GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
REPAIR/MAINT OF 33/11KV MRS,11KV HT INSTNS,11KV OH LINES AND UG CABLES,HT CVB S/SF6 BREAKERS, MAINT OF POWER/DISTRIBUTION TRANSFORMER, LT/HT SWITCHGEAR AND PANEL AND ITS CONNECTED EQUMNTS AT DMRL, RCMA, ATC DEVATALAGUTTA UNDER GE I RND KBAGH, HYD.
2022_MES_534773_1
GE I KBAGH TOKEN 11 OF 2022 2023
Open Tender
Electrical and Maintenance Works
Item Rate
27 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹97,760
Yes
24 Aug 2022
30 Jun 2022
29 Jul 2022
30 Jun 2022
27 Jul 2022
14 Jul 2022
1 Jul 2022 - 8 Jul 2022
Amount
Testing and setting the relays of VCB's/SF6s breakers of 33 KV by primary injection method of any make/model and servicing the mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all the complete to the entire satification of Engr-in-charge.
Disconnecting and removing the unserviceable 33 KV burnt out 6/8 eight bolt clamps and supply and fixing new eight bolt type Aluminium clamps suitable for panther aluminium jumpers / pipes including nuts, bolts, washers and testing complete all as specified and directed.
S&F digital type volt meter suitable for Eleven KV breaker ranging (0-11KV/0 to 440 V) suitable for auxilary voltage 230 volts complete including taking down old unserviceable voltmeter complete all as directed. Make- MECCO/CONZERV
Disconnecting and taking down the worn out jumpers in 33 KV yard and supply and fix new jumpers cutting to adequate length of ACSR conductor panther complete all as specified and directed.
Servicing of HT OCBs 400 Amps, after manually operating and removing of old oil and top up with new oil and testing & commissioning complete all as directed.
Dehydration and filtration upto 5 MVA transformer 33/11 KVA, HT OCB oil indoor/outdoor/ isolation type at different location and different size of transformer from 63 KVA to 1000 KVA or any capacity Transoformer on DMRL/ATC location with centrifuging machine, manually operated and achieve BDV 60 KV including carrying out oil testing before and after the dehydration process for each OCB complete all as directed. Note : Required oil for top up will be measured and paid separately under relevant item of schedule.
Supply only transformer/OCB oil as per IS :335, break down voltage not less than 60 KV all as specified and directed. Make :- Power Oil/Electrol
Supplying, installation, commissioning and testing in replacement of 33 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 400/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE, HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 95 sqmm 3 core all as directed. Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE, HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 120 sqmm 3 core all as directed. Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:- Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
2 core x 10 Sqmm
4 core x 16 Sqmm
4 core x 25 Sqmm
4 core x 35 Sqmm
3.5 core x 50 Sqmm
3.5 core x 70Sqmm
3.5 core x 120Sqmm
3.5 core x 185 Sqmm
3.5 core x 150 Sqmm
3.5 core x 300 Sqmm
3.5 core x 400 Sqmm
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11/33 KV control panel including associated wiring, if reqd, complete all as specified and directed.
Supply, Lay & Test & Commissioning cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 16 core 2.5 Sq mm.
M&L for Repairs/maintenance of 11KV HT VCB/ SF6 breakers Panel including bus coupler of any type, size and capacity complete including the following :- Taking out 11KV HT VCB/OCB/SF6 breakers of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical/motorised system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and cleaning/servicing the entire motorised mechanism of VCB including all spare parts required at site, reassembling the VCB connection, testing, commissioning and putting on load to the entire satisfaction of Engr-in-charge.
S&F Earthing complete with copper plate electrode 600x 600x 3 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level with top edge of earth plate, not less than 1.5 mtr below normal ground level connected to copper strip earth lead of size 20 x 3 mm by means of bolts, nuts/check nuts and washers etc of galvanised iron, protected by galvanised iron pipe light grade 50 mm dia and connected to main switch/control board including necessary excavation earth work in any type of soil and PCC 1:3:6 type C1 for earth chamber, 40 mm thick RCC cover slab 1:2:4 type B1 with 6 mm dia TMT Bars at 140 mm cc both ways, watering pipe 20 mm dia light grade GI, funnel, wire mesh, lugs, charcoal and salt etc complete all as shown in Electrical plate No. 3 SSR Part I and testing complete including removing unserviceable any type of items all as specified and directed. Note : Copper strip and GI pipe 50 mm dia beyond 7.5 metres per earth will be measured and paid separately.
Ditto all as per item No: 17 above but using 32 x 6 mm galvanised MS strip earthing lead and MS galvanised plate of size 600 x 600 x 6 mm as earth electrode.
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated location for loop earthing etc. as required of size 32x6mm GI strip complete all as specified and directed.
Supply & Fix Gasket in replacement for upto 5 MVA transformer (SRC RC 70C Grade) with including all required T&P for drain out and refilling trainsformer oil after proper filteration,comminissioning and testing complete complete all as directed.
Supply installing testing and commissioning in replacement the relay module Micom P111 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge.
Testing and re-setting and calibration of protection relay of 11 KV RMU/VCBs/SF6 breaker (indoor/outdoor) for incoming and out going feeders with control panel and control cable differential relay through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Checking the condition of transformers (Oil & winding temp and B/H relay) and taking corrective checking and operating the switchgear and trip circuit of HT panel/breakers for its proper functioning complete all as specified and directed. Note:- Reports after calibration to be submitted and the autherised techinicion should attend the malfunctioning/routine service complints as and when required for entire contract period under warrenty.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm.
M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 240 to 300 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L stay assembly complete with accessories as shown in electrical plate no 1 including loop type isolator stay clamps stay strands excavation work and PCC work with 20 mm dia complete all as specified and directed.
Supply, fix and testing power pack with battery backup input 230 V AC, output 110 V DC, 1Amp suitable for existing HT 11 KV VCB panel complete all as specified and directed.
Supply, fix, testing and commissioning of Air break gang operated switch, triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT polymeric insulators and steel channel frame, GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated including locking arrangement for operating handle with and including 7 levers Navtal lock complete suitable for current rating of 400 Amps HT 11 KV working pressure all as specified and directed.
Supply and Fix Dropout fuse unit, horn gap type single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts washers etc, synthetic bounded fuse carrying tube complete with line taps and suitable for current carrying capacity upto 40 Amps only all as specified and directed.
M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat, one under coat and one finishing coat of paint.
Supply, Install and erect steel tubular swaged pole type 410 SP-55 of 11.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed. Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, coping of poles, cross arms, clamps shall be measured and paid separately. Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing.
Supply, Install and erect steel tubular swaged pole type 410 SP-31 of 9.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed. Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, coping of poles, cross arms, clamps shall be measured and paid separately. Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing
Material and Labour for PCC 1:3:6 type C2 wiring 40 mm stone aggregate for foundation of poles/transformer bed/cable duct foundation/panel base/ chain link supports etc including necessary form work etc complete all as specified and directed.
Material and Labour for PCC 1:2:4 type B1 wiring 20 mm graded stone aggregate for coping of pole including necessary form work etc complete all as specified and directed.
Material and Labour for Brick work with sub-class bricks straight or curved on plan exc 6m mean radious in CM (1:6) complete all as specified and directed.
Material & Labour for 10mm thick rendering in cement motar (1:6) mixed on brick or concrete surfaces finished even & smooth w/o using extra cement complete all as specified and directed.
Material & Labour for Providing precast cement concrete in landing cover slab type B-1 1:2:4 (20mm graded agg) set in cement 1:4 complete all as specified and directed.
M&L for spreading the 20mm coarse aggregate in various sub stations and other locations complete all as directed.
Supply and fix in repair of Impluse Emergency First aid kit box with basic medicine like Band Aid strips of min 20 Nos, Anteseptic cream, Cotton, Surgical tape 1 inch, non sterial gauge swabs, Hydrogen peroxide bottle, medical spirit bottle complete all as specified and directed.
M&L for Preparation of old painted inner and outer surfaces of indoor/out door HT/LT panels, spray painting the same with two coat of synthetic enamel paint grey an a coat of red oxide to achive smooth finish including writing of SM/MES No complete all as directed.
Testing and re-setting and checking connection of control cable from transformer tap changer to panel of auto tap changer relay up to 5 MVA transformer through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Tap changer panel l/breakers and tranformer control panel complete for its proper functioning complete all as specified and directed.
M&L for maintenance servicing, Calibration of existing APFC panel with and including repair/replacement of unsv of capacitor with existing size complete upto 500KVAR APFC Panel all as directed.
Supply and fix in repairs of Alarm annucator 12 window of model MBAS-0600 suitable for 33/11KV HT breaker complete all specified and directed.
S&F cable jointing kit for straight through joint (epoxy) for 1.1 KV grade XLPE, PVC insulated and sheathed aluminium conductor under ground cable including thimbles, nuts & bolts, washers etc and testing after jointing complete, all as directed for the following sizes. Make: M-seal/Raychem/Transeal/Denson
6 sqmm to 16 sqmm 4 core
25 sqmm to 50 sqmm 3.5 core
70 sqmm to 120 sqmm 3.5 core
150 sqmm to 400 sqmm 3.5 core
Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint complete all as specified and directed.
All as per Item No: 48 above but four/Six pole structure Make of Paint for item No. 48 & 49 : Asian/Nerolac/Berger.
M&L Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable for spreading the stone aggregate including disposing all the waste to a distance not exc 100m from the site all as directed by the Engr-in-Charge.
S&F digital type Ammeter suitable for Eleven KV breaker ranging (0-400) Amps suitable for auxilary voltage 230 volts including taking down old unserviceable Ammeter complete all as directed. Make- MECCO/CONZERV
M&L for spreading the 40mm coarse aggregate in various sub stations/Structure premises and other locations complete all as directed.
Cutting of trees and tree branches of girth up to 20cm and to a radius of 3M all around LT/HT OH line complete all as directed. Note: The distance between two adjacent poles will be considered as one span
M&L 11KV grade pin type, composite polymeric/ insulator insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer including all galvanised steel fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board.
M&L for LT line zig zag PVC spacer including replacing the broken u/s spacers and necessary ladder arrangement should be made by the contractor during replacing as required at site.
M&L in replacement horn gap fuse assembly mounted on porcelan insulator and steel frame, D or Channel type for HT 11 KV, 400Amps rated current including base frame made with 'C' channel cross arms of suitable size shall be including removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set.
M&L in replacement of Lightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set.
Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating parts etc after cleaning, removing carbon deposits including testing and commissioning the same for operation complete all as directed by Engr-in-charge. Note: The repairs to three poles of AB switch will be measured as on job.
Labour only for removing the binding of ACSR conductor of HT 3 phase 4 wire over head line from insulator, removing the jumper, connector, service wire, UG cable and restringing the existing ACSR conductor of any size, length, span upto desired sag and fixing the same ACSR conductor on insulator by proper binding, jumper connection etc complete all as specified and directed.
M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., complete all as specified and testing on completion.
S&F rust free Acrylic Danger notice plate duly marked voltage danger and conventional skull and bones in signal red colour written in one local language and english with retro reflective stickering and fixing with GI/MS. clamps, bolts and nuts of approved size, for LT 440volts all as specified.
All as per item No 61 above but for HT 11000 volts.
M&L for fixing the Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge.
Material and labour for tracing the cable route using ultra sonic cable route locator of any HT/LT UG cables complete all as specified and directed.
Supply and fixing rectangular RCC cable route indicator of size not less than 1m long with curved on top surface duly marking with size of cable, location including painting with two coats of synthetic enamel paint on surface directed. Make : As approved by GE.
M&L for fabricating feeder distribution layout board on ACP sheet of thickness 3mm and size as required at site designing the layout as per the sketch provided by the Engr-in-charge using ecosolvent print including lamination and fixing to the wall using necessary fixing nuts, bolts and spares as required at site. The job includes removing of old layout board from its position complete all as specified and directed.
S&F/lay GI earth wire 4 mm dia on walls/floor as earth continuity conductor connected to DBs/ panels etc.
S&F in repairs MS chequered plate of 6 mm thick confirming to FE 290 grade 165 including provision of lifting handle for each plate on existing cable ducts and manhole covers for semi under ground sumps including painting with two coats of synthetic enamel paint over a coat of red oxide primer all complete all as directed.
Supply only Male contacts suitable for 33/11 KV Air Break switch complete all as directed.
Supply only Female contacts suitable for 33/11 KV Air Break switch complete all as directed.
Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed.
Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at both ends after laying the cables including taking out old GI tubing complete all as directed.
All as per iem No 73 here-in-before but 80mm dia Make for item Nos.73 &74: ZENITH/ TATA/ JINDAL/SWASTIC
S&F in repairs MCCB 200 Amps, 4 pole 50 HZ, , complete all as directed.
S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, complete all as directed.
S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, complete all as directed.
S&F in repairs MCCB 400 Amps, FP, 50HZ, complete all as directed.
S&F in repairs MCCB 630 Amps, 4 pole 50 HZ, , complete all as directed. Note for item No. 75 to 79:- Cost of fixing on to walls/surface on suitable angle iron bracket support and civil work shall be included quoted rate.
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P upto 250Amps capacityof existing size complete all as directed.
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P 400/630Amps capacityof existing size complete all as directed.
Replacement of air breather of any type up to 5MVA transformer complete with filled silica gel complete all as directed.
Disconnection of all Primary/Secondary connection of the defective transformer of any KV rating, out door / indoor any make taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repair and bringing back and install, with all connections as per directions, after repair to its existing position, upto 5MVA capacity of transformer complete with testing and commissioning, complete all as directed.
Opening of the 11 KV / 0.433 KV transformer upto 500 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of leaked cork seal with insulator or LT/HT bush (which is unsv) complete from the shell and making again connections of LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformer testing & commissioning complete all as directed Note : HT/LT bush will measured and paid separately under relevant item and cork seal with insulator is deemed to be included in quoted rate.
M&L for opening the top of Transformer upto 5000 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level and testing the tranformer complete all as directed.
Supply & fixiing in repair of air termination single pointed copper rod 12mm dia and 300mm long including removal of the existing and complete all as directed
S & F Aluminium strip 25 x 3 mm with saddles and fixing screws etc for roof conductors and down conductors above ground including removal of existing and complete all as directed
M&L for Renewal of Fuse wire by using appropriate amp rating tinned copper fuze wire with all safety precaution like hand gloves Earth rod at site of any height of six/four/two pole structure all as directed. One Job includes all three fuse wires)
Supplying only Tinned Copper fuse wire of 16SWG to 22 SWG or 30 Amps to 200 Amps capacity .
S&F in repairs for Test point terminal block made out of gun metal or phosphorus bronzed size 75x75x25mm, drilled and screwed including 03 Nos 8mm dia 25mm long hexagonal head screw all as specified and directed
S&F in repairs for GI pipe light grade 50 mm bore , 1.2 mtr long duly threaded on both side for fixing GI socket & making necessary arragement for holding of air terminal rod all as specified & directed
M&L for opening the top of Transformer upto 625 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level for completing the work and testing the tranformer complete all as directed.
Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transforme upto 5000KVA capacity complete all as directed.
Supply and fixing of LT rod / studs for upto 5000 KVA capacity transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed.
M&L for replacement of Aluminium conductor, steel reinforced,Weasel type complete all as directed.
Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transformer up to 5 MVA capacity complete all as directed.
Supply and fixing of LT rod / studs for up to 5 MVA transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed.
M&L Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65/100mm dia for 550 volts grade complete all as directed.
Supply and fixing in repairs post top porcelain insulator vitreous brown with GI clamp, nuts, bolts etc suitable for 11000 Volts grade working pressure complete all as directed.
M&L in replacement of Shackle Type insulator 1100V 100mm hight 115 mm dia same as per existing complete.
M&L in replacement of analog type Winding tempreture indicator ,50-60 HZ ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperature for any type/size /capacity transformer all as specified and directed
M&L in replacement of analog type Oil tempreture indicator, 50-60 HZ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperatureor any type/size /capacity transformer all as specified and directed
M&L in replacement of Mog Magnetic oil level indicator,of aluminium body, industrial use of size 1500mm, temparature indication upto 30 DC , works on max pressure4Kg/sqcm accuracy 95% complete for any type/size /capacity transformer all as specified and directed
M&L in replacement of buchholz relay/gas operative relay of existing size and shape all as specified and directed.
M&L for Charcoal dust/breeze to fill in existing earthing pit to recharge the pit
M&L for common salt to fill in existing earthing pit to recharge the pit
M&L for 2 core round flexi copper wire of 1sqmm dia for AC/DC supply connections to VCBs/SF6 with suitable size glandsand insulated lugs of required qty complete all as directed.
Supply, Lay & Test & Commissioning cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizesround flex control cable of size 12 core 1.5 Sq mm.VCBs/SF6 with suitable size glandsand insulated lugs of required qty complete all as directed.
M&l in replacement of analog type winding temperature indicator/ Oil temperature indicator , 50-60Hz, 110-220V, IP 48 tempreture 0-160 degree mild steel body and indicator for oil/tempreture for any type/size /capacity tranformer all as specified and directed.
Supply, erect, Testing & Commissioning of numerical protection relay relay Model Micom P127, complete control wiring with material, Programming/setting/calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- Schneider or Techno Commercially equivalent ABB/L&T/Semiens
Supply, erect, Testing & Commissioning of numerical protection relay relay Model Micom P 122, complete control wiring with material, Programming/setting/calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- Schneider or Techno Commercially equivalent ABB/L&T/Semiens
Supply, erect, Testing & Commissioning of VAA Auxilary relay Alstom Model VAA11,22,33,21,3123 , 110V complete control wiring with material, Programming/setting/calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- ALSTOM or eqiuvalent in ABB/ L&T / SEIMENS
M&L for replacement of UNSV push button of existing size in breakers/panels complete all as directed.
Supply, erect, Testing & Commissioning of numerical directional over current & earth fault relay model Micon P-643 complete control wiring with material programming/setting /calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- Schneider or eqiuvalent in ABB/L&T/SEIMENS
Supply, erect, Testing & Commissioning of numerical directional over current & earth fault relay model Micon P-645 complete control wiring with material programming/setting /calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- Schneider or eqiuvalent in ABB/L&T/SEIMENS
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Supply and spreading of natural, clean, dry, river sand in trenches for cable protection / transformer yard/ two pole structure yard complete all as directed. Note:- Punned thickness only shall be measured for payment purpose.
Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1 with peak, size 300mm x 180mm x 40mm complete all as directed.
Making Primery/Secondary coil with insulating copper wire of required gauge, craft paper cotton tape HT/LT insulation as per specification of old transformer up to 5000 KVA including making of coil as required of various capacity of transformer including taking out burnt winding complete all as directed
Reconditioning of over heated 33/11 KV coil of transformer from to up to 5000 KVA after removing all old insulation any type and re-insulation as required and remaking of coils complete all as directed .
M & L for Inspection and servicing of OLTC of transformer of capacity 1.5 MVA and checking the electrical/manual operation of tap changer mechanism, check the integrity of the active components /contact surface mating for all tap positions, voltage ratio test for all tap position etc including cleaning of the OLTC complete all as directed. Note : The Contrator shall be responsible for correct servicing of the OLTC and servicing to be done through OEM of OLTC.
Supply and fix wiring and commissioning including thormostate switch space heater 200w for VCB/SF6 breaker/RMU complete all as directed.
Servicing of capacitor bank 200 KVAR, 12 KV, 3 Ph Dry Type Series Reactor and checking of capacitance of capacitor including control & power wiring, barrel fuses cleaning of spare parts including testing of relay & contactor, tightening of nuts/bolts etc after taking shutdown as per electrical safety norms complete all as directed Note: Spares costing upto 1500.00 shall be deemed to be included the in quoted rate.
S&F in repairs Silica gel complete all as directed.
LEO ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .