| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.6 LAccepted-AOC 111 YADAV ELECRIC MARKET GB MARG LUCKNOW LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | ₹25.6 L Quoted ₹26.0 L | L1 | Accepted-AOC BEING LOWEST BIDDER |
| 2 | L2₹26.8 LRejected-Finance | ₹26.8 L | L2 | Rejected-Finance NOT BEING LOWEST |
| Sl No | Description | Qty | Unit | H C CONSTRUCTION L2 | Industrial Traders L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation on wall/ floor and testing of isolation transformer 2 kva ,single phase 240 Volts AC ,50 Hz 1:1 ratio of input and output voltage copper wound air cooled for preventing passege of voltage transient,spikes and voltage leakage to maintain E_N voltage near to one all as specified and directed Make- blue bird/Sai electricals/Volina/vinitec | 20 | Each | 14,000 ₹2.8 L | 20,000 ₹4 L |
| 2.00 | M& L for Earthing complete with galvanised steel earth plate electrode 60cm x 60cmx6 mm thick burried directly in ground (earth pit not less than 3.28 metres deep below normal ground level) with top edge of plate not less than 2.38 metre below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I with and including connecting to earthing test point block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw and testing on completion with and including 15 mm bore light grade G.I. protection pipe (upto 7.5 M beyond outer edge of earth pit) PCC pit in mix 1:3:6 type C1 with RCC 1:2:4 type B-1 40 mm thick cover reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore medium grade G.I. watering pipe, common salt and charcoal filling in alternate layer of 150mm all around earth plate and necessary excavation and earth work including Earthing pit marker/ identifier of Iron plate of size 300mm X 200mm X 3mm and alongwith one meter long medium grade GI pipe of size 15 mm dia weilded with steel plate including painting with applying one coat of red oxide and two coat of painting with synthetic enameled paint of approved quality including writing letters Colour coding on indicator plate will be done including testing on completion all as specified and directed. | 28 | Each | 5,800 ₹1.6 L | 6,200 ₹1.7 L |
| 3.00 | S&F Submain wiring with two single core PVC insulated FRLS-H multistrand copper conductor cable of size 2.5 Sq mm drawn into and including non metallic heavy duty rigid concealed PVC conduit except RCC wall / col not less than 25 mm size ISI marked ivory colour (Pressfit or similar brand ) with all fittings / accessories and 2.5 Sq mm FRLS multistrand copper conductor cable as continuous earth wire complete including making good the disturbed surface of wall etc complete all as directed.
Note :- For submain wiring : Two run of single core cable and one run of earth wire will be measured as one length and conduit with its accessories is deemed to be included in the unit rate quoted for this items. | 260 | RM | 200 ₹52,000 | 170 ₹44,200 |
| 4.00 | S&FSheet metal enclosure, powder coated single pole and neutral with two pin and earth plug and socket (Mettalic) complete with one single pole MCB for 240 volts 20 Amps rating rupturning capacity 10 KA completeMake- Legrand/Havells/Anchor | 41 | Each | 650 ₹26,650 | 1,300 ₹53,300 |
| 5.00 | Supply, Installation, commissioning & testing split air conditioner cap 1.5 TR ,single phase 230 Volts AC workng on non CFC refrigerent with outdoor unit and fan coiled type cooling unit (evaporator) to be mounted outside building on wall complete all as mentioned below :-(a) Outdoor unit shall consist of compressor ,copper condensor coil ,fan with motor,copper tubes mounting on MS bracket / brick plateform etc.(b) Cooling unit (evaporator) shall be fan coil type with copper coil & electrically operated fan to be mounted out side bldg and designed to maintain proper air flow with MS outdoor type enclosure duly painted and connected with ducts all as specified and directed. (c) Copper tubing/pipes of adequate size between outdoor and cooling coil ,cordless remote control unit ,copper multicore cable to connected with mains,outdoor , fan coil unit and all other acessories required (d) Designing,fabricating and testing ducts with galvanised steel sheet of 24 gauge of suitable size including providing proper insulation with aluminium cladding and providing grills / louvers,MS angle ,nut bolts etc.(e) M & L including connecting electrically operated dampers in ducts with sensors ,contactor,motor and copper wiring etc(f) M & L for making hole in brick wall of suitable size as per duct making good all as specified & directed. Make of outdoor unit : Hitachi / Carrier/ Daikin/ Voltas | 2 | Each | 2,10,000 ₹4.2 L | 70,000 ₹1.4 L |
| 6.00 | Supply installation & testing auto switch timer machanism for single phase 230 volt AC of 1.5 TR cap operating one out of two at a time with and including timmer for setting hrs run , contactors relays of suitable size not less than 20 amps including internal copper wire connecting in a sheet metal enclosure factory made 1.6 mm thick painted with two coats of synthetic enamel paint over a red oxide primer ,dust vermin proof with locking arrengement complete all as specified and directed | 1 | Each Job | 13,500 ₹13,500 | 12,000 ₹12,000 |
| 7.00 | M&L for Flameproof submain wiring with two run of single core PVC FRLS insulated unsheathed multi stranded copper conductor cable of size 4 Sqmm FRLS-H 1100 volts grade and one run of PVC insulated unsheathed solid copper conductor cable of size 4 Sqmm 1100 volts grade as earth continuity conductor drawn through in steel conduit concealed / surface conduit of suitable size on roof/wall/ceiling including making good the disturbed surfaces of wall etc complete all as directed. | 20 | RM | 300 ₹6,000 | 250 ₹5,000 |
| 8.00 | M&L for chemical earthing(bore earthing) by drilling a hole of 100 mm dia and 4 mtr in depth in any kind soil and providng a 3.0 mtr long pure copper strip of size 32x6 mm duly encapsulated in a Copper of pipe of 88 mm OD and filling the hole with advance non toxic earth enhancing back fill compound qty not less than 30 kg and water till complete soaking of chemical water mixture and providing a cylindrical type FRP earth pit chamnber of size 254 mm dia at top , 330 mm dia at bottom and 260 mm height and 7.5 m long copper strip of sizxe 32 mm x6 mm as earth lead conductor duly protrcted with 65 mm bore suitable bore of pipe medium grade GI pipe from terminal point to earth test point and duly connected with terminal point through breezing and to connect with earth test point with brass bolt nuts and washer of suitable size and fixed on wall by mounting the strip of frp /DMC bridge insulator and providng a test point a terminal block made of gun metal of phosphorus bronze of size 75 mmx75mmx25mm duly drilled and screwed and fixed on wall on insulators including 3 nos 8 mm dia 25 mm long hex haed brass scew complete with removing of excavated soil to a distance not excedding 50 meter and height n. exc. 1.5 m from the starting point including Transformer not less than 1KVA 1:1 ratio single phase to put E-N voltage within limit all and testing on completion all as specified and directed.
Note- 1. Addl lenght of conductor beyond 7.5 mtr if required at site shall be measured and paid sperately undr resperctive item
2.On testting afer completion of job if desie earth resisirance less than permissible limit is not found ther earthing shalll be redone at no extra cost o to govt. | 2 | Set of two | 34,000 ₹68,000 | 45,000 ₹90,000 |
| 9.00 | Supply and fixing copper strip of size 32mm x 6 mm complete with saddles and fixing screws for fitting the strip for earth continuity conductor complete all as specified & directed. | 10 | RM | 1,050 ₹10,500 | 900 ₹9,000 |
| 10.00 | M&L for earthing complete with copper plate electrode of size 60cm x 60cm x 3.15 mm thick burried directly in ground vertically at a depth not less than 3.25 metre deep below normal ground level with top edge of the plate not less than 2.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using copper strip 20 x 3 mm by means of bolts, nuts, check nuts and washers made of copper and protected by light grade 40 mm dia GI pipe connected to test point and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 3 of SSR Part I ,all as specified and directed. | 4 | Each Job | 18,000 ₹72,000 | 25,000 ₹1 L |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
16 Nov 2023, 6:00 pmClosed
GE (AF) BKT
GE (AF) BKT LUCKNOW
PROVN OF QTY 20 NOS ISOLATION TRANSFORMER 2KVA FOR AFNET L2 SWITCH AND LIGHTING ARRESTER, EARTHING AND CERTAIN E/M ITEMS AND ELECTRICAL CABLE WORK IN AIRMEN AND DSC MESS AND FIRE PROOF AIR CONDITIONER WITH FAN COIL UNIT WITH AUTO SWITCH AT KIRAN FSS
2023_MES_622358_1
8733/BKT/E8
Open Tender
Civil Works
180 days
GE (AF) BKT
7 documents required · 7 mandatory
₹500
GE (AF) BKT
₹58,000
24 Jun 2026
9 Oct 2023
18 Nov 2023
9 Oct 2023
16 Nov 2023
28 Oct 2023
Amount
Supply, installation on wall/ floor and testing of isolation transformer 2 kva ,single phase 240 Volts AC ,50 Hz 1:1 ratio of input and output voltage copper wound air cooled for preventing passege of voltage transient,spikes and voltage leakage to maintain E_N voltage near to one all as specified and directed Make- blue bird/Sai electricals/Volina/vinitec
M& L for Earthing complete with galvanised steel earth plate electrode 60cm x 60cmx6 mm thick burried directly in ground (earth pit not less than 3.28 metres deep below normal ground level) with top edge of plate not less than 2.38 metre below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I with and including connecting to earthing test point block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw and testing on completion with and including 15 mm bore light grade G.I. protection pipe (upto 7.5 M beyond outer edge of earth pit) PCC pit in mix 1:3:6 type C1 with RCC 1:2:4 type B-1 40 mm thick cover reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore medium grade G.I. watering pipe, common salt and charcoal filling in alternate layer of 150mm all around earth plate and necessary excavation and earth work including Earthing pit marker/ identifier of Iron plate of size 300mm X 200mm X 3mm and alongwith one meter long medium grade GI pipe of size 15 mm dia weilded with steel plate including painting with applying one coat of red oxide and two coat of painting with synthetic enameled paint of approved quality including writing letters Colour coding on indicator plate will be done including testing on completion all as specified and directed.
S&F Submain wiring with two single core PVC insulated FRLS-H multistrand copper conductor cable of size 2.5 Sq mm drawn into and including non metallic heavy duty rigid concealed PVC conduit except RCC wall / col not less than 25 mm size ISI marked ivory colour (Pressfit or similar brand ) with all fittings / accessories and 2.5 Sq mm FRLS multistrand copper conductor cable as continuous earth wire complete including making good the disturbed surface of wall etc complete all as directed. Note :- For submain wiring : Two run of single core cable and one run of earth wire will be measured as one length and conduit with its accessories is deemed to be included in the unit rate quoted for this items.
S&FSheet metal enclosure, powder coated single pole and neutral with two pin and earth plug and socket (Mettalic) complete with one single pole MCB for 240 volts 20 Amps rating rupturning capacity 10 KA completeMake- Legrand/Havells/Anchor
Supply, Installation, commissioning & testing split air conditioner cap 1.5 TR ,single phase 230 Volts AC workng on non CFC refrigerent with outdoor unit and fan coiled type cooling unit (evaporator) to be mounted outside building on wall complete all as mentioned below :-(a) Outdoor unit shall consist of compressor ,copper condensor coil ,fan with motor,copper tubes mounting on MS bracket / brick plateform etc.(b) Cooling unit (evaporator) shall be fan coil type with copper coil & electrically operated fan to be mounted out side bldg and designed to maintain proper air flow with MS outdoor type enclosure duly painted and connected with ducts all as specified and directed. (c) Copper tubing/pipes of adequate size between outdoor and cooling coil ,cordless remote control unit ,copper multicore cable to connected with mains,outdoor , fan coil unit and all other acessories required (d) Designing,fabricating and testing ducts with galvanised steel sheet of 24 gauge of suitable size including providing proper insulation with aluminium cladding and providing grills / louvers,MS angle ,nut bolts etc.(e) M & L including connecting electrically operated dampers in ducts with sensors ,contactor,motor and copper wiring etc(f) M & L for making hole in brick wall of suitable size as per duct making good all as specified & directed. Make of outdoor unit : Hitachi / Carrier/ Daikin/ Voltas
Supply installation & testing auto switch timer machanism for single phase 230 volt AC of 1.5 TR cap operating one out of two at a time with and including timmer for setting hrs run , contactors relays of suitable size not less than 20 amps including internal copper wire connecting in a sheet metal enclosure factory made 1.6 mm thick painted with two coats of synthetic enamel paint over a red oxide primer ,dust vermin proof with locking arrengement complete all as specified and directed
M&L for Flameproof submain wiring with two run of single core PVC FRLS insulated unsheathed multi stranded copper conductor cable of size 4 Sqmm FRLS-H 1100 volts grade and one run of PVC insulated unsheathed solid copper conductor cable of size 4 Sqmm 1100 volts grade as earth continuity conductor drawn through in steel conduit concealed / surface conduit of suitable size on roof/wall/ceiling including making good the disturbed surfaces of wall etc complete all as directed.
M&L for chemical earthing(bore earthing) by drilling a hole of 100 mm dia and 4 mtr in depth in any kind soil and providng a 3.0 mtr long pure copper strip of size 32x6 mm duly encapsulated in a Copper of pipe of 88 mm OD and filling the hole with advance non toxic earth enhancing back fill compound qty not less than 30 kg and water till complete soaking of chemical water mixture and providing a cylindrical type FRP earth pit chamnber of size 254 mm dia at top , 330 mm dia at bottom and 260 mm height and 7.5 m long copper strip of sizxe 32 mm x6 mm as earth lead conductor duly protrcted with 65 mm bore suitable bore of pipe medium grade GI pipe from terminal point to earth test point and duly connected with terminal point through breezing and to connect with earth test point with brass bolt nuts and washer of suitable size and fixed on wall by mounting the strip of frp /DMC bridge insulator and providng a test point a terminal block made of gun metal of phosphorus bronze of size 75 mmx75mmx25mm duly drilled and screwed and fixed on wall on insulators including 3 nos 8 mm dia 25 mm long hex haed brass scew complete with removing of excavated soil to a distance not excedding 50 meter and height n. exc. 1.5 m from the starting point including Transformer not less than 1KVA 1:1 ratio single phase to put E-N voltage within limit all and testing on completion all as specified and directed. Note- 1. Addl lenght of conductor beyond 7.5 mtr if required at site shall be measured and paid sperately undr resperctive item 2.On testting afer completion of job if desie earth resisirance less than permissible limit is not found ther earthing shalll be redone at no extra cost o to govt.
Supply and fixing copper strip of size 32mm x 6 mm complete with saddles and fixing screws for fitting the strip for earth continuity conductor complete all as specified & directed.
M&L for earthing complete with copper plate electrode of size 60cm x 60cm x 3.15 mm thick burried directly in ground vertically at a depth not less than 3.25 metre deep below normal ground level with top edge of the plate not less than 2.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using copper strip 20 x 3 mm by means of bolts, nuts, check nuts and washers made of copper and protected by light grade 40 mm dia GI pipe connected to test point and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 3 of SSR Part I ,all as specified and directed.
M&L for copper strip 20x3mm complete with saddles and fixing screws ,seperator,insulator for fitting the strip for earth continuity conductor complete all as specified & directed.
M & L for Galvanised iron tubing, 50 mm bore,light grade with all fittings for fixed to pole/wall/ in ground including all fixing accessories complete for protection of earth strip up to the test point complete all as specified and as directed.
M&L for Material and labour Aluminium strip 25 X 3 mm with saddles and fixing screws Etc. for roof conductor and down conductor above ground level.
Supply and fixing new air termination,multi pointed alluminium rod 12mm dia and 300mm long connecting with lightening conductor system complete all as specified and directed.
M&L for brazing/soldering to the copper earth strip of size 20x3 mm complete all as specified and directed.
Supply install and testing of isolation transformer 1.5/2 kva ,240 Volts AC ,50 Hz 1:1 ratio of input and output voltage copper wound air cooled with MS sheet metal enclosure factory made duly painted with 3 core copper conductor PVC insulated cable with plug top to maintain E_N voltage less than 2 volts Make blue bird/Sai electricals/Volino
S&F ceiling Rose, surface, bakelite 65 x50 mm three terminals, AC, 230 Volts complete all as directed.
Supply installation and testing of wall mounted Air circulator 200 mm sweep with high speed and aerodynamically designed metalic blades/body, heavy duty, jerk free and smooth oscillation and inbuilt regulator system chord complete all as specified and directed by EIC.
Supply installation and testing of wall mounted Air circulator 450 mm sweep with high speed and aerodynamically designed metalic blades/body, heavy duty, jerk free and smooth oscillation and inbuilt regulator system remote operated complete all as specified and directed by EIC.
Supply installation and testing of wall mounted Air circulator400 mm sweep with high speed and aerodynamically designed metalic blades/body, heavy duty, jerk free and smooth oscillation and inbuilt regulator system chord complete all as specified and directed by EIC.
Supply & fix exhaust fan made of sturdy engineering plastic complete with louvers shutter volt 230 V 50 Hz RPM 950 copper winding of sweep 300 mm all as specified and directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out complete all as specified and directed.
Returning filling in including spreading, levelling watering and well ramming in layers not exceeding 25 cm thickness complete all as specified.
Removal of surplus soil to a distance not exceeding 50m and depositing wgere directed at a level not exceeding 1.5m above the starting point complete all as specified.
Supply and laying dry sand cushioning for cable protection in trenches 8 cm before laying cable and 15sm deep cover the cable complete all as specified and directed.
Supply and laying bricks for protection of cables using sub class "B" bricks laid dry flat across length of the cable with width equal to the length of brics complete all as specified and directed.
Supply and laying cable XLPE insulated screened PVC bedded, galvanized steel strip armored, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor size of 95 sqmm 3.5 core.
Ditto all as per item No 27 but for size of 70 sqmm 3.5 core.
Ditto all as per item No 27 but for size of 35 sqmm 3.5 core.
Supply and fixing tubes light grade galvanised 80 mm dia with all fittings and fixed complete to walls, road and poles for protection of cable.
Boring of holes under road pavement hard standing by any means including 80mm dia HDPE pipe suitable for 0.4 mpa working pressure including necessary fitting complete all as specified and directed
M&L for three phase Submain wiring with four single core PVC insulated FRLS-H multistrand copper conductor cable of size 16Sq mm drawn into and including non metallic heavy duty rigid concealed PVC concealed conduit of suitable size on roof/wall/ceiling including with all fittings / accessories and 16Sq mm FRLS-H multistrand copper conductor cable as continuous earth wire complete making good the disturbed surfaces of wall etc complete all as directed by Engr-in-Charge .
M&L for submain wiring with two run of single core PVC FRLS-H insulated unsheathed multi stranded copper conductor cable of size 4 Sqmm FRLS-H 1100 volts grade and one run of PVC insulated unsheathed solid copper conductor cable of size 4 Sqmm 1100 volts grade as earth continuity conductor drawn through in and including rigid non metallic PVC concealed conduit except RCC portion of suitable size on roof/wall/ceiling including making good the disturbed surfaces of wall etc complete all as directed by Engr-in-Charge (Note : Two run of single core cable and one run of earth wire will be measured as one length and conduit and its accessories is deemed to be included in the unit rate).Make of Cable - Havells,Plaza,Polycab. Make of Conduit - AKG, Finolex, Plaza
S&F Sheet metal enclosure V TPN 4 way double door distribution board when MCCB to be used as incomer, 415 volt complete all as specified and directed
S&F Sheet metal enclosure V TPN 6 way double door distribution board when MCCB to be used as incomer, 415 volt complete all as specified and directed
S&F Sheet metal enclosure TPN 4 way double door distribution board when MCB to be used ,415 volt all as specified and directed
S&F MCCB 4 pole ,63 Amp,415 v with breaking capacity 10 KA
S&F MCB TPN 63-100 Amps 415 volt rupturing cap 10 ka "C" series all as specified and directed.
S&F MCB SP 32 to 40 Amps 240 volt,50 hz,10 KA breaking capacity :C" curved type complete all as specified and directed.
S&F MCB SP 6 to 32 Amps 240 volt,50 hz,10 KA breaking capacity :C" curved type complete all as specified and directed.
M & L for point wiring with two single core PVC insulated & PVC unsheathed FRLS-H multistranded copper conductor cable of size 1.5 sqmm 1100 volt grade in non metallic rigid PVC concelled conduit medium grade not less than 25 mm dia with all accessories mounting all the surface of wall/ceiling/roof/etc with suitable size of module metal flush boxes and including modular front cover plate & back plate for mounting modular type switches /socket/fan/ regulator etc including provision of one single core PVC insulated and unsheathed multi stranded copper cable of size 1.5 sqmm 1100 volt grade as earth continuty conductor connected to common earth dolly switch board complete for One 3 pin 5 amps switch socket outlet point on independent board
All as per the item no 10 herein before but with 2.5 sqmm conductor for 5 pin 15 Amps switch socket outlet.
S&F switch socket outlet 2 in 1, 5 pin, 15 Amps modular type 3 module
S&F switch socket outlet 5 Amps modular type 2 module
S&F switch modular type 1 module single pole, one way 5 amp complete all as specified and directed.
M&L for PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified.
M & L for Brick work with sub class `B` bricks, straight or curved on plan exc 6m mean radius, built in CM 1:6 complete all as specified and directed.
M&L PCC 1:2:4 type B1 (using 20mm graded agg) as in coping incl necessary form work
Returning filling including spreading levelling, watering and well ramming in layers n.exc 25 cm thick
Removing excavated materials ( soil) to a distance n. exc. 50m and depositing where directed.
M&L for hard core broken bricks of gauge n. exc. 63mm, deposited, spread and levelled in layers n. exc. 15cm thick, water and rammed to a true surface complete all as specified and directed.
M&L PCC 1:4:8 typeD-2 (40 mm graded stone agg) as cement concrete 100 mm thick as in flooring, surface finished etc. complete all as specified and directed.
M & L ceramic tiles 300 x 300 x 7mm non skid ceramic coloured tiles in floors etc set jointed in neat cement slurry in floors and pointed in white or coloured cement to match incl 15mm th. Screed bed in CM (1:6), complete all as specified and directed.
S&F non skid ceramic coloured tiles 7 to 8mm thick (squre/rectangular) area of each tile exc 0.18sqm but n.exc 0.38 sqm, as in skirting etc.set and jointed in neat cement slurry over and including 15mm thick rendering in cement mortar (1:4) and pointed in white cement with pigment to match the colour of tiles complete all as specified.
S&F Solid PVC Door frame of Size 50x47mm made out of 5mm plain colour PVC sheet reinforced with M.S squre tube,supplying &fixing in opening as per specification &drawing
S&F factory made solid panel PVC door shutter 30mm thick(style) consisting of frame made out of M.S tubes for top&bottom rails ms frasme shall be covered with heat moulded plain colour PCV "c" channel having a pvc sheet striip of 20mm width struck inside with solvent cement for stile and plain coloured PVC sheet for top rail lock rail and bottom rail on either side & as gap insert for top rail and bottem rail panelling of plain colour PVC sheet to be fitted in the MS frame welde / sealed to the stile and rails with suitable PVC sheet beading and jointed together with solvent cement suppling and fixing to frame at site as per specificcation and drawing incl Aluminium Mongrar ( two 200mm towe bolt two 150mm handle) fixed as required
S&F aluminium handeles fabricated type anodised 150mm size.
S&F aluminium anodised barrel tower bolt of extruded section 200mm length 200mm long.
S&F butt hinges 100 mm size stainless steel.
S & F anodized aluminium window and ventilators powder coated (minimum thickness of powder coating 50 micron) shutters aluminium section weighing 0.55 kg/m including necessary jointing cleats, glazing clips, rubber neoprene packing, etc. complete all as specified.
M&L for rendering 15 mm thick in cm 1:6 on faces of brick without using extra cement or concrete surfaces and finishing even and smooth complete all as specified and directed by Engr in Charge.
M&L for rendering 15 mm thick in cm 1:4 on faces of brick or concrete surfaces and finishing fair and even complete all as specified and directed by Engr in Charge.
M&L for preparation of newly or previously untreated surfaces and applying three coats of white wash on walls
S&F Rolled Mild Steel sections confirming to Fe 410 - S as in main and cross beam, hip and jack rafters, purlins, wind tie where connected to common rafters fixed with angle cleats or other connecting plates.
M&L preparation of New or previouly untreated surface of steel and iron surface of any description and applying two coats of synthetic enamel paint over a coat of red oxide primer complete
S&F pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified.
S&F 15 mm bore GI tubing medium grade, galvanised with all fitting and fixed complete to walls and ceilings or laid in floors all as specified and directed.
S&F 20 mm bore GI tubing medium grade, galvanised with all fitting and fixed complete to walls and ceilings or laid in floors all as specified and directed.
S&F bib taps 15mm dia, cast copper alloy with crutgch or butterfly handle, chromium plated fancy type, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and directed.
S&F 15mm bore stop valves of cast copper alloy, screwed down, high pressure with crutch or butter fly handle, fancy type, chromium plated, with long shank and cup (concealed type) complete all as specified.
S&F 20mm bore stop valves of cast copper alloy, screwed down, high pressure with crutch or butter fly handle, fancy type, chromium plated, with long shank and cup (concealed type) complete all as specified.
S&F 15mm bore pillar tap, cast copper alloy, with capstan heads, chromium plated, screwed down high pressure, with or without lettered ‘Hot’ or ‘Cold’ with long screwed shanks and fly-nuts, screwed for iron pipe complete all as specified.
S&F vitreous china wash down water closet pan (padestal pattern) coloured incl fixinf bolt and plastic water closet seat black closed pattern with flat bottom cover complete all as specified.
S & F 10 ltr cxapacity PVC valveless , syphonic actoin type, flushing cistern, low level white, with inlet ball valve , float & handle including brackets with flush pipe 32mm dia.
S&F PVC Connection 600mm long of dia 15mm complete all as specified.
S&F CP soap dish/holder shade and size as approved by Engr in Charge complete.
S&F vitreous china wash basin white flat back size 550x400 mm including bracking PTMT waste fitting 32 mm bore and pvc waste pipe complete
S&F tubular towel rail chromium plated 20 mm dia D type 60 cm long between flanges complete all as specified and directed by engr in charge
S&F Grating PTMT squre of size 150mm
S&F 500 ltr rotational moulded double layered polythylene water storage tanks with cylindrical vertical with closed top hoisted and fixed in position.
M&L PCC 1:3:6 type C-2 (40 mm graded stone agg) as in plinth protection finished even & smooth without using of extra cement 75 mm thick.
M&L PCC 1:2:4 type B-1 (12.5mm graded aggregate) damp proof course 40mm thick to horizontal surfaces including necessary fornwork.
S & F 75 mm dia PVC (SWR) floor trap, plain with grat-ing including joint-ing with solvent cement complete all as specified and directed
S&F 110mm PVC (SWR) pipes single socketed in any length with rubber rings joints laid in fixed to walls including clamps
Cutting into existing manholes for connecting new drains pipes of 150mm dia making good to pipe & rendering, cutting out existing benching for & forming branch channel in cement concrete 1:2:4 type B-1 smooth finished,complete all as specified.
S&F 110mm PVC (SWR) pipe bend any radiaus complete all as specified and directed.
M&L for point wiring with two single core PVC insulated & PVC unsheathed FRLS-H multistranded copper conductor cable of size 1.5 sqmm 1100 volt grade in non metallic rigid PVC concelled conduit medium grade not less than 20 mm dia with all accessories with suitable size of module metal flush boxes and including modular front cover plate & back plate for mounting modular type switches /socket/fan/ regulator etc including provision of one single core PVC insulated and unsheathed multi stranded copper cable of size 1.5 sqmm 1100 volt grade as earth continuty conductor connected to common earth dolly switch board complete for following-One light point controlled by one switch SP 5 Amps ,240 V
One fan point controlled by one switch SP 5 Amps ,240 V
One 5 pin 5 amps socket point on same board
M&L ceiling rose,PVC/polycarbonate, isolated body all as specified and directed.
M&L for Sleek LED mirror light 10 watt rating with diffuser 2ft long twisted flexible copper wire (approx 0.5 mtr long) complete all as specified & approved by EIC.
Supply & fix exhaust fan mettalic complete with louvers shutter volt 230 V 50 Hz RPM 1200 copper winding of sweep 250 mm all as specified and directed.
Taking down chowkats or frames (without taking down shutter from the frame) not exceeding 1.5 Sqm each complete all as specified.
M&L for Brick work with subclass 'B' bricks, old size bricks, straight or curved on plan exceeding 6 metre mean radius built in cement mortar 1:6 all as specified etc complete.
Taking down cement plaster on brick or stone walls etc including raking out joints, hacking for key, scrubbing down with water etc of any description complete all as specified and directed.
Material and labour rendering 15 mm thick on fair faces of brick or concrete surface walls, in cement mortar 1:6 , rendering is to be finished even and smooth without using extra cement complete all as specified and as directed.
M&L for preparation of new plastered surfaces of walls & applying two coats of oil bound distemper over two coat of wall care putty and one coat of primer complete all as specified and as directed.
Material and labour for Applying two coats of Oil bound distemper on old surfaces of walls over one coat of wall care putty including preparation of surfces complete all as specified.
Material and labour for Applying one coats of white wash on old surfaces of ceiling including preparation of surfaces etc complete all as specified and directed.
Material and labour for (a) repairing aluminium shutters ( Door/ Window) including refixing, tightening and making good with using rubber/beads and others small fixtures/fittings if required and making serviceable all as specified and directed by Engr-in-charge.
(b) Aluminium door locks ( Sample approved by Engr-in-charge)
Taking down copper/aluminium point wiring for (light, fan, socket or power) complete including unserviceable fittings such as switches, ceiling rose, holders, sockets,light fittings etc. and making good the disturbed surfaces on wall/floor etc complete all as specified and directed.
Taking down old and unserviceable sheet metal enclosure distribution board any type capacity including fuses,mcbs insulator,rccb etc
M&L for flame proof point wiring with two single core FRLSH PVC insulated & PVC unsheathed stranded copper conductor cable of size 1.5 Sqmm 1100 volts grade drawn through concealed stove enamelled steel conduit of size 20 to 25 mm with all accessories including making good the distrubed surfaces of wall with colour washing/ distemparing the surface to match the existing and one single core PVC insulated & PVC sheathed solid FRLS copper cable of size 1.5 Sqmm 1100 Volts grade as earth continuity conductor connected to common earth dolly, switch board complete incuding cutting chessing on wall/ flour/ ceiling etc. all as specified for one light / fan point controlled by one 5 Amps switch one way complete.
M&L switch flame proof rotory type with termination box in LM 6, 16 A,single phase 230 volts,complete all as specified and directed Make- sudhir / Bajaj
Supply and fixing LED Light Fitting 2x16 Watt flame proof ,CMRI certified recommended for gas/vapour group of IIA &III B ,zone 1 and 2 and IP 65 Protection with die cast alluminium housing with heat resistant toughned glass with LED tube light, fixtures, driver holders ,connectors etc complete with all accesories prewired and including connecting with three core flexible copper conductor cable with suitable size complete all as specified and directed Make- Sudhir /bajaj / Havells
M&L for flame proof point wiring with two single core FRLS-H PVC insulated & PVC unsheathed stranded copper conductor cable of size 4 Sqmm 1100 volts grade drawn through concealed stove enamelled steel conduit of size 20 to 25 mm with all accessories including making good the distrubed surfaces of wall with colour washing/ distemparing the surface to match the existing and one single core PVC insulated & PVC sheathed solid FRLS copper cable of size 4.0 Sqmm 1100 Volts grade as earth continuity conductor connected to common earth dolly, switch board complete incuding cutting chessing on wall/ flour/ ceiling etc. all as specified for one 15 amp socket outlet point complete.
S&F Flame proof and waterproof multiple entry junction box in LM 6 or cast iron for distribution board 6 way TPN when MCB to be used ,AC 415 V complete all as specified & directed
S&F MCB TPN 63-100 Amps 415 volt rupturing cap 10 ka "C" series all as specified and directed.
S&F MCB single pole, 6 to 32 Amps, 240 Volts 50 HZ, 10 KA breaking capacity complete all as directed.
S & F Flame proof switch socket & plug combined in LM6 cable termination box in LM 6,16 A 250V 2P+Earth Make- Shudhir/ Bajaj
S& f flameproof mettalic body exhaust fan single phase 230 Volts ,50 Hz ,16 inch sweep 1440 RPM with louverrs and shutters including civil work complete all as specified & directed Make - Shudhir/ Bajaj
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4.0 core laid through suitable size conduit on wall through suitable saddle/clipping or any means complete all as specified and directed .
Supply,installation and testing Flame proof split Air Conditioner indoor / outdoor complete of cap 2 TR, single phase electric driven 230 V ,50Hz with Non CFC ecofreindely refrigerant Gas with remote control unit duly tested certified from CIMFR & BIS complete all as specified & directed .Make - M/S Sudhir , M/S Shyam switch gear pvt ltd Mumbai Note :- (i). Cutting holes in walls/window of any thickness for installation of AC etc, connection and making good the disturbed surface to match with the existing surface after work shall be done and rate is included in above rate . (ii) Electrical cable required to connect outdoor unit wih indore unit and indore unit to voltage stabilizer inclusive in above rate. (iii) copper piping/drain piping is included in above rate. (iv) stand for fixing out door unit is included above rate.
Supply & Fix wall mounted digital display voltage stabilizer copper winding, for automatic voltage correction single phase, naturally air cooled, designed for input voltage between 140 Volt to 280 Volts and out put voltage 230Volt and High / low voltage cut off with facility of including instant start & time delay relay of 3 minute capacity 5KVA. Make : Marc Arora, V guard, Microtek
Supply installation & testing auto switch timer machanism for single phase 230 volt AC of 2.0 TR cap operating one out of two at a time with and including timmer for setting hrs run , contactors relays of suitable size not less than 20 amps including internal copper wire connecting in a sheet metal enclosure 1.6 mm thick painted with two coats of synthetic enamel paint over a red oxide primer ,dust vermin proof with locking arrengement complete all as specified and directed
H C CONSTRUCTION
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid