| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.1 CrAccepted-AOC PALIN KRA DAADI DISTRICT ARUNACHAL PRADESH 791118 | PALIN | KRA DAADI | ARUNACHAL PRADESH | 791118 | ₹36.1 Cr | L1 | Accepted-AOC Being lowest |
| 2 | L2₹36.7 CrRejected-Finance | ₹36.7 Cr | L2 | Rejected-Finance Not lowest |
| 3 | L3₹42.7 CrRejected-Finance GAMGU VILLAGE MEKA ROING LOWER DIBANG VALLEY ARUNACHAL PRADESH 792110 | ROING | LOWER DIBANG VALLEY | ARUNACHAL PRADESH | 792110 | ₹42.7 Cr | L3 | Rejected-Finance Not lowest |
| 4 | L4₹45.6 CrRejected-Finance HOUSE NO 59 ZOO NARENGI ROAD GEETANAGAR GUWAHATI 781021 ASSAM | KAMRUP METRO | ASSAM | 781021 | ₹45.6 Cr | L4 | Rejected-Finance Not lowest |
| 5 | L5₹53.1 CrRejected-Finance | ₹53.1 Cr | L5 | Rejected-Finance Not lowest |
| Sl No | Description | Qty | Unit | Som Projects Pvt Ltd L9 | HTE INFRA LLP L6 | ASHIS DHAWA L5 | SHIVAM TRANSCON PRIVATE LIMITED L4 | M/s Margo Enterprises L1 | MGD Enterprises L3 | M/S ALLIED CONSTRUCTION L8 | Brahmaputra Commerce and Trade L7 | T.Y Global Enterprise L2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| .00NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates. | ||||||||||||
| 1.00PHASE I & II | ||||||||||||
| 1.01 | Lumpsum price workedout by the tenderer for BUILDING & STRUCTURE WORKS as listed in Schedule ‘A’ Part-I(A) | 1 | Lump-sum | 39,44,62,217.97 ₹39.4 Cr | 33,71,00,000 ₹33.7 Cr | 31,80,00,000 ₹31.8 Cr | 23,30,40,000 ₹23.3 Cr | 24,00,00,000 ₹24 Cr | 21,53,82,083 ₹21.5 Cr | 41,12,00,000 ₹41.1 Cr | 35,62,57,755 ₹35.6 Cr | 24,60,00,000 ₹24.6 Cr |
| 1.02 | Lumpsum price workedout by the tenderer for CAST-IN-SITU PILE as listed in Schedule ‘A’ Part-I(B) | 1 | Lump-sum | 5,47,40,587.28 ₹5.5 Cr | 3,92,35,000 ₹3.9 Cr | 4,15,00,000 ₹4.2 Cr | 4,05,43,531 ₹4.1 Cr | 3,00,00,000 ₹3 Cr | 5,08,23,113.77 ₹5.1 Cr | 4,41,35,997 ₹4.4 Cr | 4,95,00,000 ₹5.0 Cr | 3,00,00,000 ₹3 Cr |
| 2.00 | Lumpsum price worked out by the bidder/ tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule 'A' Part-II. | 1 | Lump-sum | 33,70,081.32 ₹33.7 L | 28,92,720 ₹28.9 L | 40,00,000 ₹40 L | 39,04,345 ₹39.0 L | 32,00,000 ₹32 L | 49,55,441.06 ₹49.6 L | 28,91,691.6 ₹28.9 L | 36,50,000 ₹36.5 L | 32,00,000 ₹32 L |
| 3.00 | Lumpsum price worked out by the bidder/ tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-III. | 1 | Lump-sum | 42,40,405.68 ₹42.4 L | 33,50,580 ₹33.5 L | 18,00,000 ₹18 L | 18,41,375 ₹18.4 L | 15,00,000 ₹15 L | 18,18,067 ₹18.2 L | 32,63,197.1 ₹32.6 L | 21,00,000 ₹21 L | 15,00,000 ₹15 L |
| 4.00 | Lumpsum price worked out by the bidder/ tenderer for INTERNAL ELECTRIFICATION INCLUDING AVIATION LIGHT as listed in Schedule 'A' Part-IV. | 1 | Lump-sum | 92,12,562.41 ₹92.1 L | 66,11,300 ₹66.1 L | 74,50,000 ₹74.5 L | 69,19,383 ₹69.2 L | 56,50,000 ₹56.5 L | 75,58,770.3 ₹75.6 L | 70,06,971.2 ₹70.1 L | 19,50,000 ₹19.5 L | 56,50,000 ₹56.5 L |
| 5.00 | Lumpsum price worked out by the bidder/ tenderer for ROAD, PATH, CULVERT & HARDSTANDING as listed in Schedule 'A' Part-V. | 1 | Lump-sum | 3,49,76,844.47 ₹3.5 Cr | 2,56,23,000 ₹2.6 Cr | 1,50,00,000 ₹1.5 Cr | 1,79,68,234 ₹1.8 Cr | 1,50,00,000 ₹1.5 Cr | 1,07,70,368.91 ₹1.1 Cr | 2,35,13,348 ₹2.4 Cr | 2,50,00,000 ₹2.5 Cr | 1,50,00,000 ₹1.5 Cr |
| 6.00 | Lumpsum price worked out by the bidder/ tenderer for EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-VI. | 1 | Lump-sum | 4,78,945.16 ₹4.8 L | 3,59,100 ₹3.6 L | 2,30,000 ₹2.3 L | 2,18,025 ₹2.2 L | 1,78,000 ₹1.8 L | 2,45,900.28 ₹2.5 L | 4,00,174.3 ₹4.0 L | 3,50,000 ₹3.5 L | 1,78,000 ₹1.8 L |
| 7.00 | Lumpsum price worked out by the bidder/ tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-VII. | 1 | Lump-sum | 1,02,02,313.24 ₹1.0 Cr | 68,35,000 ₹68.3 L | 40,50,000 ₹40.5 L | 51,23,402 ₹51.2 L | 42,00,000 ₹42 L | 52,84,979.38 ₹52.8 L | 63,33,649.6 ₹63.3 L | 68,00,000 ₹68 L | 42,00,000 ₹42 L |
Updated dates
Tender Value
₹43.9 Cr
EMD Value
₹15 L
Closing Date
11 Dec 2025, 6:00 pmClosed
CE SHILLONG ZONE
CE SHILLONG ZONE SPREAD EAGLE FALLS, SHILLONG MEGHALAYA 793011
PROVISION OF MD ACCN AT GUWAHATI PH 1 OF TWO PHS UNDER GE GUWAHATI
2025_MES_729681_1
89815/GUA/E8
Open Tender
Civil Works
920 days
GUWAHATI
All AS PER NIT AND TENDER DOCUMENT
2 documents required · 2 mandatory
₹3,000
GE GUWAHATI
₹15 L
Yes
11 Mar 2026
6 Sept 2025
13 Dec 2025
6 Sept 2025
11 Dec 2025
29 Nov 2025
Amount
NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
PHASE I & II
Lumpsum price workedout by the tenderer for BUILDING & STRUCTURE WORKS as listed in Schedule ‘A’ Part-I(A)
Lumpsum price workedout by the tenderer for CAST-IN-SITU PILE as listed in Schedule ‘A’ Part-I(B)
Lumpsum price worked out by the bidder/ tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule 'A' Part-II.
Lumpsum price worked out by the bidder/ tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-III.
Lumpsum price worked out by the bidder/ tenderer for INTERNAL ELECTRIFICATION INCLUDING AVIATION LIGHT as listed in Schedule 'A' Part-IV.
Lumpsum price worked out by the bidder/ tenderer for ROAD, PATH, CULVERT & HARDSTANDING as listed in Schedule 'A' Part-V.
Lumpsum price worked out by the bidder/ tenderer for EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-VI.
Lumpsum price worked out by the bidder/ tenderer for EXTERNAL ELECTRIFICATION as listed in Schedule 'A' Part-VII.
Lumpsum price worked out by the bidder/ tenderer for SEWAGE DISPOSAL as listed in Schedule 'A' Part-VIII.
Lumpsum price worked out by the bidder/ tenderer for AREA DRAINAGE as listed in Schedule 'A' Part-IX.
Lumpsum price worked out by the bidder/ tenderer for COMPOUND WALL/ FENCING & GATE as listed in Schedule 'A' Part-X.
Lumpsum price worked out by the bidder/ tenderer for FIRE FIGHTING SYSTEM as listed in Schedule 'A' Part-XI.
Sch 'A' Sec-XII (Miscellaneous Items) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
Rough excavation and bringing approved earth (as approved by Garrison Engineer) from sources outside defence land including cost or royality if any, transportation, taxes etc. Note: . (i) Earth required for the item, shall be supplied by contractor, from out side MOD land at his own arrangment. (ii) All cost of procurement of earth including cost of transportation, roualties, taxes etc. shall be deemed to be included in the unit rate quoted by the contractor. (iii) With referance to clause 3.6 of MES schdule Part-II on serial page No 18 it is clarified that measurement of the above item shall be of finalised embankment/traverse of filled earth after consolidation and 10% deduction shall be made from measured and calculated volume to allow for increase in bulk.
S&F pulley operated clothes drying system of 9 ft length consisting of anodised aluminium pipes, each of outer dia 22mm and inner dia 19.8mm Pulley made up of detrin with rope gude mounted on channel pair of length 24" (distance between two pipes is adjustable) Locking system to hide rope knot Channel to be mounted or fixed with self -tapping screws provided in kit Rope will be polyester braided of 4mm dia fixed to ceiling complete all as specified and directed.
S&F pulley operated clothes drying system of 6 ft length consisting of anodised aluminium pipes, each of outer dia 22mm and inner dia 19.8mm Pulley made up of detrin with rope gude mounted on channel pair of length 24" (distance between two pipes is adjustable) Locking system to hide rope knot Channel to be mounted or fixed with self -tapping screws provided in kit Rope will be polyester braided of 4mm dia fixed to ceiling complete all as specified and directed.
Supply, Installation, testing & comissioning of intregral LED 4ft luminaire of CRCA housing and PC diffuser (Diffuser-Non yellowing type). The luminaire should have a 18Watt LED with colour consistency SDCM< 5,CRI> 80 and colour temperature - 4000 to 6500K, Luminaire shall be designed to emit at least 2000 nominal lumens at a system efficacy of at-least 120 lumen/watt, power consumption should not be more than 20W (+5%). the life of fixture (including Driver): 50000 burning Hrs.@ L70B50 Lumen maintenance @ design ambient temp 50 deg C. The electronic driver used shall have a power factor >0.95 and THD < 10% suitable for an operating voltage range of 150-270V AC current Ripple<5% internal surge protection should be minimum 2.5KV, electrical insulation class should be Class I &driver should be of class B serviceablility. The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have in house NABL accredited lab conduct LM79, type test as per IS10322 & "FAT" before dispatch as per IS 10322. The contractor must submit the NABL accredition certificate for luminaire manufacturer along along with technical bid. the LED Luminaire & It's driver both should be BIS registered contractor shall submit the following reports before supply of material for approvals LM79 issued by NABL accrediated lab, LM80 issued by LED manufacturer type test certificate for luminaire as issued by NABL accrediate lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver complete all as specified and directed.
S&F Integral / batten LED 2ft, 10 watt 220 V, luminaire made of CRCA housing and PC diffuser (Diffuser-Non yellowing type). The luminaire should have a LEDs with colour consistency SDCM ≤ 5, CRI ≥ 80 and CCT of 6500K. Luminaire shall be designed to emit at least minimum 2000 system lumens at a system efficacy of at-least 120 lumen/watt. Power consumption should not be more than 10W (± 5%). The Life of fixture (Including Driver):50000 burning Hrs. @ L70B50 Lumen maintenance @ design ambient temp 45 deg C. The electronic driver used shall have a power factor 0.95 and THD ≤10%, suitable for an operating voltage range of 140-270V AC, Current Ripple ≤ 5%, Internal surge protection should be minimum 4KV, electrical insulation class should be Class I & driver should be of Class B serviceability. The luminaire shall be IP20 & IK02 compliant. The minimum dimensions (± 5mm) of the batten shall be 63mm(±5mm) X 63mm (±5mm)X 610mm(±5mm). The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & "FAT" before dispatch as per IS 10322. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer along with Technical bid. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 issued by NABL accrediated lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accrediate lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver complete all as specified and directed.
S&F LED type wall mounted light fitting sutable for LED lamp 9-20 W , housing- glass, frosted type, metallic frame and including one LED lamp 12 watt complete all as specified and directed.
S & F Bldg security light fittings high-quality group control enabled integrated LED Building security Light with a minimum system lumen of 3000 lm and system wattage not exceeding 25W with a nominal system efficacy of 110 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 75K hours@L70. The product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The LED used in the luminaire shall be SMD type only & shall be from either Lumileds, Osram, Nichia, Cree & APT Electronics make or equivalent. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2.
12.007 Continued..... The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & "FAT" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with sample approval. The LED Luminaire & it's driver both should be BIS registered. contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver and including 1.2m long 32mm dia GI pipe light grade bend to shape and fixed using two nos clamps fabricated using MS Flat iron 40x5mm including necessary nut bolts and washers and making electrical connection using 1.5sqmm, 3 core multi-stranded copper conductor PVC insulated and over all PVC sheathed cable form light fitting complete all as specified and directed
S&F wall mounted type fans of 200 mm sweep, 03 blades aerodynamically balanced with 60 degree oscillation, working Voltage range 230 V, with service value not less than 1.2 BEE 5 star rated with brush less direct current motor(BLDC), the super efficient BLDC motor 50Hz and Noise level not more than 64 dB with 2 years warranty complete all as specified and directed.
S&F Modular blanking plate modular type suitable for fixing in modular switch board, complete all as specified and directed.
S&F power unit suitable for upto 2.0 ton Air Conditioner having push ON-OFF push button switch, motor starter type, single phase, 4 module with and including mudular metal flush box with cover plates complete all as specified and directed. (For AC)
S&F modular socket 2 module, 25 Amps , including mudular switch 20 Amps/25 Amps one way , 1 module with and including three module metal flush box with cover plates and the socket shall be housed in metallic enclosure with locking arrangement flushed in wall complete all as specified and directed. (For Car Charging)
S&F modular type telephone socket. RJ11, 1 module complete all as specified and directed.
S&F modular type TV socket. RJ46, 1 module complete all as specified and directed.
S&F Surge Protection Device (SPD) Single Phase and neutral, T2 -limb, Imax 20 KA per pole complete fixed in distribution board and making connections complete all as specified and directed
Supply , installation, testing and comission of Smart energy prepaid Meter confirming to IS-16444: 2015 (Reaffirmed 2020) and as ammended time to time, AC whole current, three phase, 4 wires Smart Energy Meter of rating 415 Volt, 10-100 Amps,50 Hz , Class 1, enclosed in polycarbonate box complete as specified in CEA notification. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I. The slection of communication technology should be as per the site conditions and as per design consideration of AMI Implementing agency to meet the performance. The smart meters should be based on RF Mesh communication technology or Cellular communication technology and carry min 5 yrs warranty.
S&F Surge Protection Device (SPD) 4 module, 25 KA, 3Ph+N Right, T1+T2, limp 8 KA per pole, T2-60KA, complete fixed in Essential DB and making connections by using necessary thimble/washersetc of copper/brass material complete all as specified and directed.
S&F digital time switch 2 module, with Astronomical Function for swtching ON/OFF lights according to sun rising/ sun setting, with combination function for creating switching programs in which the devices are switched according to astronomical time and/ or fixed preset times, having daily astronomical calculation of the sunrise/sunset times based on the entered location or location coordinates complete having 2 output 16 AMps, 250 volts, 50 HZ, Astronomical function 2x28 programs 2 channel, suitable for din rail mounting in essential DB complete all as specified and direcetd.
Supply, laying & testing PVC insulated, PVC sheathed cable FRLS with stranded copper conductor of size 1.5 Sqmm, 2 Core, 1100 Volts grade complete all as specified and directed.
M&L for PCC (1:3:6) type C-2 using 40 mm graded crushed stone aggregate as in concrete bed to hume pipes including packing under and haunching against the sides of pipes after they are laid and tested complete all as specified and directed.
M&L for CI/DI pipe fittings Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs complete all as specified and directed
Supply, laying and jointing of ductile iron pipes of 150mm bore with spigot and socket ends conforming to IS 8329 : 2000, suitable for push on rubber joint centrifugally cast, class (K-9), inner side cement lining and outer side black bitumen coating and any length, laid in trenches or fixed in floors or on walls including push on rubber (EPDM) ring with ISI marked complete all as specified and directed.
S&F Cast iron sluice valves of size 150 mm dia (6") class PN 1.6 ISI mark with stainless steel spindle heavy duty conforming to IS 14846 (2000) both end flanged drilled with cast iron wheel at top including nut and bolts washers and rubber gasket complete all as specified and directed.
S&F cast iron sluice valves of size 100 mm dia (4") class PN 1.6 ISI mark with stainless steel spindle heavy duty conforming to IS 14846 (2000) both end flanged drilled with cast iron wheel at top including nut and bolts washers and rubber gasket complete all as specified and directed.
S&F Non Return Valve, reflux, with by-pass arrangement, 100 mm (4”) dia, 1.6 PN, both end flanged drilled including nut and bolts washers and rubber gasket complete all as specified and directed.
Supply, installation testing and commisioning open well horizontal type submersible pumpset, electric driven motor 3 Phase, insulation class B, voltage range AC 350 to 440 Volt, flater efficiency curve, 50Hz, CED coating, head 50 mtr, discharge 300 LPM, suction and delivery dia as per standard design of OEM suitable for delivery 300 LPM discharge at delivery pipe inclusive of suitable length (from submersible motor to starter) submersible cable PVC insulated and sheathed flat submersible cable with stranded copper conductor of size 3 core 6 Sqmm 1100 Volts grade including lugs and fixed in submsersible pump & starter etc complete all as specified & directed. (1 W + 1 SB) complete all as specified and directed.
Supply, installation testing and commisioning open well horizontal type submersible pumpset, electric driven motor 3 Phase, insulation class B, voltage range AC 350 to 440 Volt, flater efficiency curve, 50Hz, CED coating, head 50 mtr, discharge 150 LPM, suction and delivery dia as per standard design of OEM suitable for delivery 150 LPM discharge at delivery pipe inclusive of suitable length (from submersible motor to starter) submersible cable PVC insulated and sheathed flat submersible cable with stranded copper conductor of size 3 core 6 Sqmm 1100 Volts grade including lugs and fixed in submsersible pump & starter etc complete all as specified & directed. (1 W + 1 SB) complete all as specified and directed.
S&F SCADA ready actuated electric butterfly valve for 80 NB size water supply systems, with open area installation line pressure maximum-7 Bars, Ends-wafer, Duty -on/off, 230 V AC/24 V DC, IP 67, enclusore, insulation class F, complete with travel switch and torque switch of size 100 NB (may reduce as per site). The specified butterfly valve shall be equipped with QR codes designed for geo-tagging purposes. These QR codes shall integrate with an asset management system, allowing for efficient tracking and management of the level sensor. By scanning the QR code, userrs should be able to access derailed information about the asset's location, usage history, maintenance schedules, and performance data . This system shall enhance the visibility and control over the assets, ensuring the are effectively monitored and maintined. Geo-tagging via QR codes should provide a streamlined solution for asset tracking, improving operational efficiency and reucing the risk of asset loss or mismangement complete all as specified and directed..
Supply, Installation, Testing & Commissioning of Magnetic Float Operated Switch (FPS) high, low or intermediate point level switching and ideal for over head tanks with inaccessible tops or bottoms complete with following Specifications :- Installation : Normally slide / Top for special applications Enclosure X Cable entry : Cast AI IP66 x PG 11 Gland MOC : SS316 Float Dia x Min SG : Ø50/Ø60 x SS (≥0.7 SG) Process Connection : Flanged or srewed Magnetic Switch Assembly : Micro switch in hermetically sealed casing (SPDT) 5A, 250VAC / 24 VDC Switching Differential : Fixed : 15 ± 5 mm Adjustable : between 40 & 300 mm depending upon float, trim length & cam positioning for SS MOC Repeatability / Accuracy : ± 1 mm / ± 2 mm Load / Insulation : Resistive / 150 M Ohm at 500 VDC (Min) Temperature Range : Standard Finish : Regular
Supply, Installation Testing & Commissioning of Indoor type PLC (Programmable Logic Controller) /RTU (Remote terminal Unit) based Automation, Protection Panel for Pumps & Valve operation, energy monitoring, with feature of wireless Dual SIM Card based communication, suitable for control and monitoring, 2 Nos. Open Well Submersible Pump, 1 Nos. Energy Meters, 1 Nos. Motorized Butterfly Valves, 2 Nos Float Switch, 1 Nos. pressure transmitters, 01 Nos. electromagnetic Flow Meters. The panel should be of adequate size, double door, front opening type, fabricated from 2.00 mm thick CRCA Sheet & mounting channel 40x40x5mm made out of Angle iron with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size. The Panel should have the following functionalities complete all as specified and directed:- (a) Blank (b) Automatic Pump On/Off (c) Automatic Operation of Motor Actuated Butterfly Valves & level control of OH tank (d) Automatic Toggling of Pumps (e) Auto Change Over in Case of Pump Failure (e1) Remote monitoring & Operation of Pump & Water levels in UG Sump & OH service tank (e2) Pressure Gauges / Transmitters shall be installed at Delivery Header (f) Single Phasing Prevention, phase sequence corrector (g) Isolation transformer with regulated output voltage of 230V ± 5%. (h) Manual / auto Mode Operation (all connected sub systems at filtration plant) from the RTU/ PLC based Control Panel.
Sr. Item No. 12.034 Contd/… (j) Additionally the panel should have following specifications:- (i). Discrete Input Logic: - Sink/Source, Discrete Output Logic: - Positive Logic(Source). (ii). Should have suitable No. of Discrete Input conforming to IEC 61131-2 Type - 1 & Discrete Output: - Relay/Transistor (iii). Protocol supported : isolated serial link: Modbus master/slave and DNP 3.0 (iv). Standard supported :- ANSI/ISA 12-12-01, CSA C22.2 No 142, CSA C22.2 No 213, EN/IEC 61131-2:2007 (v) Web Services: - Integrated Web Server (vi) Should have 02 Nos. isolated RS 485 communication port, 1 Nos. Ethernet communication port with 10BASE-T/ 100BASE-TX. Should be able to latch with minimum number of Slave: - 64 Modbus TCP, & adequate DNP3.0 master/ slaves. (vii) RTU/ PLC shall be based on ARM based Controller with at least 600GHz clock frequency and 512MB RAM (viii) PLC/RTU shall be certified by NABL for electromagnetic compactability and radio distrubance standards as per CISPR22, IEC 61000-4-2:2008, IEC61000-4-3:2010, capable of sending data to multiple route and on precise location.
Supply, Installation Testing & Commissioning of Indoor type PLC (Programmable Logic Controller) /RTU (Remote terminal Unit) based Automation, Protection Panel for Pumps & Valve operation, energy monitoring, with feature of wireless Dual SIM Card based communication, suitable for control and monitoring, 2 Nos. Open Well Submersible Pump, 1 Nos. Energy Meters, 1 Nos. Motorized Butterfly Valves, 3 Nos Float Switch, 1 Nos. pressure transmitters, 01 Nos. electromagnetic Flow Meters. The panel should be of adequate size, double door, front opening type, fabricated from 2.00 mm thick CRCA Sheet & mounting channel 40x40x5mm made out of Angle iron with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size. The Panel should have the following functionalities complete all as specified and directed:- (a) Blank (b) Automatic Pump On/Off (c) Automatic Operation of Motor Actuated Butterfly Valves & level control of OH tank (d) Automatic Toggling of Pumps (e) Auto Change Over in Case of Pump Failure (e1) Remote monitoring & Operation of Pump & Water levels in UG Sump & OH service tank (e2) Pressure Gauges / Transmitters shall be installed at Delivery Header (f) Single Phasing Prevention, phase sequence corrector (g) Isolation transformer with regulated output voltage of 230V ± 5%. (h) Manual / auto Mode Operation (all connected sub systems at filtration plant) from the RTU/ PLC based Control Panel.
Supply, Installation, Testing and Commissioning of pressure transmiters in the water supply lines. The Pressure Transmiter needs to be with proper wiring including necessary with following specification all as specified and directed.:- Pressure Range: 0 bar to 16 bar Enclosure : Weather proof IP 65 Ambient temperature : -40 TO 70 Deg C Accuracy : 0.5 % Must have RS485 Modbus enabled communication
M&L for construction of valve chamber of size 950mm X 950mm X 950mm (Internal dimensions) including necessary earth work in any type of soil, PCC 1:3:6 type C-2, (using 40mm graded crushed aggregate) as in base concrete, brick work (one and half brick thick) in CM 1:6 with 20 mm thick cement plaster internally and externally (15cm depth below GL) in two layers of (12 mm and 8 mm) in cement mortar 1:4, 3 mm thick mild steel sheet cover and 50 mmx 50 mm x 6mm thick mild steel angle iron frame including locking arrangement, handle etc, frame welded to base plate of size 150 mm X 12 mm thick (All structural steel are grade E-165 and conforming to IS 15911: 2010), base plate fixed with all fixing arrangement in 200 mm thick PCC coping 1:2:4 type B1 (using 20mm graded crushed aggregate) including painting exposed steel surfaces with two coats of bituminous paint and embedded surfaces of steel with two coats of tar, finishing exposed faces of concrete surfaces and plaster surfaces with three coats of white wash as per drawing No. TD/EM/6 sheet Nos 1/2 & 2/2 of HQ CE Shillong Zone complete all as specified and directed.
Supply, Installation, testing and commissioning of Package type/ unitised 11KV/433V Outdoor Sub-station, 500 KVA made from GI enclosure complete as required confirming to IEC 62271-202 only and relevant IS specifications including K-10 temperature class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 PCC foundation of suitable size extending 500mm all around the outdoor enclosure and 1000mm height (above the ground level ) complete with suitable sizes of GI pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40X40X5 mm MS all along with the corner of the foundation od CSS shall be from OEMs only. Licensed System Integrators of approved OEM are not allowed to supply complete all as specified and directed.
Sr. Item No. 12.042 Contd/.... Package Substaion will have the following euipment :- HT Swichgear :- 11 KV 630 Amps 21 KA / 3Sec Non Extensible Ring Main Unit Compact Switchgear consisting of direct cable module & 1 No motorized Circuit Breakers Module in SF6 insulated stainless enclosure with sries trips, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall perferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through IC x 95 sq. mm Aluminium XLPE cable - 1 No. Vacuum Interrepter & RMU shall be of same make to ensure life cycle optimization. Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along wtih series trip coil (Modbus RS485 complaint. Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. SF6 Gas pressure indicator. Operating sequence of VCB must be O-0.3sec-CO-3 Mins CO - Protection CT shall be minimum 40/1A, 2.5VA, 5P10 - 3 nos. All modules of the RMU shall be suitable for cable termination of 3C x 95 Sq.mm AI XLPE Cable, incoming cable termination is included within the scope of work - 1 set. TRANSFORMER: - 11/0.433KV, 500KVA, 50Hz, Off load Tap Changer switch, Three Phase, natural transformer oil type transformer in corrugated tank i) Standard IS : IS : 2026 and IS 1180 with latest amendments (2021) ii) Losses as per 1180 level 2 and Temperature rise shall be as per IS 1180 with latest amendments iii) Outdoor Installation iv) Vector group : Dyn 11
Sr. Item No. 12.042 Contd/.... v) Rating 500 KVA vi) Cooling System : KNAN (K for transformer oil) vii) Winding ; Copper viii) Magnetic Core : Prime grade of M4 or better ix) High voltage : 11 KV - 50 Hz x) Low Voltage : 433 V - 50Hz xi) System highest Voltage : 12 KV at the HV side xii) Percentage Impendance Value : As per IS 1180 xiii) Manufacturing testing labotatory to be NABL certified with in house core cutting facility for proper control & monotoring of quality & to avoid mixing of prime core with second grade / defective core materials xiv) Insulation Level : HV Power Frequency (KV rms) : 28 KV HV, Impulse withstand voltage (KV peak) : 75 kVp xv) Tapping : +5% to -15% OLTC @ 2.5% xvi) HT Termination - Cable Box xvii) LT termination - cable box and with all accessories i.e. first filling of filtered dehydrated oil and confirming to ID & standard accessories required. LT PANEL LVS PANEL 1000 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminium as 1 A./sq.mm; LT panel made up of 1.5/2 mm thick CRCA sheet.
Sr. Item No. 12.042 Contd/.... (iv) The Capacitor bank shall be internet of things (IoT) enabled and communicable / intergrable with EMS. The APFC panel should have the capability for environmental monitoring where it is able to provide the real time data for the temperature and humidity inside the panel ambient. The environmental sensors shall be used with a access point, which can be used for multiple sensors, using Green Power wireless communication protocol to transfer the information on real time basis the exact and detailed temperature monitoring.All Civil works such as PCC/RCC foundation, Platform, Filling trench and pedestal etc as per CSS manufacturer's recommendation are included in scope of work. OUTDOOR ENCLOSURE Outdoor type enclosure of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable designed for better heat dissipation and providing robust construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitably handling any arcing inside the compartment illumination lamp with door operated switch shall be provided for each compartment.
Supply, Installation, testing and commissioning of Package type/ unitised 11KV/433V Outdoor Sub-station, 160 KVA made from GI enclosure complete as required confirming to IEC 62271-202 only and relevant IS specifications including K-10 temperature class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 PCC foundation of suitable size extending 500mm all around the outdoor enclosure and 1000mm height (above the ground level ) complete with suitable sizes of GI pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40X40X5 mm MS all along with the corner of the foundation od CSS shall be from OEMs only. Licensed System Integrators of approved OEM are not allowed to supply complete all as specified and directed.
Sr. Item No. 12.043 Contd/.... Package Substaion will have the following euipment :- HT Swichgear :- 11 KV 630 Amps 21 KA / 3Sec Non Extensible Ring Main Unit Compact Switchgear consisting of direct cable module & 1 No motorized Circuit Breakers Module in SF6 insulated stainless enclosure with sries trips, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall perferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through IC x 95 sq. mm Aluminium XLPE cable - 1 No. Vacuum Interrepter & RMU shall be of same make to ensure life cycle optimization. Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along wtih series trip coil (Modbus RS485 complaint. Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. SF6 Gas pressure indicator. Operating sequence of VCB must be O-0.3sec-CO-3 Mins CO - Protection CT shall be minimum 40/1A, 2.5VA, 5P10 - 3 nos. All modules of the RMU shall be suitable for cable termination of 3C x 95 Sq.mm AI XLPE Cable, incoming cable termination is included within the scope of work - 1 set. TRANSFORMER: - 11/0.433KV, 160KVA, 50Hz, Off load Tap Changer switch, Three Phase, natural transformer oil type transformer in corrugated tank i) Standard IS : IS : 2026 and IS 1180 with latest amendments (2021) ii) Losses as per 1180 level 2 and Temperature rise shall be as per IS 1180 with latest amendments iii) Outdoor Installation iv) Vector group : Dyn 11
Sr. Item No. 12.043 Contd/.... v) Rating 160 KVA vi) Cooling System : ONAN (Natural transformer oil) vii) Winding ; Copper viii) Magnetic Core : Prime grade of M4 or better ix) High voltage : 11 KV - 50 Hz x) Low Voltage : 433 V - 50Hz xi) System highest Voltage : 12 KV at the HV side xii) Percentage Impendance Value : As per IS 1180 xiii) Manufacturing testing labotatory to be NABL certified with in house core cutting facility for proper control & monotoring of quality & to avoid mixing of prime core with second grade / defective core materials xiv) Insulation Level : HV Power Frequency (KV rms) : 28 KV HV, Impulse withstand voltage (KV peak) : 75 kVp xv) Tapping : +5% to -15% OLTC @ 2.5% xvi) HT Termination - Cable Box xvii) LT termination - cable box and with all accessories i.e. first filling of filtered dehydrated oil and confirming to ID & standard accessories required. LT PANEL LVS PANEL 400 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminium as 1 A./sq.mm; LT panel made up of 1.5/2 mm thick CRCA sheet.
Sr. Item No. 12.043 Contd/.... (iv) The Capacitor bank shall be internet of things (IoT) enabled and communicable / intergrable with EMS. The APFC panel should have the capability for environmental monitoring where it is able to provide the real time data for the temperature and humidity inside the panel ambient. The environmental sensors shall be used with a access point, which can be used for multiple sensors, using Green Power wireless communication protocol to transfer the information on real time basis the exact and detailed temperature monitoring.All Civil works such as PCC/RCC foundation, Platform, Filling trench and pedestal etc as per CSS manufacturer's recommendation are included in scope of work. OUTDOOR ENCLOSURE Outdoor type enclosure of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable designed for better heat dissipation and providing robust construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitably handling any arcing inside the compartment illumination lamp with door operated switch shall be provided for each compartment.
S&F HT 11 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting,Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating complete with drop out fuse having 12 insulators of rating upto 200 Amps complete all as specified and as directed
Supply, install, test and commissioning of LT FEEDER PANEL, TPN 415 Volts, 50 Hz, out door cubical type floor mounted CPRI approved factory made, double door dust and vermin proof IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50x50x6 mm with cable chamber for individual feeders for incomming and outgoing connections, one set of LED indicator lamp RYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley aluminium bus bar suitable for carrying of current 200 Amps with suitable connections from MCCB out going to main bus bar shall be carried out with TPN aluminium bus bars of suitable rating and connections from main bus bar to out going MCCB's (intake point) will be carried out with TPN aluminium bus bar as per MCCB rating duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.35 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :- (for 50 KVA DG Set Standby Supply) Incoming: a) MCCB 4 Pole, 415 Volt, 50 Hz with Microprocessor release 100 Amp with breaking capacity 16 KA - 01 No. Outgoing: b) MCCB AC 3 Phase 415 V, 50Hz, 4 pole 40 A capacity 16kA with adjustable type thermal and magnetic setting release - 03 Nos. (One for each Bldg (Two Bldg) & one Spare) c) MCCB AC 3 Phase 415 V, 50Hz, 4 pole 32 A capacity 16kA with adjustable type thermal and magnetic setting release - 03 No. (one for Pump -01, Street Light-01 & Spare) d) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breaker”
Supply, install, test and commissioning of LT FEEDER PANEL, TPN 415 Volts, 50 Hz, out door cubical type floor mounted CPRI approved factory made, double door dust and vermin proof IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50x50x6 mm with cable chamber for individual feeders for incomming and outgoing connections, one set of LED indicator lamp RYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley aluminium bus bar suitable for carrying of current 200 Amps with suitable connections from MCCB out going to main bus bar shall be carried out with TPN aluminium bus bars of suitable rating and connections from main bus bar to out going MCCB's (intake point) will be carried out with TPN aluminium bus bar as per MCCB rating duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.35 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :- (for 30 KVA DG Set Standby Supply) Incoming: a) MCCB 4 Pole, 415 Volt, 50 Hz with Microprocessor release 63 Amp with breaking capacity 16 KA - 01 No. Outgoing: b) MCCB AC 3 Phase 415 V, 50Hz, 4 pole 40 A capacity 16kA with adjustable type thermal and magnetic setting release - 02 Nos. (One for Bldg & one Spare) c) MCCB AC 3 Phase 415 V, 50Hz, 4 pole 32 A capacity 16kA with adjustable type thermal and magnetic setting release - 03 No. (one for Pump -01, Street Light-01 & Spare) d) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breaker”
Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 400 Amps capacity Aluminium bus bar for phase and 400 Amps Aluminium bus bar capacity for neutral, colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, provision of connecting earth strip from 2 sides, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:- (for Residential Load) Incoming: a) MCCB 4 Pole, 415 Volt, 50 Hz with Microprocessor release 400 Amp with breaking capacity 36 KA - 01 No. Outgoing: b) 600 Amps capacity Aluminium bus bar for phase and 600 Amps Aluminium bus bar capacity for neutral, colour coded for each phase and neutral, insulated on epoxy type insulators d) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breaker
Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 400 Amps capacity Aluminium bus bar for phase and 400 Amps Aluminium bus bar capacity for neutral, colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, provision of connecting earth strip from 2 sides, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:- (for Residential Load) Incoming: a) MCCB 4 Pole, 415 Volt, 50 Hz with Microprocessor release 200 Amp with breaking capacity 36 KA - 01 No. Outgoing: b) 300 Amps capacity Aluminium bus bar for phase and 300 Amps Aluminium bus bar capacity for neutral, colour coded for each phase and neutral, insulated on epoxy type insulators d) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breaker
S&F cable PVC insulated industrial flexible FRLS 1100 volt grade with stranded copper conductor of size 1.5 sqmm 3 core in and including suitable PVC comduit complete all as specified and directed
M&L for Loop in Loop out box of FRP made with IP65 Protection of thermalplastic breaker box with metric knock out for cable entry & exist , combi clamate cable lagands IP 66/67 for cable enrty and grommets IP 65 for conduit for cable exist with MCB 6 Amp SP 10KA C curve terminal as PVC connector heavy duty 32 Amp 4 Way for cable with necessary fixing arrangement and cable lagand etc all as specified and directed
S&F LED street light fitting of high-quality group control enabled integrated LED Street Light with a minimum system lumen of min 6300 lm and system wattage not less than 45W with a nominal system efficacy of 140 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 50K hours@L70B50. The product should be designed for continuous operation (10-12 Hrs. per day).
12.051 Continued..... The Ingress protection should be minimum IP66 & impact resistance shall be IK10. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2. The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & "FAT" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with Sample Approval. The LED Luminaire & it's driver both should be BIS registered. The contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver complete including with necessary brackets / pipes clamps & nuts & bolts for holding the street light fitting and three core copper flexible cable of 1.5 Sqmm as required at site.
Supply, install, test and commissioning of Street Light Panel of 6 KW capacity , TPN 415 Volts, 50 Hz, out door cubical type floor mounted, factory made, double door dust and vermin proof IP-54 protection, fabricated out of CRCA sheet duly powder coated fixed on angle iron pedestal made out of 40x40x6 mm with cable chamber for individual feeders for incomming and outgoing connections, including necessary PCC foundation of minimum 0.35 m height positioned and fixed with suitable nut, bolts, washers etc to the street light panel complete all as specified and directed comprising of the following :- (a) Range : 6 KW (b) Conforms to IS /IEC 60947-4-1 (c) Provided with Protection Degree IP-54 (d) Extended wide band coil (e) FRLS internal wiring (f) In-built Short-circuit Protection (g) Class H Insulation (h) Contractor Rating - 32 A TP (j) MCB Rating - 40 A TPN (k) Time Switch - Astronomical
M&L for RCC septic tank conventional type for 150 users design to carry sewage and sludge water constructed with RCC M-30 (Design Mix) including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/STD-02 sheet 1/2 & 2/2 and complete all as specified and directed.
M&L for soakage well of size 2.4 m dia and 4.5 m effective depth including Brick masonary intercepting chamber and screen chamber, including excavation in soft disintegrated rock earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
M&L for Construction of Steel gate 5.50m wide & 1.4m height with RCC pillar including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2017/TD-034, sheet 1/3 & 3/3 complete all as specified and directed.
M&L for Construction of Steel gate 5.50m wide & 2.1m height with RCC pillar including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2017/TD-034, sheet 1/3 & 3/3 complete all as specified and directed.
S&F Pressure Gauge suitable for 0-14 kg pressure range with 4" dial, die cast aluminium body with white background & black marking, 1/2" Male NPT threaded connection, suitable to work in service temp. of -20 °C to 80 °C having accuracy of ± 1 % FSD assembled with ball valve, nipple, socket, etc. for pump suction & delivery lines of fire pump sets near the flow switches all complete as specified and directed.
M&L for XLPE insulated armoured cable conforming to IS 7098-1: 1988, having stranded aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984 of size 6 Sqmm , 3 core, 1.1 KV grade copper conductor, including necessary clamping / dressing with cable ties and termination complete all as specified and directed.
S&F PN 1.6 rated 100 mm NB Cast irom (CI) 'Y' type strainer for suction conforming to IS 907: 1984 with SS filter screen and flange drilling standard end connection conforming to IS 1538: 1993 and necessary accessories for suction side of fire pumps complete all as specified and directed.
Supply, installation, testing and commissioning of PN 1.6 rated 100 mm NB CI swing check type reflux (non return) valve, conforming to IS 5312-1: 2004 having cast iro body, cast iron bolted cover, nitrile rubber gasket, stainless steel hinge pin & body seat ring, renewable seat with premium quality rubber flap with flange drilling standard end connection conforming to IS 1538: 1993 and necessary accessories complete all as specified and directed.
S&F PN 1.6 rated air vent valve having brass body, cover, adopter, disc assembly & cap, stainless steel strainer, plastic float and 25 mm screwed threaded ends suitable for maximum operating temperature 100 °C installed on all high points in the water piping system to automatically remove the trapped air with necessary accessories all complete as specified and directed.
S&F indoor type wall-mounted lockable hose cabinet of size 600 mm (H) x 800 mm (L) x 250 mm (D) suitable to house 2 Nos. of 15 m RRL hose and 2 Nos. branch nozzles, made of 18 gauge MS sheet with double door & 3 mm thick glazed glass with water proof rubber beading, red out side and white inside with two coats of enamel paint over a coat of primer, having "HOSE CABINET NO." painted on the inner face of the glass in 50 mm size block letter, including the cost of break glass box containing the key of the cabinet complete all as specified and directed.
S&F swinging type 30 m long First Aid Hose Reel, conforming to IS:884-1969, having 19 mm NB thermoplastic reinforced hose reel tubing, conforming to IS 12585: 1988, 25 mm NB ball valve, stop cock, terminating with gunmetal coupling & nozzle of 6 mm NB outlet with shut-off valve, conforming to IS 8090: 1976 complete with MS socket for tap-off, red colour drum, brackets (including painting) for fixing on wall with anchor fastner, bolts, nuts, etc. complete all as specified and directed.
S&F fire hydrant single outlet oblique type landing valve, conforming to IS 5290: 1993, having 75 mm NB (3") flanged inlet as per ANSI / IS 1538 (Part IV), brass spindle controlled 63 mm NB female instantaneous outlet type, gunmetal body, cast iron hand wheel,working pressure of 10.5 kg/cm2, seat test presure of 16 kg/cm2, body test pressure of 30 kg/cm2 gunmetal coupling, ABS plastic blank cap, carbon steel chain, twist release type lug & all accessories including fixing and flanged tapping from stand post type fire hydrant complete all as specified and directed.
S&F non-percolating rubber reinforced lined RRL hose type- A 15 m long fire hose of 63 mm NB size, conforming to IS 636: 1988, rated for bursting pressure of 35.7 kg/cm² complete with gunmetal male & female coupling conforming to IS 903: 1993, bound and rivetted to the hose pipe with copper rivets and 1.5 mm² copper wire complete all as specified and directed.
S&F orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete all as specified and directed.
S&F CL#150 rated three-piece design 25 mm NB Cast Steel (CS) Straight pattern ball valve, conforming to IS 9890: 1981 and tested as per BS 6755-1, having Cast iron body, Stainless steel AISI 304 ball, renewable PTFE seat & gland packing, CS fastners & lever having screwed / socket weld end connection with accessories complete all as specified and directed.
S&F Air cushioning tank (Air vessel) 250mm dia x 1000mm high with dished top, made of minimum 6mm thick MS pipe /plate complete with 20mm dia. Brass air valve (ball type), 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete fixed on top of suitable flange hydrant line complete all as specified and directed.
S&F Electrically operated water pressure switch Universal type with necessary mounting/connection with control wiring with conductor and mechanical connection to operate at pressure range of 0 to 10 Kg/sqcm for automation all directed.
Supply, installation, testing and commissioning of FM approved and UL listed microprocessor- based, true peer-to-peer networkable, Single loop addressable Fire Alarm Control Panel (FCAP) with its own microcontroller memory, communication module, fire device loop interface cards for intelligent initiating and indicating devices and peer-to-peer networkable with other addressable fire alarm panels. conforming to UL 2572 mass notification systems & NFPA 72, with required accessories complete all as specified and directed. The FACP shall meet the following specifications / functional requirements. [i] The FACP shall have one isolated intelligent Signalling Line Circuits (SLCs) capable of connecting up to 99 detectors and 99 modules per SLC upto 200 detector and modules. [ii] The FACP shall have a degrade mode and the loops shall work in degrade mode in case of the CPU failure.
12.073 Continued... [iii] The FACP shall have 640 character LCD backlit display/ Touch Screen display, full QWETRY program keypad, LED indicators viz. power; fire alarm; supervisory; system trouble; other event; signals silenced; point disabled; CPU failure; controls active; etc. membrane switch controls viz. acknowledge; signal silence; drill; system reset; lamp test; etc [iv] The FACP shall have four access levels, flash EPROM, 240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition. [v] The FACP shall have manual sensitivity adjustment up to nine levels, built-in alarm; trouble; security and supervisory relays, history file with 4000-event capacity in non-volatile memory plus separate 1000-event alarm-only file, keypad operation, LCD unit to indicate fire / fault signal of individual unit, in built printer to log all incoming data, etc. [vi] The FACP shall have integrated 8 channel digital voice evacuation system controller capable of broadcasting evacuation messages on the same peer-to-peer network, fire fighter's telephone two-way communication system capable of supervising all the speaker circuits with adequate zone control and accessories etc. Note : [i] The FACP shall be servicable by any system integrator & shall not have dependency on specific system integrator. [ii] The FACP shall have feature to "ADD", "EDIT" & "DELETE" field devices like detectors & modules without dependency on PC / Software / Special tool / dongle.
Supply, installation, testing and commissioning of FM approved and UL listed surface / semi- flush mounted Dual Action Manual Pull Station "Push In & Pull Down" including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed.
Supply, installation, testing and commissioning of UL listed of Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, built-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete all as specified and directed.
Supply, installation, testing and commissioning of FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (e.g. Horns, Strobes, Horn Strobes, etc.) having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed.
M&L for low smoke zero halogen (LSZH) flame retardant fire alarm cable of size 1.5 sqmm 2core, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed.
M&L for low smoke zero halogen (LSZH) flame retardant fire alarm cable of size 2.5 sqmm 2core, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed.
Supply, installation, testing and commissioning of FM approved and UL listed (fire fighter's) addressable Telephone Jack mounted to a single-gang electrical back box with suitable interface module for two way communication with the Central Fire Fighter Telephone Console complete with accessories as specified and directed .
Supply, installation, testing and commissioning of FM approved and UL listed Fire Fighter's Telephone Handset for two way communication with the Central Fire Fighter Telephone Console complete with accessories as specified and directed.
S&F dry chemical powder (ABC) type fire extinguisher 6 kg capacity, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. (1 No. at entry/exit of each floor)
S&F 4.5 kg light-weight squeeze grip COշ type fire extinguisher, conforming to IS 15683: 2006, with COշ gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the Engineer-in-Charge. Note : [i] Operating pressure: 10 to 15 bars [ii] Operating temperature : -30 °C to + 55°C [iii] Performance criteria : Discharge time not less than 45 sec , throw not less than 4 meters [iv] Hydro test and burst pressure test : Shall pass hydro test pressure of 35 bars 2.5 minutes and with stand a burst pressure of 55 bar
S&F Galvanized mild steel Fire bucket (FILLED WITH DRY SAND) conforming to IS 2546: 1974 round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket complete as specified and directed.
S&F signages made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners Signage of size 300 mm X 100 mm reading 'EXIT' in 12.5 mm block letters in Green and white background, properly spaced to provide good legibility located directly in corridor near to each staircase and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level complete all as specified and directed.
S&F signages made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners Signage having size of 500 mm X 500 mm, indicating the "Floor Number" in bold type and at 75 mm high numerals in red and white background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board, posted and maintained within each stair enclosure on every floor, securely attached to the stair side of the door in a way that the bottom of the sign is not above 1.5 m from the finished floor level complete all as specified and directed.
S&F signages made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners Signage having size of 450 MM X 150 MM reading "FIRE EXTINGUISHER" in 12.5 mm block letters in White and Red background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board,properly spaced to provide good legibility located directly in corridor near to each Manual call point/Fire Extinguisher and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level complete all as specified and directed.
S&F signages made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners Signage having size of 150 mm X 600 mm, posted and maintained at each lift landing and on the side of the stairway door from which egress is to be made on every floor, indicating the "STAIRCASE" by an alphabetical letter in bold type and at 75 mm high letters in red and white background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board,securely attached to the side of the stairway door from which egress is to be made in a way that the bottom of the sign is not above 1.5 m from the finished floor level complete all as specified and directed.
Supply, installation, testing and commissioning of wall mounted 6 Watt type CD Speakers with 100V LMT & ABS complete all as specified and directed
Supply, installation, testing and commissioning of control consule all as specified and directed
S&F PVC insulated FRLS copper conductor cable of size 24/0.2 mm for Loudspeaker complete all as specified and direceted
Design, Supply, install, tesing and commissioning of eletrically operated machine room less (MRL) passenger lift of capacity 8 passenger lift (544 kgs Capacity) in the lift well, 1.5 m/s speed with automatic GIEN micro stroke button control, microprocessor based controller, simplex full collective control suitable for 3 phase, 50 HZ 415 volts AC supply independent operation with AC variable voltage variable frequency (AC VVVF) control closed loop with power saving regenerative drive with suitable motor and gear unit to serve ground plus six upper floors i.e with 7 stops and 7 landings with or with out attendent suitable for synchronised operation automatic power operated centre opening sliding stainless steel door with Moon Rock finish of 16 gauge (not less than 1.5 mm) with infra-red sensors all along the height for car door with automatic rescue/leveling device (ARD) (with + or -5 mm) with suitable dry maintenance free batteries, haul position digital indicators in car and all landing with call indicating lights etc including necessary joists and beams for mounting machine in the machine room including all civil works required in connection with erection of lifts complete all as specified. The lift shall be provided with and including the following : (Size of well available is 2100 mm x 1800 mm) Type of Drive: Regenerated AC variable voltage and variable frequency drive along with converter unit.The regenerated power shall be used to charge the battery of UPS, ARD and emergency lights. Type of Machine: Gearless permanent magnet and directly coupled to horizontal traction machine. Note 1: Counter weight shall be of cast iron block.
12.092 Continued... (a) Fire man switch. (b) Automatic rescue device (A.R.D) during power failure including manual operation provision with suitable capacity of battery designed for running the lift with full load. (c) Seperate Battery operated emergency light (LED ceiling fitting ), alarm (speaker for emrgency alarm system to be fixed) and stop buttion in car with rechargeable arrangement for battery. (This system shall be seperate from ARD batteries.) (d) Integrated Roof RL20 Stainless Steel Ring Lighting LED (e) One sleek circular PVC heavy duty fan in false ceiling. (f) Aluminium chequered plate (3mm thick) as flooring joint in chequered plate should not more than one and top covering with 20 mm Recess & Granite Stone. Car skirting material: Brushed stainless SUS304 (g) Non stop button /independent operation (h) Over load warning indicator both audio and visual type with tripping system having relays etc (overload protection/tripping system). (j) Front landing door of stainless steel moon rock finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. (k) Car size shall be in confirmity with IS -3534-1976 and body to be stainless steel of 16 gauge moon rock finish with stainless steel hand rail 38mm hairline finish (l) Limit switches as specified in IS (m) Mirror of 6mm thickness of suitable size. (n) Hand rail 38mm hairline finish. (o) Opening with see through glass of 8 mm thick 200 x 600 mm size in all the doors (Car/Landing doors) (p) Specification plate with complete details. (q) Continuous earthing for machine and equipments. (r) Steel Wire rope of adequate size as per relevent IS and as per manufacturer specification
12.092 Continued... (s) Other standard fixtures and fittings like guide rails, sheaves, counter weights with guards, buffers, gear unit brakes, control panel, locks, governor, car operational panel, power, control and trailing cables complete. (t) Car operating Panel 1 Full Height Dark grey brushed StSt Tempering glass Segmented LCD display Round flush mounted KDS96 – stylish touch panel Landing Signalization-Tempered glass Segmented LCD display Flush Mounted Tempered glass Round flush mounted KDS96- stylish touch panel (u) Main drives and control shall be of latest, high effective and low power consumption. (v) Suitable phase reversal relay shall be provided on the controller to protect lift/equipment against phase reversal, phase failure and low voltage. (w) Over load and floor announcement audio and visual arrangement. Features Common to Specifications 1. Digital Direction & Position Indicator in Car and at all landings 2. Emergency Alarm at the main landing 3. Facia Plate 4. 2 Phase Fireman Drive, Fireman’s switch at the main landing. (In case Fireman Drive is activated the elevator will come to the main landing and open the door). 5. Advanced door operation (Ensures smooth opening & closing of the doors at adjustable door speed) 6. Additional Pressure Sensing Device 7. Load Weighing Device (Audio visual over load indicator in the car for better safety) 8. Full Height Infra-Red Curtain 9. Pit Ladder 10. Emergency Light, Intercom and Alarm with Maintenance Free Rechargeable Battery operation.
12.092 Continued... 11. +6% To-10% Volt. Fluctuation Withstand Capacity 12. Over speed governor (Electro-mechanical device that prevents free fall in case the elevator is travelling at speed more than 10% of the rated speed in downward direction) 13. Automatic Rescue Device (To rescue the passengers in case of emergency- this device will bring the car to the nearest floor automatically and will open the doors). 14. Steel Ropes 15. Special Car Door Lock 16. Fire Rated Doors-2 hour. 17. Automatic Brake Testing. 18. PMS MOTOR with ECO Disk Drive 19. Linear Motor Technology & Close Loop Arrangement. 20. 24x7 Connected Services. 21. Car & Landing Doors –Moon rock finish
Design, Supply, install, tesing and commissioning of eletrically operated machine room less (MRL)passenger lift of capacity 13 passenger lift (884 kgs Capacity) in the lift well, 1.5 m/s speed with automatic GIEN micro stroke button control, microprocessor based controller, simplex full collective control suitable for 3 phase, 50 HZ 415 volts AC supply independent operation with AC variable voltage variable frequency (AC VVVF) control closed loop with power saving regenerative drive with suitable motor and gear unit to serve ground plus six upper floors i.e with 7 stops and 7 landings with or with out attendent suitable for synchronised operation automatic power operated centre opening sliding stainless steel door with Moon rock finish of 16 gauge (not less than 1.5 mm) with infra-red sensors all along the height for car door with automatic rescue/leveling device (ARD) (with + or -5 mm) with suitable dry maintenance free batteries,haul position digital indicators in car and all landing with call indicating lights etc including necessary joists and beams for mounting machine in the machine room including all civil works required in connection with erection of lifts complete all as specified. The lift shall be provided with and including the following : (Size of well available is 2100 mm x 1800 mm) Type of Drive: Regenerated AC variable voltage and variable frequency drive along with converter unit.The regenerated power shall be used to charge the battery of UPS, ARD and emergency lights. Type of Machine: Gearless permanent magnet and directly coupled to horizontal traction machine. Note 1: Counter weight shall be of cast iron block.
12.093 Continued... (a) Fire man switch. (b) Automatic rescue device (A.R.D) during power failure including manual operation provision with suitable capacity of battery designed for running the lift with full load. (c) Seperate Battery operated emergency light (LED ceiling fitting ), alarm (speaker for emrgency alarm system to be fixed) and stop buttion in car with rechargeable arrangement for battery. (This system shall be seperate from ARD batteries.) (d) Integrated Roof RL20 Stainless Steel Ring Lighting LED (e) One sleek circular PVC heavy duty fan in false ceiling. (f) Aluminium chequered plate (3mm thick) as flooring joint in chequered plate should not more than one and top covering with 20 mm Recess & Granite Stone. Car skirting material: Brushed stainless SUS304 (g) Non stop button /independent operation (h) Over load warning indicator both audio and visual type with tripping system having relays etc (overload protection/tripping system). (j) Front landing door of stainless steel moon rock finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. (k) Car size shall be in confirmity with IS -3534-1976 and body to be stainless steel of 16 gauge moon rock finish with stainless steel hand rail 38mm hairline finish (l) Limit switches as specified in IS (m) Mirror of 6mm thickness of suitable size. (n) Hand rail 38mm hairline finish. (o) Opening with see through glass of 8 mm thick 200 x 600 mm size in all the doors (Car/Landing doors) (p) Specification plate with complete details. (q) Continuous earthing for machine and equipments. (r) Steel Wire rope of adequate size as per relevent IS and as per manufacturer specification
12.093 Continued... (s) Other standard fixtures and fittings like guide rails, sheaves, counter weights with guards, buffers, gear unit brakes, control panel, locks, governor, car operational panel, power, control and trailing cables complete. (t) Car operating Panel 1 Full Height Dark grey brushed StSt Tempering glass Segmented LCD display Round flush mounted KDS96 – stylish touch panel Landing Signalization-Tempered glass Segmented LCD display Flush Mounted Tempered glass Round flush mounted KDS96- stylish touch panel (u) Main drives and control shall be of latest, high effective and low power consumption. (v) Suitable phase reversal relay shall be provided on the controller to protect lift/equipment against phase reversal, phase failure and low voltage. (w) Over load and floor announcement audio and visual arrangement. Features Common to Specifications 1. Digital Direction & Position Indicator in Car and at all landings 2. Emergency Alarm at the main landing 3. Facia Plate 4. 2 Phase Fireman Drive, Fireman’s switch at the main landing. (In case Fireman Drive is activated the elevator will come to the main landing and open the door). 5. Advanced door operation (Ensures smooth opening & closing of the doors at adjustable door speed) 6. Additional Pressure Sensing Device 7. Load Weighing Device (Audio visual over load indicator in the car for better safety) 8. Full Height Infra-Red Curtain 9. Pit Ladder 10. Emergency Light, Intercom and Alarm with Maintenance Free Rechargeable Battery operation.
12.093 Continued... 11. +6% To-10% Volt. Fluctuation Withstand Capacity 12. Over speed governor (Electro-mechanical device that prevents free fall in case the elevator is travelling at speed more than 10% of the rated speed in downward direction) 13. Automatic Rescue Device (To rescue the passengers in case of emergency- this device will bring the car to the nearest floor automatically and will open the doors). 14. Steel Ropes 15. Special Car Door Lock 16. Fire Rated Doors-2 hour. 17. Automatic Brake Testing. 18. PMS MOTOR with ECO Disk Drive 19. Linear Motor Technology & Close Loop Arrangement. 20. 24x7 Connected Services. 21. Car & Landing Doors – Moon Rock Finish
Supply, Installation, testing and commissioning complete of manufacturer or OEM manufactured, static silent (Sound Proof enclosure) Diesel Engine Driven Generating Set capable of delivering 24 KW (30 KVA), 415 Volts (AC three phase, 4 Wire system of supply) 50 HZ at power factor 0.8 minimum. The DG Set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacturer, fuel tank with mounting arrangements and inlet, outlet return inlet oil arrangement, exhaust pipe complete and suitable for conditions prevalent at Dinjan (Capacity of Engine, alternators shall be worked out taking all derating factors into consideration) including PCC foundation (of suitable size leaving at least 0.5 M all around for ease of movement and 0.5 M height), anti-vibration pads, including all features to comply with latest CPCB IV guidelines and Comprising of followings:-
12.094 Continued... (i) ENGINE(Prime Mover): Diesel Engine 1500 RPM , direct injection, 6 cylinders, four stroke, radiator cooled, performance class of generator set ISO 8528-5 G2, turbo charged, capable of giving adequate BHP to drive Alternator capable of delivering 24 KW(30 KVA) at outdoor atmospheric conditions at Dinjan, (Taking all derating factor into consideration), 12/24 Volt (as per manufacturer recommendations) electric battery start, complete withy fly wheel all standard fittings/fixtures as per manufacturer and including suitable panel with tachometer, lub oil temperature, pressure gauge and frequency meters and also including self starter system, dynamo, fuel electric control panel with electronic governor (ECPG) and Engine protection system (Shut down, low lub oil, oil pressure, over speed etc) fuel tank and first fill of lub oil and other consumables etc . (ii) Alternator: Brushless AC alternator, 3 Phase, 415 Volt, 4 wire, rated for output of 24 KW(30 KVA), Minimum power factor 0.8, 1500 RPM, IP 23 Protection class enclosure, insulation Class "H", salient pole, revolving field, sealed bearing automatic voltage regulator coupled through flexible coupling with and to match the above engine :- (iii) BASE PLATE: made out of structural steel as per manufacturers recommended design/specifications. (iv) ACOUSTIC ENCLOSURE: Sheet metal fabricated cope type silent enclosure manufactured on CNC machines as per CPCB norms and powder coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition . (v) Foundation/Plinth/Base: Shall be provided as per manufacturers recommendations, however minimum 0.5 m Space should be available all around the Set and height of plinth shall not be less than 0.5 M
Supply, Installation, testing and commissioning complete of manufacturer or OEM manufactured, static silent (Sound Proof enclosure) Diesel Engine Driven Generating Set capable of delivering 40 KW (50 KVA), 415 Volts (AC three phase, 4 Wire system of supply) 50 HZ at power factor 0.8 minimum. The DG Set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacturer, fuel tank with mounting arrangements and inlet, outlet return inlet oil arrangement, exhaust pipe complete and suitable for conditions prevalent at Dinjan (Capacity of Engine, alternators shall be worked out taking all derating factors into consideration) including PCC foundation (of suitable size leaving at least 0.5 M all around for ease of movement and 0.5 M height), anti-vibration pads, including all features to comply with latest CPCB IV guidelines and Comprising of followings:-
12.095 Continued... (d) All standard relays, circuits and protection required for automatic operation of Gen set (e) Data logging : Engine hours, Control hours and upto 5 recent fault codes (f) AC Alternator Protection : Over/under Voltage, Over/under frequency, Loss of AC sensing, Over speed, Over Current, KW Overload (viii) MISC: Tool kit, Operation and Maintenance catalogue, spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturer standard practices. (ix) First fill of Lubricants, Coolant & Fuel: - First fill of oil, coolant as per OEM recommendations and diesel during testing for 12 hrs as per CA provn. Note: PCC foundation for DG Set shall be deemed to be included in the rate quoted for all DG sets: - (a) DHPP for testing purpose shall be supplied by the contractor without any extra cost to Department (b) The contractor shall arrange for artificial load (water load/Electrical load) for testing for final testing of DG Set at site and the cost is deemed to be including in above offer. (c) Testing of sound level should carried out at the site in presence of Engineer-in-Charge (d) One set of latest Spare part catalogue with price, exploded view of parts and user's manual are deemed to be included in the offer. (e) All civil works including foundation for DG Set as per manufacturer's drawing/ specification, foundation for AMF panel. (f) The rate quoted is deemed to be included for initial filling of radiator coolant and lubricating oil upto level
S&F Hot water storage (Geyser) 25 Ltrs capacity, BEE 5 star rated, vertical type, digital temperature display with suitable size of fastner and incl provision and connecting up of ss braided pipe with adopter for inlet and outlet water connection, copper element corrosion resistance antiscaling magnesium anode, having adjustable knob for temperature control and inner tank material of superior glassline coating / percelain Enamel Coating / Titanium Enamel Coating / Nano Blue Diamond Glass Coating / Coating with Single Weld line tank and outer body material ABS with high pressure with standing capacity upto 8 bar pressure, Multiple safety systems for protection against dry heating, overheating and over pressure, IPX4 waterproof technology for longer product life having heating element 2 KW and minimum two year warranty on product, minimum 3 years warranty on heating element 5 years on tank complete all as specified and directed.
Supply, installation, testing and commissioning of stainless steel electric kitchen chimney 90 cm with 1500 Cum/Hr suction intelligent auto clean wall, curved glass, baffle filter, motion sensor control, oil collector tray with inbuilt LED light including aluminium flexible pipe of 150 mm dia of suitable length with suction cover, with all accessories including making/cutting hole of 150mm dia suitable for aluminium exhaust pipe and making good complete all as specified and directed.
Design, Supply, Installation, Testing and commissioning incl comprehensive maint for 10 years of Roof Top Solar Power Generation Plant of capacity 30 KWp (AC) at output Voltage 415 Volt, 50Hz, on grid connected complete with structure and foundation comprises Design and construction of foundation, civil supporting structure, modules, inverters, DC junction, Distribution & combiner boxes, AC junction & combiner boxes, lighting arrester, weather station, SCADA system, earthing, connecting wires / cables with all accessories required for SPV complete all as per MNRE/SECI specifications and technical specifications as (Detail Brief Report and Technical Specification for SPV Plant) complete all as specified and directed
Design, Supply, Installation, Testing and commissioning incl comprehensive maint for 10 years of Roof Top Solar Power Generation Plant of capacity 10 KWp (AC) at output Voltage 415 Volt, 50Hz, on grid connected complete with structure and foundation comprises Design and construction of foundation, civil supporting structure, modules, inverters, DC junction, Distribution & combiner boxes, AC junction & combiner boxes, lighting arrester, weather station, SCADA system, earthing, connecting wires / cables with all accessories required for SPV complete all as per MNRE/SECI specifications and technical specifications as (Detail Brief Report and Technical Specification for SPV Plant) complete all as specified and directed
Supply, installation, Testing and commissioning of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Roof conductor holder for parapet- Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Polyamide roof cable holder for flat roof : DIn 48829 form B1 closed form with bottom, filling weight 1 Kg (frost resisant concrete), sleeve from polyethylene, black . Conductor holder @ 1 meter distance along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of 2 mtr vertical air terminal with mounting accessories on the flat surface to meet the requirements of IS/IEC 62305 part-3 Nominal size Ø 10/16 mm aluminium rod, semi hard (E-AlMgSiO5 corresponds to DIN 48801) suitable for high wind load complete with necessary accessories as recommended by OEM / Manufacturer complete all as specified.
Supply, installation, Testing and commissioning of stand for fang fix system 16 Kg with base size 373mm and clamp, made up of frost resistant concrete and tested upto 100KA lightning current complete with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of stand for fang fix system 16 Kg with base size 365mm and clamp, made up of frost resistant concrete and tested upto 100KA lightning current complete with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of cross universal connector for T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts along with necessary accessories as recommended by OEM / Manufacturer complete all as specified.
Supply, installation, Testing and commissioning of expansion piece with connector for equalising temperature related length changes. Necessary on conductors length over 30 meters for round conductor Rd 8/ALU along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Connector for T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Bridging cable from flexible CU cable of 16mm² with black colur coating, chlorinated India rubber mixture. Exclusively used for indoor & outdoor application to make continuity at terminals with along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Bridging cable: From flexible CU cable of 16mm² with black colur coating, chlorinated India rubber mixture. Exclusively used for indoor & outdoor application to make continuity at terminals with Clamping Shoe, 8 mm along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of 10mm dia solid, round conductor with 100 micron copper coating along with necessary accessories as recommended by OEM / Manufacturer complete all as specified and directed .
Supply, installation, Testing and commissioning of Cross connector for earth fixing point suitable for FL 30. Installed with 2 hexagonal bolts along with necessary accessories as recommended by OEM/Manufacturer complete all as specified and directed.
Supply, installation, Testing and commissioning of Earth fixing point along with necessary accessories as recommended by OEM/Manufacturer complete all as specified and directed
Supply, installation, Testing and commissioning of rubber clamp suitable for 50x6mm dia CU strip at every 3mtr along with necessary accessories as recommended by OEM/Manufacturer complete all as specified and directed.
Boring for Bored cast in situ piles of dia 600 mm and 17 metre long in soil and getting out and disposal of spoil to a distance not exceeding 50 metres using DMC method (Direct mud circulation) complete all as specified and directed.
Boring for Bored cast in situ piles of dia 600 mm and 15 metre long in soil and getting out and disposal of spoil to a distance not exceeding 50 metres using DMC method (Direct mud circulation) complete all as specified and directed.
Boring for Bored cast in situ piles of dia 600 mm and 12 metre long in soil and getting out and disposal of spoil to a distance not exceeding 50 metres using DMC method (Direct mud circulation) complete all as specified and directed.
M&L for reinfored cement concrete M-30 Design mix (using 20 mm graded crushed stone agrregate) as in cast-in-situ bored pile from cut off level excluding HYSD bars for reinforcement, but including temporary metal sheating upto 1.5m provided as guide, cost of all materials mixing, laying with mechanical vibrators, ramming, consolidating, finishing and curing etc. and vertical load (cyclic) as per ISI specification; complete all as specified and directed. Note: The rate include for wastage allowance of 1.5m from cut off level due to inter mixing of clay slurry with concrete.
Carrying out initial pile load tests for 600 mm dia pile (test load: upto 260 MT) by anchor reaction method as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed.
Conducting initial pile load test for 600 mm dia pile (test load : upto 15 MT) by lateral method as per IS: 2900-Part-IV with calibrated measuring device complete all as specified and directed.
Conducting initial pile load test for 600 mm dia pile (test load : upto 130 MT) by pullout/uplift method as per IS: 2900-Part-IV with calibrated measuring device complete all as specified and directed.
Conducting low strain integrity test on required diameter RCC cast-in-citu piles, data analysis and submission of report. (min 10 piles per visit) complete all as specified and directed.
Carrying out routine pile load tests for 600 mm dia pile (test load: upto 156 MT) by anchor reaction method as per IS: 2911- Part 4 with carrying out necessary calibrated measuring devices like load/pressure guage, hydraulic jack, dial gauges and magnetic stands, submitting all the test reports to GE with proper presentation complete all as specified and directed.
Conducting routine pile load test for 600 mm dia pile (test load : upto 196.5 MT) by lateral method as per IS: 2900-Part-IV with calibrated measuring device complete all as specified and directed.
Conducting routine pile load test for 600 mm dia pile (test load : upto 78 MT) by pullout/uplift method as per IS: 2900-Part-IV with calibrated measuring device complete all as specified and directed.
Mobilization/ Transportation, erection of T & P alongwith all accessories for boring 150mm dia bore hole at various locations and dismantling of all reburied equipment at proposed site including deployment of suitable personels for effective soil investigation as directed.
Carrying out soil investigation as per relevant IS, complete all as specified and directed including the following:- Boring 150mm dia holes for minimum 25 meters depth at various locations as shown at Site by Engr in charge in any kind of soil but excluding rock, collection of undisturbed sample and disturbed sample as per clause 7.2 of IS 1892-2021 and conducting standard penetration test as per relevant IS at an interval of 1.50m . Additional SPT shall be carried out at the termination depth.
12.127 Contd... Carrying out the following laboratory tests on the soil samples as per IS codes on each Bore hole. (i) Recording of water table and making cognigence of maximum water level during monsoon. (ii) Liquid limit & plastic limit (iii) Sieve analysis and index properties (iv) Natural moisture content (v) Bulk density and dry density (vi) Direct/triaxial shear test (vii) Unconfined compression test (viii) Consolidation test (ix) Specific gravity (x) DFS test (xi) Chemical test (xii) Test for free swell index (xiii) Organic Impurities (xiv) Hydrometer analysis (2) Depth of bore holes shall be measured from EGL.
Submission of soil investigation report duly vetted by any IIT/NIT or Govt Engineering College.Notes:- 1. Following points to be included in SSI report (not comprehensive, appropriate data/information may be added as per requirement:- (a) Introduction (c) Site conditions (c) Field investigations (d) Laboratory test results
12.128 Continued.... (e) Soil profile (f) Allowable bearing capacity- based on ‘N’ values, ‘c-Ø value and permissible settlement with sample calculations. Complete calculations will be submitted in soft copy in the same CD containing the SSI report. (g) Liquefaction analysis with calculations. (h) Confirmation of suitability of adopted foundation design and pile capacities of adopted piles. (i) Clear recommendations duly vetted by IIT/NIT/ Govt Engg College. A table showing building name, BH No, depth & coordinate of the BH corrected SPT ‘N’ values and the recommended SBC and clear recommendation for any required soil improvement matching with the site plan should form part of the recommendations. (j) Annexure including bore logs, c-Ø and indicated for BHs, likelihood of water- logging at site must also be checked. 2. If the soil/water has high (more than permissible) contents of sulphate, chlorides or any other deleterious material, the same should be brought out and appropriate recommendation be offered. The required chemical analysis needs to be undertaken for the same. 3. All relevant IS code on the subject should be followed and mentioned at appropriate places. Signed copy to be submitted.
S&F concealed type two way bib tap for 15 mm bore pipe, chromium plated with long shank and cup for using tap and health faucets complete all as specified and directed.
S&F swan neck sink mixer for 15 mm bore pipe with a long hose of 450 mm deck mounted having dual spray modes and 360 degree swivel with aerated spray and ring shower pull out sprayer, chromium plated complete all as specified and directed.
S&F GI tubing 65 mm bore medium grade including all fittings such as bends, elbows, tee, short pieces, connectors, backnuts, diminishing pieces, caps, plugs, unions, fixing clips, wall hooks and wooden plugs fixed to wall / ceiling or laid in floors complete all as specified and directed.
PHASE III Comprehensive annual maintenance of DG Set 50 KVA at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed. Note : (i) The contractor shall provide two years annual maintenance of DG Sets within defect liability period at his own cost (ii) The contractor shall provide two years annual maintenance of LIFTs and contractor shall also provide 01 lift technician during day and 01 lift technician during night within defect liability period at his own cost
Comprehensive annual maintenance of DG Set 50 KVA for Ist year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of DG Set 50 KVA for 2nd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of DG Set 50 KVA for 3rd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of DG Set 30 KVA for Ist year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of DG Set 30 KVA for 2nd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of DG Set 30 KVA for 3rd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 8 passenger Lift for 1st year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 8 passenger Lift for 2nd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 8 passenger Lift for 3rd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 13 passenger Lift for 1st year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 13 passenger Lift for 2nd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed.
Comprehensive annual maintenance of 13 passenger Lift for 3rd year after defect liability period at Guwahati military station (Phase I of two phases) as per scope given in particular specification complete all as specified and directed. Notes for serial item Nos 13.001 to 13.012 (i) The contractor shall provide two years annual maintenance of DG Sets and lifts within defect liability period at his own cost
Provision of services of lift technician (01 No during day and 01 No during night for passenger lift for 1st year after defect liability period at Guwahati military station (Phase I of two phases) complete all as specified and directed.
Provision of services of lift technician (01 No during day and 01 No during night for passenger lift for 2nd year after defect liability period at Guwahati military station (Phase I of two phases) complete all as specified and directed.
Provision of services of lift technician (01 No during day and 01 No during night) for passenger lifts for 3rd year after defect liability period at Guwahati military station (Phase I of two phases) complete all as specified and directed. Note for serial item Nos 13.013 to 13.015 (i) The contractor shall provide two years annual maintenance of LIFTs and contractor shall also provide 01 lift technician during day and 01 lift technician during night within defect liability period at his own cost
T.Y Global Enterprise (BID ID -3489392)
MGD Enterprises (BID ID -3489258)
SHIVAM TRANSCON PRIVATE LIMITED (BID ID -3495071)
ASHIS DHAWA (BID ID -3495009)
HTE INFRA LLP (BID ID -3489677)
Brahmaputra Commerce and Trade (BID ID -3489373)
M/S ALLIED CONSTRUCTION (BID ID -3488988)
Som Projects Pvt Ltd (BID ID -3488700)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.75 MB
1Contents_merge.pdf
Tender Documents • 4.23 MB
BOQ_816888.xls
BOQ • 0.75 MB
tddrawings.pdf
Additional Documents • 29.80 MB
DRGSTR.pdf
Tender Documents • 15.60 MB
ARCHEMDRGSET1.pdf
Additional Documents • 31.26 MB
Download all tender documents and submit your bid