GE NAGROTA
GE NAGROTA
REPAIR MAINTENANCE OF LT OH LINE, LT PANEL WITH OTHER CONNECTED ITEMS UNDER GE NAGROTA
2024_MES_653483_1
CA NO GEN-06/2024-2025
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
NAGROTA
Class D category b i
8 documents required · 8 mandatory
₹500
GE NAGROTA
₹90,000
Yes
14 Sept 2024
11 May 2024
18 Jun 2024
11 May 2024
10 Jun 2024
28 May 2024
Amount
SCHEDULE ‘A’ PART-I Excavation in trenches in any type of soil not exc 1.5m wide and n.exc 1.5m in depth and getting out complete all as specified & directed
Returning, filling in. including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in any type of soil complete all as specified & directed
Removing excavated surplus material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified & directed.
Supply & fixing of Sand cushioning to under ground cable laid in trenches for laying of LT UG cable 8 cm depth before laying the cable and 15 Cm after laying and punned down to depth of 10 cm as per MES SSR Part -I ( 2009) all as specfied and directed. Note : Thickness of sand cushion after punning down will be measured and paid.
Material and labour for laying of bricks locally available sub-class 'B' brick (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the directon of cable complete all as specified and directed.
All as per Srl item No 5 above but using old retrived serviceable bricks
M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete in foundation of pole/stays etc complete all as specified & directed
M&L for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation, filling and mass concrete in foundatin of pole/stay, complete all as specified and as directed.
M&L for PCC 1:2:4 type B-1, (using 20 mm graded crushed stone aggregate) as in copying above ground level around the pole, complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 300 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 150 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sqmm 3.5 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sqmm 4 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16sqmm 4 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 4 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 2 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 06sqmm 2 core laid in trenches / through duct/pipe incl aluminium cable gland / lugs/ thimble incl taking out old unserviceble cable complete all as specified and directed.
Supply, laying connecting ,testing of Cable jointing kit for 1.1 KV (Earthed) grade cable for outdoor heat shrinkable cable termination type joint complete with jointing material and acessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 sqmm complete all as specified and directed . .
Cable jointing kit for 1.1 KV (Earthed) grade cable for outdoor heat shrinkable cable termination type joint complete with jointing material and acessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm complete all as specified and directed ..
Cable jointing kit for 1.1 KV (Earthed) grade cable for outdoor heat shrinkable cable termination type joint complete with jointing material and acessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmmcomplete all as specified and directed ..
Supply & fixing of Service cable/wire 1100 Volt flat twin core aluminium stranded conductor of size 6 Sqmm complete all as specified and directed.
Supply & fixing of Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 10 Sqmm complete all as specified and directed.
Supply & fixing of Service cable/wire 1100 Volt flat twin core aluminium stranded conductor of size 16 Sqmm complete all as specified and directed.
Supply & fixing of Steel tubing galvanized(Light grade) 100 mm bore conforming to IS -1239 for passing cable under road /floor or fixing to poles for protection of underground cable complete all as specified and directed..
Supply & fixing of Steel tubing galvanized(Light grade)80mm bore conforming to IS -1239 for passing cable under road /floor or fixing to poles for protection of underground cable complete all as specified and directed..
Supply & fixing of Steel tubing galvanized(Light grade)50mm bore conforming to IS -1239 for passing cable under road /floor or fixing to poles for protection of underground cable complete all as specified and directed..
Supply & fixing of Steel tubing galvanized(Light grade)40mm bore conforming to IS -1239 for passing cable under road /floor or fixing to poles for protection of underground cable complete all as specified and directed..
Supply & fixing of Steel tubing galvanized(Light grade)25mm bore conforming to IS -1239 for passing cable under road /floor or fixing to poles for protection of underground cable complete all as specified and directed..
Labour only for re-stringing restraching ACSR conductor laid over, over head LT line on steel / PCC poles after removing binding from insulator and rewinding the conductor with insulator including providing spacer and new binding wire jumpering provide with after restraining and removing unavoidable sags in the line and Trimming of tree and branches on LT line for min clearance complete all as specified & specified
S&F in repair PVC line spacer of superior quality suitable for four line of ACSR over head lines, complete all as specfied and directed.
S&F in repair PVC line spacer of superior quality suitable for three line of ACSR over head lines, complete all as specified and directed.
Supply & fixing of Aluminium conductor, steel reinforced of any size on LT Poles including straining,binding with insulators with Al/copper binding wire with insulators as in OH conductors, providing PVC Sleeves for jumper fixed as in repairs complete all as specified and directed .
Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT Feeder Piller box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from stainless steel totally encloused ,dust, weather & vermin proof , 3.15 mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 500 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement, with & incl MCCB 4P 400 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate. (f) Wiring complete with suitable size of copper cable PVC insulated from incoming to bus bar and bus bar to out going controls of size matching current rating of control. (g) Civil work including PCC for fixing of panel and other work as directed by Engr-in-Charge.
Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT Feeder Piller box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from stainless steel totally encloused ,dust, weather & vermin proof , 3.15 mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 400 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement, with & incl MCCB 4P 250 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT Feeder Piller box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from stainless steel totally encloused ,dust, weather & vermin proof , 3.15 mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 400 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement, with & incl MCCB 4P 200 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT Feeder Piller box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from stainless steel totally encloused ,dust, weather & vermin proof , 3.15 mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 200 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement, with & incl MCCB 4P 100 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
Feeder piller box out door type ‘factory made’ made out from 16 SWG MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick of size 75cm x60cm x45 cm with 04 Nos aluminium bus bar of 400 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement provn for incoming and outgoing cables with glands including painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge Note:- Feeder pillar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
S&F in repair for fabrication and installation of feeder pillar box outdoor canopy type, size 40cm (Height) x 30 cm (width) x 12 cm (thick), size of canopy 30cm x 13 cm complete with locking arrangement, 4 Nos aluminium busbar size 20 x 5mm, 8 Nos nut bolt, & 8 Nos aluminium cable socket and with MCB TPN 63 Amp for incoming and outgoing cable embeded in PCC foundation with 2 Nos angle iron leg 25mm x25mm, 400 mm long as per sample including taking down complete all as specified and as directed.
S&F in repair for fabrication and installation of feeder pillar box outdoor canopy type, size 40cm (Height) x 30 cm (width) x 12 cm (thick), size of canopy 30cm x 13 cm complete with locking arrangement, 4 Nos aluminium busbar size 20 x 5mm, 8 Nos nut bolt, & 8 Nos aluminium cable socket suitable for upto 120 sqmm cable embeded in PCC foundation with 2 Nos angle iron leg 25mm x25mm, 400 mm long as per sample including taking down complete all as specified and as directed.
Taking out existing Steel/PCC pole and refixing at another location complete all as specfied and directed. Note : The Quoted rate include the erection with help of hydra Machine or Manually.
M & L for servicing of feeder pillar box/ LT Cubical Panel, LT pannel after dismantling the incoming and outgoing connections from MCCB/ Bus bar and replacing the old burnt/ overheated unserviceable lugs, terminals, nuts, bolts, washers supporting insulators etc and welding the hinges of Pannel door and fixing the door in original positions also checking the serviceability of MCB / MCCB, earth continuity conductor and strip etc complete all as specified. Note: (i) Spare parts such as terminals, lugs, nut bolts, etc will be measured and paid under respective item in the schedule, (ii) Labour for fixing charges of the spare parts deemed to be included in the rate quoted for the items.
Supply and fix wall mounted Busbar chambers 415 V, 3 phase, 4 wire 50 Hz AC supply system fabricated from stainless steel with 3 mm thick for outer cell TPN aluminium busbar of cap 63 Amp 4 pole 6 way connected with proper Nut and bolt complete all as specified and directed . . Make Havells Cat Part No IHBC006306 or equivalent make as specified in PS
Supply and fix wall mounted Busbar chambers 415 V, 3 phase, 4 wire 50 Hz AC supply system fabricated from stainless steel with 3 mm thick for outer cell TPN aluminium busbar of cap 100 Amp 4 pole 8 way connected with proper Nut and bolt complete all as specfied and directed by Engineer -in-charge Make Havells cat Part No IHBC006308 or equivalent in Indo asian
Labour and tools for trimming tree branches up to 100 mm grith of any location around existing HT/LT OH lins giving clearance of 1.5 m on all sides after arranging shut down and taking all precaution while working on lines incl all T&P required for the purpose complete all as specified and directed . . . Note : The contractor shall arrange the tree cutting machine and vehicle mounted telescopic ladder for the same.
Supply and fixing of male contact/moving contact blade 200 amp of Air Break switches complete with nuts and Bolts of capacity 11 KV, complete all as specified and directed . .
Supply and fixing of female contact/Fix contact Jaw 200 amp of Air Break switches complete with nuts and Bolts of capacity 11 KV, complete all as specified and directed
Supply and fixing of tinned copper flexible jumper 200/400 amp with MS jumper carrier for Air Break switches complete with nuts and Bolts of capacity 11 KV, complete all as specified and directed.
Supply and fixing of Switch air break gang operated (Swing out expulsion ruse insulators), tripple pole mechnical operated from ground level mounted on insulator and steel frame (12 insulators type) out door type suitable for vertical installation single break provided with locking arrangement consisting of MS channel HT post top insulator with drop out fuses operating rod 20mm dia GI medium grade pipe worked from ground levelconfirming of IS 1818 of 1972 and contineous current rating upto 200 amp and volt 11 KV complete in repairs complete all as specified and directed . .
Refixing existing Aluminium strip of any size from building,Store house, Bunkers with porcelain insulator and tightly fix around the building complete all as specified and directed. Note : Necessary Saddles and Nails required for fixing the strip on wall shall be deemed including in items Rate.
S&F in repairs12 mm dia and 300 mm long air termination, single pointed aluminium rod , complete all as specified and directed.
Supply and fixing in repair of aluminium strip 25 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground, complete all as specified and directed.
Supply and fixing of GI strip of size 25 x 4 mm for earth continuity conductor or main earthing lead fixed to wall burried in ground fixed alongwith poles complete all as specified & specified
M & L for preparation of old painted steel surface by cleaning, removing rust, grease and apply one coat of synthetic enamel paint of approved shade (Spray painting outside/inside surface) of the feeder pillar box / LT Panels Outdoor / Indoor type of approximate size 900 x 600 x 500 mm complete with prior permission of Engineer in Charge. Base frame with Black enamel paint (Rate quoted shall deem to be included of Numbering of Panel/ Feeder pillar) complete all as specified & specified and directed by Engineer charge
Supply and fixing in replacement of adjustable type thermal & Adjustable magnetic setting MCCB 630 amps capacity FP 415 volt with breaking cap 50 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable type thermal & Adjustable magnetic setting MCCB 400 amps cap 4P 415 volt with breaking cap 36 KA .complete all as specified and directed . .
Supply and fixing in replacement of adjustable type thermal & Adjustable magnetic setting MCCB 3 phase 415 volt 4P 320 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable type thermal & Adjustable magnetic setting MCCB 3 phase 415 volt FP 250 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable type thermal & Adjustable magnetic setting MCCB 3 phase 415 volt FP 200 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable thermal and fixed magnetic setting MCCB 3 phase 415 volt FP 160 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable thermal and fixed magnetic setting MCCB 3 phase 415 volt 4P 125 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable thermal and fixed magnetic setting MCCB 3 phase 415 volt 4P 100 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable type and fixed magnetic setting MCCB 3 phase 415 volt 3 pole 250 amps with breaking cap 36 KA.complete all as specified and directed . .
Supply and fixing in replacement of adjustable type and fixed magnetic setting MCCB 3 phase 415 volt 3 pole 200 amps with breaking cap 36 KA. complete all as specified and directed . .
Supply and fixing in replacement of adjustable type and fixed magnetic setting MCCB 3 phase 415 volt 3 pole 160 amps with breaking cap 36 KA complete all as specified and directed . .
S & F Change over switch off load type with enclosure, conforming IS 13947 part I & III 415V, 4 pole of rating 100/125 amps, including taking out old unserviceable one, complete all as specified and directed
Supply and fix aluminium lugs of any type / shape of capacity from 10 Sqmm to 25 Sqmm complete all as specified and directed . .
Supply and fix aluminium lugs of any type / shape of capacity from 35 Sqmm to 95 Sqmm complete all as specified and directed . .
Supply and fix aluminium lugs of any type / shape of capacity from 120 Sqmm to 300 Sqmm complete all as specified and directed . .
S&F Extension link four set for MCCB of cap 125/160 Amp.complete all as specified and directed . .
S&F Extension four link set for MCCB of cap 250 Amp complete all as specified and directed .
S&F Extension four link set for MCCB of cap 400 / 630 Amp complete all as specified and directed . .
M & L for Earthing complete with galvanised mild steel earth plate electrode 60cmx60cmx6mm thick, burried directly in ground preferably in vertical position (Earth pit not less than 2.25 mtr below ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 25×4 mm by means of bolts, nuts, check nuts and washers of galvanised iron including pit of PCC (1:2:4) type B-1, pre cast RCC cover slab of size 550x550x75mm, XPM reinforced not less than 1.60Kg/Sqm with suitable built in handle made from 12mm dia MS round bar, excavation and earth work in any type of soil, 20mm dia bore medium grade galvanised iron water tubing fixed with cast iron funnel and wire mesh at one end, 15mm bore light grade galvanised iron protection pipe for earth lead wire upto 5m length, charcol, common salt complete all as shown in electric plate No 3 of SSR 2009 Part I connected to equipment, complete all as specified and testing on completion complete all as specified and directed . .
M & L for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, complete all as directed .Dismantling and taking out damage/rusted cross arms, bracings, supports, clamps and back plates from existing poles / dismantled poles / pole structures complete all as specified and directed .
Note: The work under subject BoQ (item No. 1.00 to 81.00 ) are meant for maint of External Electric in Nagrota Mil Stn ( Including Katra, Sanjhi Chat, Charli Hill ). The work shall be executed on ground on required basis. Contractor shall deploy sufficient resources to keep smooth working of External Electric Supply at Station. Contractor or his representative will daily attend the complaints at E/M complaint cell and in addition any breakdown shall be communicated to contractor or his representative by concerned Engineer-in-charge/JE E/M through phone call, text message, complaint slip and or in writing through site order book or through other means. Non complying of attending breakdown by contractor within 24 hours after notify the complaint, recovery @ Rs 1500/- per day shall be recovered from contractor's payment for each complaint so notified.
M/S KALSI ENGINEERS AND CONTRACTORS
MAMTA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .