Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.3 CrAccepted-AOC H NO 1100 SECTOR 3 124001 | ROHTAK | HARYANA | 124001 | ₹2.3 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹2.4 Cr+₹10.3 L (4.48%)Rejected-AOC SCT 3 H NO 2030 ROHTAK SCT 3 H NO 2030 ROHTAK 124001 | ROHTAK | HARYANA | 124001 | ₹2.4 Cr+₹10.3 L (4.48%) | L2 | Rejected-AOC Rejected |
Tender Value
₹1.9 Cr
EMD Value
₹3.8 L
Closing Date
19 May 2021, 6:55 pmClosed
EE PHED No.1 Rohtak
Jhajjar Road Rohtak
Kahnaur Estimate for FHTC Const. of Raw Water Pump House Augmentation Repair of Structure Laying of Rising Main and Distribution system in Village Kahnaur Under Jal Jeevan Mission Construction of Raw Water Pumping Station at
2021_HRY_171555_1
DNIT Approved vide SE Endst No.951 dt.07.05.2021
Open Tender
Civil Works
Works
450 days
VPO Kahnaur
Kahnaur Estimate for FHTC Const. of Raw Water Pump House Augmentation Repair of Structure Laying of Rising Main and Distribution system in Village Kahnaur Under Jal Jeevan Mission Construction of Raw Water Pumping Station at
3 documents required · 3 mandatory
₹15,000
₹3.8 L
Yes
5 Jun 2021
14 May 2021
20 May 2021
14 May 2021
19 May 2021
14 May 2021
Amount
Desinging , Testing , Commissioning of automated PLC controlled SCADA based water purification plant of 1.00 MLD capacity at Existing Water Works Kahanaur, all other installation etc. comprising of DI pipe from raw water main/pump, inlet box of WTP and to CWT to C.W. suction well, inlet channel, Alum dozing, Flash mixing, Clari floculator, filter box, over head Reservoir for back wash including pump sets and electric control panel, waste water tank including pump sets and electric control panel, DI pipes, DI specials, manhole covers, air scour equipment, chemical house including chlorination equipment and arrangement of floe measurement and sand bed with automation complete in all respects as per NIT (Sluice valve of make IVC/ VAG )
Pumping Machinery Raw water pump sets
Supply & Eraction of Horizontal spindle split casing type pumping sets of following duties directly coupled to AC squirrel cage induction type motor with accessories as described in Schedule No II complete in all respect with priming arrangement with complete base frame a) RAW WATER PUMPING STATION NEAR KAHNAUR DISTRI. AT RD 154610-L
3000 LPM with 30 M. Head & 35 BHP
B) For Existing Water Works
2700 LPM with 40 M. Head & 40 BHP For Clear Water
Supply & fixing following CI D/F pipe and sluice valve/ non return valves/ bell mouth / reflux valve including cost of jointing materials, excavation, laying jointing refilling including making adequate supports of masonry/ concrete steel for delivery and suction pipe from bell mouth in the collecting tank upto the rising main laid by the department as per plan shown from the foundation wall of the pump chamber for all the raw water and clear water pumping sets at water works as per specification given in schedule No.II Details of pipe and specials. CI D/F
CI D/F pipes 100mm i/d
Supply erection, testing & commissioning of HT metering panel 11 KV consisting of One No. Electric Trivector meter 3 phase 4 wire 0.5 class of accuracy on KW hour point basis complete with HT CTs of 20/5 amp 15 VA burden and class of 0.5 accuracy and HT PT 11000 V. 15 VA burden and class of 0.5 including metering cubical complete in all respects as per site requirement. For Raw Water Pump House (at Transformer)
Supply, erection, testing & commissioning of wall mounted electrical L.T. Panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900 mm and 400 mm deep having follwing items. (i) Incomar switch 200 Amp (ii) Aluminum bus bar Chamber of 200 Amp. Capacity (iii) Volt meter 100 x 100mm range to 500V (AD/KAPPA/LNT) (iv) Indicating lamp one set (Raw Water Pump House & Existing Water Works (Inside Pump Chamber)
Panel Board for Motors
Supply, erection, testing and commissioning of wall mounted electrical LT panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900mm and 400mm deep having following item:- For Raw water pump set 3000 LPM x 30 M. Head = 1 Nos. (One for Each pump set) At Raw Water Pump House A Main switch 100 Amp 1 No. (L&T siemens, ABB). B Volt meter 100x100mm range 0 to 500 volt= 1 No. (AE/KAPPA/L&T) C Amp. Meter 100x100mm range 0 to 100 volt= 2 No. (AE/KAPPA/L&T) D CT 100/3 No. (AE/KAPPA/L&T) E VSS & ASS 1 No. each No. of approved make F SSP 4 No. of approved make/ minilac G Motor starter star delta 1 Nos. for 3000 LPM x 30 Head motor (L&T, Siemens, ABB) H Capacitor KVAR as per site requirement I Indicating Lamp One Set J Change over Switch 200 Amp. = 1 No.
Supply, erection, testing and commissioning of Floor mounted electrical LT panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900mm and 400mm deep having following item:- For Raw Water & Clear water pump set 2700 LPM x 40 M. Head = 1 Nos. (One for Each pump set) at Water Works A Main switch 100 Amp 1 No. (L&T siemens, ABB). B Volt meter 100x100mm range 0 to 500 volt= 1 No. (AE/KAPPA/L&T) C Amp. Meter 100x100mm range 0 to 100 volt= 2 No. (AE/KAPPA/L&T) D CT 100/3 No. (AE/KAPPA/L&T) E VSS & ASS 1 No. each No. of approved make F SSP 4 No. of approved make/ minilac G Motor starter star delta 1 Nos. for 2700 LPM x 40 Head motor (L&T, Siemens, ABB) H Capacitor KVAR as per site requirement I Indicating Lamp One Set J Change over Switch 200 Amp. = 1 No.
Supply erection testing and commissioning in HT epoxy type cable boxes for 35mm HT/ 11 KV XLPE 3 core galvanized steel strip armoured cable including material/ Required for complete erection of the same such as thimble lugs. Solder compound etc. complete in respects as described in schedule No. II as per approved NIT.
For Outdoor installation
For Indoor installation
Diesel Generating Set at RAW Water Pump House
Designing, Supply & erection of DG set 80 KVA of required capacity given below with acoustic of suitable rating with change over switch, fenced enclosure with platform for DG sets complete as per DNIT.
The rating should be at 1500 RPM
(a) Diesel Engine b) Alternator c) Bettery 24 V
(d) Base Plate
(e) 1x50 sq mm 3.0 core XLPE Aluminum = 20 m
(f) Tools
A.M.F. PANEL
(a) Motorised change over switch 100 Amp 4 P with fuse base and HRC links 100 Amp.
(b) Under voltage/ over voltage relay - 2 No. 415 VAC
(c) Engine Start relay 24 VDC 1 No.
(d) Electronic Timber 24 VDC 1 No.
(e) Electronic Timber 24 VDC 2 No.
(f) Auxiliary relay 220 VAC - 2 No.
(g) Auxiliary relay 220 VAC - 3 No.
(h) Metering set 415 VAC - 1 set (Amp. Meter, Volt Meter, ASS, VSS, Phase Indicaters, Control fuse, frequency meter, CT'S)
(i) Metering set 24 V DC (Amp. Meter, Volt Meter)
(j) Over Load protection for DC - 1 No.
(k) Battery Charger 24 V DC (Blueron make)
(l) Copper bus bar of suitable size
(m) KWH meter 96 square mm size
(n) Starting fuse button and key switch (On/Off)
(o) Engine Protection unit with Audiovisual alarm and shut down for low lubricating oil pressure and high coolant temperature.
(p) Indicating lump for low lubricating oil pressure high collant tempurature, set running, load on, DC control on.
Note: Control Panel shall have the provision to provide auto manual failure panel (AMFP).
a) Raw water Pump House
Transformer
Design, Supply & erection of transformer of standard make Required KVA 11/0.433 KVA rating outdoor type 62.5 KVA V.C.B, panel, G.O. switch, H. Pole , H.T, metering panel, APFC panel, battery charges, 62.5 KVA substation, entire cable network from G.O. switch to H.T metering equipment and from H.T metering to Transformer from metering to transformer. From transformer to main to L.T, panel earthling, safety equipment, fenced enclosure for transformer, and any other contingent thereto complete in all respect as per DNIT ( Make Kirlosker, Crompton & GEC )
Required at following sites as per respective capacity
a) Raw water Pump House
Providing & fixing of D.I. Air Valve “IVC” Brand soft seated as confirming to I.S.I. complete in all respect. (Pump House D.I.Rising main to Water Works
Supply erection testing and commissioning of exhaust fans each having a capacity of 45 cubic meters per minutes, complete with suitable G.I sheet Ducting in meter room and pump Chamber and energy for the sites. (Pump House & Water Works)
Supply erection & testing of Ceiling fan of size 48" i/d (1200 mm) of reputed ISI make complete in all respect. (Pump House & Water Works)
Supply erection, testing of light fitting including wire in the pump chamber with material upto 10 points including switch, button, plug, PVC conduict pipe & copper wire etc. as per approved specifications. (Pump House)
Providing and fixing of insulated Rubber matting suitable for HKV installation 1 meter x 2 meter x 12 mm as per specification. (Pump House & Water Works)
S&S Tank
Providing and fixing of PVC water Bar (fixo- stop) with ribs & central bulbs of size given below confirmed to IS-12200 of 1987 (fixo-stop) along with the bitumen board including cost of bitumen filler complete i) 250 mm wide x 8 to 11 mm thickness. (1 No. RCC RAW Water Reservior at Pump House, 2 Nos. RCC S&S Tank, 1 No. Clear Water Tank at Water works)
Supply erection, and commissioning electric operated dewatering pump of 3 HP Kirlosker make complete from priming with wiring starters switches etc. also the required GI pipe (B Class) valves and sight glass etc. complete.
Supply erection testing and commissioning of Flow Meter (KRONE Make) with digital display of 150 mm dia i/d complete in all respect. (For Rising main & Water works to B/Station)
Supply and Fixing of G.I. Nipple 1/2'' x 4" Complete in all respect and the entire satisfication of Engineer-in-charge (Make Jindal/ Parkesh/Tata) complete in all respect.
Supply and Fixing of G.I. Socket 1/2'' i/d Complete in all respect and the entire satisfication of Engineer-in-charge (Make Jindal/ Parkesh/Tata) complete in all respect.
Supply and Fixing of G.I. Elbow 1/2'' i/d Complete in all respect and the entire satisfication of Engineer-in-charge (Make Jindal/ Parkesh/Tata) complete in all respect.
Operation & Maintenance
Operation and maintenance for complete scope of work mention in the DNIT ( Disinfection material supplied by the PHED) as per Schedule-IV for a period 5 year after 12 month during defect liablity period 3 months trial run will be charged to the A/Mtc estimate
Operation and maintenance during defect liability period (Operation only)
Operation and maintenance during 1st year after defect liability period
Operation and maintenance during 2nd year
Operation and maintenance during 3rd year
Operation and maintenance during 4th year
Operation and maintenance during 5th year
Bidder Name
Amount
Kulbir Singh Contractor(GSTN-06ATZPS6352H1ZW)
Surinder Singh Hooda(GSTN-06AABPH9599L2Z1)
Surinder Singh Hooda
Surinder Singh Hooda
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .