Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 90 MYLAPORE CHENNAI TAMIL NADU 600004 | CHENNAI | TAMIL NADU | 600004 | Admitted-Finance |
| 3 | Admitted-Finance NO 5 THILLAI NATHAMUNI AVENUE MUGALIVAKKAM CHENNAI CHENNAI TAMIL NADU 600125 | CHENNAI | TAMIL NADU | 600125 | Admitted-Finance |
Tender Value
₹57.0 L
EMD Value
₹1.1 L
Closing Date
16 Feb 2024, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
General Manager, INRP(K)
Office of GM, 608 Building, BARC, Kalpakkam
Supply, installation, testing and commissioning of once through conditioned air ventilation system at CWMF, INRP, Kalpakkam
2024_BARC_790898_1
BARCF/INRPK-MA/CW/TR/87/2023
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
210 days
CWMF/INRPK/NRB/BARC/Kalpakkam
Please refer tender document
8 documents required · 8 mandatory
₹0
₹1.1 L
10 Apr 2024
22 Jan 2024
23 Feb 2024
23 Jan 2024
16 Feb 2024
25 Jan 2024
24 Jan 2024 - 8 Feb 2024
Amount
DX-type AHU with condensing unit: Supply, installation, testing and commissioning of 30 TR nominal capacity (7.5 TR x 4 circuits), 3000 CMH air flow, 65 mm WC static pressure, micro processor controlled, DX- type AHU with condensing unit consisting of double skin AHU, condensing unit with twin scroll hermetically sealed compressors, condenser copper tube of cross hatched & lanced fins, condenser fan, thermostatic expansion valve, temperature control, etc., as per the scope and technical specification with Liquid and Hot gas lines Copper tubing between IDU & ODU of above Packaged AC units, supply and installation of 8 swg copper conductor earthing of both ODU and IDUs.
SS ducting: Supply, fabrication, erection and testing of exhaust air ducting with 3 mm thick SS 304 complying to ASTM A 240 using TIG welding, complete with SS flanges, fasteners, elbows, gasket, etc as per technical specification and drawings. The duct weld joints shall be 100 % DP tested.
GI ducting: Supply and installation of factory fabricated GI ducting made out of lock forming class VIII, 22 G lead free GI sheet including providing of vanes, M.S angle support, angle flanges, anchor fasteners, grill collar, tees, bends, etc. as per the scope of work and technical specification.
Supply, fabrication and erection of MS structural steel in the form of angles, channels, plates along with supporting accessories and painting as per the scope of work and technical specification.
Thermal insulation: Supply and installation of thermal insulation of above ducting with 9 mm thick, closed cell Nitrile foam rubber/cross linked polyethylene thermal insulation. The insulation shall be covered with aluminum foil of 40G thick and fixed properly by self adhesive aluminum tape as per the technical specification.
Acoustic insulation: Supply and installation of 15 mm thick acoustic insulation with open cell structure, elastomeric foam based synthetic rubber, self adhesive coating and covered with protective polyethylene foil to be laid inside the duct plenum. The acoustic insulation shall be suitable for 12-30 deg C operating temperature, thermal conductivity of 0.047 W/mK, fire retarded "O" class, resistant to chemical & micro organism and sound absorption class-D.
Volume control damper: Supply and installation of Volume Control Dampers made out of 16 SWG GI sheet materials, adjustable type opposed blade with necessary flanges for duct branches connecting to main plenum and supply air branch ducts etc. and ball socketed type connecting rod between blades, PVC gears for smooth operation and suitable sturdy handle with OPEN/CLOSE position indicator.
Supply and installation of 200/300 mm dia, Volume control damper of SS 304 for fixing at fume hood outlet for regulating the air flow through fume hood.
Supply and installation of double deflection type Supply Air Grill of Extruded anodized aluminum, powder coated Off white/brown color, adjustable and locking type aluminum volume control damper having horizontal and vertical louvers. The louver portion shall be removable type for adjusting the volume control damper. (Size: 600 mm x 150 mm)
Supply and installation of double deflection type Return Air Grill of Extruded anodized aluminum, powder coated off white/brown color, adjustable horizontal and vertical louvers. (Size: 600 mm x 150 mm)
Supply and installation of 4-way type Supply Air Diffuser of Extruded anodized aluminum, powder coated off white/brown color with aluminum volume control damper. The louver portion shall be removable type for adjusting the volume control damper. ( Size: 600 mm x 600 mm with neck size 450 mm x 450 mm)
Supply and installation of 4-way type Return Air Diffuser of Extruded anodized aluminum, powder coated off white/brown color. ( Size: 600 mm x 600 mm with neck size 450 mm x 450 mm)
Supply and installation of 100 mm dia dial type differential pressure gauge - Magnehelic type complete with SS tubing, compression fittings, mounting brackets etc. for measuring pressure difference across filters range 0-50 mm WC
Supply, installation and commissioning of Annubar (averaging type pitot tube) sensor with transmitter, 4-20 mA current output for measuring air flow through supply & exhaust duct, digital panel meter for air flow indication along with complete accessories like duct flanges, screws, compression fittings, etc. Range- 0 to 10,000 CMH, duct size 600 x 500 mm.
Supply, installation and commissioning of differential pressure transmitter with 4-20 mA output signal along with digital indicator to show the room pressure.
Heater bank with controls: Supply and installation of Heater bank 6 kW (2 x 3 kW) consists of 3 phase strip heaters, cable termination box, fuse unit, humidistat to control relative humidity, air stat, thermostat, electrical contactor for strip heaters, earthing, etc. along with electrical indication panel.
JVS AIR SYSTEMS
FREEZ ENGINEERING
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .