Electric Division JPDCL Udhampur
Creation of 100 KVA, 2X63 KVA Sub stations alongwith erection of 11 KV Line on 9 mtr. ST poles, 30mm Sq ACSR conductor, LT line on 8 mtr. ST pole at WSS Kashirah under JJM
2025_PDD_272007_1
ED/UDH/39A of 2024-25 dt. 06-02-2025
Open Tender
Electrical Works
Turn-key
120 days
In Udhampur District
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Egineer Electric DivisionJPDCL
₹60,100
11 Mar 2025
7 Feb 2025
1 Mar 2025
7 Feb 2025
27 Feb 2025
7 Feb 2025
7 Feb 2025 - 15 Feb 2025
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Weasel Conductor at WSS Kashirah Stage One Near Baglamukhi Temple.
9 mtr. Long ST Pole (ST-410 SP-33)
11 mtr. Long ST Pole (ST-410 SP-56)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
11 KV GO AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
30mm² ACSR Weasel Conductor
PG Clamps for 30mm sq. ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 100 KVA Sub stn. at WSS Kashirah First Bear Baglamukhi Temple.
11/0.433-0.250 KV; 50Hz,100 KVA Aluminium wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS 1180 Part-1; 2014 as per latest upto date amendment with externally fitted MCCB with cable box an 4x4 Mtrs. 185 mm² cable
Gapless surge Arestor, 9 KV, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
185mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
9 mtr. Long ST pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting.
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clmaps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire Trivector meter with CT
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of 9 mtr long ST poles with 1 coat of Red oxide
Painting of 9 mtr long ST poles with 2 coat of Aluminium paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT line 30mm² Line on 8 mtr ST poles at WSS Ser Stage One Near Baglamukhi Temple.
8 mtr. Long poles (ST-410 SP15)
GI M Clamps for shackle insulator
30mm² ACSR Weasel Conductor
Shackle insualtor
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr. Long ST poles with two coat of Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR weasel Conductor at WSS Kashirah Stage second Airforce Road.
9 mtr. Long ST Pole (ST-410 SP-33)
Suspension/Tension clamp with eye hook
Heat Shrinkable outdoor cable termination kit
120 sqmm AB (HT) Cable (3x120+1x95mm ) XLPE (11KV 3C+Earth)
11 KV GO AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub station at WSS Kashirah Stage Second (Air Force Road)
11/0.433-0.250 KV; 50Hz,63 KVA Aluminium wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS 1180 Part-1; 2014 as per latest upto date amendment with externally fitted MCCB with cable box an 4x4 Mtrs. 120mm² cable
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
120mm² 1.1 KV Grade, PVC insulated standed conductor FRLS Type
9 mtr. long pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45KN, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting.
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire Trivector meter with CT
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. of sub stn. with 1 coat of Red oxide
Painting of ST poles 9 mtr. of sub stn. with 2 coat of Aluminium paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3-Phase 4-Wire LT 30mm² line on 8 mtr. ST pole, 30mm² ACSR Conductor at WSS Kashirah Stage Second (Airfore road)
8 mtr. Long poles (ST-410 SP15)
GI M Clamps for shackle insulator
30mm² ACSR Weasel Conductor
Shackle insualtor
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr. Long ST poles with two coat of Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR weasel Conductor at WSS Kashirah Stage Third Dibber Road.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR Weasel Conductor
11 KV GO AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
PG Clamps for 30mm sq. ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub station at WSS Kashirah Stage Third (Dibber Road).
11/0.433-0.250 KV; 50Hz,63 KVA Aluminium wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS 1180 Part-1; 2014 as per latest upto date amendment with externally fitted MCCB with cable box an 4x4 Mtrs. 120mm² cable
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
120mm² 1.1 KV Grade, PVC insulated standed conductor FRLS Type
9 mtr. long pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45KN, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting.
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire Trivector meter with CT
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. of sub stn. with 1 coat of Red oxide
Painting of ST poles 9 mtr. of sub stn. with 2 coat of Aluminium paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT 30mm² ACSR Weasel Conductor at WSS Kashirah Stage Third (Dibber Road).
8 mtr. Long poles (ST-410 SP15)
GI M Clamps for shackle insulator
30mm² ACSR Weasel Conductor
Shackle insualtor
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr. Long ST poles with two coat of Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M R ENGINEERS & TRADERS (BID ID -2337105)
M/S K.K ELECTRICALS (BID ID -2329514)
The Trikuta Engineer (BID ID -2339297)
M/S JAI DURGA ELECTRICAL CONTRACTORS (BID ID -2339734)
VEENA CONSTRUCTION CO. (BID ID -2338925)
ADITYA SHARMA (BID ID -2337996)
M/S WATT ELECTRICAL CONTRACTS (BID ID -2339194)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .