GE I RND Delhi
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REAPIR/MAINT OF TRANSFORMER, VCB PANEL INCLUDING OF HT CABLES AND CERTAIN ALLIED MISC WORKS AT METCALFE HOUSE AND JCB LAB AREA UNDER GE I RND DELHI
2026_MES_799743_1
GE/RND/T-62/DLI/2026-2027
Open Tender
Civil Works
Item Rate
180 days
Delhi
Class D and Cat b(i)
2 documents required · 2 mandatory
₹500
Yes
GE I RND Delhi
₹74,420
Yes
21 Nov 2026
21 Nov 2026
19 Dec 2026
21 Nov 2026
12 Dec 2026
5 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for disconnecting HT 11 KV electric after taking proper shut-down and taking out defective unserviceable VCB trolley/RMU of HT 11 KV, of capacity 400 to 1250 A of any make and type carefully for cleaning and servicing of HT 11 KV panel and VCB trolley by cleaning isolating contacts moving fixed parts removing dust/carbon particles from bus bar chamber spout gear mechanism including calibration for all relays and proper setting of moving parts, repair to motor charge spring mechanism tightening of nut and bolts of entire trolley components and all electric/control connections, relay/metering connections etc. and replacement of all unserviceable pasts/spares as required and all as directed, inserting in trolley, testing commissioning and putting on the supply on load complete all as specified and directed.
Note: - (i) Cleaning/Servicing/Repairs will be carried out by expert Technician of OEM's authorised dealer only.
(ii) All spares/parts shall be required for repair/replacement shall be same company/manufacture of VCB as of existing make or as recommended by the OEM.
(iii) The cost of all kind of replaced defective parts/spare etc, other than mentioned in BOQ/Sch A, as and when required to making the HT 11 KV VCB Panel fully functional, is deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect.
(iv) Any major spares/ parts required for making the motor serviceable shall be measured and paid separately under relevant items of Sch.
(v) All T&P, testing equipments shall be arranged by contractor and are deemed included in the quoted rate.
(vi) The complete test report shall be submitted by the contractor to Engineer-in-Charge. | 27 | Each Job | 100 | ₹2,700 |
| 2 | Calibration of IDMT/ BUCHHOLZ relay of 11KV HT TRF in and including setting of relay's (PSM & TMS), installed at Main Receiving Sub-station, DESIDOC, ISSA, CEPTEM and DCDA Sub-station complete all as specified and directed.
Note:- (i). All testing and calibration equipment by the contractor and rate for same is deemed to be included in quoted rates.
(ii). The complete Calibration reports shall be submitted to EIC.
(iii) Calibration will be carried out by expert Technician of OEM's or his authorised dealer only. | 27 | Each Job | 100 | ₹2,700 |
| 3 | Supply, fix, installation, testing and Calibration of electromechanical/ numerical type IDMT over current and earth fault relay of 11KV HT VCBs, suitable for CT's output 1A and 5A in and including setting of relay's (PSM & TMS), installed at Main Receiving Sub-station, DESIDOC, ISSA, CEPTEM and DCDA Sub-station complete all as specified and directed.
Note:- (i) All testing and calibration equipment with all accessories shall be brought by the contractor and rate for same is deemed to be included in quated rates.
(ii) The complete Calibration and test reports shall be submitted to EIC.
(iii) Installation of IDMT relay will be carried out by expert Technician of OEM's or authorised dealer only. | 4 | Each | 100 | ₹400 |
| 4 | S&F in replacement of fuse base suitable for cylindrical /DIN type HRC fuse of capacity 2-32A complete all as specified and directed. | 6 | Each | 100 | ₹600 |
| 5 | S&F in replacement of closing spring assembly complete all as specified and directed. | 6 | Each | 100 | ₹600 |
| 6 | S&F in replacement of tripping spring assembly complete all as specified and directed. | 8 | Each | 100 | ₹800 |
| 7 | S&F in replacement of charging motor and cut off limit switch complete all as specified and directed. | 5 | Each | 100 | ₹500 |
| 8 | S&F in replacement of spring charging handle motorized mechanism complete all as specified and directed. | 7 | Each | 100 | ₹700 |
| 9 | S&F in replacement of push button bracket assembly complete all as specified and directed. | 8 | Each | 100 | ₹800 |
| 10 | S&F in replacement of bus bar support insulator 75mm diameter including all fixing accessories complete suitable for VCB/HT Bus bar chamber with colour coding all as specified and directed. | 10 | Each set of three | 100 | ₹1,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.61 MB
BOQ_897308.xls
BOQ • 0.73 MB
TDR.pdf
Tender Documents • 1.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .