Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.2 LAccepted-AOC ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | ₹14.2 L Quoted ₹14.8 L | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹15.3 L+₹47,163 (3.18%)Rejected-Finance | ₹15.3 L+₹47,163 (3.18%) | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹17.7 L+₹2.9 L (19.2%)Rejected-Finance | ₹17.7 L+₹2.9 L (19.2%) | L3 | Rejected-Finance Not Being Lowest |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
11 Sept 2021, 6:00 pmClosed
GE Chandigarh
GE Chandigarh
REPAIR/REPLACEMENT OF INTERNAL WIRING AND RENWAL OF LED TUBE LIGHT FITTING WITH SUBMAIN, DBs AND CERTAIN WATER SUPPLY INCLUDING ALLIED WORKS AT SEC 28/29 UNDER GE CHANDIGARH.
2021_MES_468668_1
GE/CHD-48/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE Chandigarh
Class E category b(i) for contractor enlisted in MES
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹40,000
Yes
22 Dec 2021
17 Aug 2021
13 Sept 2021
18 Aug 2021
11 Sept 2021
30 Aug 2021
18 Aug 2021 - 24 Aug 2021
Amount
Taking down carefully aluminum/copper point wiring (light, fan, socket or power) complete along with fittings such as switches, ceiling roses, pendants, regulators sockets etc, and removing from site and making good disturbed surfaces of walls, floors etc., all as directed.
Taking down existing unserviceable MCB DB along with MCBs complete by disconnecting all as directed.
Taking down existing unserviceable Tube Light fitting & box type fitting.
Taking down existing unserviceable sub main wiring with 2 Runs/4 Runs of 2.5/4/6 Sqmm aluminum/copper cable all as directed.
M&L for Point wiring complete with 1.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistrandad copper conductor, drawn through and including rigid non-metallic PVC conduit and conduit accessories fixed on surface of wall/ceilings or concealed etc., including provision of PVC insulated 1.5 Sqmm FRLS cable with copper conductor for earth continuity and connected to common earth dolly concealed in wall on top for housing the switches, socket outlet etc., all as specified and as directed for One light point controlled by one, one way 5 Amps switch.
All as per item No 5 above but One ceiling fan/exhaust fan point controlled by one, one way 5 Amps switch
All as per item No 5 above but One 3 pin socket outlet 5 Amps on independent board
All as per item No 5 above but One 3 pin socket outlet 5 Amps on same board
All as per item No 5 above but One light point controled by two, two way 5 Amps switches.
All as per item No 5 above but One bell/ buzzer point controled by one bell push on same board with other switches or on independent board.
M&L for Point wiring complete with 2.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non-metallic PVC conduit and conduit accessories fixed on surface of wall/ceilings or concealed etc., including provision of PVC insulated 2.5 Sqmm FRLS cable with copper conductor for earth continuity and connected to common earth dolly concealed in wall on top for housing the switches, socket outlet etc., all as specified and as directed .
M&L for Sub main wiring/power wiring complete with two runs of 4.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including suitable size of rigid non metallic PVC conduit pipe and accessories on surface wall/floors/concealed etc., with one run of PVC insulated, 4.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. MAKE : Polycab / Finolex / havells NOTE :- Two runs of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length.
All as per item No 12 here in above but with 2x6 Sqmm for phase and neutral and 1x6 Sqmm for earth wire complete. Make : Polycab / Finolex / havells/Plaza.
Disconnection and removing the u/s 3x1.5 Sqmm PVC insulated unsheathed cable from the existing conduit and M&L for 3x1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor drawn in the existing metal/ PVC conduit & Casing capping including connecting of the ends into the switch / socket/ DB complete. Note : Three runs of cable measured as one unit.
All as per Item No 14 here in above but of 3x2.5 Sqmm.
All as per Item No 14 here in above but of 3x4 Sqmm.
All as per Item No 14 here in above but of 3x6 Sqmm. Note: for item No 12 to 17: Make of PVC cables : Finolex/Polycab,Havells, Make of PVC Conduit Mecury/Sudhaker/Avon Plast
Supply and fixing switch piano flush type single pole one way 5 amps 230 volts. Make:- Anchor/SSK/Leader/Bajaj
Supply and fixing socket piano flush type universal 2 in 1,3 pin 5 Amps, 230 volts. Make :- Anchor/Cona/Leader/SSK
Supply and fixing switch piano flush type single pole one way 15 amps 230 volts. Make:- Anchor/SSK/Leader/Bajaj
Supply and fixing socket flush type universal 2 in 1, 3 pin 5 &15 Amps, 230 volts. Make :- Anchor/Cona/Leader/SSK
Supply and fixing two way switch universal 5 amps 230 volts. Make:- Anchor/SSK/Leader/Bajaj
Supply and fixing bell push universal 5 Amp, 230 volts. Make:- Anchor/SSK/Leader/Bajaj
Supply and Fixing Ceiling rose 3 terminal 5 Amps 230 volts PVC/Polycarbonate, insulated body. Make : Anchor/Cona/Leader/SSK
Supply and Fixing step type electronic fan regulator of capacity 100 watts 230 volts for ceiling / exhaust fan flush type. Make :- Anchor/Cona/Leader/SSK
Supply and Fixing Ding Dong Bell AC. 230 volts,. Make :- Anchor/Cona/Leader/SSK
Supply & Fixing 6 Amps 1 way one module switch complete. Make :- Anchor/Cona/Leader/SSK
Supply & Fixing 6 Amps 2/3 pin socket two module complete. Make :- Anchor/Cona/Leader/SSK
Supply & Fixing 6 Amps 2 way module switch complete. Make :- Anchor/Cona/Leader/SSK
Supply & Fixing 16 Amps one way one module switch complete. Make:- Anchor/Cona/Leader/SSK
Supply & Fixing modular multi socket outlet 6A/16 Amps 2/3 Pin socket 2 module complete. Make :- Anchor/Cona/Leader/SSK
Supply & Fixing 6 Amps bell push one module switch complete. Make :- Anchor/Cona/Leader/SSK
Disconnection and removing the u/s PVC casing caping and S&F PVC casing caping of size 20mm including cut to shape and size to match the existing conduits suitable for LT electric supply along with necessary fixing arrangements complete. Make : Pressfit/AKG/Prestolast
All as per Item No 33 here in above but of size 25mm
S&F MCB DB, SPN, 2 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 8 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 12 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB SP 6-32 Amps 230 volts 10 KA ISI marked complete all as specified and directed by Engg-in-Charge. Make : Legrand/L&T/ Siemens / Standard.
All as per Item No 38 here in above but of capacity MCB SPN 40 Amps
All as per Item No 38 here in above but of capacity MCB SPN 63 Amps
All as per Item No 38 here in above but of capacity MCB DP 63 Amps
Disconnection and removing the u/s MCB plug and socket unit and S&F Single pole and neutral enclosure with a two pin earth plug and socket complete controlled by one single pole MCB 20 Amps 240 Volts, complete all as specified and as directed. Note for Item No 35 to 42 : Make : IndoAsian/Siemens/ Standard/Havells/Legrand
Disconnection and removing the u/s light fitting and S&F as in repair batten for LED tube light 1X18/20 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with three core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed. MAKE:Philips/Wipro/C&S/Crompton
S&F as in repair LED tube Rod 18/20 Watt complete all as specified and directed by Engg-In-Charge.Make : Philips/Wipro/C&S/Crompton
Disconnection and removing the u/s light fitting and S&F as in repair batten for LED tube light 1X9 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed. Make : Philips/Wipro/C&S/Crompton
S&F as in repair LED tube rod 9/10W complete all as specified and directed by Engg-In-Charge. Make : Philips/Wipro/C&S/Crompton
Supply and Fixing lamp holder,Batten/ angular type, PVC/ polycarbonate with back plate of capacity 5 Amps 230 volts suitable for general lighting system complete all as specified and as directed. Make : Anchor/Cona/Leader/Bajaj
Disconnection and removing the u/s LED lamp and S&F LED lamp 9 watts complete all as spfd and directed. Make: Philips/Wipro /Halonix/Crompton
Disconnection and removing the u/s LED lamp and S&F LED lamp 12 watts complete all as specified and directed. Make : Philips/Wipro/Halonix/Crompton
S&f in repair LED inverter lamp 12 watt, 4 hrs backup time, cool white at mains supply and 450 lumens at backup 230 volt, 50 hz, all as specified and directed. Make : Crompton /Philips/Havells.
S&F as in repair batten Led 22 w inveter LED tube light complete fitting 230 volt energy saving, 04 hrs battery backup, CRI ≥80 more than, driver efficiency ≥ 85%, operating voltage 230 volt, 50hz operating temp (-10°C to 50°C) complete accessories internally pre wired and including connecting up with flexible copper conductor cable with suitable size complete all as specified and directed by engineer-in-charge. Make : Halonix/CG/Syska.
Supply & fixing energy efficient Intergral type 25W LED Street light luminaire comprising of epoxy powder coated hsg, enclosed with glass cover in frame mounted on MCPCB and testing compelte all as specified and directed Make:Havells/Bajaj/Crompton/Wipro/Finolex
Supply & fixing GI bracket of size 32mm dia from the pole / building and M&L for street light bracket made out of 25 mm dia GI tubing medium grade upto 1.5 mtr long including bending, welding ,drilling holes as required and fixing with flat iron clamps 50x 6 mm thick (02 Nos) with suitable nut, bolts and washers to building complete all as specified and as directed.
M&L for earthing with GI earth plate electrode 60cm x 60cm x 6.0 mm thick burried directly in ground vertically to depth of not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to GI earth wire of 4.0 mm dia by means of bolts, nuts, washers of GI and provision of earth lead, GI protection pipe with 15mm light grade galvanized including necessary earth work in any type of soil, PCC 1:3:6 type CI (using 20mm graded stone aggregate) earth chamber and 1:2:4 type B1 RCC cover fitted with50mm thick with 6mm dia MS bars complete all as shown in SSR Pt - 1 electrical plate No 3. Note : Qoted rate deemed to include the cost or excavation and earth work PCC Chamber, funnel cover etc. complete all as specified and directed by Engg-In-Charge
Taking down existing control board (Meter Box) and supply and fixing sheet metal board made of 1.6mm thick metal sheet and painting 2 coats with synthetic enamel paint over a coat of primer including copper bus bar and fixed with wall for fixing meter complete with wiring, fitting and accessories, locking arrangements with handle (minimum size of box 65cmx75cm and adequate depth for the following equipment, internal wiring and termination of external cable, lugs and glands and conduits as required complete all as specified and directed by Engg-In-Charge
Excavation in trenches in soft/loose soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth; for foundation, etc. and getting out complete, all as specified. NOTE:- (i) Excavation in trenches/Cutting of road etc at sector 28&29 to be done with consulation of UT Staff an it shall be the responsibility of the contractor. (ii) Cutting of road shall be repaired in consulation with UT staff. (iii) The rate shall deemed to be included for note (i) & (ii) above in the quoted rates by the contractor.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each, complete, all as specified.
Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete, all as specified.
S&F GI Tubes 15 mm bore, ‘medium grade’, ISI marked, galvanized with all fittings and fixed complete laid in trnches or walls and ceilings or laid in floors, complete all as specified. Make : JINDAL, TATA, BST, PRAKASH TUBES, OSWAL.
S&F GI Tubes 20 mm bore, ‘medium grade’, ISI marked, galvanized with all fittings and fixed complete laid in trnches or walls and ceilings or laid in floors, complete all as specified. Make : JINDAL, TATA, BST, PRAKASH TUBES.
S&F GI Tubes 25 mm bore, ‘medium grade’, ISI marked, galvanized with all fittings and fixed complete laid in trnches or walls and ceilings or laid in floors, complete all as specified. Make : JINDAL, TATA, BST, PRAKASH TUBES, OSWAL.
Taking up or down steel tubing and connections,15 mm bore complete all as specified and as directed.
Taking up or down steel tubing 20 mm bore and connections, including cleaning for re-fixing or removal to store complete all as specified.
Taking up or down steel tubing 25 mm bore and connections, including cleaning for re-fixing or removal to store complete all as specified.
Re-fixing old steel tubes and connections of size 15 mm bore in new or old position (walls, ceilings, floors/trenches etc.) complete all as specified. .
Re-fixing old steel tubes and connections of size 20 mm bore in new or old position (walls, ceilings, floors/trenches etc.) complete all as specified.
Re-fixing old steel tubes and connections of size 25 mm bore in new or old position (walls, ceilings, floors/trenches etc.) complete all as specified.
Cutting existing 15 mm bore, ‘medium grade’, galvanized tubes, for alteration or additions (Each cut measured) providing threads etc.complete all as directed by the Engineer- in-Charge.
Cutting existing 20 mm bore, ‘medium grade’, galvanized tubes, for alteration or additions (each cut measured) providing threads etc.complete all as directed by the Engineer- in-Charge.
Cutting existing 25 mm bore, ‘medium grade’, galvanized tubes, for alteration or additions (each cut measured) providing threads etc.complete all as directed by the Engineer- in-Charge.
Gun-metal, globe or gate valves, ISI marked with iron wheel head, screwed both ends for iron pipe and fixed of size 15mm dia, in repairs, complete all as specified. MAKE: SANT,BIR, ZOLOTO, KIRLOSKAR
Gun-metal, globe or gate valves, ISI marked with iron wheel head, screwed both ends for iron pipe and fixed of size 20mm dia, , complete all as specified. MAKE: SANT,BIR, ZOLOTO, KIRLOSKAR
Gun-metal, globe or gate valves, ISI marked with iron wheel head, screwed both ends for iron pipe and fixed of size 25mm dia, in repairs, complete all as specified. MAKE: SANT,BIR, ZOLOTO, KIRLOSKAR
S&F in Repair 15mm Bib taps, Cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and as directed. Make:-Jal,Jainko,Prayag, Shakti
Arresting of water leakage from existing pipe line in position from GI pipe of size 15mm bore ,including excavation through Men/Mechnical power ,cutting threading,welding as per site requirement, incl jointing material such as GI (Bend,socket,reducer,tee,funel, union ,solution,thread etc) and refilling etc complete all as specified. Note :- (i) Excavation up to 1x1x6 Mtr will be deem to incl in quoted rate. More excavation will be measured and paid saperately. (ii) Pipe length will be measured and paid saperately.
Arresting of water leakage from existing pipe line in position from GI pipe of size 20mm to 25mm bore ,including excavation through Men/Mechnical power ,cutting threading,welding as per site requirement, incl jointing material such as GI (Bend,socket,reducer,tee,funel, union ,solution,thread etc) and refilling etc complete all as specified. Note :- (i) Excavation up to 1x1x6 Mtr will be deem to incl in quoted rate. More excavation will be measured and paid saperately. (ii) Pipe length will be measured and paid saperately.
J V ELECTRICALS
SINGARI ELECTRICAL WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .