Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹14.8 L+₹2.6 L (21.7%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹15.0 L+₹2.8 L (23.0%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹18.0 L+₹5.8 L (47.3%)Rejected-Finance 179 URBAN ESTATE RAM TIRATH ROAD NR GURUDAWARA DARSHAN SINGH AMRITSAR PUNJAB 143001 | AMRITSAR | PUNJAB | 143001 | L4 | Rejected-Finance Other than lowest bidder |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
17 Oct 2019, 6:00 pmClosed
GE AF Jammu
GE Air Force Station Jammu
REPAIR/REPLACEMENT INCLUDING DAY TO DAY MAINT OF STREET LIGHTS, SECURITY LIGHTS, EARTHING AND MISC E/M WORK AT KALUCHAK UNDER GE AF JAMMU
2019_MES_281342_1
CA NO GE/AFJ-39/2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE AF Jammu
As per tender documents and as per policy in vague
8 documents required · 8 mandatory
₹500
Yes
₹30,000
4 Jan 2020
11 Sept 2019
19 Oct 2019
11 Sept 2019
17 Oct 2019
3 Oct 2019
Amount
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for laying of LT UG cables, foundation of poles, etc. complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site which will be handed over to the appropriate authority as directed by Engineer-in-Charge
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard dense soil
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point
Relaying only of serviceable bricks/PCC slab cover obtained from item No 1.00 to 8.00 here-in-before for cable protection cover laid width wise along length of cable complete all as specified and as directed by the Engineer-in-Charge.
Sub class 'B' old size bricks well burnt as covering to under ground cables , laid dry, flat over the cables on sand cushioning with width equal to length of the brick as mechanical protection to cable, complete all as specified and directed.
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed by Engr-in-Charge. NOTE Only punned thickness shall be measured for payment purpose.
Material and labour for shackle type porcelain vitreous white, brown or green insulator incl GI mild steel strip, washer, insulator bolts, washers and nut for working pressure 1100 volts section of strips 31 x 3 mm bolt dia 12 mm, max dia 90 mm, height 75 mm on poles upto 9 metre long incl taking down old unserviceable one.
Trimming of tree branches below, top and around the LT OH line and cleaning not less than two metres around the line and keeping the line clear throughout the contract period by trimming the branches repeatedly as many as times required depending on the growth of new branches including cleaning the site by depositing the branches to a distance not exceeding 50 mtr. all as directed by Engr-in-Charge. Note :- contractor will provide all necessary tools and required safety equipment for working on LT lines.
M&L for ACSR conductor on HT/LT poles of any type of conductor as required at site including binding and jointing to insulator with suitable size of binding aluminium wire for connectors, jumpers, etc. complete including taking out old unserviceable ACSR conductor from overhead line all as specified and directed.
Supply and Fixing MCCB 100 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 15 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 200 Amps 4 pole 36 KA with thermal magnetic release, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 48 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 250 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 49 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of aluminium paint, including taking down old broken steel complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repairs installation, commisssioning and testing factory made CPRI approved, outdoor cubical type feeeder pillar box totally enclosed over all size not less than 750 x 500 x 750mm, fabricated with 3.15 mm thick CRCA sheet (Heavy duty) over a frame of 40 x 40 x 6mm angle iron and mounted on platform all around and dust and vermin proof, IP-65 protection, back side openable, fixed with nuts and bolts and front side openable with hinged shutter and locking arrangement by operate alen key individuals for MCCBs and overall front panel double door shutter with powder coated finished both internally and externally suitable for 415 volts, AC, 50 Hz, 3 Phase, 4 Wire system by means of copper bus bar of size 50 x 5mm (Main) duly wrapped with coloured insulating tape/sleeves mounted on porcelain insulators with provision of fixing MCCBs necessary inter connections with copper strips of size 30 x 5mm and providing following equipments including connection with all incoming/outgoing calbes of different size duly crimping with suitable size copper lugs complete all as specified and as directed by Engr-in-Charge: -
INCOMING: (a) MCCB, 400 Amps, 4 pole, 415 V, 36 KA, 50Hz with extended terminals adjustable microprocessor, release industrial type, adjustable thermal (40%-100%) & adjustable magnetic (6-10 times)-01 No, Make: Legrand/L&T/Schneider OUTGOING: (a) MCCB, 160 Amps, 4 pole, 415 V, 36 KA, 50Hz with extended terminals adjustable microprocessor, release industrial type-01 No, Make: Legrand/L&T/Schneider (b) MCCB, 125 Amps, 4 pole, 415 V, 16 KA, 50Hz with extended terminals adjustable microprocessor, release industrial type-01 No, Make: Legrand/L&T/Schneider. (c) LED Phase indicator lamp - 01 Set (Set of three)
Supply and fixing in repairs installation, commisssioning and testing factory made CPRI approved, outdoor cubical type feeeder pillar box totally enclosed over all size not less than 1500 x 1000 x 600mm, fabricated with 3.15 mm thick CRCA sheet (Heavy duty) over a frame of 45 x 45 x 6mm angle iron and mounted on platform all around and dust and vermin proof, IP-65 protection, back side openable, fixed with nuts and bolts and front side openable with hinged shutter and locking arrangement by operate alen key individuals for MCCBs and overall front panel double door shutter with powder coated finished both internally and externally suitable for 415 volts, AC, 50 Hz, 3 Phase, 4 Wire system by means of copper bus bar of size 50 x 5mm (Main) duly wrapped with coloured insulating tape/sleeves mounted on porcelain insulators with provision of fixing MCCBs necessary inter connections with copper strips of size 30 x 5mm and providing following equipments including connection with all incoming/outgoing calbes of different size duly crimping with suitable size copper lugs complete all as specified and as directed by Engr-in-Charge: -
Supply and Fixing GI tubing light grade 50mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing light grade 80mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 20 x 3.15 mm copper strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing not exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4 mm dia galvanised earth lead wire by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32 x 6 mm galvanised earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Material & labour for Earthing using Copper earth plate electrode of size 60cm X 60cm X3.15mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers including refilling with good earth as specified and electrode connections by using Copper strip of size 20x3mm by means of bolts, nuts, check nuts and washers made of copper/brass and provision of GI pipe medium grade 40 mm dia for protection of earthing lead and 20mm dia for watering arrangement including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on plate No 5 of SSR Part-I 2009.
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Supply and Installation of advance Maintenance free tripod ring earthing system by boring the required nos of holes in semi hard soil or hard soil consisting of 03(three) Nos. UL 467 listed and CPRI tested copper bonded high tensile low carbon steel core electrode rod of 17.2 mm dia with a minimum coating thickness of 250 microns and length of 3 metres tested according IEC 62561-2 with min 10 years life span (the rod should be marked as per the UL certification) Model: AGE-APLI with up and down both side copper plate welded with GI 40mm tube as outer cover of electrod internaly and externaly covered with compound min 3X 25kgs/electrode of earth enhancing compound for each earthing pit (PROCEM) NABL certified, CPRI tested, ecofriendly, tested as per the IEC 62561-7 and needs to be considered to fill the 200mm bored hole surrounding to the outer/external cover of electrod.In one tripot earthing minimum 09 electrod to be fixed considreded as one earthing. The earth enhancing compound should have resitivity less than 50 ohm-meter with chemically inert to sub soil that should not pollute the environment and non corosive to the earth electrode itself including refilling with good earth as specified.
Provision of the connectors for connecting electrode with earthing conductor/strip including fastener made of stainless steel having suitable size according to the electrode and earthing conductor dimensions. All the three earthing electrode would be seperated by appropriate distance and connected to earh other by the incl 25mmx3mm copper strips/copper wire to make ring earth and upto test point terminal and to be burried in appropriate depth not less than 40cm below normal ground level and earth pit chamber of suitable size not less than 250x250x250mm internal dimension made of FRP material complete with flush moundted removable and lockable cover able to withstand 15KN for each earth electrode all as directed by Engineer-in-Charge.Provision of the connectors for connecting electrode with earthing conductor/strip including fastener made of stainless steel having suitable size according to the electrode and earthing conductor dimensions further connected up to equipment.
The earth result should be less than one ohms other wise payment will not be considered for the work executed under item of earthing. The chamber should have facility for marking earth resistance and latest testing date by paint at the cover including testing and taking out old UNSV earthing pit for credit complete all as specified and directed by Engineer-in-Charge. Make : ASHGEL ELECTRODE/ OBBettermann /FUrse/KLK/Erico all as per the descrition of Engineer-in-Charge.
NOTE: - (a) The rate shall include excavation, earth work, removal of surplus soil, returning filling with back fill compound, etc. (b) Earthing resistance result should be confirming to the value as specified in clause 19.146.14 of SSR Part-I 2009. If the result do not confirm, then the contractor will carry out the earthing in seperate location/site given by the Engineer-in-Charge after taking out of earth electrodes all without any extra cost to the Govt. (c) The contractor will provide all the required and necessary certificate(s) as per the specifications for required item(s) mentioned above from the same company before incorporating the same in the work as directed by Engineer-in-Charge and the rep of Company should be available at the site for the installation of the earthing as per their recommendation and specification to obtain the minimum resistance valve.
NOTE: - (d) Test equipment will be duly tested from authorized Govt Lab/CPRI Lab and sealed by the testing authority and produce test certificate of testing equipment before testing for which no extra payment shall be borne by the Govt. (e) Testing of earthing after completion of work will be carried out in presence of the GE, Engineer-in-Charge, rep of user and the Contractor. (f) Contractor will provide the gurantee for earthing and result for the period of minimum 05 years. (g) Copper strip beyond test point shall be measured and paid separately.
Marking Earthing Pit with white/ coloured Hylam sheet/per pex sheet 3mm thick of size 200x150 mm fixed with MS angle iron 20X20X4 mm and .75 mtr long lncluding painting with synthetic eneamelled paints 2 coats over a coat of red oxide primer fixed by means of 2 nos nuts,bolts,washer of suitable size and grout the maker nearer to the earth pit with PCC 1:2:4 of size 0.15 x 0.15x 0.15 m including necessary earth work.Maker shall be written the following letters (letter of size 25 mm)
CHEMICAL TRIPOD EARTHING EARTH PIT NO: EQUIPMENT/BUILDING CONNECTED: DATE OF TEST: EARTH RESISTENCE IN OHMS :
Name plate white/coloured hylam sheet/perpex of 3mm thick of size 150x100 mm and fixer to the equipment/building or nearest to the equipment on the wall by screwing and name plate shall be written the following letters (letters of size 25 mm) CHEMICAL TRIPOD EARTHING EARTH PIT NO: EQUIPMENT/BUILDING CONNECTED: DATE OF TEST: EARTH RESISTENCE IN OHMS :
Cutting wild grassess,bushes,creepers,unwanted vegetations, etc. from surrounding poles/stays including cleaning cripper climbed on poles as and when directed and removing the spoil and deposit where directed (size of cuttng 90x90 cm around pole/stay) & entire satisfaction of Engr-in-Charge . Note :- The item shall be operated maximum three times in the entire period of the contract.
Plain cement concrete 1:2:4, type B-1 (using 20 mm graded crushed stone aggregates) as in steps, seismic and other similar bands, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, cills, lintels upto 1.50 metre clear span, copings etc. and in similar works including weathering, slightly rounded or chamfered angles and throating and necessary form works, including demolition of broken PCC complete all as specified and directed by Engineer-in Charge.
Supply and fxing in repairs indus series powdered coated pressure die cast aluminium compact high power LED street light fittings with heat resistant toughned glass with lens having 45 watts with lens including making electric connection using two run of 1.50 sqmm single core unarmoured wire from junction box, complete all as specified and as directed by Engineer-in-Charge. Note :(i) A certificate from the manufactures for warranty minimum upto 2 years shall be obtained and submitted to the AGE/GE (ii) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Cat Part No: LTESS 18 x 2.5 HP LED of C&S or equal approved in Bajaj/Philips
Supply and fixing in repairs street light bracket 1.50 mtr long made out of 32 mm bore GI pipe, light grade, bend to shape, welding etc and fixing on existing LT pole with 50 x 6mm flat iron MS clamps including necessary nuts, bolts and washers etc and including painting two coats with synthetic enamel paint over a coat of red oxide primer after removal of galvanising with moderate solution complete all as specified and directed.
Attending complaints for checking of existing street light, security light, electrical cable, panel in any location at Kaluchak area for continuty, no light due to cable fault including carrying out minor repairs etc as required to make the item functional and replacing burnt cable ends, small pieces of cable, tightening of losse connecttions etc and alos maintenance and repair of all types of earthing system like GI, aluminium, Copper, Chemical earthing, etc complete all as specified and as directed by Engineer-in-Charge. Note: 1. Due to security point of veiw one electrician with helper shall be present daily round the clock with required T&P, spares and transport for attending unserviceable security/street light complaints received from users. The Contractor will ensure attendance of electrician and helper before JE E/M and the same will be produce before Engineer-in-Charge for payment. 2. Repair/replacement of spares/loose connection of particular fittings shall be measured and paid as one job for one day irrespective of any numbers of complaints attended in a particular day. 3. Street light complaints should be attended and rectified within the same day failing which recovery at double the rate quoted by contrator against this item shall be affected from his becoming due's
Supply and fixing fixed in repairs cable Junction Boxes with terminals` IP 66 "halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) Cable Size 16/25 Sqmm, Box Dimensions-200 x160 x 98, Catalog No-KF 9255(hensel) complete taking out of loop of cable from ground by neccessary earth work all as spcefied and directed by Engr-in- charge. Make- Hensel/Dowells
Supply and fxing in repairs indoor decorative LED batten T8 tube light fitting 20 watt, 4 feeet long, white with PVC extruded batten complete in all respect including 20 watt retrofit tube complete all as specified and as directed by Engineer-in-Charge. Note :(i) A certificate from the manufactures for warranty minimum upto 2 years shall be obtained and submitted to the AGE/GE (ii) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. Make: Cat Part No: LTDC30120WLED/WD of C&S or equal approved in Bajaj/Philips
Supply and fixing in repairs change over switch, 100 A rating, four pole, LT heavy duty, 415 volts, 50 Hz with side handle complete all as specified and as directed by Engineer-in-Charge. Make: IHBFFE0100 (HSD Code 8536) of Havells or equal approved in Standard/C&S
Spray painting of transformer/stabilizer externally with synthetic enamel paint of grey colour after cleaning surface thoroughly with thinner and scrapper and preparing the surface to required standard including writing and marking MES No on the body of transformer complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repairs CTs for LT panel's amp metering unit of capacity 0 to 100 amp including testing complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repairs volt meter 0 to 500 volts digital type of suitable size for LT panel/voltage stabilizer complete in all respect including testing complete all as specified and directed by Engr-in-Charge.
M & L for existing feeder pillar box/LT panel, bus bar, hinge, handle, locking arrangement foundation, thimble, loose connection including welding to door, legs, back door, etc. complete all as specified.and directed by Engr - in- Charge
Supply and fixing in repairs Timelite distribution board 32 amps, 3 pole, 230 volts, analog timer switch for timely ON and OFF street/security lights including testing, complete all as specified and directed by Engr-in-Charge. Make :Cat Part No: TL032ABB0 (HSD Code 8537) of Indoasian or equavalent to Havells/Bajaj
SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder.
Note: (1) The repair has to carried out as and when required basis and accordingly site will be available in piecemeal wise and as directed by Enginer-in-Charge in the Air Force station area
asian traders
M/S ROMESH KUMAR SHAN
Mahajan Construction Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .