Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.9 LAccepted-Finance C 5 156 YAMUNA VIHAR EAST DELHI DELHI 110053 | NORTH EAST DELHI | DELHI | 110053 | ₹97.9 L | L1 | Accepted-Finance Selected |
| 2 | L2₹98.8 L+₹90,162 (0.92%)Accepted-Finance 114 BASEMENT MALL ROAD KINGSWAYS CAMP NORTH WEST DELHI DELHI 110009 | NORTH | DELHI | 110009 | ₹98.8 L+₹90,162 (0.92%) | L2 | Accepted-Finance Selected |
Tender Value
₹78.4 L
EMD Value
₹1.6 L
Closing Date
10 Aug 2026, 12:00 pmClosed
Executive Engineer (E)
O/o EE(E) PWD EMD M-351, R.No.185, Old Sectt Delhi
RMO Electrical and Mechanical Services at Delhi Vidhan Sabha, Old Sectt., Delhi. (SH- Repair/ Replacement of Defective AC Chiller Plant, AHU and associated accessories).
2026_PWD_295875_1
32/2026-27/EMD M-351/EE(E)/2nd Call
Open Tender
Electrical Works
Percentage
90 days
Delhi Vidhan Sabha
Please refer Tender documents.
10 documents required · 10 mandatory
₹0
₹1.6 L
7 Sept 2026
24 Jul 2026
10 Aug 2026
24 Jul 2026
10 Aug 2026
24 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1AIR COOLED SCROLL CHILLERS Supplying, installation, testing and commissioning of following capacity Air-Cooled Scroll Chiller package complete with VFD (Variable Frequency Drive), hermetic/semi hermetic, multiple scroll type compressors each with step less capacity control of 25 % to 100 % of the rated capacity, with microprocessor based control panel, motor, starter panel (VFD), machine mounted, aircooled condensers, factory fitted chiller insulation, water flow switch , vibration spring Isolators, victaulic couplings, integral refrigerant piping and wiring with single/ two circuits, automatic and safety controls mounted in central console panel and i/c suitable foundation/mounting structure made of RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-incharge. Motor shall be suitable for 415V ±10% 50 cycles. 3 phase AC supply. Refrigerant gas used shall be R-410A. The chiller shall be Building Management System (BMS) compatible The system shall be in confirmation to IS : 16590 and CPWD Specification as amended upto date. BEE Star labeling and CPWD Specification as amended upto date and tested as per IS 16590. Chilled water Leaving Temp. (6.67 0C) Chilled water Entering Temp. (12.2 0C) Evaporator fouling factor = 0.018 m2. 0C/Kw Condenser air entering temp. : As per Site Dry Bulb Temperature Suitable for Seismic Zone and Altitude as per location/site. Microprocessor based controller. | |||||
| 1.01 | 3 x 50 TR BEE 3 Star Rated | 150 | TR | 21,991 | ₹32,98,650 |
| 2 | Supplying, installation, testing and commissioning of 7.5 KW/10 HP Monoblock pump set for the existing Central AC plant suitable for operation on 3 phase 415 volt 50 Hz. having discharge range at a head 14-22 mtr., having RPM 1430 RPM i/e connection etc. complete as required. | 6 | Nos | 52,728 | ₹3,16,368 |
| 3Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastomeric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. | |||||
| 3.01 | 150mm dia. (32 mm thick insulation) | 100 | Mtrs | 5,089 | ₹5,08,900 |
| 3.02 | 80mm dia.(32 mm thick insulation) | 80 | Mtrs | 2,656 | ₹2,12,480 |
| 3.03 | 65mm dia(32 mm thick insulation) | 130 | Mtrs | 2,139 | ₹2,78,070 |
| 4Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. | |||||
| 4.01 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified | - | - | - | - |
| 4.02 | 125 mm dia | 6 | Nos | 8,505 | ₹51,030 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.38 MB
32TenderNotice.pdf
Tender Documents • 2.36 MB
BOQ_393699.xls
BOQ • 0.43 MB
DateExtended.pdf
PDF • 0.01 MB
32Date.pdf
PDF • 0.55 MB
Corri-32.pdf
PDF • 0.62 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .