Executive Engineer ED JPDCL Reasi
Office of Executive Engineer Electric District Complex Reasi
for Creation of 250 KVA S/Stn along with HT/LT line for Water Supply Scheme Bakkal Under Deposit Contribution Works of Railways on turnkey basis
2024_PDD_269230_1
eNIT32of20242025Dated30122024
Open Tender
Electrical Works
Turn-key
45 days
Bakkal Reasi
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
Executive Engineer ED Reasi
₹36,000
16 Jun 2025
31 Dec 2024
11 Jan 2025
31 Dec 2024
10 Jan 2025
31 Dec 2024
31 Dec 2024 - 10 Jan 2025
Amount
Scope of works for creation, Testing & commissioning of 250 KVA Distribution transformer Sub station
Supply Errection ,testing & Commissioning of 11/0.433-0.250KV;50Hz, Copper wound 250 KVA Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-I; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and 4x4 Mtrs. suitable cable of ratings
Supply, Transportation, Erection of 9 Mtr Long ST Pole STP-410SP33) duly painted with red oxide &Al. Paint (2 Coats) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Installation, Testing & Commissioning of 11 KV11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
Supply, Installation, Testing & Commissioning of 11 KV 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA withpolymer housing, Stn. Type
Supply & installation of PVC Cable 400 mm² single Core 1.1kV Grade, PVC Insulated Stranded ConductorFRLS type
Providing & Fixing of LT Distribution Box LT Distribution Box for 250kVA DTR with MCCB for incomer & SFU's for OutgoingCircuits
Providing of Earthing of substation --Excavation of earth pit ofdia 650 mm & depth 3000 mm, installation ofEarthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GIStrip for neutral earthing of size 25 mm x 3 mm forconnection of transformer body,G.O Set &lightening arrestor as per IS 2629/85, GI nuts &bolts,refilled with earth enhancement materials
Cement bottoming 1:2:4 mix as per REC standards0.5cum/pole
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mmdiameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing &fixing of CT/PT 15/5 with trivector meter
Particulars of works for erection of 11KV line with ACSR Weasel Conductor on 9 Mtrs ST poles
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Transportation, Fabrication & Fixing of GI (Cross arms with Top Bracket) Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated,along with GI nuts & bolts
Supply, Laying & Stringing of ACSR (30mm²) Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti-Climbing Device with Clamps
Providing & installation of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 Mtr long through GI Strip.
Providing of Cement Bottomining (1:2:4)(0.5cum each pole)
Providing & Fixing of Aluminium Jointing Sleeves
Providing & erection of Galvanized Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Particulars of works for erection of LT with ACSR Weasel Conductor on8 Mtrs ST poles
Transportation, Erection of 8 Mtr Long ST Pole (ST410-SP15)including excavation of pit and back filling of soil & consolidating by ramming, watering etc&duly painted with two coats of Red Oxide and Al. paint)
Providing & Fixing of GI U-Clamp with Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts
Supply, Laying & Stringing of ACSR Weasel Conductor through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of LT Line Spacers
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Cement Bottoming 1:2:4 mix as per REC standards .45cum/poleof poles
Particulars of works for erection & commissioning of Isolation point
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply ,Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply ,Laying & Stringing of ACSR Rabbit Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of PG Clamps for 30mm² ACSR Conductor
Supply, Installation, Testing & Commissioning of 11 KV GO AB Switch, 3-phase, 3-pole, 400 Amp/11 KV Link Set (450 x 50 x 6mm)
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, line Type
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Supply & Fixing of Danger Plates with Clamps
Supply & Fixing of Anti Climbing device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip(2 nos for ST poles & ino. For G O Switch/LA)
Providing of Cement Bottomining (1:2:4)(0.5cumeach pole)
M/S KOHLI CONSTRUCTION (BID ID -2307541)
M/S K.K ELECTRICALS (BID ID -2307468)
udhay partap singh (BID ID -2308155)
VEENA CONSTRUCTION CO. (BID ID -2307952)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .