Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹34.6 L
EMD Value
₹69,220
Closing Date
22 Oct 2026, 4:00 pm4d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Estates Officer, SKUAST-Jammu
Estates Officer, SKUAST-Jammu, Main Campus Chatha
Providing electric repair work by way of SITC of new LT panel board complete and other allied works to be installed near Directorate of extension and Central Library building at Main Campus, Chatha
2026_SKUST_328287_1
AU/Estates/2026-27/12 dated 15-10-2026
Open Tender
Electrical and Maintenance Works
Item Rate
Main Campus, Chatha
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,000
Yes
Assistant Comptroller (Estates), SKUAST-Jammu
₹69,220
Yes
16 Oct 2026
16 Oct 2026
23 Oct 2026
16 Oct 2026
22 Oct 2026
16 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for IP 65 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc Makes ( L&T (D Sine) , Legarnd(DPX3), and Schineder (NSX-NS)) including dismentaling of existing LT panel etc as Directed by eng-in- charge. | |||||
| 1.1 | Moulded case circuit Breakers shall be Micro Processer based type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% | - | - | - | - |
| 1.3 | All metering current transformers shall be Class 1, 15 VA. | - | - | - | - |
| 1.4 | (Outdoor Type) | - | - | - | - |
| 1.5 | Incomer(Power Panel) | - | - | - | - |
| 1.6 | ACB 1600 Amp 50 KA 4P MDO Micro Processer based - 2no | - | - | - | - |
| 1.7 | Complete with mechenical and electrical interlocking. | - | - | - | - |
| 1.8 | MFM Meter - 2 set | - | - | - | - |
| 1.9 | Bus Bar | - | - | - | - |
| 2.1 | 2400 ampre rating alum busbar of electrplytic grade E 91 with Earth +copper wiring and all accessories | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
BOQ_1111537.xls
BOQ • 4.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .