Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹24.8 LAccepted-AOC 41 A COLONELGANJ CANTT FATEHGARH DISTT FARRUKHABAD UP 209601 | FATEHGARH | FARRUKHABAD | UP | 209601 | 1 | Accepted-AOC Being lowest | |
| 2 | 2₹27.7 L+₹2.9 L (11.5%)Rejected-Finance | 2 | Rejected-Finance Not being lowest | |
| 3 | 3₹34.9 L+₹10.1 L (40.6%)Rejected-Finance | 3 | Rejected-Finance Not being lowest |
Tender Value
₹27.1 L
EMD Value
₹54,280
Closing Date
30 Oct 2021, 6:00 pmClosed
HQ CWE Agra
112 Taj Road Agra Cantt
PROVISION OF MEDICAL GAS PIPE LINE SYSTEM FOR CENTRALIZED SUPPLY OF MEDICAL GASES FOR COVID-19 WARDS UNDER AGE (I) FATEHGARH
2021_MES_473581_2
86086/E8
Open Tender
Civil Works
Item Rate
120 days
Fatehgarh
MES contractors enlisted in Class D category a(i) and b(i) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹500
AGE (I) Fatehgarh
₹54,280
Yes
8 Nov 2021
13 Oct 2021
5 Nov 2021
13 Oct 2021
30 Oct 2021
16 Oct 2021
13 Oct 2021 - 15 Oct 2021
Amount
Excavation in trenches, n. exc. 1.5 m wide and n. exc. 1.5 m in depth, for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, etc n.exc. 10 sqm on plan and n. exc. 1.5 m in depth and getting out in soft / loose etc complete all as specified and directed.
Excavation in post holes (or similar holes) each n.exc 0.5 cum in any type of soil, getting out, returning, filling in, watering and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm and removing surplus soil to a distance n.exc 50m and making good surfaces complete all as specified and directed.
M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) as in foundation, filling & mass concrete, sub base complete all as specified and directed.
M&L for plain cement concrete 1:2:4 type B-2 (using 40mm graded stone aggregate) as in posts including caps and bases complete all as specified and directed.
M&L for moorum / red bajri filling in floors or pavings, laid in layers n. exc. 15 cm thick, spread, levelled and rammed including watering etc complete all as specified and directed.
M&L Brick work with sub class 'B' bricks (using old size brick work) straight or curved on plan exc 6m mean radius built in CM 1:6 Complete all as Specified and directed
M&L 15 mm thick rendering in CM (1:4) on fair faces of brick work or concrete surfaces and finishing the surfaces even and smooth without using exra cement complete all as specified and directed.
M&L 15 mm thick rendering in CM (1:6) on stone masonry surfaces or surfaces other than fair faces of brick work or concrete surfaces and finishing the surfaces even and smooth without using extra cement complete all as specified and directed.
M&L preparation of newly plastered surfaces of wall and applying two coats of cement base paint over a coat of white cement primer on walls complete all as specified and directed.
M&L preparation of newly plastered surfaces of wall and applying three coats of white wash on walls complete all as specified and directed.
S&F mild steel framed work such as grills, gratings etc with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framed work and similar works conforming to Fe-290 Gd E-165 complete all as specified and directed.
S&F for MS pipes as in vertical posts fixed with angle cleats or other connecting plates, rivets, nut bolts etc conforming to Fe-410W (Gde E-250) quality B etc complete all as specified and directed.
S&F rolled mild steel in roof trusses, (framed), trussed purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee,angle,channel or flat sections) including distance pieces, cleats etc. conforming to Fe-410-W Gde E-250 quality A including necessary welding / jointing and related work etc complete all as specified and directed.
M&L for MS work as in framed work as in doors or gates of angle or other section with gusset plates, rails, braces etc complete drilled for fixing of steel sheeting or other covering, doors, etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering running rails and guides) and hanging, also fasterning and fixing complete conforming to Fe-410 W (Gde E-250) quality A complete all as specified and directed.
S&F for expanded metal n. exc. 4 Kg per sqm, cut to length, bent to shape required and tying with and including annealed mild steel wire not less than 0.9 mm dia or fixing with galvanized steel staples supplied and fixed complete to wood or steel members etc complete all as specified and directed.
S&F for Pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screws complete all as specified and directed.
S&F for Pre-painted galvalume aluminium zinc coating GI based plain steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screws complete all as specified and directed.
M&L for hardcore of broken stone gauge n. exc. 63 mm, deposited, spread and levelled in layers n. exc. 15 cm thick, watered and rammed to a true surface etc complete all as specified and directed.
M&L for plain cement concrete 75 mm thick type C-1, 1:3:6 (20 mm graded stone aggregate) as in plinth protection complete all as specified and directed.
M&L for two coat of synthetic enamel paint over a coat of red oxide primer, including preparation of new steel surfaces of any description over 10 cm in width or girth, not otherwise described etc complete all as specified and directed.
M&L for surface excavation not exc 30 cm deep and averaging 15 cm deep and getting out in soft / loose soil, complete all as specified and directed
M&L for plain cement concrete 100mm thick with 1:2:4 type B-2 (using 40 mm graded stone aggregate) laid in alternative bays (size of panels not exc. 2.00 m x 2.00m) including finishing surface of concrete pavement by brooming and filling the joints with a mixture of sand and bitumen (1:1) complete all as specified and directed.
Ditto all as per item No. 25 above but copper pipe of size 15 mm OD and 0.9 mm thickness complete
Ditto all as per item No. 25 above but copper pipe of size 22 mm OD and 0.9 mm thickness complete
Supply installation, testing and commissioning of Oxygen gas outlet point with probe confirming to DIN type complete all as specified and directed.
Supply installation, testing and commissioning of Bed Head panel 3' length with 2 outlet and socket point complete all as specified and directed.
Supply installation, testing and commissioning of Medical Gas alarm Panel (Analog type) for 1 gas service complete all as specified and directed.
Supply installation, testing and commissioning of fully automatic panel for oxygen manifold system complete all as specified and directed.
Supply, installation, commissioning & testing of oxygen manifold extendable type confirming to ISO standards without cylinder suitable to withstand a pressure 145Kg / Sqcm, along with high pressure copper annealed tail pipes with end brass adapter suitable for 8+8 manifold oxygen cylinder and manifold, top frame comprising of high pressure copper pipe of size 1/2" ID x 15 SWG with high pressure brass fittings made of high tensile brass and connection through non return valve of non halogenated polymer materials, high pressure copper tail pipes, made of high pressure copper pipe of size 1/4" ID x 15 SGW..The design of middle and bottom frames should be provided to fit both round and flat bottom cylinder safety. The manifold shall be tested hydraulically and necessary test certificate must be produced with the supply and necessary pointing with specified colour code complete all as specified and directed.. Make :- Oxicareengineers / Globalmedlife solution / Lifeline medisal / AKTIV / LMPL
Supply, installation, commissioning & testing of oxygen manifold extendable type confirming to ISO standards without cylinder suitable to withstand a pressure 145Kg / Sqcm, along with high pressure copper annealed tail pipes with end brass adapter suitable for 2+2 manifold oxygen cylinder and manifold, top frame comprising of high pressure copper pipe of size 1/2" ID x 15 SWG with high pressure brass fittings made of high tensile brass and connection through non return valve of non halogenated polymer materials, high pressure copper tail pipes, made of high pressure copper pipe of size 1/4" ID x 15 SGW..The design of middle and bottom frames should be provided to fit both round and flat bottom cylinder safety. The manifold shall be tested hydraulically and necessary test certificate must be produced with the supply and necessary pointing with specified colour code complete all as specified and directed.. Make :- Oxicareengineers / Globalmedlife solution / Lifeline medisal / AKTIV / LMPL
Note for item No.32 & 33 :- (a) The cylinder will be provided by user. (b) The quoted rate is deemed to be inclusive for the provn of cylinder brackets and fixing chains which will be zinc plated for cylinder placing arrangement. (c) The manifold shall be tested (hydraulically) at 250 Kg / Sq cm and the rate inclusive for the same. Each header bar shall be with pigtail connections to suit cylinder valves as per IS : 3224. (d) The copper tail pipes are fitted to the individual non return valves of the cylinder oxygen manifold for easy removal of cylinders without disturbance to system operation and the rate inclusive for the same. (e) The sizes of copper pipe mentioned are of minium size and the quoted rate deemed to be inclusive of provn of higher sizes, if any, as per OEM requirement.
Supply, installation, commissioning & testing of 12 mm OD medical line valve or isolation valve as per CE certified / HTM-2022/02-01/DIN/ISO/BS EN 1057 as per BS1057, rated at 400 Psig as well as full vaccume (29.9" Hg) valves go from full ON to full OFF by turning the vinylgripped valve handle 90 degree locking type handles and copper tubing is factory installed to pravent valve seat damage during soldering and connection to copper pipe complete all as specified and directed. Make :- CONEX /RB/RN/SIM/AUDCO/AKTIV
All as per item No.34 above but valve size 15 mm OD complete all as specified and directed.
All as per item No.34 above but valve size 22 mm OD complete all as specified and directed.
Supply, installation, testing and commissioning of BPC flow meter with humidifier bottle 0-15 LPM flow rating complete all as specified and directed.
Supply, laying and testing LT XLPE insulated, armoured heavy duty electric cable 70 sqmm, 3.5 core, screed PVC bedded with aluminium conductor 1100 V grade ISI marked, IS : 7098 Part-I, laid in trenches / along poles, ducts or through sleeve including taking out existing unserviceable cable complete all as specified and directed. Note :- Earth work, sand cushioning and bricks will be measured and paid separately under relevant items.
All as per item No. 38 above but size 35 sqmm 3.5 core complete all as specified and directed.
All as per item No. 38 above but size 10 sqmm 2 core complete all as specified and directed.
Supply & installation of steel tubular swaged & welded pole 9.0 m long type 410 SP-31 complete with CI base plate and finial tapper plug, bolts nuts screw conforming to SI : 2713 (Part-I to III) complete painting of pole with two coat of aluminium paint over a coat of red oxide primer and applying one coat of synthetic enamel paint alternate yellow & black strips painting ( 05 Nos each strip 300 mm wide) complete all as specified and directed.
M&L writing letters or figure (block, Roman, Italic or Indian) n. exc. 30 cm high complete all as specified and directed at site.
S&Fstreet light IP-66 LED light fitting of capacity 70 watt, 240 volts single phase 50 Hz consisting of aluminium pressure die cast housing with street optic LENS for uniform light distribution with glass silicon gaskets complete compact & trendy assembly with LED and accessories toughened glass prewired upto terminal block confirming to IS 10322 part 5/sec 1 : 1967 with inbuilt integrated electronic LED driver with driver efficiency >85%, 50,000 burning hours as per L70 criteria power factor > 0.95, THD < 10% voltage surge protection not less than 3 KV,multistage isolated constant current- constant voltage operated driver with range 150-270 V AC and safety of extra low voltage safe level <60V DC as per IEC standard, the LED lumen output colour temperature to 6500K, with luminous efficiency of 125 lm / watts with LM 79 & LM 80 certification complete all as specified and directed. Cat part No.LR02-781-XXX-57-G2 of make Wipro or equivalent of Philips / Bajaj / Syska/Jaquar
M&L for DL Thermoplastic cable junction boxes IS 65 with metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 3.5/4 core and fixed to the PCC / steel poles by means of suitable size of clamp with nut and bolts and including provn for fixing 01 No of single pole MCB SP 0.5-3 Amp 'C' series inside the box and complete all as specified and directed. Make :- Sintex / Hensel
S&F street light bracket made out of GI tubing 40 mm bore medium grade n. exc. 1.5 metre long bent to shape as directed including suitable MS clamp of FI 50 x 6 mm with MS bolts nuts and washer fixed to steel tubular pole / PCC pole duly painted with two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
M&L for boring holes horizontally under road (trenchless) without damaging the surface of road (minimum 1.0 metre below the road surface with the help of GI tubing not exc. 80 mm bore (dia) for passing UG cable, complete all as specified and directed. Note :- GI pipe will be measured and paid separately under respective item.
S&F 80 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor / wall for cable protection with suitable size of MS clamps nut and bolts / washers complete all as specified and directed.
S&F 40 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor / wall for cable protection with suitable size of MS clamps nut and bolts / washers complete all as specified and directed.
Supply, installation, commissioning and testing out door type LT feeder pillar box size 0.90 m x 0.75 m x 0.45 m in depth as per IS : 61439 made out of 3.15 mm thick CRCA sheet and MS structural section of 50 x 50 x 6 mm comprising of copper bus bar suitable for 3 phase, 4 wire, 415 volts, 50 Hz, AC supply mounted on suitable bus bar insulators, 200 Amps rating suitably drilled and tapped for bolts with openable two part front and rear shutter, hinged front and rear panels and locking arrangement, bottom plate provided with the require numbers of cable entries / opening including cable glands and cable lugs with heat shrinkable PVC sleeving having RYB-B colour code, powder coated, with two coat of synethetic enamel paint over a coat of red oxide primer complete embedded in PCC 1:3:6 type C-2 (using 40 mm graded aggregate) n. exc. 0.45 cum including with following complete all as specified and directed :- INCOMER (a) MCCB 4 pole, 100 Amp, Icu=16 KA with thermal magnatic release & adjustable over load (min 70% to 100%), Ics=100% Icu=01 No. OUTGOING (a) MCCB 4 pole, 63 Amp, Icu=16 KA with thermal magnatic release & adjustable over load (min 70% to 100%), Ics=100% Icu=01 No. (b) Amper meter (96 mx 96 mm) digital type incl CT coils - 01 (0 to 200 Amp) (c) Volt meter (96 mm x 96 mm) digital type - 01 No (0 to 500 V)
Excavation in trenches in soft / loose soil n. exc. 1.5 mtr wide and n.exc. 1.5 mtr depth and getting out pole foundation / cable trench complete all as specified and directed.
M&L for returning filling in soft / loose soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick complete all as specified and directed.
M&L for Removal of surplus excavated soil to a distance not exc 50 mtr and deposting where directed at a level n.exc 1.5 m above the starting point, complete all as specified and directed .
M&L for sand cushioning with dry clean sand 8 cm below cable and 15 cm above the cable complete all as specified and directed.
Supply and laying burnt bricks in trenches for cable protection with length of brick perpendicular to length of cable complete all as specified and directed.
Supply, installation, testing and commissioning of diesel engine driven generating water cooled set with acoustic cover to control the noise level as per limit of central pollution control board (CPCB) 20 KVA capacity 3 phase 415 volts, 1500 RPM, 4 wire, 50 Hz with following and including two year maintenance spares and set of tools as recommended by manufacturer comprising the following complete all as specified and directed :- (A) PRIMER MOVER :- Suitable for driving 20 KVA alternator, water cooled, battery start diesel engine as per IS : 10001/10002 of adequate BHP conforming to BSS frame pedestal support with anti vibration pad rated for continuous running capable of taking 10% over load for one hour in any 12 hours operation with following standard accessories for engine (i) Battery as per OEM recommended (ii) Fly wheel and flexible coupling with guard (iii) Hour meter and RPM meter (iv) Instrument panel with Lubricant oil termpature and pressure gauge, battery charge indicator meter, high temperature gauge (v) Fuel tank as per manufacture design (vi) Exhaust pipe brought out side the room covered with 12 mm dia asbestos rope, supply and installation of silent Diesel engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS : 10001 / 10002 and
(B) ALTERNATOR : Alternator shall be brush less type, suitable for continuous operation at 1500 RPM developing 415 volts, 3 phase, 4 wire, 50 Hz, 0.8 power factor (lagging) under NTP conditions in accordance with IS -4722, 4 pole, screen protected, drip roof, horizontal foot mounted type, the degree of protection will be IP-23 enclosure, voltage regulation +/- 1%, self excited & self regulated with static excitation system, Class 'H' insulation and operation will be suitable for tropical condition at Fatehgarh. (C) AMF PANEL :- AMF panel for 20 KVA DG set factory made enclosure of CRCA sheet cubical type floor mounted complete with internal connection of and accessories including digital type volt meter, ammeter, frequency meter, power factor meter, indicators, set of relays and associated accessories for starting the engine on main feature as well low voltage, over and under voltage relay, auxillary contactor with timer (On delay). Note :- (i) Any fittings / fixture are deemed to be included above which are required for its proper functioning (ii) Necessary foundation for installation of DG set shall be provided as per manufacture design and cost is deemed to be inclusive in the unit quoted rate. (iii) Make of AMF panel shall be as per recommendation of manufacturer / OEM of the DG set. Engine - Kirloskar / Ashok Leyland / Greaves Cotton / Cummins Alternator - Crompton / Jyoti / Stamford / Kirloskar electric OEM - M/S Powerica / M/S Sudhir / M/S Jackson / Prasha / C&S / GPS Power System Pvt Ltd / Perfect Generators Technologies Pvt Ltd / Tanwar Industries
M&L for earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 M below normal ground level ) with top edge of the plate not less than 1.50 M below normal ground level connected to and including galvanized steel Strip of size 25 x 4 mm as earth lead soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers, of galvanized iron or steel with connected to pole test point and testing on completion including 40 mm GI light grade pipe for earth lead protection from earth point to earth plate, including provn adequate quantity of charcoal dust mixed with 35 % common salt to a packed thickness of not less than 15 cm in alternate layers of charcoal and salt on all sides of earth plate with 20mm bore medium grade GI Pipe for watering,GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in any type of soil, returning filling in, removal of surplus soil to a distance 50 metre,,PCC 1:3:6 type C-1 as in earth pit, 40 mm thick RCC cover using cement concrete 1:2:4 type B-0 reinforced with & including 6 mm dia mild steel TMT bar @ 75 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified and shown in electrical plate No 3 of MES SSR Part I 2009 complete all as specified and directed. NOTES:- (i) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor. (ii) GI strip and protection light grade GI pipe (50 ECC grade) upto 7.5 mtr shall be deemed to be in the rates.
Supply only GI strips 25 x 4 mm and connecting from earth plate by means of nut, bolts and washer etc beyond 7.5 mtr complete all as specified and directed. Note :- This item will be measured and paid separately if strip is required at site beyond 7.5 mtr under item No.55
M/S shree traders
M/s Kamal Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .