| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.3 LAccepted-AOC 15 CP COLONY MORAR GWALIOR MP 474 006 | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | L1 | Accepted-AOC Being a lowest tender | |
| 2 | L2₹26.5 L+₹2.0 L (8.23%)Rejected-Finance C 187 NIRMAN VIHAR DELHI 92 | L2 | Rejected-Finance Not a lowest tender | |
| 3 | L3₹29.3 L+₹4.8 L (19.7%)Rejected-Finance | L3 | Rejected-Finance Not a lowest tender |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
7 Aug 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF TA GWALIOR
GE AF TA GWALIOR 474020
REPAIRS/MAINT OF EARTHINGS/LIGHTENING PROTECTION INFRASTRUCTURE AT WSA, MMPUs IN TECH AREA AT AF STN MAHARAJPUR
2020_MES_357146_1
8900/1235/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF TA GWALIOR
As per tender documents
7 documents required · 7 mandatory
₹500
GE AF TA GWALIOR
₹50,000
Yes
21 Aug 2020
1 Jul 2020
11 Aug 2020
1 Jul 2020
7 Aug 2020
16 Jul 2020
60 days
Amount
Disconnecting & taking up or down existing unserviceable / deshaped, aluminium / GI earth strip or taking down conductors of any size and in any position, stacking properly the serviceable strips for re-use in the work including making good the distrurbed surfaces to match with the existing surfaces complete all as specified and directed.
Supplying, fixing & connecting aluminium earth strip 25 mm x 3mm as in roof conductors / down conductor fixed on walls / roofs with saddels/appoxy insulator including screws required at site complete all as specified and directed.
Fixing only in position & connecting the retrieved old serviceable aluminium/ GI earth strip/ earth lead / down conductors of any description and in any size, after making necessary addition / alterations, fixed on walls / roofs over and including M&L for suitable new insulators (Porcelain/vitreous) provided at a distance not exceeding 50 cm centre to centre and insulators fixed with suitable saddles and screws complete all as specified and directed. Note : Old retrieved earth strip of any shape and size in serviceable condition shall be re-used in the work
Supply and fixing earth continuity conductor or main earthing lead 32x6mm GI strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by GI nuts, bolts and washers in addition to brazing at every joint complete all as specified and directed.
Supply and fixing earth continuity conductor or main earthing lead 32mm x 6mm, copper strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by tinned copper/brass nuts, bolts and washers in addition to brazing at every joint complete all as specified and directed.
Supply and fixing earth continuity conductor or main earthing lead 20mm x 3mm, copper strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by tinned copper/brass nuts, bolts and washers in addition to brazing at every joint complete all as specified and directed.
Supply and fixing earth continuity conductor or main earthing lead 25mm x 3mm, copper strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by tinned copper/brass nuts, bolts and washers in addition to brazing at every joint complete all as specified and directed.
Supply & fixing light grade, 40mm dia GI tubing with all fittings fixed on walls/ poles/ in trenches as in earth lead protection pipe complete all as specified and directed . Make : TATA / Jindal / TT Swastik.
Supply and fixing rigid PVC conduits (Medium grade) of size 40 mm bore with all fitting such as bends, saddels, clamps etc including cutting cheses and making good to match with existing in cement mortar 1:3 if required at site complete all as specified & directed.
Supply and fixing rigide PVC conduits (Medium grade) of size 25 mm bore with all fittings such as bends, sadels, clamps etc including cutting cheses and making good to match with existing in cement mortar 1:3 if required at site complete all as specified & directed.
Taking up or down GI pipe 40mm bore 1.2/0.6 mtr long including GI socket complete all as specified & directed.
Material & labour for GI water tubing, light grade, 40mm bore, 1.2 mtr long duly threaded on one side for fixing socket as in Air termination stand / post at roof top of hangers/bldgs complete all as specified and directed. (Make : Jindal / Tata /TT Swastik. Note : (i) GI socket & PCC/ brick masonry block for fixing of GI pipe post shall be measured and paid for separately under appropriate item of Schedule `A' (ii) GI pipe 1.2 mtr will be in a single length & no joint will be allowed.
All as per item 12 here-in-before but 40 mm bore, 0.6 metre long
Fixing only GI pipe, 40mm bore, 1.2 mtr long obtained from taking down in serviceable condition as in Air termination stand / post at roof top of hangers/bldgs complete all as specified and directed. Note : (i) Old GI pipe obtained in serviceable condition shall be re-used in the work (ii) GI socket & PCC / brick masonry block for fixing of GI pipe post shall be measured and paid for separately under appropriate item of Sch`A'.
All as per item 14 here-in-before but 40mm bore, 0.6 metre long.
Taking up or down GI pipe 50mm bore 1.2 /0.6 mtr long including GI reducer (50mm x 40mm) complete all as specified & directed.
Material & labour for GI water tubing, light grade, 50mm bore, 1.2 mtr long duly threaded on one side for fixing socket as in Air termination stand / post at roof top of hangers/bldgs complete all as specified and directed. (Make : Jindal / Tata / TT Swastik ) Note : (i) GI socket & PCC/ brick masonry block for fixing of GI pipe post shall be measured and paid for separately under appropriate item of Sch 'A’. (ii) GI pipe 1.2 mtr will be in a single length & no joint will be allowed.
Material & labour for GI water tubing, light grade, 50mm bore, 0.6 mtr long duly threaded on one side for fixing socket as in Air termination stand / post at roof top of hangers/bldgs compete all as specified and directed. (Make : Jindal / Tata / Swastik ) Note : (i) GI socket & PCC/ brick masonry block for fixing of GI pipe post shall be measured and paid for separately under appropriate item of Sch `A'. (ii) GI pipe 0.6 mtr will be in a single length & no joint will be allowed.
Fixing only GI pipe, 50 mm bore, 1.2 mtr long obtained from taking down in serviceable condition as in Air termination stand / post at roof top of hangers/bldgs complete all as specified and directed. Note : (i) Old GI pipe obtained in serviceable condition shall be re-used in the work (ii) GI socket & PCC / brick masonry block for fixing of GI pipe post shall be measured and paid for separately under appropriate item of Schedule `A'
All as per item 19 here-in-before but 0.6 metre long.
M & L for providing test point terminal block made out of Gun metal or phosphorous bronze of size 75 mmx75 mm x25 mm drilled and screwed including 03 nos 8 mm dia 25 mm long hexagonal head screws complete all as specified and directed
Taking up or down GI socket 40mm / reducer socket 50x 40mm bore including aluminium gutaka complete all as specified & directed.
Fixing only GI socket 40mm bore , on vertical pipe post / stand complete all as specified and directed. Note : Old retrieved GI socket obtained in serviceable condition shall be re-used in the work.
Supply & fixing GI socket 40mm bore, on vertical pipe post / stand complete all as specified and directed.
Supply & fixing GI reducer (50mm x 40mm bore ), on vertical post / stand complete all as specified & directed.
Fixing only GI reducer (50mm x 40mm, bore ), on vertical post / stand complete all as specified and directed. Note : Old GI reducer obtained in serviceable condition shall be re-used in the work.
Taking up/down aluminium gutka 40mm/reducer socket 50x40mm bore including aluminium gutka carefully so that serviceable gutkas can be reused comlete all specified & directed.
Supply & fixing aluminium gutka 40mm dia having internal thread of 12mm dia and external thread of 40mm dia and fixed on GI socket complete all as specified and directed.
Fixing only aluminium gutka on GI socket complete all as specified and directed. Note:- Old gutka obtained in serviceable condition shall be re-used in the work.
Taking up or down existing unserviceable aluminium air termination rod, 12mm dia, 1200/ 300 mm long with existing aluminium block from vertical pipe supports of any description complete all as specified and directed
Supply and fixing aluminium Air termination rod single pointed at top and properly threaded at bottom end, 12mm dia and 1200 mm long complete all as specified and directed.
Supply and fixing aluminium Air termination rod single pointed at top and properly threaded at bottom end, 12mm dia and 300 mm long complete all as specified and directed.
Fixing only aluminium Air termination rod single pointed , 12 mm dia complete all as specified & directed. Note : Old Air termination rod obtained in serviceable condition shall be re-used in the work.
M & L for PCC 1:2:4 for block, type B-I using 20mm graded stone aggregate for block size 150 mm x 100mm X 150mm, set in Cement Mortar 1:4, with and including necessary form work and all exposed surfaces finished even and smooth without using extra cement including removal of old broken unserviceable PCC block at site complete all as specified & directed. Note : A second class hard wood gutty of size 25mm x 25mm x 38mm made to shape shall be embedded in the above PCC block for fixing the screw of saddle / insulator of down conductors / earth strips.
M &L for PCC 1:2:4 for & around lightening conductor pipe on roof of building, type B-I using 20mm graded stone aggregateof size 350mm x 350mm X 350mm, set in Cement Mortar 1:4, with and including necessary form work and all exposed surfaces finished even and smooth without using extra cement including removal of old broken unserviceable PCC / block at site complete all as specified & directed. Note : contractor is responsible to arrange his own T&P for carrying the PCC material on roof of any building .
M & L for earth pit of internal size 300x300x300mm with wall thickness 100mm casting at site with and including PCC base 500X 500X100mm made of PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded stone aggregate), rainforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle etc.including removal of old broken unserviceable earth pit from site complete all as specified & directed.
Material & labour for earth pit cover, pre cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate, 320mm x 320mm x 40mm thick, cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle with and including necessary form work complete all as specified & directed.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm x 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 of MES Schedule Part-I, earth lead connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC 1:3:6 type C-1 using 20mm graded stone aggregate for earth pit with pre cast RCC 1:2:4 type B-1 using 20mm graded stone aggregate, 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh,etc complete all as specified and directed including dismantling and taking out eisting one Note:- The cost of earth lead upto and including 7.5 metre only from the top of earth electrode are deemed to be included under this item and additional earth lead, if any required shall be measured and paid for seprately under appropriate item of Sch A.
Material and labour for earthing complete with copper plate electrode 600mm x 900mm x 5mm thick buried directly in ground vertically to a depth not less than 4.7 meter below normal ground level (with top edge of earth plate not less than 3.6 meter below ground level & complete size of earth pit 1.60m x 1.60m x 5.00m) connected to copper strip 32mm x 6mm as main earthing lead by means of tinned copper / brass bolts, nuts, check nuts and washers besides brazing at all joints all as directed and connected to earth test point all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to test point, made of phosphorous brongze/gun meter of size 75mmx75xmmx25mm dril and screwed including 03 Nos 8mm dia 25mm long hexagonal head screwed, 50mm bore GI medium grade for protection of earth lead from top of plate to test terminal complete, adequate quantity of charcoal dust, magnesium sulphate & common salt in alternate layers of 100mm thick all around the plate, under and above the plate and returning, filling of earth spread, levelled, watered and compected to required level, PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate), rainforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI medium watering pipe 25mm bore with funnel and wire mesh complete all as specified and directed . NOTE : (i) The cost of earth lead and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are deemed to be included under this item and additional earth lead , if any, required at site shall be measured and paid for separately under appropriate item of Schedule `A’. (ii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted.
M&L for earthing complete with copper Earth Plate 600mm X 600mm X 3.15mm buried directly in ground vertically to a depth not less than 3.10 meter below normal ground level (with top edge of earth plate not less than 2.10 mtr below ground level), connecting to copper strip 32mm x 6mm main earth lead by means of tinned copper / brass bolts , nuts, check nuts and washers besides brazing at all joints all as directed and connected to earth test point all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to test point, made of phosphorous brongze/gun metal of size 75mmx75xmmx25mm dril and screwed including 03 Nos 8mm dia 25mm long hexagonal head screwed, adequate quantity of charcoal dust & common salt in alternate layers of 100mm thick all around the plate, under and above the plate and returning, filling of earth spread levelled, watered and compected to required level, PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded stone aggregate), rainforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI medium watering pipe 25mm dia with funnel and wire mesh and 40 mm bore GI light grade earth lead protection pipe complete all as specified and directed including dismantling and taking out eisting one. NOTE : (i) The cost of earth lead and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are deemed to be included under this item and additional earth lead , if any, required at site shall be measured and paid for separately under appropriate item of Schedule `A’. (ii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted.
Material and labour for earthing complete with galvanised steel pipe electrode, 40 mm bore, medium grade, 2.5 metres length, burried directly and perferably vertically in ground level connected with earthing strip of size 25 x 4 mm galvanised iron strip all as shown in plate No 2 to the earthing test point all as specified and indicated including testing on completion including dismantling and taking out eisting one.
S&F in repair GI funnel with wire mesh for watering the earth pit made to shape and size with using PGI sheet minimum 1.0mm thick and fixed in position complete all as specified and directed.
S&F PVC insulation sleeve for 20 to 32 mm GI /copper /aluminium strip complete all as specified and directed.
S&F PVC flexible pipe of 40 mm bore heavy duty (ISI marked) complete all as specified and directed.
All as per item 43 here-in-before but of size 25 mm bore complete all as specified and directed.
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr depth in soft / loose soil and getting out for removing / laying of pipe lines complete all as specified and directed
Returning and filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
Removal of surplus soil to a distance not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed.
M&L for brazing of copper strip size 32x6 mm complete all as specified and directed.
S & F PVC insulated single core Aluminium conductor cable (un armoured) of size 150 sqmm with saddles and clamp complete all as specified & directed.
S & F PVC insulated single core Copper conductor cable( un armoured) of size 70 sqmm complete all as specified & directed.
M&L, for appoxy insulator 1100 volt grade including fixing on wall/RCC piller with fasteners including de-screwing of strip and re-connecting of strip on insulator with suitable screw/nuts/bolts etc complete all as specified and directed.
Demolition/cutting of PCC/Bitumen road for fixing/laying of pipe 40 mm bore minimum 200 mm depth &300mm width and making good with M&L for PCC 1:3:6 (using 20 mm graded stone aggregate) type C-1 complete all as specified and directed.
M&L for marker fabricated with 14 gauge MS sheet of size 300mmx180mm rectangular with 20 mm square hollow bar 60 cm long duly painted of colour as directed and writing ER value, date of testing and due date for testing, Earth pit No etc complete all as specified and directed.
M&L for painting on earth pit & cover , complete job & colour all as specified and directed.
M&L for painting on Earth pit marker /frame and writing earth pit No and earth pit for the equipment complete all as specified and directed.
Labour for rep/maint of of existing tilted/embeded earth pit by digging not exceeding 3 feet deep around earth pit , filling by nearby soil & re-adjusting the earth pit in proper manner all as directed .
M/S KAPIL CONSTRUCTION CO
JNK BOND
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .