Superintending Engineer
Electricity Transmission Circle-I, U.P. Power Transmission Corporation Ltd. 57- George Town, Prayagraj
154-ETC-I(A)/ 2022-2023
2023_UPTCL_766749_3
154-ETC-I(A)/ 2022-2023
Open Tender
Electrical Works
Item Rate
60 days
Sangipur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE,ETC,PRAYAGRAJ
₹22,000
15 May 2023
14 Mar 2023
28 Mar 2023
14 Mar 2023
27 Mar 2023
14 Mar 2023
Amount
Erection, Testing and commissioning of 160 MVA 220/132 kV Transformer-II
Filling the T/F oil in oil tank and its centrifuging upto required BDV value and creating the vacuum inside the 160MVA T/F before filling the T/F oil inside the main tank.
Safe handelling and shifting of all acces. Of new 160MVA T/F-II such as radiators, conservator tank, bushing, coolings fans, motor drive mechanism of RTCC panel, oil pipe lie etc. from store place of subsatation sangipur to erections site including other associated work also if required for compltetion of job satisfactorly.
Complete erection of 220/132/11 KV 160 MVA T/F -II by erection of radiator, conservator tank, all bushing, their turrets connection of pipe lines cooling fan,PRV,OSR, motor drive mechanism of tap changer, RTCC Panel and all associated oil pipe lines etc to complete the job satisfactorily including 1st filling of oil and topping up of transformer oil(not circulation) in tank, radiator, oil pipe lines, conservators tank etc. and attending the oil leakage if any and all other associated work for satisfactory completion of work at 220KV S/S Sangipur. Crane, T&P shall be provided by contractor, all assistance in getting the transformer AND successfully commissioned by providing qualified manpower till commissioning.Complete evacuation of main tank of transformer and filling of nitrogen in vacuum up to required pressure and again evacuation the transformer tank after required time interval using centrifuging machine. Scope of work involves providing nitrogen gas or dry air generator having dew point 60 to 65 degree centigrade and filling it in main tank of transformer up to pressure of 5PSI or as per instruction of site engineer of BHEL and maintaining it in the tank as per direction of service engineer required for dry out of T/F. This process shall be repeated till the desired value of 5PPM or as direction of BHEL service engineer.
Centrifuging of complete T/Fs oil in T/Fs main tank by connecting centrifuging pipes circulating the T/F oil through centrifuging machineand taking the BDV, meggar value & IR values of the oil periodically till the required value in achieved as per direction of Supervising Engineer. The work includes all the work related to centrifuging the oil and filling the oil in T/F tank(centrifuging machine and operator shall be arranged by the contractor)
Laying, dressing and binding of cable including fixing of cable tray support structure and termination of cable making the top and its ferruling as per schedule and inter connection as per as per requirement of turrets , WTI, OTI, Bucholz relay, PRV, cooling fans, Pumps, OLTC, marshaling box etc. with proper ferruling as per drawing etc.
Earthing of T/F body, marshaling box, OLTC, RTCC Panel, at two point with 75x10 mm and 50x6mm M.S Flat from 40mm M.S Round(M.S Flat to be provided by departement)
Painting of earthing strips above the ground level by one coat of red oxide and two coat of bus green paint.
Delta earthing for 220/132/11 kv ,160 MVA T/F consisting of delta set with 3 nos.40 mm dia size 3 Mtrs. Long electrode its placing inside the ground and connecting all the three electrodes with 75x10mm M.S Flat 700 mm deep and connecting the same with eartmat at two places ( M.S round bar & flat provided by the department)
carriage of 40/20 KL oil tank including loading and unloading from UPPTCL s/s to 220 kv Sangipur s/s within approx 120 km distance
Testing of centrifuge T/F oil (DGA, ppm, BDV)of 160 MVA T/F at 220/132 KV S/S Sangipur, from government approve laboratory at the time of commissioning of transformer and after charging on load (preferbarly after 15 days)
Pre-erection and pre-commissioning testing as per site requirement for charging of 160MVA, 220/132KV T/F at 220KV S/S Sangipur under ETD-Pratapgarh. Testing kit and skilled operator shall be provided by contractor on their own cost and job includes to and fro charges per visit. the details of Pre-erection and pre-commissioning test are as followes :
insulation resistance measurement
Current ratio of LV& HV bushing
OTI and WTI calibration .
Transformer primary, secondary and tertiary winding capacitance, dissipation factor (Tan delta test), bushing capacitance test before erection and after erection on T/F.
Protection rely operation check.
Magnetizing current test
Vector group test.
Open circuit &Short circuit test
Magnetizing balance test
Voltage ratio test
winding resistance Measurement
Erection, Testing and commissioning of 40 MVA 220/132 kV Transformer-II
Centrifuging of complete T/Fs oil in T/Fs main tank by connecting centrifuging pipes circulating the T/F oil through centrifuging machineand taking the BDV, meggar value & IR values of the oil periodically till the required value in achieved as per direction of Supervising Engineer. The work includes all the work related to centrifuging the oil and filling the oil in T/F tank(centrifuging machine and operator shall be arranged by the contractor)
Testing of centrifuge T/F oil (DGA, ppm, BDV)of 40 MVA T/F at 220/132 KV S/S Sangipur, from government approve laboratory after charging of transformer on load (preferbarly after 15 days)
pre-commissioning testing as per site requirement for charging of 40MVA, 220/132KV T/F at 220KV S/S Sangipur under ETD-Pratapgarh. Testing kit and skilled operator shall be provided by contractor on their own cost and job includes to and fro charges per visit. the details of pre-commissioning test are as followes :
insulation resistance measurement
Current ratio of LV& HV bushing
OTI and WTI calibration .
Protection rely operation check.
Magnetizing current test
Vector group test.
Open circuit &Short circuit test
Magnetizing balance test
Voltage ratio test
winding resistance Measurement
Erection of following equipments as per instruction manual of various equipments and technical specification including shifting of material/equipment from store to erection site including all other associated work to complete the job satisfactorily.
Erection, Testing and commissioning of 250KVA, 33/0.4 KV Station T/F with all access. and fittings As per maunal as direction of enginner incharge
Erection of 36 KV Current Transformer (800-400-200/1A) with all accss. & fittings
Erection, Testing and commissioning of 245kV Line Isolators with one earth switch (Motorised) with all accs., disconnector box & fitiings as per manufacture manual
Erection, Testing and commissioning of 245kV Tandem Isolators (Motorised) with all accs., Disconnector box & fitiings as per manufacture manual
36kV Drop Out Fuse Set with Post Insulators
Alingnment, Testing and commissioning of 245kV Bus Isolators without E/S (Motorised) with all accs. & fitiings as per manufacture manual
Erection and commissioning of 245kV Post Insulators for support
Erection of Pale Fencing
Termination of following size of power cable by providing proper size of Aluminum Dowell/Jenison make lugs its crimping and connecting with equipments including cost of lugs and all other associated works to complete the work satisfactorily as per technical specification. The rates of termination of power cable includes the all cores of cable at one end with lug)
400 sq mm power cable terminations
Erection of Auxiliary Structure, mast etc required for installation of CTs, LA,TI,PI,BSI etc at 220KV S/S Sangipur. The job consist shifting of all material i.e. structure parts, nuts, bolts, washers etc, from store to site of erection. Erection of structure as per relevant drawing and using flat/spring washer with each bolt matching holes, cutting notching of members if required shall also be done by the contractor without any extra cost of complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor on his own cost.
Interconnection & jumpering of various equipments with ACSR Zebra between Main and Transfer Bus Conductors, jack bus, Post Insulator equipments with the help of suitable clamps (to be provided by department) with all other associated cutting , bending and shifting of conductor works forsatisfactory completion of the job as per technical specifications. (1 Job includes Interconnection and jumpering of all the equipments in that Bay) :
Transportation of 160 MVA T/F from 220 KV Substation Sahupuri to 220KV S/S Sangipur (Pratapgarh) including gasket replacement, loading, unloading and shifting approx 80MTR of T/f at both substation if required.
Katyani Construction Co.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .