped and arrangement for the same with be on the cable
All as per item No. 10 hereinbefore but size 16 Sqmm, 4 Core .
All as per item No. 10 hereinbefore but size 35 Sqmm, 3.5 Core .
All as per item No. 10 hereinbefore but size 50 Sqmm, 3.5 Core .
All as per item No. 10 hereinbefore but size 95 Sqmm, 3.5 Core .
All as per item No. 10 hereinbefore but size 120 Sqmm, 3.5 Core .
All as per item No. 10 hereinbefore but size 240 Sqmm, 3.5 Core .
Supply and fixing non transparent looping SMC kiosks pole box 3 phase of size 310 x 210 x 120 mm made out of engineering plastic one piece moulding Siemens grey colour with hold fast including 4Nos aluminium strips 60 amp of required size fixed on unbreakable insulator and one no single pole MCB 1to3 amp 'C' curve including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing LED street light fitting of capacity 70 watts ,cool white complete with drivers and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge. Make : Havells/CG/PHILIPS
Supply and fixing LED street light fitting of capacity 90 watts ,cool white complete with drivers and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge. Make :Havells/CG/PHILIPS
M&L for 150 watt energy , saving environmental friendly, long life exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural features or retail spaces, including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge. Make : Havells/Philips/CG
Supply and fixing 9 watts LED bollards rounded shape(diameter 180mm), integral decorative with model number BCP 150LED/NW PSU 220-240V 7043 including Steel pole, length requirement as per site requirement and PCC foundation size is 1.5' x1' x 1' and necessary connections and taking out of old unserviceable one., complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of post top light fitting as per matching to existing type of capacity 40/45W made in die-cast aluminium decorative clear optics IP-65 complete all as specified and as directed by Engineer-in-charge.
Supply and fix replacement of Highly efficient high power LED flood light without lens , pressure die cast aluminium housing, reflector and enclosed with toughened glass Capacity 200 Watt . IP 66, complete all as specified and as directed by Engr-in-charge. Make :Havells/Crompton/PHILIPS
Supply & Fix copper conductor five core cable of size 2.5sqmm stranded PVC insulated for connection of fittings of high mast lights complete all as specified and as directed by Engineer-in-charge.
S&F in replacement of MCCB 4 pole, 63A, 16KA, fixed in bus bar trunking or in DBs, complete all as specified and as directed by Engr-in-charge. Make Havells IHLGNF0063 or equivalent in makes specified in list of makes.
S&F in replacement of MCCB 4 pole, 125A, 16KA, fixed in bus bar trunking or in DBs, complete all as specified and as directed by Engr-in-charge. Make Havells IHLGNF0125 or equivalent in makes specified in list of makes.
S&F in replacement of MCCB 4 pole, 160A, 25KA, fixed in bus bar trunking or in DBs, complete all as specified and as directed by Engr-in-charge. Make Havells IHLGHF0160 or equivalent in makes specified in list of makes.
S&F in replacement of MCCB 4 pole, 250A, 36KA, fixed in bus bar trunking or in DBs, complete all as specified and as directed by Engr-in-charge. Make Havells IHLFNF0250 or equivalent in makes specified in list of makes.
S&F in replacement of MCCB 4 pole, 400A, 36KA, fixed in bus bar trunking or in DBs, complete all as specified and as directed by Engr-in-charge. Make Havells IHLLSEBF0400 or equivalent in makes specified in list of makes.
Preparation of old painted exposed surface of steel tubular LT poles 9 mtr long with street light brackets etc complete, painting and numbering of poles with existing size and type as under:- (i)from bottom up to 1.2 mtr height one coat of black synthetic enamel high glow paint make berger (ii) 1.2mtr to 1.30mtr height one coat of red & blue luminous paint/tape. (iii)1.30 mtr height to top of the pole two coats of aluminium paint.
S&F street light panel/ feeder box made out of MS/ CRCA sheet 3.15mm thick with MS angle iron frame of size 40x40x6mm outdoor type with locking arrangement of size 0.6mx0.45mX0.35m with powder coating paint including PCC 1:3:6 type C-1 foundation of size 0.60 x 0.45 x 0.35 mtr, copper bus bars and internal wiring & taking down old panel box complete of suitable size with following switchgears accessories:- (a) MCCB 4 pole 415V 63Amps 16KA - 01 No. (b) LED indicator lamp 01 Set. (c) Timer switch- 01 No. (d) 40Amps TP power contactor - 01 No (e) MCB TPN 32Amps - 1No (f) MCB SP 6-32 Amps - 06 Nos (g) Single phase preventor - 1 No.
Supply & Fix in replacement of Environmental friendly LED Flood light of capacity 42/40W with IP-65 protection 230V complete all as specified and as directed by Engineer-in-charge. Make:- Havells/ Bajaj/ HPL
S&F out door type cubical panel board suitable for 3 phase, 4 wire, 415V, 50 Hz and tested at CPRI at 415 volts factory fabricated in an approved factory with CRCA sheet not less than 3.15mm thick having modern fabrication process powder coating in approved shade having thickness not less than 100 microns provided with suitable gasket to make it dust and vermin proof and general constructions conforming to IS : 8623/93. The LT Panel shall be front and back openable and having inner and outer shells. The inner shells duly compartmentalized for each control gears. The panel shall have suitable size of Copper Bus -bar three phase 4 wire system having current carrying capacity not less than 1.2 times the rated current carrying capacity of the incomer ACB/MCCB. The panel shall have the following incoming and outgoing controls duly fixed with the panel by means of suitable link plates complete all as specified and as directed by Engr-in-Charge. (PCC 1:3:6 type C-2 platform of suitable size for mounting the feeder pillar box is deemed to be included in the quoted rate ) of approved manufacturer including dismantling of LT panel and provision & accommodation of the following incoming and outgoing controls of suitable size:- INCOMING (i) MCCB 250 A, 36 KA, 4 pole -1 No
(ii) Digital Multi functional meter VAFPP (voltage, current,frequency, power factor- 1 No (iii) Phase indicator lamp (LED type) 1 set of three) OUT GOING (i) MCCB 125A, 25 KA, 03 pole - 01 Nos (ii) MCCB 100A, 25 KA, 03 pole - 02 Nos (iii) MCCB 63A, 16 KA, 03 pole - 03 Nos Make of panel: Conelec Systems/Tricolite/Mc Layer/Indo Asian
M&L for defect rectification electric cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc.including and additional excavation in normal alluvial strata required for exposing the cable fault removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 400 Sq mm 3.5 core. The fault locating equipments shall be brought to site within the hours of instruction from Engr-in-Charge.
Supply and jointing LT 1100 Volt grade cable straight through heat shrinkable type complete suitable for aluminium conductor cable of size 3.5 Core 120 Sqmm to 400 Sqmm complete all as specified and as directed. Make: Denson/Cabseal/M-Seal
All as per item No. 35 here in before but suitable for cable size upto 95 sq mm.
Supply and laying GI tube light grade 40 mm bore for cable protection including bend, clamps with nut and bolts as required complete all as specified and directed by Engr-in-charge.
S&F in replacement time switch type Alpharex3 D 21 astro, complete all as specified and directed by Engr-in-Charge. Make : Legrand Cat Part No.412654 or equivalent out of makes specified in list of makes.
Supply and fixing in replacement 40 amps TP power contactor, complete all as specified and directed by Engr-in-Charge. Make - Legrand Cat Part No-412549 or equivalent out of makes specified in list of makes.
M&L for two coats painting to exposed LT Panel inside and out side of the panel including LT panel legs as per specified colour code after cleaning and scraping out old paint including writing/ marking 27 ED/31 MCU location complete all as specified and as directed by Engr-in-charge.
Supply and laying of 2.5 mm thick insulated synthetic mat of confirming to IS 15652 : 2006 and meeting the requirements of IS 5216 (Part 1.2 & 3) IS 8437, IFC-479 Pub-1, alongwith suitable adhesive/chemibound, PU resin, waterproofing compound and sealing material as per in service recommendation of IS : 15652 class – B suitable for working voltage up to 11 KV with trolley movement complete all as specified and as directed by Engineer-in-charge. Make : SAFEVOLT/INSULICA
Dismantling of mechanism system of defecitive 11 KV VCBs, repair/replace the unserviceable items such as closing/triping coil, vaccum interrupter tube,moving contact and spring charging motor etc including overhauling the same by the service engineer after necessary cleaning with CTC, and providing silicon grease to the all moving parts including adjustment of all springs etc and made 100% serviceability and testing complete. Note:- closing/triping coil,vaccum interruptertube,moving contact and spring charging motor shall be measured and paid separately.
Supply only replacement of closing/triping coil suitable for 11 KV VCB's like as Crompton Greaves/areva/ABB) complete all as specified and as directed by Engr-in-charge.
Taking out of defective /unserviceable /obsolete model indicator lamp from 11 KV VCB's, supply and fix indicator lamp LED type of different colour of existing, 60 mm dia 30 volts (Make - Siemens/L&T) complete all as specified and as directed by Engr-in-charge.
M&L for Spray painting outside for 11 KV VCB's panel/bus copler with one coat of synthetic enamel paint Ist grade (moisture proof) after preparation/cleaning of steel surfaces complete all as specified and as directed by Engr-in-charge.
Supply & fixing bus bar insulators suitable for 11 KV VCB's complete all as specified and as directed by Engr-in-charge. Make - as per sample
Calibration, injecting and testing in artificial way for over load and earth fault IDMT relay at11 kv switch gear complete all as specified and as directed by Engr-in-charge.
Taking out of old unserviceable/defective/old vintage/ obsolete model of relays from 11 KV VCB's and Supply and fixing over current and earth fault electronic relay. Make - L&T cat no- MC61A-nX2200 suitable for 11 KV VCB like as CG/ABB/Areva including necessary addition/ alternation of VCB front panel including cutting/welding of front side of panel board to match & fixed the new relays to the existing panel board/position including necessary touch up to the panel board all as completed testing of over load and earth fault protection complete all as specified and as directed by Engr-in-charge.
M&L for Taking out of Air Circuit Breaker LT 415 volts up to 800 amps from existing position, dismantling the same, overhauling/maintenance/repair the same including replacement of minor spares and assembling the same refixing to the existing position including adjustment of load and testing complete all as specified and as directed by Engr-in-charge.
M&L for Painting to electrical equipments steel sections, rolling shutters etc with two coat of synthetic enamel high glow paint Ist grade including preparation/cleaning of steel surfaces complete all as specified and as directed by Engr-in-charge.
Dehydration of tranformer oil, obtained from transformers/ voltage stabilizer etc. Dielctric strength shall not be less than 40 KV in 2.5 mm gap electrode after dehydration. Dehydration of transformer shall be carried out by using electrically operated dehydration machine including replacement of unserviceable silica gel and toping up/ replacement of unserviceable transformer oil complete all as directed. Note:-- Transformer oil for filling/toping up and Silica gel shall be measured and paid against respective item.
Supply & filling, topping up of transformer oil of dielectric strength 40 kv and above in transformer at different loaction in situ (testing of oil shall be carried out in prensece of Engr in charge by an authorised agency and testing certificate shall be submitted duly signed complete all as specified and as directed by Engr-in-charge.
Supply and replacement of Silica gel of superior quality of size 5 to 10 mm complete all as specified and as directed by Engr-in-charge.
M&L for Dismantling of defective GOD switch 200/400 amps capacity and repairs to the same including replacement of Male & Female metal contact, arcing horn and all rusted GI nuts, bolts & washers, making proper connection of ACSR conductor/cables and necessary greasing etc to make 100% serviceability and proper functioning of GOD switch complete all as specified and as directed by Engr-in-charge.
Dismantling of PT pump assy from DG set of Make - Cummins /ruston/kirloskar engine for repair, cleaning, serviceable, overhauling of pump assy with necessary calibration including replacement of spares parts, complete all as specified and directed by Engineer-in-Charge.
M&L for Taking out self starter 12/24 volt from the DG Set, transportation to workshop opening/disconnecting all internal connection, cleaning the same taking out burnt armature, segregation serviceable parts for re-use, rewinding of armature with existing size of copper wire. Reassembling the same with replacement of of carbon brush 01 set, Beadex pinion 01 no, Half clutch assy 01 No, Field coil 01 No, solonoid switch 01 No., commitator 01 nos, fixing the self starter on the engine at site and testing, complete all as specified and directed by Engineer-in-Charge.
M&L for Dismantling of starting system of 100/63/40/25KVA DG set at 27 ED/31 MCU including necessary wires and supply and fixing new starting system with maint free lead acid battery 12 V ,150 AH 01 No with copper terminal cable of 25 Sqmm single core approx length 1.5 Mtr each for negative and positive terminal and 0.5 mtr for inter connection including necessary brush terminals complete of DG set including testing, complete all as specified and directed by Engineer-in-Charge. Make Exide/Amaron with 24 months replacement warranttee.
M&L for Dismantling of starting system of 125 KVA DG set at 27 ED, including necessary wires and supply and fix new starting system of maint free lead acid battery 12 V ,200 AH 01 Nos Make Exide with copper terminal cable of 25 Sqmm single core approx length 1.5 Mtr each for negative and positive terminal including necessary brush terminals complete of DG set including testing, complete all as specified and directed by Engineer-in-Charge. Make Exide/Amaron with 24 months replacement warranttee.
Dismantling of injector any DG Set in MCU and ED,s for repair, cleaning of and overhauling of the same with necessary calibration including replacement of necessary parts as required, complete all as specified and directed by Engineer-in-Charge. Note : spares parts required shall be measured under separate item).
Supply only replacement of kit Injector for incorporation to the injector assy DG Set Capacity upto 125 KVA complete all as specified and directed by Engineer-in-Charge.
Inspection of the DG Set of capacity 25 to 125 KVA in ED & MCU area finding out defects, cleaning dismantling repair/recondition servicing of the complete DG set, setting of valve timing by replacement of spares as required including wiring testing , complete all as specified and directed by Engineer-in-Charge. Note : Spares parts required shall be measured under separate item here in after).
Spring washer Cat part No-602160100100
Spring washer Cat part No -602180100120
Binjo screw injector Cat part No - 604043200023
Set of flexible fuel pipe Cat part No - 123200190058
O' ring injector Cat part No -604931040203
Set of copper washer Cat part No - 123200190098
Fuel filter elements set pre mico.
Set of belts
Disposalable oil filter elements
Set of Hoses Cat part No - 123200190258
Air filter complete.
Set of hoses clips Cat part No -123200190268
Cylinder liner with 'o' ring Cat part No -62320132044
Set of rings Cat part No -123200190278
Complete set of gasket Cat part No -123200193567
Piston ring set
Sleeve
connecting rod bearing pair
Rubber hose
Washer cranks case
Fuel pipe
Hex screw tappet cover
Hex screw oil sump
Allen screw
Tappet adjusting screw
water pump set
cooling water pipe
HRC fuse
Supply , filling and toping up of lubricating oil from existing DG Set of any capacity and supply & filling lubricating oil grade as required at site, complete all as specified and directed by Engineer-in-Charge. Make - HP/Castrol
Supply , filling and toping up coolant in DG set of any capacity, complete all as specified and directed by Engineer-in-Charge. Make - HP/Castrol
M&L for repair of radiator set complete with rusted out parts like coils, tanks hose pipes, fan bels, fan blade complete all as specified and as directed by Engineer in charge.
M&L for painting to the DG Set of 125 KVA capacities by applying Ist grade synthetic enamell spray duco paint in existing colours including fuel tank foundation base ,canopy and panel board and cleaning & removing of existing rust grease oil spot etc and preparation of surfaces, complete all as specified and directed by Engineer-in-Charge. Make : Berger/Asian
Detecting the fault of any capacity of DG Sets and any location by providing skilled trademan & helper with necessary safety and working equipment such as ,multimeter ,speedometer and other reqd tools and plants and rectified the defects on top priority basis/as and when reqd including testing, complete all as specified and directed by Engineer-in-Charge.
Supply and incorporation of distilled water for lead acid battery, complete all as specified and directed by Engineer-in-Charge.
M&L for providing Chemical Earthing with copper earth plate 900mm x600mm x5mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc complete with alternate layer of salt crystal and charcoal and Magnesium sulphate crystal as specified below:- (a) The earth pit should be of minimum 12 ft depth and 4 ft width. (b) The copper plate should be of 3 ft x 2ft and 5mm thick. (c) The copper strip should be of 32mmx6mm dimensions (cross section) up to 7.5 mtr. (d) The quantity used should be:- (i) Charcoal - 250 Kg (ii) Salt crystal - 200 Kg (iii) Magnesium sulphate crystal - 100 Kg (e) 3/4 inch dia GI pipe of enough length to reach just above copper plate fitted with funnel, meshed along with cap and running water should be provided for keping the soil wet approx one mtr GI pipe be kept out side for connection of running water. (f) The pit shall be constructed in PCC 1:2:4 type B1 using (using 20mm grage stone aggregate) RCC slab shall be provided in RCC 1:2:4 type B-1 (using 20mm grade stone aggregate) 50 mm thick pit cover reinforced with 8mm dia TMT bars 75mm c/o both ways MS handle 12mm dia, PGI funnel wire mesh and GI watering pipe of 20mm bore (light grade) and earth lead protection pipe 50 mm bore (light grade) shall be including the item.
M&L for earthing in replacement of with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip 32x6mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge.
Supply and fix replacement of test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 nos.8mm dia 25 mm long hex .head screw fixed inside cubical shape enclosure made out CRCA sheet 2.0 mm thick with front detachable cover, anodized fixing screws, cap washers 4 nos to be mounted on wall with wooden plugs & screws 4 nos, duly painted inside and outside by two coat of aluminium paint over a coat of primer, over all dimension of enclosure200mm x 150mm x 100mm (depth).
Supply and fix replacement of copper strips of size 25mm x 3 mm all fixing arragement such as clamps/MS screws/saddles /PVC gutka/Brass Nut bolt/Porcelain insulator & washers etc complete all as specified and directed .
Supply and fix replacement of Aluminium strips of size 25mm x 3 mm all fixing arragement such as clamps/MS screws/saddles /PVC gutka/Brass Nut bolt/Porcelain insulator & washers etc complete all as specified and directed .
Supply and fix replacement of galvanized iron strip of size 25mm x 3 mm all fixing arragement such as clamps/MS screws/saddles /PVC gutka/Brass Nut bolt/Porcelain insulator & washers etc complete all as specified and directed .
S&F of lightning conductor air termination, single pointed Aluminium rod 12 mm dia and 300 mm long including fixing of MS clamps with nuts & bolts and screws all as specified and directed .
Testing of earthing Resistance as and when required with working equipments such as earth tester etc in prensece of user & MES rep and maintaining test result to the binding resister for record all as directed by the Engr in Charge. Note:1) The contractor should report with in two days after intimatation to carry out the Earth Test as a whole or partially of the building. 2) Earth testing will be done in monthly basis. 3) Each month of each earthing measured seprately.
Repairs of earth pit cover including PCC1:2:4 work ,brick work & excavation including plastering all as directed and specified by the Engr-in-charge and levelling/returning filling of earth surface.
M&L for treatment of existing high resistance earthing pit by pouring of salt water solution made of 20 ltrs of water and 5 Kg of salt in the trench to be prepared all around the existing earth pit with radious 60 cm from the centre of the earth pit to the centre of the trench with a depth not less than 30 cm below ground level all as directed and specified by the Engr-in-charge and levelling/returning filling of earth surface.
Balancing the load of LT 415 Volt overhead/under ground system of any bldg / feeder/ panel board any location by providing skilled trademan & helper with necessary safty and working equipment scuh as clamp meter , high voltage megger tools, safty belts, hand gloves, crimping tool ,other reqd tools and plants and rectified the unbalance load on top priority basis/as and when reqd including testing complete all as specified and as directed.
Disconnection the transformers 11 kv /433 volts of any capacity and ED/MCU location AF station palam by providing skilled trademan & helper with necessary safty and working equipment scuh as clamp meter, high voltage megger, safty belts, hand gloves, crimping tool, other reqd tools and plants and serveceing /cleaning of transformer and HT/LT bushings, tightning of cable lugs and replacement of burnt lugs/socket on top priority basis and reconnection the same including testingcomplete all as specified and as directed.
Disconnection the electric supply and dismantling the section of high mast 16/20 mtr hegiht including fittings complete if requried by manually / hydra at AF station palam for servecing, repair of gear motor and replacement of steel rope and chain etc Refixing the same after repair/replacement of above items and testing complete all as specified and as directed.
Supply and fix replacement of solar panel, Model No SELE-20-20W, Die-casting high quality aluminium alloy housing capacity 20W LED,6000K,160LM/W, LI-PO4 battery : 48AH, 12.8V,Solar charging time:10-12 hrs by bright light sunlight, lighting Time : 3 Nights with different lighting mode, Mounting height : 3- 5 Mtrs,Working Temperature range : charging temperature 0 degree to 45 degree centigrade discharging temperature: 20 degree centigrade to 60 degree centigrade, and complete connecting accessories GI Bracket size upto 32mm dia GI pipe medium grade upto 1.2 Mtr Length bend in shape as required with MS flat iron clamp nut and bolts,washer etc as per suitable street light/solar light pole and connecting accessories ,necessary connection and testing complete all as specified and as directed by Engr-in-charge.
Labour Only for lifting of Solar street light pole with help of manual/ Hydralic crane after breaking PCC foundation with the help of hammer drill etc as per standard engineering practice and carefully loading and shifting from original location to a distance of not more than 1 KM carefully for erection with including foundation nut and bolt and connecting accessories necessary connection and testing complete all as specified and as directed by Engr-in-charge (Concrete foundation measure seperately).
Notes:- (a) The amount of Rs. 67,270/- against Schedule of Credit on Page No. 120 shall be deducted from the total amount quoted against Sch 'A' while deriving the Contract Sum for Acceptance. (b) As contract is maintenance nature the site shall be handed over in pieces as per site availability from users. (c) Contractor/ contractor rep shall take complaint from MES comlaint cell on every day and these complaints shall be rectified with in 48 Hrs. As water supply/sewage system is of vital nature, If any complaint/ work is not completed with in 48 Hrs that can be get executed from any other agency and cost of the same shall be deducted from contractor's dues.
PARKASH ENTERPRISES
J.P. Enterprises
M/s Prakash Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .