Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.1 LAccepted-AOC 72 USMAN ENCAVE SECTOR O ALIGANJ LUCKNOW 226004 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226004 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹18.1 L+₹4.0 L (28.0%)Rejected-Finance HN 2 PREETI NAGAR PHASE II FAIZULLAGANJ LUCKNOW UTTAR PRADESH 226020 | LUCKNOW | UTTAR PRADESH | 226020 | L2 | Rejected-Finance Not lowest |
Tender Value
₹19.8 L
EMD Value
₹39,600
Closing Date
28 Jul 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) Bareilly
HQ CWE (AF) Bareilly-243002
REPAIR/REPLACEMENT OF HT NETWORK AND OTHER ALLIED WORK AT AIR FORCE STATION BKT
2022_MES_533438_1
81320/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BKT
As per NIT
8 documents required · 8 mandatory
₹500
GE(AF) BKT
₹39,600
Yes
17 Aug 2022
24 Jun 2022
30 Jul 2022
24 Jun 2022
28 Jul 2022
9 Jul 2022
25 Jun 2022 - 4 Jul 2022
Amount
Testing of 33/11 KV, 01 MVA step down transformer on site and generation of testing report and earth resistive test, O.T.I/ W.T.I , Buchholz circuit test serviciability and wiring from VCB panel to transformer , including following tests complete all as specified and as directed : - a) Insulation Test (IR/ Megger Values ) b) Open Circuit/Ratio test. c) Short Circuit Test. d) Magnetic Balance Test. e) Magnetization current Test. f) BDV Value of T/F Oil.
Servicing of HT(33 KV) HT panel (1 incoming 02 outgoing ) , detection of defective components, replacement of worn out parts and servicing/ cleaning of through authorized representative service centre of Panel manufacturer channel partner /OEM or UPPCL approved vendor for Panel repairing agency and Testing for smooth operation complete all as specified and directed by Engr-in-Charge. Note: Replacement of Worn out minor parts shall be deemed to be included in unit rate.
Servicing of 33KV VCB (out door type) at MRS substation, dismantling cleaning greasing the complete VCB with attached numerical relays bus bar etc insulation testing setting the contact gap by measuring as required reassembling the VCB and reinstalling back to its original position checking repairing the current circuit panel wiring ,relay testing and calibration and provision of minor spares as required complete including operational testing and commissoning complete all as specified and directed.
Servicing of RMU 11 KV (02 incoming 06 outgoing and buscoupler) , detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components, through authorized representative service centre of RMU manufacturer channel partner /OEM or RMU repairing agency, Testing for smooth operation manual/ remote after caliberation of relay and resetting & generation of testing report by the primary injection set For 11 KV RMU for OC / EF, parameter of relay setting for healthy system , complete all as specified and directed by Engr-in-Charge. Location : MRS BKT Note: Replacement of Worn out minor parts shall be deemed to included in quoted rate.
Servicing of 11 KV VCB at SPL Garriage substation, dismantling cleaning greasing the complete VCB with attached numerical relays bus bar etc insulation testing setting the contact gap by measuring as required reassembling the VCB and reinstalling back to its original position checking repairing the current circuit panel wiring, relay testing and calibration and provision of minor spares as required complete including operational testing and commissoning complete all as specified and directed.
Servicing of 11 KV RMU 3 way for, dismantling cleaning greasing the complete VCB with attached numerical relays bus bar etc insulation testing setting the contact gap by measuring as required reassembling the VCB and reinstalling back to its original position checking repairing the current circuit panel wiring, relay testing and calibration and provision of minor spares as required complete including operational testing and commissoning complete all as specified and directed.
Dehydration /Filteration of transformer oil at site by means of centrifuging machine in order to improve di-electric strength of oil as per IS-355. Break down voltage should not be less than 50 KV complete all as specified and directed.
M&L for Transformer oil having di-electric strength of 60 KV as per IS complete for top up/ replacement complete all as specified and as directed . (Oil should be supplied in sealed barrel of Power/Transol brand) Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations.
M&L for Painting of transformer after preparation of existing surface of transformer , remove oil stains, dust etc and applying two coat of synthetic enamel paint by spray paint incl writing SM No / MES No , capacity of transformer of following capacity complete all as specified and directed.
(a) 25 KVA to 100 KVA
(b) 150 KVA to 315 KVA
Supply & fixing of Silica gel in granular form for transformer air breather complete all as specified & directed.
Supply & fixing in repairs Brass metal studs nut, bolt & washers suitable for 1.1 KV LT side of transformer 100 KVA to 315 KVA complete all as specified and directed.
Supply & fixing in repairs Brass metal studs nut, bolt & washers suitable for 11 KV HT side of transformer 100 KVA to 315 KVA complete all as specified and directed.
Supply & fixing LT Bushing suitable for upto 315 KVA Transformer complete all as specified and directed.
Supply & fixing HT Bushing suitable for upto 315 KVA Transformer complete all as specified and directed.
Servicing and repairing/ carrying out maintenance of 11KV/440V transformer including the following works for 100 to 315 KVA capacity as detailed here under including the following complete all as specified and directed. :- (a) Removing from platform and disconnecting electrical connection from HT and LT side including transporting the transformer to work shop including loading unloading complete.. (b) Dismantling the transformer, drain out transformer oil, lift the cover, coil assembly keep up the assembly in oven upto the preparation of inside chambers by cleaning inside, scraping complete all around old parts of the transformer. (c) M & L for two coats of oil resistance painting inside transformer over a coat of red oxide primer. (d) Cleaning the core iron sheet laminations assembly by oil complete, removing the carbon sediments, dust in the coil and core gently without making any damage to coil and core. (e) Re-assembling all dismantled parts including provision of new gasket, nut, bolts, refilling with transformer oil and transporting back to original location including electrical connection, testing and commissioning complete.
Note :- (i) Oil filtration, supply of new oil will be measured separately in respective item of BOQ. (ii) All petty parts including nut, bolts, gasket minor weldings, oil for cleaning etc. and any other minor works and material (other than listed separately in tender) required for re-assembling all dismantled parts are deemed to be included the rate quoted by contractor. (iii) The rate for transport and lifting of transformer by crane should be deemed to include in the rate quoted.
M & L for rewinding of transformer, including dismantling, removing the core coil assembly from transformer remove the weak /unserviceable HT coil assembly rewinding with correct gauge super enamelled copper wire including drying, baking etc complete and remove the secondary coil assembly remove the insulation rewind with same coil and re-insulated. Assembling the primary and secondary coil in core, re-fitting for top lid cover of transformer including HV & LV Terminal Bushing without any damage to transformere-assembling the transformer complete refill with transformer oil, install, test and commissioning complete. NOTE : (i) Transformer oil will be measured and paid separately. (ii) Rate deemed to be included for transportation, lifting, testing and commisioning including guarantee of one year.
(a) Transformer 200 KVA Capacity
Supply and fixing in repairs of transformer gasket, nut, bolts, washers etc as per existing location for transformer upto 315 KVA complete all as specified and directed.
M&L for Repair of 11KV RMU at MRS BKT substation, cleaning servicing the complete RMU and mechanical parts of manual charging handle male end and wheel parts etc of minor spares as required complete including operational testing and commissoning complete all as specified and directed. Make: Schineder
Supply and fix disc type porcelain vitreous ball and socket type white brown double disc assembly insulator confirming to IS : 731 - 1971 & IS: 2486 Part - II - 1989 for tension with tension clamp for conductors working pressure 33 KV complete all as specified and directed.
M&L for Pin type porcelain vitreous,brown of white insulator to suit 11 KV HT of working pressure of size 150mm height, 150mm dia, including one galvanised mild steel spindle, two galvanished iron washer and one GI nut complete including dismantling existing old insulator from position complete all as specified and directed.
M&L for Post insulator suitable for 11 KV HT working pressure including all connected accessories including dismantling existing old insulator from position complete all as specified and directed.
Replacement of ACSR type jumpers (appx 1.5 RM in length) of suitable dia including aluminium lugs of suitable size for HT structures and yards including PVC insulation pipe and cleaning of carbon deposited on joints, applying jelly to each contact points and GOD male & female contacts and dismantling old jumpers complete all as specified and directed.
Dismantling and supply and fixing for outdoor type Gang operated Air break switch triple pole, mechanically operated, mounted on insulator and steel frame,with operting mechanism worked from ground level with GI pipe medium grade, for current rating upto 200 Amps suitable for vertical mounting fixed type complte with 09 Nos HT insulators suitable for HT 11 KV complete all as specified and directed. Make :- Jaipuria/ Pactil /GEC
All as per Item No. 23 above but for current rating upto 400 Amps, Make :- Jaipuria/ Pactil /GEC
Dismantling and supply and fixing SF6 Spring charging motor mechanism complete suitable for 11 KV RMU for operation ON/Off of switchgear complete all as specified and directed. Make Schnieder
Material & Labour for Lightning Arrestor (LA) zinc oxide type complete with all fittings transmission class, discharge capacity 30 KA, suitable for 11 KV complete all as specified and directed. Make :- Jaipuria/ Jaisree /Southern Insulators
Repairing / Servicing the Air break isolating switch 11 KV 200 Amps by replacing the defective major spares including provn of worn out bolts nuts etc, applying petrollium jelly on moving/ fixed contacts complete all as specified and directed. Note :- Major spare will be measured & priced seperately under relevant item No. 28 of BOQ here-in-after.
Supply only Airbreak switch spares :-
(a) Male contact/moving Contact Blade
(b) Female contact/Fix Contact Jaw
(c) Tinned copper Flexible jumper 200A/400 A
(d) MS jumper carrier
(e) Back Connector plate
Supply and fix cable jointing kit for 11KV grade cable for Outdoor end termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11KV grade cable for Indoor end termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11KV grade cable for Straight through joint cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm complete all as specified and directed.
M&L for graded taking out old coarse aggregate (broken stone or boulders) of any size and M&L for graded coarse aggegrate of size 40 mm for spreading and levelling at substation yard complete all as specified and directed.
Detection of pin point fault in HT cable (burried in ground/under road/path up to depth of 1.5 m) by cable fault locating machine comprising impulse generator,acoustic fault locator and reflectometer (laptop based) complete all as specified and as directed by Engr-in-Charge. Notes-(i) Cable fault locating machine to be arranged at site with in 12 hrs after intimation. (ii) Earth work will be measured seperatly. (iii) Cost of transpotation in unit rate is deemed to be included. Location:-AF stn BKT.
M&L for hammer tone spray painting of 33/11 KV Main Receiving Station switch yard including preparation of surface of Steel Structure, removal of dust etc and applying two coat of aluminium paint complete all as speciifed and directed.
M&L for preparation of old cement coated surface, cleaning the surface of the steel tubular HT pole above the ground level incl coping area with 2 coats of exterior aluminium paint over a coat of primer after preparation of surface including 12 cm existing colour paint around the pole and pole number in red when paint all as directed.
M & L preparation of old painted external surfaces of HT, 2 pole structures consisting of cross arms, GOD assy with pipe, DO fuse assy, clamps etc., of any description and applying one coat of Aluminium paint by mannualy complete all as specified and directed.
All as per item No 36 here in before but for 4 pole structure complete all as specified and directed.
Supply, laying, jointing and testing of HT XLPE PVC insulated PVC sheathed armoured heavy duty electric cable with aluminium conductor for working voltage upto 11000 Volts (E) , graded of cross sectionsal area 95 sqmm 3 core , complete all as specified and directed.
Excavation in trenches n.exc 1.5M wide & n.exc 1.5m in depth for laying & removing of cable any sizes and getting out in hard/dense soil complete all as specified and directed.
Returning filling in excavated earth work including spreading, levelling, watering and well ramming in layers n.exc 25cm thick in any strata
Removing excavated soil to a distance n.exc 50m, depositing where directed at a level n.exc 1.5M above the starting point complete all as specified and direcetd.
Supply and laying for dry sand cushioning to underground cables with 8 CM thick before laying of cables and 15CM thick after laying and stretching of cable complete all as specified and directed. Note : Punned thickness only will be measured and paid.
Supply and lay precast concrete cable covers,class HV,type- I flat size 300 x 180 x 40 mm complete all as specified and directed. Make: Mehtab, Topaz, National
M & L for single post insulator, 33 KV with mounting spindle etc. complete all as specified and directed.
M & L for Pin insulator, 33 KV with mounting spindle etc. complete all as specified and directed.
Supply and fix Cable end termination kit cold shrinkable type outdoor type, suitable for XLPE cable 3 core, 120 sqmm, 33 KV HT supply, complete all as specified and directed.
All as per Serial item No. 46 above, but indoor type, suitable for XLPE cable, 3 core, 120 sqmm, 33 KV HT supply complete all as specified and directed.
M & L for straight through joint cold shrinkable type suitable for XLPE cable, 3 core, 120 sqmm, 33 KV HT supply complete all as specified and directed.
Supply only HT type Insulating Tape non heat shrinkable type of 38 mm width and 10 Mtr length complete all as specified and directed.
Supply anf fixing 11KV Rubber insulating mat ISI Marked complete all as specified and directed.(Location: MRS Substation, Mafi substation No.1 & 2 and Solar substation)
Material & Labour for steel cross arms, angles, bracing supports, clamps and back plates fabricated from structual steel sections including nut bolts washers welding bending cold or hot drilling hole for bolts in any shapes or size as indicated or directed and inclusive of one primer coat and one finishing coat of silver paint complete all as specified and directed.
Material & Labour for ACSR Conductor of weasel type for HT connection complete all as specified and directed.
S & F in repair emergency Power system consisting of invertor equipment 3.5 KVA, 48 Volt,Single Phase protections for overload deep discharge, short circuit and reverse polarity and display for mains available Battary Charging, Battary Charging level inverter switched ON low Battary Indication overload indication etc complete all as specified and directed. Make: Luminious Model: Cruze 3500 48V Location : MRS 33 KV
Supply and fixing Battery 2 Volt 100 AH for battery Bank installed in 33 KV MRS for HT control Panel complete with termination clips complete all as specified and directecd.
M&L for earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6 mm thick burried directly in ground earth pit n. less than 3 Mtr deep below the ground level with top edge of the plate n. less than 1.5m below ground level and filling with cotton soil of volume 0.5 CUM brought from outside and Magnesium sulphate of 100 kg, salt of 100 kg and charcol of 100 kg and connected to GI Strip 32 x 6 mm by means of bolts,nuts,checks nuts and washers of galvanised steel including necessary earth work and excavation in any strata and PCC 1:3:6 type C2 chamber and chamber RCC cover and light grade GI pipe 50 mm dia of required length for protection of GI strip and water funnel and wire mesh with GI pipe medium grade 20 mm dia etc complete all as per electrical plate No. 3 of SSR Part-I and as directed including connections and testing on completion complete all as specified and directed.
M&L for Earthing complete with copper earth plate electrode 600x600x3.15mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to copper earth lead strip 20 x 3mm size by mean of nut/bolt and washer of copper as shown in electrical plate no 5 of SSR part I including necessary excavation and earth work GI pipe 20mm dia light grade for watering etc, PCC pit chamber with PCC cover in cement concrete 1:2:6 Type C2 with 40 mm thick Precast RCC cover slab 1:2:4 type B 0 with 8 mm dia TMT bar and handle with lifting hooks, adequate quantity of charcoal dust and common salt etc including testing complete complete all as specified and directed.
Re- Stringing only existing HT OH line including dismantling of existing old binding wire complete all as specified and directed. Location : MRS BKT to Indurabhagh Note: (a) Restringing of 3 wires shall be measured as one RM (b) Rate deemed to included for binding wire.
Cutting and trimming of tree branches 3 mtr all around of any size obstructing lumination of HT Over head line including removing trimmed tree branches complete all as specified and directed.
Labour only for removing all vegetation from 33 KV MRS yard of size 60 Mtr length x 35 Mtr width and complete all as specified and directed.
Labour only for removing all vegetation from 11 KV/433Volt upto 315 KVA Transformer yard of any size and all as specified and directed. (Total Number of transformer yard - 19 (Location- Airforce station,Bomb dump, Indhurabhagh))
Supply only Lugs of 25 sqmm to 75 sqmm complete all as specified and directed.
Supply only Lugs of 95 sqmm to 150 sqmm made up of GI complete all as specified and directed.
Supply only electrical rubber hand gloves suitable on working pressure of 33 KV complete all as specified and directed.
Supply only fibre glass discharge rod suitable for 11 KV working pressure including all accessories complete all as specified and directed.
Supply only fibre glass discharge rod suitable for 33 KV working pressure including all accessories all as specified and directed.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .