Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.2 LAccepted-AOC | ₹13.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹15.0 L+₹1.8 L (13.3%)Rejected-Finance 252 22 NEAR SOCITY BUS STAND INDRA COLONY PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | ₹15.0 L+₹1.8 L (13.3%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹16.0 L+₹2.8 L (20.9%)Rejected-Finance R O Y K PURA QAZIGUND ANANTNAG 192221 J K | ANANTNAG | JAMMU AND KASHMIR | 192221 | ₹16.0 L+₹2.8 L (20.9%) | L3 | Rejected-Finance Not Lowest |
| 4 | L4₹16.3 L+₹3.1 L (23.1%)Rejected-Finance | ₹16.3 L+₹3.1 L (23.1%) | L4 | Rejected-Finance Not Lowest |
| 5 | L5₹19.5 L+₹6.3 L (47.4%)Rejected-Finance | ₹19.5 L+₹6.3 L (47.4%) | L5 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹54,000
Closing Date
5 Jun 2021, 6:00 pmClosed
GE
GE 860 EWS
REPAIR/ MAINTENANCE TO LT PANEL BOARD, FEEDER PILLAR BOXES, JUNCTION BOXES, REMOVAL OF LT PANEL BD AND CONNECTED WORK SERVICES AT KARU ZONE I UNDER GE 860 EWS
2021_MES_442955_1
8134/2021-22/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Karu
Class D Category b i
9 documents required · 9 mandatory
₹500
Yes
GE 860 EWS
₹54,000
Yes
20 Jul 2021
15 May 2021
7 Jun 2021
15 May 2021
5 Jun 2021
29 May 2021
Amount
S&F, in replacement, MCCB, 415 volts, 04 pole, 63 Amps, 16 KA, ICS = 100% ICU, with Thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 100 Amps, 35 KA, ICS = 100% ICU, with Thermal - Magnetic Release, including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 160 Amps, 36 KA, adjustable type , including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 200 Amps, 36 KA, adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 250 Amps, 36KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 400 Amps,36 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
S&F, in replacement, MCCB, 415 volts, 04 pole, 630 Amps, 50 KA adjustable type including spreader terminals, phase barriers, complete all as specified and directed by Engr-in-Charge.
Taking out old UNSV LT panel board / Junction box of any size complete all as specified and directed by Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 400 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 200 Amps, 415 Volt, AC ,25 KA = 02 Nos (O/G) (c) MCCB 4 pole, 160 Amps, 415 Volt, AC, 25 KA = 02 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts = 10 Nos (O/G)
(e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 600 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,35 KA = 01 Nos (I/C) (b) MCCB 4 pole, 160 Amps, 415 Volt, AC ,35 KA = 02 Nos (O/G) (c) MCCB 4 pole, 100 Amps, 415 Volt, AC ,35 KA = 02 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 11 Nos (O/G)
(e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,25 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC ,25 KA = 03 Nos (O/G) (c) MCB SPN, 63 Amps, 230 Volt, AC, = 04 Nos (O/G) (d) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (e) Phase indicating lamp = 03 Nos (R, Y, B)
(f) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 200 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G) (e) Star Delta Starter suitable for 30 HP centrifugal pump set, 415 Volt, = 01 Nos Make : Havells or equivalent
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 250 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G)
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,35 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC ,35 KA = 02 Nos (O/G)
(c) On load change over switch (side handled) 4 pole, 100 Amps, 415 Volt = 01 Nos (d) MCB SPN 63 Amps, 230 Voltst, AC = 2 Nos (O/G) (e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 02 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G)
(e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 02 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 04 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G)
(e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, of Feeder Pillar box , cubical type, factory made, outdoor type, dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, and mild steel angle iron frame complete with openable shutters in front and rear having proper locking arrangement including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate). Feeder Pillar box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 250 Amps, 415 Volt, AC ,50 KA = 01 Nos (I/C) (b) MCCB 4 pole, 100 Amps, 415 Volt, AC, 25 KA= 01 Nos (O/G) (c) MCCB 4 pole, 63 Amps, 415 Volt, AC, 25 KA= 03 Nos (O/G) (d) MCB SPN 63 Amps, 230 Volts, AC = 04 Nos (O/G)
(e) Multifunction meter MFM 4400 LED meter Cl 0.5S with RS485 Make : L&T or equivalent (f) Phase indicating lamp = 03 Nos (R, Y, B) (g) Aluminium bus bar of capacity 400 amps four strip with colour coding should be shrinkable sleeves 4 Nos fixed on insulators-01 Set of four Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Supply, installation, testing and commissioning, in replacement, Junction box , cubical type, factory made, outdoor type of Size 45cm(l) x30cm(w)x 60cm(h) , dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, complete with openable shutters in front and rear having proper locking arrangement including including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) and aluminium bus bar of size 400 Amps capacity , Three phase and neutral bus bar , making hot and cold drilling holes to aluminium bus bar . Junction box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, testing and commissioning, in replacement, Junction box , cubical type, factory made, outdoor type of Size 45cm(l) x30cm(w) x60cm(h) , dust and vermin proof, fabricated out of mild steel sheet not less than 3.15 mm thick, complete with openable shutters in front and rear having proper locking arrangement including including 04 Nos legs made out of angle iron of suitable size and height of each leg shall be grouted in PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) and aluminium bus bar of size 400 Amps capacity , Three phase and neutral bus bar , making hot and cold drilling holes to aluminium bus bar . Junction box shall be spray painted internally and externally with two coats of synthetic enamel paint over a priming coat of red oxide primer and connecting all incomming and outgoing cables with suitable size of Aluminium lugs complete all as specified and as directed by Engineer-in-Charge and comprising of following accessories/fittings :- (a) MCCB 4 pole, 160 Amps,240/415 Volt, 50Hz, 10 KA= 01 Nos (I/C) (b) MCB SPN 63 Amps, 240 Volts - 04 Nos (O/G)
Note : Unit rate quoted by the contractor here-in-before also includes for fixing and connecting of MCBs and installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the Galvanised earth lead wire 4.0 mm dia by means of bolts, nuts , check nuts and washers of galvanized iron and steel earth wire protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 3 of SSR 2009 Part-I and connecting to Poles all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge.
VIMAL TRADERS AND SUPPLIERS
M/S BHAT ENGINEERS
HILL AND CO.
M/S ASHRAF HUSSAIN
M/S TRADE LINK
M/S Behl Sons
M/S ASHISH AND CO
satyabhama and co
M/S KARAN BUILDERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .