Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹55.2 LAccepted-AOC BHAGIRATHIPUR DOMKAL MSD | DOMKAL | MURSHIDABAD | WEST BENGAL | 742101 | L1 | Accepted-AOC Quoting Lowest rate | |
| 2 | L2₹55.4 L+₹21,200 (0.38%)Rejected-Finance 159B M G ROAD HARIDEVPUR KOLKATA WEST BENGAL 700082 UDYAM WB 10 0018308 | KOLKATA | WEST BENGAL | 700082 | L2 | Rejected-Finance Quoting Higher Rate | |
| 3 | L3₹55.7 L+₹49,200 (0.89%)Rejected-Finance | L3 | Rejected-Finance Quoting Higher Rate |
Tender Value
Refer Docs
EMD Value
₹1.2 L
Closing Date
22 Nov 2023, 3:00 pmClosed
Superintendent Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Construction of 100 Beded Covid Ward at Furfura PHC, Hooghly .............. ARRANGEMENT OF POWER SUPPLY CABLE and EXTERNAL El WORK and Arrangement of HVAC with Negative Pressure..
2023_WBPWD_597266_1
WBPWD/SEWEC /HED /NIQ124/2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Hooghly
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.2 L
Office of the Superintending Engineer, Western Ele
13 Dec 2024
31 Oct 2023
24 Nov 2023
31 Oct 2023
22 Nov 2023
7 Nov 2023
31 Oct 2023 - 6 Nov 2023
6 Nov 2023
Amount
ARRANGEMENT OF POWER SUPPLY CABLE & EXTERNAL El WORK
Supply and delivery of 1.1 KV grade, 4 Core 185 sq mm. XLPE Insulated & Sheathed Armoured Aluminium Conductor cables [Make: UNIVERSAL, HAVELES, POLYCAB, RR KABLE or as approved by EIC]
Laying of two cables above 35 sqmm and upto 185 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed. [2(b)/F-2]
Laying of one cable above 150 sqmm and upto 300 sqmm through existing covered masonry trench incl taking out RC covers, sotting them in order, mending good the damages Tilling the trench with line dry sand incl. supplying sand [4(b)/F-3]
Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for sinqle. 2, 3, З'/з and 4 core [3(b)/F-1]
Supplying & fixing medium gauge Gl Pipe (ISI-Medium) Protection with necessary fittings and jointing melarials as required
a 80mm dia [11 (f)/F-61
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-prool entry ot XLPE/PVC armoured cables as below[F-4/7c]
For 4 Core UDto 185 somm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl, supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials[F- 5/Bb-xiil
For 4 Core upto 105 stjmm
Supplying and fixing PVC- Rigid Conduit 'FR‘ [Precision Make] ol tallowing sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works
25 mm size ( 7(b)/ E- 16 ]
Supplying and Drawing 1 1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire ot the following sizes in the 25mm piclaid PVC rigid conduit including necessary copper socketing arrangement as per GS.jMake : KEI/Havells or as approved by E I C] |NS)
4x(150 sqmm)
.Supplying & fixing medium gauge Gl Pipe ( ISI-Medium) Protection with necessary fillings and jointing melarials as required
100mm dia [11(g)/F-6]
Supplying and fixing of 415V TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts [Make L& T model No. SK90492 or equivalent model of Havells /HPL as approved by EIC.]
a. 630A TPN SFU
Supplying and fixing sheet steel (16 SWG) iron clad Busber chambers on angle iron frame on wall incl. earthing attachment and painting as required - (As per Drawing no. 470 of PWD specification book - may 1991).
4bars of rating-415 V 600 A with dimension of copper bars [85mm long]: 4x(2x40x5mm); Dimension of sheet metal Box 500x150mm [D-13/19(b))
Arrangement of HVAC with Negative Pressure.
Supply of Air Conditioning Units Supply of Ceiling Mounted Ductable DX type Air Conditioning Unit with 198000 btu/hr Cooling capacity,6600 CFM Air Flow, with 3 nos, Scroll compressor, 400V/3 PH/50 Hz Microprocessor based Controler of 16.5 TR nominal capacity with R-410A Refrigerant..(Hitachi/Mitsubishi/O-General/ Daikin )
Supply of Exhaust System Supply of Single Skin Centrifugal Cabinet Type Fan complete with DIDW- forward curved belt driven centrifugal blower Rotaion of fan 1760 RPM, Epoxy/ galvanized steel sheet cabinet with service access doors, Inlet & outlet drilled flanges 5.6 KW, 4 pole, IE - 2, IP -55 Standard 3Ph/415V/50 hz VFD Motor(Make: ABB/Cromptom) with Fixed base, common base frame with spring isolators,Flange at inlet and outlet are provided to facilitate duct connection necessary hanging/supporting members, water prof VFD Panel for Fan's Speed control etc. Sound level-65 dba. Capacity 70mm/wc Static pressure, 7500 CFM, (Elta/Edgetech/VTS).
SITC of Treated Fresh Air arrangement with multi stage filtration, Control damper, Actuator, complete with linkage control, Bird screen, etc.
SITC of 10 Micron Pre Filter with Frame, it will be fitted on Centrifugal Exhust fan, TFA Units & on the Fresh air Damper (Make: Spectrum/ AFI).
SITC of 10 Micron Fine Filter with Frame, it will be fitted on Centrifugal Exhust fan, TFA Units & on the Fresh air Damper (Make: Spectrum/ AFI).
SITC of MERV-17 0.3 Micron Hefa Filter with minimum 450mm Depth, it will be fitted on Centrifugal Exhust fan.(Make: Spectrum/ AFI).
Supply and fixing of UVC EMIITTER for the above fan's for prevention of fungus , The minimum UV intensity in the coils shall be 700-800 UW-SEC/CM2. The unit shall be UL.Listed (UL-1995) to be fitted on Centrifugal Exhaust and IDUs.
Installation, Testing & Commissioning of the above Exhaust & Air Conditioning systems with all necessary accessiores for hanging Indoor & Outdoor Units
For 15.5 TR Ductable Units.
For 7500 CFM Centrifugal Exhaust system.
Copper refrigeration pipe line for liquid and suction line with hard drawn copper piping with supports & brackets
Cu.HD Pipes Liquid line dia 12.7 mm .with 9mm thick nitrile insulation.
Cu.HD Pipes Suction line dia 22.2 mm with 13mm thick nitrile insulation.
Supply and fixing of necessary electrical arrangements of Air Conditioning Units, PVC insulated FRLS grade Copper cable for connection betweeen indoor and outdoor units, 1.1 KV grade.
7 core x 1.5 mm²
4 core x 6 mm²
Supply & fixing of dia UPVC drain pipes with all necessary hanging arrangements & 9mm Heat Retardant Thermal insulutaion.
Dia 32mm
Dia 25mm
SITC of Site Fabricated G.I Sheet Metal Square Air Duct complete with Angle, Fastner, supports, dampers etc. as per specifications & site requirement.
For 24 SWG
For 22 SWG
For 20 SWG
Supply and Fixing of Air Duct Insulation.
Supply and fixing Heat Retardant closed cell Class'O' 9mm thk Nitrile Rubber insulation inside Supply Air duct.
Supply and fixing Heat Retardant closed cell Class'O' 9mm thk Nitrile Rubber insulation with AI Foil Faced Outside Supply Air duct.
Supply & Fixing of Air Diffuser With VCD. (Duct Bottom Surface Mounted)
Supply & Fixing of Liner type AI Powder Coated Continuous Grill with VCD for Exhaust Air. (Duct Bottom Surface Mounted monted)
Supply and Fixing of Motorized Volume Control Damper.
Supply and Fixing of Motorized Non-Return Type Flow Control Damper .
Supply & Fixing of Fusiable Link Fire Damper,Galvanized Steel Sheet with 125 GSM Zink Coated, Certified by CBRI ( U-555, 1995),with minimum fire rating not less than 120 min, must be Fusiable Link Spring with 74°C Temerature rating Ul Listed
Providing and fixing fire retardant nonporous double layer flexible connection between IDU, Exhaust, TFA units and duct.
SITC of heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration.
Supply & Fixing of G.I Cable tray 50mmx 300mm x 50mm
Lifting Shifting of Indoor and Outdoor units,TFA Units, Exhaust units, Scafolding, Minor Civil Work for mending the goods and Carriage of Lowside materials
Supplying, fabrication & fixing 03 Nos. M.S. Angle/M.S C chanel of size (75 mm x 75 mmx6mm) for placing the outdoor unit of ductable split AC incl. drilling 05 nos holes in each Angle including cutting holes into the wall & grouting the same (1:1 ½ :3) etc for Air Conditioning Units
Supplying, fabrication & fixing 4 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame table type for installation of Exhaust Cabinet incl. drilling 2 nos holes in each channel. fabricated with 4 Nos.Baricated the same for maintenance horizontal angle of 50 mm x 50 mm x 6 mm Inscl Platform as per direction of E.I.C.. Area of Platform 9mtr x 1.8mtr for Placing the Exhaust Units & TFA.
MONDAL ENTERPRISE
DAS TRADING CO
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .