Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹7.1 L+₹18,570.92 (2.68%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹8.6 L+₹1.7 L (24.4%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹10.0 L+₹3.0 L (43.9%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹10.6 L+₹3.7 L (53.1%)Rejected-Finance GP RAM COLONY AMRITSAR JALANDHAR 144103 | AMRITSAR | AMRITSAR | PUNJAB | 144103 | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
2 May 2022, 6:00 pmClosed
AGE(I) AIR FORCE AMRITSAR
ASST. GARRISON ENGINEER AIR FORCE STATION AMRITSAR
REPAIR TO CONVENTIONAL STREET LIGHT, PERIMETER LIGHT WITH LED FITTINGS AND REPAIR TO DG SET AT AIR FORCE STATION AMRITSAR
2022_MES_517580_1
AGE(I) AF/ASR/T-05/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE(I) AIR FORCE AMRITSAR
CLASS E AND CATEGORY b(i)
8 documents required · 8 mandatory
₹500
Yes
AGE(I) AIR FORCE AMRITSAR
₹16,000
Yes
14 May 2022
11 Apr 2022
5 May 2022
11 Apr 2022
2 May 2022
18 Apr 2022
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cables and foundation of poles etc. and getting out complete all as spceified and directed.
Returning, filling in trenches (soil) including spreading leveling and well ramming in layers not exc 25 cm thick complete all as specified and directed.
Removal of surplus excavation soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L sand cushioning with a layer of dry river sand 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts. Complete all as specified and directed Note: Punned down thickness (overall 18cm), shall be considered for measurement and payment.
M&L, locally available , sub class 'B' bricks (old size) laid flat and dry in trenches over the cable for protectionprependicular to the direction of cable adjacent to each other complete all as specified and directed.
M&L, GI pipe light grade 40 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc all as specified and directed.
Supply , laying jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 35 Sqmm 4 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as specified and directed.
Supply , laying jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 25 Sqmm 4 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as specified and directed.
Supply , laying jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 16 Sqmm 4 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as specified and directed.
Material and labour for painting of steel tubular pole with 2 coats of synthetic enamel paint upto 1.5m above ground level (in white and black strips of 30cm each) and 2 coats of aluminum paint above 1.5 mtr height including cross arms, bracing ,clamps GI pipe fittings etc as per site after preparation of surface including writing pole Nos, feeder Type with black paint complete all as specified and directed.
Material and labour for painting of PCC pole with 1 coats of Cement base paint upto 1.5m above ground level (in white and black strips of 30cm each) and 2 coats of aluminum paint to bracing ,clamps GI pipe fittings etc as per site after preparation of surface including writing pole Nos, with black paint complete all as specified and directed.
Supply and fix in replacement, outdoor type, factory made cable junction box dust, weather and vermin proof, IP-65 protection, with aluminium bus bar strip 25mmx3mm and MCB 6Amps, 10KA, 'C' curve, MS strip of size 25mmx4mm made, MS clamps, bolts, Thimbles etc for fixing arrangement for each street light including cable gland and locking arrangements , complete all as specified and directed. Make Sintex
Supply and laying fixing 1.5 sqmm (nominal area) copper conductor, twin core, PVC insulated unsheathed cable, drawn in steel/PCC pole for connection to street light fitting and making incl PVC Pipe of suitable size connections, complete all as specified and directed.
S&F the following unsv parts of automatic mains failure (AMF) panel 12 v DC and 440 V AC supply operated system, all as specified and directed by engr-in-charge
(a) Alternator voltage monitor relay 3 phase 415 V
(b) Solid state electroniccard
(c) Battery charging rectifier 4 plate, 12 volts DC Cart No. 4.H878.07.000
(d) Self Start electronic cantrol panel
Supply and fixing of battery 12 Volts, 180 AH suitable for DG Set complete all as specified and directed.Make: Exide,Amron.
Supply and fixing of battery 12 Volts, 150 AH suitable for DG Set complete all as specified and directed.Make: Exide,Amron.
Supply and fixing driver for LED flood Light 100 Watt capacity all as specified and directed by engr-in-charge.
Supply and fixing driver for LED flood Light 150 Watt capacity all as specified and directed by engr-in-charge.
Supply and fixing driver for LED street Light 60 Watt capacity all as specified and directed by engr-in-charge.
Supply and fixing driver for LED street Light 70 Watt capacity all as specified and directed by engr-in-charge.
SERVICE AND MAINTENANCE OF DG SET
CAPACITY 25 KVA TO 45 KVA (a) Servicing of DG set 25 KVA to 45 KVA of any make including changing of engine oil sump gasket with nuts bolts and check the all nuts bolts complete of engine and alternator alogwith replacement of defective parts, complete all as specified and directed. Note : All parts make kirloskar (i) 25 KVA - 01 Nos (Sewage pump) (ii) 30 KVA - 03 Nos (SMC & 41 WEU Khasa PH No. 2 Domestic area) (iii) 35 KVA - 03 Nos (PH No. 01, Domestic area) PH No. 03 (Tecg area) & PH No 4 (Muradpur area) (iv) 45 KVA - 02 Nos (immols & Airmen Mess) (b) S&F in replacement lube oil filter element complete all as specified and directed by Engr-in-Charge. (c) S&F in replacement fuel filter element complete all as specified and directed by Engr-in-Charge. (d) General servicing of DG set by opening of tappet cover/top cover tappet clearance setting with injector timing adjustment refixing of tappet/top cover including replacement of tappet cover packing set, shellac/bostic tube all as directed. (e) S&F in replacement element air cleaner complete all as specified and directed by Engr-in-Charge. (f) Tighting of all electrical connection AVR connection, alternator connection and panel connections. (g) Tightining of all the hoses, Fuel connection. (h) Testing of Engine on load for 30 Minutes.
CAPACITY 75 KVA TO 125 KVA (a) Servicing of DG set 75 KVA to 125 KVA of any make including changing of engine oil sump gasket with nuts bolts and check the all nuts bolts complete of engine and alternator alogwith replacement of defective parts, complete all as specified and directed. Note : All parts make kirloskar (i) 75 KVA - 01 Nos (AF Net) (ii) 82.5 KVA - 01 Nos (Muradpur for security light) (iii) 125 KVA - 02 Nos (PH No. 03 for security light & Radar) (b) S&F in replacement lube oil filter element complete all as specified and directed by Engr-in-Charge. (c) S&F in replacement fuel filter element complete all as specified and directed by Engr-in-Charge. (d) General servicing of DG set by opening of tappet cover/top cover tappet clearance setting with injector timing adjustment refixing of tappet/top cover including replacement of tappet cover packing set, shellac/bostic tube all as directed. (e) S&F in replacement element air cleaner complete all as specified and directed by Engr-in-Charge. (f) Tighting of all electrical connection AVR connection, alternator connection and panel connections. (g) Tightining of all the hoses, Fuel connection. (h) Testing of Engine on load for 30 Minutes.
CAPACITY 200 KVA TO 250 KVA (a) Servicing of DG set 200 KVA to 250 KVA of any make including changing of engine oil sump gasket with nuts bolts and check the all nuts bolts complete of engine and alternator alogwith replacement of defective parts, complete all as specified and directed. Note : All parts make kirloskar (i) 200 KVA - 01 Nos (Muradpur area) (ii) 250 KVA - 01 Nos (RPH Tech area) (b) S&F in replacement lube oil filter element complete all as specified and directed by Engr-in-Charge. (c) S&F in replacement fuel filter element complete all as specified and directed by Engr-in-Charge. (d) General servicing of DG set by opening of tappet cover/top cover tappet clearance setting with injector timing adjustment refixing of tappet/top cover including replacement of tappet cover packing set, shellac/bostic tube all as directed. (e) S&F in replacement element air cleaner complete all as specified and directed by Engr-in-Charge. (f) Tighting of all electrical connection AVR connection, alternator connection and panel connections. (g) Tightining of all the hoses, Fuel connection. (h) Testing of Engine on load for 30 Minutes.
M&L for repairing cleaning/ servicing of radiator assembly of DG set including decaling of tubes with solution and chemicals and compressed air blast including soldering/gas welding of leaking tubes including cutting welding of rusted ms tubes with new tubes transportation to workshop, and back and re fixing after testing complete and making it leak proof complete all as specified and directed.
S&F fan belt set of DG set of existing size complete all as specified and directed engineer –in-charge
S&F in replacement head gasket of DG set complete.
M&L for rewinding of DG set self start assembly of any capacity with super enamelled copper winding wire of existing gauge including replacement of unserviceable spare parts of existing make and re-assembling connecting and testing on load all as directed by the Engr-in-charge.
Supply and filling of multigrade Diesel engine oil 20w/40 suitable for DG Set complete all as specified and directed.
Supply only coolant suitable for DG Set against respective items, complete all as specified and directed.
Demolition of cement concrete ( unreinforced) of any description and in any position not otherwise specially provided for including removal of debries out of defence land complete all as specified and directed
Material and labour for 100 mm thick plain cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in sub base of floors, complete all as specified and directed.
Material and labour for 50 mm thick plain cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as in floors, finished the surface even and fair, complete all as specified and directed.
Note: The Total amount shall subject to adjustment of credit for old Materials as per Schedule of Credit.
pee kay construction
innovative associates
kapoor and co
AAR KAY BEE ENTERPRISES
M/S SIMRAN WALIA ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .