Loading…
Loading…
Tender ID
Tender Value
₹161.3 Cr
EMD Value
₹1.6 Cr
Closing Date
30 Mar 2026, 8:30 pmClosed
Karnataka Power Transmission Corporation Limited
KRISHNA REDDY GT
Establishing 2x200MVA, 220/132 kV & 1x20MVA, 132/11 kV sub-station at PM MITRA TEXTILE PARK, Kalaburagi. 2) Construction of 220kV DC Line on 220kV towers (Design Based) using Twin Moose conductor from 400/220 kV Ferozabad sub-station to proposed 220/132/11kV PM Mitra Textile Park sub-station at Nadisinnur village for a distance of 1.985km in Kalaburagi Taluk & District under DCW Basis.3)Construction of 2 nos. of 220 kV Terminal Bays at 400/220 kV Ferozabad(Kalaburgi) sub-station for proposed 220/132/11kV PM Mitra Textile Park sub-station at Nadisinnur in Kalaburgi taluk Kalaburgi district. 4) Establishing 2x20MVA, 132/33 kV and 2X20MVA, 132/11 kV sub-station at PM MITRA Textile Park (STATION-1) at Nadisinur village in Kalaburagi Taluk and District Under DCW Basis. 5)Construction of 132kV MC Line on 132 kV MC NBT Towers(Design based) using panther conductor from proposed 220/132kV PM Mitra Textile Park sub-station at Naddisinur village to the proposed 132/33/11kV PM Mitra Textile Park sub-station-1 for a distance of 1.811km at Keeranagi Village in Kalaburagi Taluk and District Under DCW Basis. 6) Establishing 2x20MVA, 132/33 kV and 2X20MVA, 132/11 kV sub-station at PM MITRA Textile Park (STATION-2) at Keeranagi village in Kalaburagi Taluk and District Under DCW Basis. 7) Construction of 132kV MC Line on 132 kV MC NBT Towers(Design based) using panther conductor from proposed 132/33/11kV PM Mitra Textile Park sub-station-1 at Keeranagi village to the proposed 132/33/11kV PM Mitra Textile Park sub-station-2 for a distance of 1.114km at Keeranagi Village in Kalaburagi Taluk and District Under DCW Basis.
KPTCL/2025-26/SS/WORK_INDENT3254
KPTCL/2025-26/SS/WORK_INDENT3254
Open
Sub-Station
Two Tender Document System(Two Cover)
KPTCL CEE Corporate Office Tendering and Procurement Bengaluru
4 documents required · 4 mandatory
Documentary proof for Clause No. 3.2(b)(i) of ITT such as P.O, LOI/LOA, DWA, Work done Certificates, Performance Certificates issued by the end users not below the rank of Executive/Divisional Engineer.
Documentary proof for Clause No. 3.2(b)(ii) of ITT such as P.O, LOI/LOA, DWA, Work done Certificates, Performance Certificates issued by the end users not below the rank of Executive/Divisional Engineer
Cl.No.3.2(d)(A)(3)Qualifying Requirements for Tower Manufacturer as a Bidder: i) Shall upload Necessary documentary evidence for Cl.No 3(a), (b) of Cl.No 3.2(d)(A)issued from Utilities such as P.O. copies, LOA/DWA, Performance Certificates issued by the end users (Power Utilities) not below the rank of Executive/Divisional Engineer, should be uploaded along with the offer
Cl.No.3.2(d)(A)(3)Qualifying Requirements for Tower Manufacturer as a Bidder: ii) The bidder shall upload the relevant documents in support of Cl.No.3(c) of Clause No.3.2(d)(A) above such as copy of the approved letter issued from utility approving design documents, copy of the Purchase Order containing the details of scope of work, ISO certificate, certificate issued by Utility Or Chartered Engineer in support of In-house design department indicating the details of infrastructure & Technical Personnel /Registration certificate issued by the Government Authorities in support of In-house design department.
Cl.No.3.2(d)(A)(4) Qualifying Requirements for Power Transformer manufacturer as a Bidder: Shall upload Necessary documentary evidence for Cl.No 4(b) &(c) of Cl.No.3.2(d)(A) issued from Utilities such as P.O. copies, LOA/DWA, Performance Certificates issued by the end users (Indian Government Power Utilities) not below the rank of Executive/Divisional Engineer, should be uploaded along with the offer
Documentary proof for Clause No. 3.2(d) (B)(1) of ITT High Performance Conductor (HPC) Manufacturer such as P O/LOI/LOA/DWAcopies/performance certificate issued by the end users issued by the end users not below the rank of Executive Engineer for having supplied to Indian Utilities/ Consumers of High Performance Conductor (HPC)equivalent to same or higher size of same technology as stipulated in technical specification of the subject tender in the last 10 (Ten) years as on the date of Bid Submission and the same shall be in satisfactory operation for a period of at least Two years as on the date of bid submission
Documentary proof Clause No. 3.2(d) (B)(1) of ITT such as list of all the type tests carried out as per latest IEC and KPTCL specifications indicating reference of relevant clauses of IEC and KPTCL specifications test description / details and date of testing along with the copies of the Type test reports
Audited financial statements including Balance sheets, Profit and Loss statements, Turnover Certificate, Auditors Reports of the last five years preceding the date of bid submission of the Bidder & Consortium member(In case of Consortium)
Documentary proof for Clause No: 3.6 of ITT: Assessed available tender capacity such as, Statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent or verified and certified by Chartered Accountant/Cost Auditor as sought in Note of the said clause in the prescribed format as in clause No: 1.5 of Qualification Information by the lead Bidder and Consortium member(In case of Consortium).
The Tenderer shall upload Bankers Certificate of lead Bidder & Consortium Partner (if applicable) duly signed by authorized person in the prescribed format as at Annexure XVIII of Section-4 and as per the clause no.3.3 (b) of ITT (Liquid Assets and /or availability of credit facilities)
self-declaration as sought in Clause No. 3.6 Note (ii) of ITT by the Lead Bidder & Consortium partner(in case of Consortium) stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Certificate from Chartered Accountants for split details of financial Turnover and GST in the prescribed format (Annexure-XX) of Lead Bidder & Consortium partner (In case of Consortium).
Cl.No.3.2(d)(A)(4) Qualifying Requirements for Power Transformer manufacturer as a Bidder: Necessary documentary evidence for Cl.No.3.2(d)(A)(4) (a) wrt to registration of manufacturing company shall be uploaded.
Type test reports of Power transformer as per Clause No. (4)(d) & (e) of Cl.No.3.2(d)(A).
Dynamic Short Circuit test reports as per Clause No. (4)(f) of Cl.No.3.2(d)(A).
Undertaking-1 wrt to Type test reports & Dynamic Short Circuit test reports if Power transformer manufacturer participates as a Bidder.
Lead Bidder & Consortium partner (in case of Consortium) shall upload self-declaration (proof of purchase to be uploaded) as per the format mentioned in clause no. 1.6 of section 3 of tender documents wrt to Equipment Capabilities as per Cl.No 3.3(a)
In case of lease/hire, the Lead Bidder & Consortium partner (in case of Consortium) shall upload hiring/Rental agreement wrt to Equipment Capabilities as per Cl.No 3.3(a).
Self-declarations of Lead Bidder & Consortium partner (In case of Consortium) in respect of Litigation, dis-qualification due to non-performance, Risk & cost clause and Restriction on border sharing as specified in Annexure- XVI& Annexure-XVII as per Clause No.2.4of ITT
Consortium Agreement
Power of Attorney in favour of all the persons signing the documents, Power of Attorney for Consortium, combined power of attorney signed by the signatories of all the members of consortium as an evidence of authorization for nominating leader (Prime Bidder) of consortium.
Valid Super Grade Electrical Contractors License of both Lead Bidder & Consortium partner (in case of Consortium) issued by the Govt. of Karnataka
Certificate of Incorporation of the Individual/Consortium or any relevant document in respect of Partnership/Proprietorship firms as per the tender document
The bidder and Consortium Partner(in case of Consortium) should have valid GST registration with GSTIN number PAN Card and ISO Certificates.Note The successful Bidder and his consortium partner who have GST registration in other States should have GST registration in the State of Karnataka mandatorily at the time of execution of the Contract Agreement.
No Deviation Certificate
Letter of Undertaking as in Annexure
The Qualification and experience of key Personnel proposed for carrying out the Work
Description of the Tools & Plant available with them for execution of the Work
undertaking to source the supply of equipment/material from KPTCL approved Vendors only as per the QR for Vendor registration, available in the KPTCL website i.e., https://kptcl.karnataka.gov.in, Link Tender and Procurement - application for Vendor registration etc.
undertaking to source the supply of equipment/material from Vendors who meet the eligibility clauses regarding restriction on procurement from a country which shares land border with India as specified in Annexure- XVII.
Details of Works on hand and Ongoing contractual commitments
Upload all relevant documents as per Section-3 Qualifying information, NIT, Terms & conditions as stipulated in the Tender Document.
Copies of original documents defining the Constitution or Legal Status, place of Registration and Principal place of Business of the Bidder (Lead Bidder & Consortium Partner) , written Power of Attorney to the Signatory of the Bid to commit the Bidder (Lead Bidder & Consortium Partner) to the Contract along with the resolution passed in this regard by the Board of Directors all the Partners of the Firm.
The Tenderer shall upload declarations for Deviations, if any as per Schedule-5 and Schedule-6 of the Techno Commercial sheets
Please note that the Filled in Techno commercial sheet shall be uploaded along with all other QR documents. Offers shall be quoted in the item-wise bid Financial offer, provisioned in the e-procurement portal. In case the Prices are uploaded in/along the Techno commercial Bid, then Bid will be summarily rejected. The Techno-commercial sheets shall be uploaded in KPTCL excel formats only.
Bidder shall upload Dynamic Short Circuit test reports for 200MVA, 220/132/11kV Power Transformer as per Cl.No 3.2(e).
The Bidder should have In-House Design department with experience of design and testing of 220kV or higher voltage class Towers & foundations in the last 10 years as on the date of bid submission. The same shall be in satisfactory service for a period of 2 years from the date of bid submission. ii.The Bidder should have conducted detailed survey/Check survey of 220kV or higher voltage class Transmission lines in the last 10 years.iii.The bidder shall upload the relevant documents in support of (i) & (ii) above such as copy of the approved letter issued from utility approving design documents, survey report, copy of the Purchase Order containing the details of scope of work, ISO certificate, certificate issued by Utility Or Chartered Engineer in support of In-house design department indicating the details of infrastructure & Technical Personnel /Registration certificate issued by the Govt Authorities in support of In-house design department, performance certificates issued by utility not below the rank of EE.
The Bidder shall invariably upload the following documents (as indicated in technical specifications) related to the tower design proposed in this tender failing which the offer will be rejected:Designing of Lattice type Towers:1.Tower loading calculations, loading trees, line diagram of the tower indicating live metal clearances, ground clearance, mid span clearance, shielding angle etc., for Lattice type of towers.2.Line diagram of the tower indicating all the dimensions including base width, panel height, and steel section used, redundant pattern etc., for Lattice type of towers.3.Detail design calculation of the tower and foundation for Lattice type of towers.4.Typical foundation sketches adopted for all types of soil for Lattice type of towers.
Undertaking-2 by the Bidder wrt to Dynamic Short Circuit test reports of 200MVA, 220/132/11kV Power Transformer.
₹7,500
₹1.6 Cr
27 Feb 2026
27 Feb 2026
31 Mar 2026
27 Feb 2026
27 Feb 2026
POWER TRANSFORMERS:
a) 200MVA, 220/132/11 kV Power Transformer, 3Ph, 50Hz, Core Type, 2 winding Auto Transformer star/Delta, Vector Group: YNa0d11, OLTC, Bushing CT for Tertiary of Ratio 2020/1A, 5P...
Power Transformer:
b) 20 MVA, 132/33kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group DYn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel, Numeri...
Power Transformer:
c) 20 MVA, 132/11kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group DYn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel, Numeri...
Nitrogen Injection Fire Extinguishing System:
a) Supply, Erection & Testing and Commissioning of Nitrogen Injection fire extinguishing system as per the recommendations of the supplier of the fire fig...
b) Supply, Erection & Testing and Commissioning of Nitrogen Injection fire extinguishing system as per the recommendations of the supplier of the fire fighting system & as per Technical Specification...
CIRCUIT BREAKER : SF-6 Circuit Breaker with rigid bi-metallic terminal connector suitable for Al. Tube/Moose/Twin Moose ACSR with spring / semi-pneumatic / pneumatic type operating mechanism and with...
ii) SF6 Gas circuit breaker with Semi Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting Structures arrangements with rigid, bimetallic terminal connectors complete...
iii) SF6 Gas circuit breaker with Semi-Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting Structures arrangements with rigid, bi-metallic terminal connectors comple...
220kV electrically cum manually operated double break type disconnects with solid core insulators, terminal connector suitable for AL. tube/Moose ACSR/Twin Moose ACSR conductor, marshalli...
b) Upright without Earth Switch
i)Live Point Height 8250mm
ii)Live Point Height 5750mm
c) Under hung without Earth Switch
II) 220kV, 1600A, 50kA Double break type.
(i) 3-pole with one earth switch.
ii) 3-pole with two earth switch.
iii) 1-pole (3Phase) Tandem operated ISO without E/S.
b)Upright mounting type without Earth Switch (LPH 5750mm)
c)Upright mounting type without Earth Switch (LPH 8250mm)
d)Underhung mounting type without Earth Switch
V)245kV, 3000A, 50kA Double break type.
(i) 3-pole with one earth switch.
ii) 3-pole with two earth switch.
V) 132kV class Isolators:
132kV, double break electrically cum manually operated isolators with solid core insulator, terminal connector suitable for Al. tube/Moose ACSR/Twin Moose/Drake ACSR conduc...
b)Upright mounting type without Earth switch(LPH 7000mm)
c)Upright mounting type without Earth switch LPH 5000mm.
d)Underhung Mounting without earth switch
a) Upright mounting type without earth Switch (Live Point Height 7000mm)
b) Upright mounting type without earth Switch (Live Point Height 5000mm)
c) Underhung Mounting without earth switch.
Terminal connectors for Isolators in 220KV PM Mithra sub station shall be as follows :
Rigid type suitable for Twin Moose ACSR conductor - 108 Nos
VI)33KV calss Isolator 800A, 31.5KA Class Double Break Manually operated isolator with terminal connectors suitable for Moose/Drake ACSR/75 mm pipe/63 mm pipe.
a) Upright mounting type with Manually ...
b)Upright mounting type without Earth switch. .(Live point height 3750mm)
c)Upright mounting type without earth switch. (Live point height 4750mm
Terminal connectors for Isolators in 132/33/11 sub station-1+ 2 shall be as follows :
Rigid type suitable for Moose ACSR- 102+1...
CURRENT TRANSFORMERS :
Current transformers including marshalling boxes, Single phase,oil filled outdoor type with rigid bimetallic terminal connectors suitable for Al. Tube/Moose/Twin Moose/Drake AC...
2)220kV, 50kA CT of Ratio 3000-2000/1-1-1-1-1A
For Metering : Accuracy 0.2s, Burden 20 VA
For Differential /Distance protection PS class
Vk = 1600V at 1600/1 A RCt 8ohms,
800V at 800/1A RCt...
3)220kV, 50kA CT of Ratio 1200-800-400-300/1-1-1A with additional 2 Cores of 1200/1A Type-1 (2 nos. main CT is used as NCT)
For Metering : Accuracy 0.2s, Burden 10VA
For Differential /Distance protect...
4) 132kV 40kA CT of Ratio 1000-800-600/1-1-1A [(Required for 200MVA Transformer & bus coupler. and lines)
For Metering : Accuracy 0.2s, Burden 10 VA
For Backup protection : Accuracy 5P20. Burden 30 V...
5) 132 kV class, 40 KA, CT of ratio 600-400/ 1-1-1A for Lines and Bus Coupler
For Backup Protection: 5P20, Burden 30VA
For Metering: Accuracy 0.2S, Burden 10VA
For Differential Protection: PS Class, ...
5)132kV 40kA CT of Ratio 200-100/1-1-1A (Required for 132/33 and 132/11kV Transformer)
Core - 1 : Vk-800 V at 400A, Rct 4 ohm at 400/1A, Accuracy class PS-Dist/Dif
Core- 2 : 10 VA, Accuracy class 0...
7)33 kV class, 31.5 KA, CT of ratio 400-200/ 1-1-1A
Core - 1 : Vk-240 V, Rct 5 ohm at 400/1A, Accuracy class PS-Dist/Dif
Core- 2 : 10 VA, Accuracy class 0.2s- Metering
Core - 3 : 30 VA, Accuracy c...
8) 11kV Class, 25kA, NCT of ratio 2000-1200/1-1-1A for (Required for 132/11kV Transformer)
1. All the CTs in each kV class shall be of one and the same make for inter-changeability & reliabilit...
VOLTAGE TRANSFORMERS : Single phase, 3 core, oil filled outdoor type with rigid bimetallic terminal connectors suitable for Moose ACSR/ Al Tube with marshalling box KIOSK as per technical specificatio...
2) 132 kV class 132kV/RT3/110V/RT3/ 110V/RT3/ 110V/RT3
Core - 1 : 300 VA, Accuracy class 0.2-Metering
Core - 2 : 200 VA, Accuracy class 3P-Protection
Core - 3 : 50 VA, Accuracy class 3P. Open delt...
3)33KV, VTs of Ratio 33KV/RT3/110V/RT3-110V/ RT-110V/RT3,
Core-1-Metering - 300VA, Accuracy 0.2
Core-2-Protection - 200VA, Accuracy 3P
Core-3-Protection - Open Delta, 50VA, Accuracy-3P
CAPACITIVE VOLTAGE TRANSFORMERS:
245 kV CVT, 4400 pF, 1 Ph CVT with 2 secondaries, terminal connector suitable for Twin Moose ACSR conductor with marshalling box etc., complete as per technical speci...
SURGE ARRESTOR:
Porcelain/Polymer type, with terminal connector suitable for Twin Moose ACSR conductor as per technical specifications.
a) 198kV Metal Oxide with surge counter Arrestor class : Statio...
b) 216 kV, Metal Oxide with surge counter Arrestor class : Station Medium Duty (SM) - Discharge Class 3
Note : Surge arrestors are with surge monitors & insulating base
c) 120 kV, Metal Oxide with surge counter Arrestor class : Station Medium Duty (SM)
Note : Surge arrestors are with surge monitors & insulating base
d)30KV, Metal Oxide with surge counter, station medium duty (SM) - Discharge class-3
e)9 kV, 10 KA with connector and clamp
Control and Relay & Protection Panels complete as per specifications:
I. C&R Panel compatible to IEC 61850 communication protocol for Sub-station Automation System, complete as per technical specific...
2) 220/132 kV Power Transformer panel Type 2T1 (as per annexure RPP2-SAS)
3) 220 kV Bus coupler panel Type 2BC (as per annexure RPP1-SAS)
4) 220 kV Bus Bar Protection panel Type 2BBA (as per annexure RPP3-SAS)
5) 132 kV line - Type 1L (as per annexure RPP4-Cable-SAS)
6) 132 kV Bus coupler panel Type 1BC (as per annexure RPP6-SAS)
7) 132/11 kV Transformer panel Type 1T1(as per annexure RPP5-SAS)
8)11kV line- Type 1L(As per Annexure RPP7-SAS)(Provision for 2 feeders to be made in one panel and provision for 1 capacitor bank & 1 feeder to be made in one panel)
1) All the C&R panels and ...
II. Control and Relay Panel complete as per specifications: (For 132/33-11 sub station 1 and 2)
Simplex type 110V DC compatible to SCADA as per EC 61850 Protocol control and relay panels complete as ...
b) For 132kV Bus Coupler
c) For 132/11kV Transformer
d) For 132/33kV Transformer
(1) The Accuracy class of metering core of CTs and also trivector meter of control & relay panels shall be 0.2S class and CVTs & VTs shall be 0.2 Class instead of that specified el...
Sub-station Automation System including erection:
Complete Sub-station Automation System including hardware and software for Sub-station and for operation from remote control centre along with associa...
Total Weight of 220kV Station structures & Mounting Structures (at 220/132kV Station)(excluding Bolts & nuts) Non Design
Total Weight of Bolts & nuts of Station structures & Mounting Structures (at 220/132kV Station) Non Design
Total Weight of 220kV Station structures & Mounting Structures (at 220/132kV Station)(excluding Bolts & nuts) Design Based
Note:This Weight Should be same as that indicated in Techno-commercial sheet ...
Total Weight of Bolts & nuts of Station structures & Mounting Structures (at 220/132kV Station) Design Based. Note:This Weight Should be same as that indicated in Techno-commercial sheet of Station Su...
Total Weight of 220kV Station structures & Mounting Structures (Excluding Bolts & nuts) at 220kv S/S at Ferozabad (Non Design)
Total Weight of Bolts & nuts of Station structures & Mounting Structures at 220kv S/S at Ferozabad (Non Design)
Total Weight of 132kV Station structures & Mounting Structures (Excluding Bolts & nuts) at 132/33/11kV sub station-1 & 2. Non Design
Total Weight of Bolts & nuts of Station structures & Mounting Structures at 132/33/11kV sub station 1 & 2. Non Design
Total Weight of 132kV Station structures & Mounting Structures (Excluding Bolts & nuts) at 132/33/11kV sub station-1 & 2. Design Based. Note:This Weight Should be same as that indicated in Techno-comm...
Total Weight of Bolts & nuts of Station structures & Mounting Structures at 132/33/11kV sub station 1 & 2. Design Based. Note This Weight Should be same as that indicated in Techno-commercial sheet of...
I) RIGID BUS WITH TAPS & CLAMPS :
i) Aluminium Tube conforming to 63401 WP of IS-5082 / 1969 (BS 1600-Sch.40) including fixing of clamp, connector jumper, corona ring etc., complete & as per tec...
At proposed 132kV Nadisinur S/S
132kV side- 600 Mtrs
At proposed 132kV Keeranagi S/S
132kV side- 600 Mtrs
iii) 63 mm size for connecting isolator to vertical tap
At proposed 220kV Textile Park S/s-
220kv Side -300mtrs
132kV side- 340 Mtrs
At proposed 132kV Nadisinur S/S
132kV side- 480 Mtrs
iv) 50mm Size for Main Bus -33 KV Side
At proposed 132kV Nadisinur S/S -82 Mtrs
At proposed 132kV Keeranagi S/S -82 Mtrs
v) 38mm Size for isolator to vertical tap - 33kV Side
At proposed 132kV Nadisinur S/S -84 Mtrs
At proposed 132kV Keeranagi S/S -84 Mtrs
vi)Inverted 'V' taps made of 63 mm Aluminium Tube (BS - 1600) of 2500mm vertical height for vertical portion and cross bus on 220 kV Side with rounded off End.
vii)Straight taps made of 63 mm Aluminium Tube (BS - 1600) of 1250mm vertical height for vertical portion and cross bus on 132 kV Side with rounded off End.
viii)Straight taps made of 75mm Aluminium Tube (BS-1600) of 2000mm vertical height for vertical portion and cross bus on 132KV Side with rounded off end. ( Rate of 63mm considered)
ix)Straight taps made of 38mm Aluminium Tube (BS-1600) of 1000mm vertical height for vertical portion and cross bus on 33KV side with rounded off end.
II) Post insulator clamps suitable for 100mm Aluminium pipe and post insulator Solid core type as per technical specifications:
b) Expansion type -(100mm Aluminium pipe)
a) Rigid type- (100mm Aluminium pipe)
b) Expansion type -(100mm Aluminium pipe)
c) Sliding type-(100mm Aluminium pipe)
3) Post insulator clamps suitable for 75 mm Aluminium pipe & Post insulator solid core type - 132kV side
a)Rigid Type-(75mm Aluminium pipe)
b)Expantion Type-(75mm Aluminium pipe)
4) Post insulator clamps suitable for 50 mm Aluminium pipe & Post insulator solid core type - 33kV side
a)Rigid Type-(50mm Aluminium pipe)
b)Expantion Type-(50mm Aluminium pipe)
c)Sliding Type-(50mm Aluminium pipe)
5) Corona Bell suitable for Aluminium Pipe of Size 220/132/11kv S/S at Textile park
a) 100 mm on 220kV Side- (12Nos)
b) 100 mm on 132kV Side-(12Nos)
220kv TB at Ferozabad
a) 100 mm on...
c) Corona Bell Suitable for Aluminium Pipe of size 75mm on 132 kV
c) Corona Bell Suitable for Aluminium Pipe of size 50mm on 33 kV
6) End cap suitable for Aluminium pipe of size
a) 63mm on 220kV side-(36 Nos)
b) 63mm on 132kV side-(39 Nos)
7) End cap Suitable for Aluminium tube of size 75mm on 132kV
8) End cap Suitable for Aluminium tube of size 63mm on 132kV
220kV Clamps and Connectors
1)Terminal Connector for CB to receive 4” IPS Al. Tube flexible/rigid type
2)Terminal connector for CT to receive
a. Twin Bersimis ACSR conductor
b. 4 inch IPS Al. tube Flexible/rigid type
3)Terminal Connector for Isolator to receive
a. 4” inch IPS Al. tube flexible/rigid type
b. 4 inch IPS Al. tube Rigid through type.
c. ACSR twin Bersimis conductor suitable for Vertical take off 250mm spacing.
4)Terminal connector for CVT to receive twin Bersimis ACSR
5)Clamps for Aluminium Tube suitable for BPI for both main bus & Interconnecting bus
a. 4” IPS Al. tube Expansion type
b. 4 inch IPS Al. tube Rigid type
6)T Clamp suitable for 4” IPS Aluminium tube to twin Bersimis conductor
7)T-clamp suitable for Quadruple Bersimis to quadruple Bersimis (Wedge type).
8)T-clamp suitable for Quadruple Bersimis to twin Bersimis.
9)T-clamp suitable for twin Bersimis to twin Bersimis.
10)Spacers for quadruple Bersimis conductor with 450mm spacing
11)Spacers for twin ACSR Bersimis conductor with 250mm spacing
12)Terminal connector for LA to receive ACSR twin Bersimis conductor suitable for horizontal take off with 250mm spacing.
13)Welding Sleeve suitable for 4 inch IPS Al. tube
14)T-clamp suitable for Drake/Twin Zebra to Twin Bersimis
BUS BAR FORMATION :
1) Moose ACSR Conductor
2) Bersimis ACSR Conductor
interconnecting Bus and transfer BUS-400Mtrs
Main Bus - 800 Mtrs
Solid core Bus Post Insulator - Cylindrical Solid core Insulator as per IS:5350, Part-II & III & as per technical specification:
1) For 220kV side -2 units/stack
220/132/11kv S/S at Te...
2) For 132kV side -1 unit/stack
At proposed 220kv Textile park
a) Post Insulators of Rigid Bus -86Stacks
b) High level Post Insulators for (200 MVA Tr -6 Nos, 20 MVA Tr -3 Nos.)-9 Stacks
3) For 33kV side -1 unit/stack
At proposed 132kv Nadisinur
a) Post Insulators of Rigid Bus -18Stacks
b) High level Post Insulators for (Tfr )-6 Stacks
At proposed 132kv Keeranagi
a) Post Insulators ...
3) 11kV,160 KN Disc Insulators:
a) 220 kV side - DoubleTension string of 15 units each-12 strings, Double Tension String of 2x16units each - 6 Strings
For quadrapulate Bersimis ACSR with 250mm Sub ...
4) 11kV,120 KN Disc Insulators:
a) 220 kV side - Single Tension string of 16 units each-12 strings, Double Tension String of 2x16units each - 18 Strings
b) 132kV Side - Double Tension String of 2x...
5) 11kV,90 KN,Disc Insulator:
a) 220kV side- Single Suspension string of 14 units each
b) 132kV side- Single Suspension string of 9 units each
6) 33kV Polymer type long rod insulator for secondary side of the Transformer
At proposed 132kv Nadisinur- 6 Nos
At proposed 132kv Keeranagi- 6 Nos
INSULATOR HARDWARE & CLAMPS as per technical specification:
1) Bolted type tension clamp to suit Moose ACSR
220KV Side - 12Nos. 132kV side - 30+54+54 Nos.
2) Bolted Type Double tension clamp to suit Twin Moose ACSR
a) 220kV side-18Nos., b) 132kV side-30+6+6Nos.
3) Bolted Type Double tension clamp to suit quadrapulate Bersimis ACSR
a) 220kV side-18Nos.
4) Bolted Type Double tension clamp to suit Twin Bersimis ACSR
a) 220kV side-6Nos.
5) Bolted Type single Suspention clamp to suit quadrapulate Bersimis ACSR
a) 220kV side-9Nos.
6) Bolted Type single Suspention clamp to suit Twin Bersimis ACSR
a) 220kV side-3Nos.
7) Bolted type suspension clamp to suit Moose ACSR
(a) 220kV Side-06Nos
(b) 132kV Side-15+30+30Nos
8) Bolted type suspension clamp to suit Twin Moose ACSR
(a) 220kV Side-18Nos
(b) 132kV Side-12+3+3Nos
9) Bolted type tension clamp to suit Drake ACSR
33KV Side - 18+18 Nos
10) C Type Wedge connector suitable for Moose to Moose ACSR.
220kV Side-48 Nos
132kV Side-39+54+54Nos
11) C type wedge connector suitable for Twin Moose ACSR to Twin Moose ACSR -18 Nos
220kV Side-30 Nos
132kV Side-42+12+12Nos
12) C Type Wedge connector suitable for Panther/Lynx to Moose- 132KV Side.
13) C Type wedge connector suitable for Twin Moose - Moose 132kV side of 200MVA Transformer
14) C Type Wedge connector suitable for Drake to Drake- 33KV Side.
15) PI Clamp suitable for post insulator & Moose ACSR 132kV Side
16) PI clamp suitable for post insulator and Moose ACSR-
220kV side of 200MVA Transformer
17) Post insulator clamp suitable for Twin Moose ACSR and 132kV Solid core insulator.
18) Post insulator clamp suitable for single Drake ACSR and 33kV Solid core insulator.
19)Clamps suitable for 75mm Al Tube to Twin Moose ACSR
20)Spacers (Rigid /flexible) for Twin Moose ACSR 132kV side
21)Spacers for Twin Moose ACSR (5 Mtr spacing)
Auxiliary Transformer:
a) Supply of Station Auxiliary Transformer with copper windings & oil, cable termination type on both HT & LT, outdoor type, with off load tap changer in steps of 2.5 % as per t...
b) Supply of Station Auxiliary Transformer-copper winding with oil, outdoor type, 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn 11 off load tap changer(5 taps) with step voltage of 2.5% along with oth...
LTAC Panel(Indoor)
1) LTAC panel (indoor ) as per technical specification comprising of voltmete & ammeter, 415V,LTAC Panel (2 I/C ACB 800A+2 O/G SFU 200A+8 O/G SFU 100A+14 O/G SFU 63 A +12 O/G SFU...
2) LTAC Distribution panel ( Indoor), 415V, comprising of Volt meter, Ammeter & 1 I/C MCCB 200A + 2 nos 3 phase, 63A O/G SFU with HRC fuse + 2 nos 3 phase 32A O/G SFU with HRC fuse + 6 nos 3 phase 16A...
AC Distribution box (Outdoor) :
a) AC distribution Box (outdoor):- double front type, 24 terminals, 1200 x 1350 x 600 mm, 2 I / C of 100 Amps, MCCB 20 KA + 24 O / G MCB 16 Amps + 2 O / G of 100 A, HR...
b) AC distribution Box single front type, 6 terminals 750 x 1350 x 300 mm , one I / C of 100 Amps MCCB 20 KA + 6 O / G MCB 16 A + 1 O / G of 100 A, HRC fuse as per technical specifications.
c) AC Distribution box (outdoor) Single front type with 6 terminals 1200 x 1350 x 300 mm one I/C of 100 A MCCB 20 KA+ 6 O/G 16 A MCB +1 O/G of 100 A HRC Fuse complete as per technical specifications...
LT Power Cable:
a) Power cable from auxiliary transformer to LTAC panel,
1.1kV PVC insulated 240sqmm Al. cable 3.5 core with glands / lugs/ferruls.
b) 1.1 kV class PVC insulated Aluminium power cable (AC supply for lighting & DFDB/SFDB etc., 70 Sq mm, 3.5 core with glands / lugs / ferruls
Supply, Erection Testing & Commissioning of 3 phase, 50Hz, 415V, 0.8 PF, 62.5KVA DG Set, mounted on a base frame, complete with inbuilt fuel tank and battery 1 no. 12 V & inbuilt standard man...
Supply, Erection Testing & Commissioning of 3 phase, 50Hz, 415V, 0.8 PF, 25KVA DG Set, mounted on a base frame, complete with inbuilt fuel tank and battery 1 no. 12 V & inbuilt standard manua...
STATION BATTERY & BATTERY CHARGER:
A) STATION BATTERY SET :
1) 220V, 300 AH Battery set (Plante/Grid Type) with cells & accessories as per technical specifications.
2) 110V, 200AH Battery set (Plante/Grid/Nickel Cadmium Type) with cells & accessories as per technical specifications
B) BATTERY CHARGER :
1) Battery charger suitable for '2 X 220 V, 300 AH, with float (2 Nos) & float cum boost (2 Nos) type battery charger including control panels, change over arrangements etc., com...
2) Battery charger- suitable for '2 X 110 V, 200 AH, Battery set (Plante/Grid/Nickel Cadmium Type) consisting cells as per specifications- 15 A float and 30 A boost (with float and boost battery charg...
PVC insulated Copper Control Cable with Lugs / Ferrules as per technical specifications.
A) 1.1 kV class. Size of cable:
1) 19 Core 2.5 Sq.mm.Copper Control Cables
2) 14 Core 2.5 Sq.mm.Copper Control Cables
3) 10 Core 2.5 Sq.mm.Copper Control Cables
4) 7 Core 2.5 Sq.mm.Copper Control Cables
5) 5 Core 2.5 Sq.mm.Copper Control Cables
6) 4 Core 2.5 Sq.mm.Copper Control Cables
7) 4 Core 6.0 Sq.mm.Copper Control Cables
9)4 Core 4 Sq.mm.Copper Control Cables
11) 2 Core 6 Sq.mm.Copper Control Cables
(Yard Lighting: 9.6+7.12+2.56+2.56Km)
12)2 Core 2.5Sq.mm.Copper Control Cables
B) Copper PVC Instrumentation Cable, Armoured (Screened Cable) Copper Cable with glands/ lugs/ferrules :1P X 0.5 Sq mm screened cable
11kV XLPE insulated UG Cable as per Technical specifications:
a) 11 kV XLPE, 95 Sq mm Aluminium cable- 3 core (for 2 Auxiliary transformers from the 11KV switchgear)
b) 11 kV XLPE cable, 1000 Sq. mm Aluminium cable- 3 Runs per phase of 1CX1000 Sq.mm cable from 110/11KV Transformers to 11KV Switchgear.
c) 11 kV XLPE cable, 240 Sq. mm Aluminium cable- 3 core to be run from 11KV Switchgear to 11KV take off DP structure & 11KV Capacitor Bank.
Cable Termination Kit suitable for following sizes as per Technical specifications:
A. Indoor type:
a) Heat shrinkable type Cable termination kits suitable for 1C x 1000 Sq.mm XLPE cable
b) Heat shrinkable type Cable termination kits suitable for 3C x 240 Sq.mm XLPE cable
c) Heat shrinkable type Cable termination kits suitable for 3C x 95 Sq. mm XLPE cable
B. Outdoor type:
a) Heat shrinkable type Cable termination kits suitable for 1Cx 1000 Sq.mm XLPE cable
b) Heat shrinkable type Cable termination kits suitable for 3Cx 240 Sq.mm XLPE cable
c) Heat shrinkable type Cable termination kits suitable for 3C x 95 Sq.mm XLPE cable
FIRE FIGHTING EQUIPMENTS WITH NECESSARY MOUNTING STANDS
i) Mechanical Foam Type Extinguisher :
ii) Water type (gas pressure type) 9 Ltr. capacity
iii) Carbon Dioxide Type 4.5 Kgs capacity
iv) Sand type G.I Buckets 15 Ltr. capacity
v) Steel stands
vi) Dry Chemical Powder -6 Kgs
Capacitor Bank: Design, Engineering, supply, erection, testing & commissioning of 2.9MVAR, 12.1kV Capacitor Bank, star connected, Double Bank with internal fuses, terminal connectors with suitable neu...
11kV Isolators & DP structure:
1) 11KV isolators, Double Break 400A, 25KA capacity with rigid bi-metallic terminal connectors suitable for coyote ACSR for Capacitor Bank
2) 11 kV isolator, single break 400 A, 25 KA capacity with Roaster switch,with LA with rigid bimetallic terminal connector suitable for coyote ACSR.
3) Supply of Double pole structure with 9.5 Mts. RCC poles WL 300 Kgs for mounting 11 kV 400 A SIngle Break Isolators and 9 kV, 10 KA surge arrestor (3 No.) complete set for outgoing feeders
4) Supply of Double pole structure with 9.5 Mts. RCC poles WL 300 Kgs for mounting 11 kV 400 A Double Break Isolators and 9 kV, 10 KA surge arrestor (3 No.) complete set for Capacitor Bank
5) Supply of DP structure with 9.5 mtr RCC poles, 11 kV 400 A double break isolators, 9 kV, 10 KA surge arrestor (3 No.), H-Frame along with DOLO/HG fuse unit, LTprotection kit/LTD box, LT Trivector m...
Maintenance Tools and Plant:
1) Earth resistance tester
2) Portable (mobile) oil pumps (1/2 HP Air pump 500 to 1000 gallons)
3) Telescopic ladder Aluminium 6 Mtr. Height
4) Ring spanner set
5) Tube spanner set
6)Pipe wrench 24 inch
7) Pipe wrench 18 inch.
8) Hydraulic crimping tools up to 1000 Sq.mm
9) Hydraulic shearing machine
10) Threading die set for pipe threading
11) Welding machine (arc welding) 10kVA
12) Heavy duty drilling machine
13) Rubber hand gloves (15 kV tested)
14) Rechargeable 5W LED hand torch
16) Insulated cutting plier 12 inch size
17) Insulated cutting plier 8 inch size
18) Line live tester AC/DC 500 V
19) Screw driver 18"
20) Screw driver 12"
21) Hammer 8 lbs
22)Hammer 2 lbs
23) Chain pulley block 5 ton capacity
24) Hydraulic jack 5T capacity
25) Pipe derrick suitable for lifting 3 MT and lift of 6 Mtr. height.
27)Box spanners
28) Transil oil di-electric break down (with 2.5 mm gap 0-60 kV) Tester.
29) Insulation megger 2.5 - 5 kV
30) Insulation megger 500 V
31) SF-6 gas leak Detector
32) Multimeter electromechanical
33) Multimeter Electronic
34) Protective goggle
MISCELLANEOUS ITEMS :
1) Rubber mats 2000 mm x 1000 mm x 12 mm size suitable.
2) First aid box.
3) Shock treatment charts, hard board, laminated with coloured pictures & literature both in Kannada & English.
4) Water filter / Water purifier : Wall mounting type (Aqua-guard type).
5) Sub-station name board duly painted.
6) Fixograph of size 1.5m x 2.5m with English / Kannada alphabets.
7) Brass cupboard lock 6 levers (best make of approved quality) 75 mm size
8) Danger board (prohibited) with support structure including fixing in front of the gate
9) Equipments name plates and earthing name plates including fixing at outdoor yard
Furniture for control room staff and maintenance staff:
1) Steel Almirahs 6 1/2 feet
2) Steel Almirahs 6 1/2 feet with glass panel doors
3) Officers tables
4) Steel slotted angle rack (big size)
5) Steel slotted angle rack (small size)
6) Steel dust bins
7) Executive Revolving chairs
8) S type arm chairs
9) Steel folding chairs
STATION & YARD LIGHTING (OUTDOOR) (To be designed, assessed & quoted by the bidder)
i)Supply and installation/ Fixing/ Provision of Outdoortype Thermoplastic Modular Panel enclosure with transpar...
STATION & YARD LIGHTING (OUTDOOR) (To be designed, assessed & quoted by the bidder):
1. Supply and installation/ Fixing/ Provision of Outdoortype Thermoplastic Modular Panel enclosure with transp...
Supply and installation/ Fixing/ Provision of Outdoortype Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shockproof, IP65 (WeatherProof), rustproof, dustproof, waterproof...
ii) Supply & Fixing of LED Street light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection...
PLCC equipments
1) Wave Trap with clamps 0.5 mH, 2000A, 50 kA, 50-500kHz Pedestal type Ph-Ph Coupling
2) 40 W Single channel Carrier terminal
3) Coupling device (LMU+LMDU)
4) Protection coupler-4 command version
5) Co axial cable 75 Ohms
6) PLCC EPAX 16/8/8
7) Push Button telephones
8) Battery charger 48V, suitable for 400 AH Battery set
9) Battery set 48V, 400 AH
10)Digital protection coupler 8 command with EI interface with 220V DC power supply.
11) 48V DCDB with independent change over b/w DC Source 1 & DC Source 2,with 20 feeders.
Note: The PLCC equipment is provisioned for Phase-Phase coupling for 220kV lines.
1) (STM-16 MADM UPTO 3 MSP PROTECTED DIRECTIONS)-BASE EQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS,OPTICAL BASECARDS,POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE AND ACCE...
2) OPTICAL INTERFACE-Transceiver
i) Optical interface card (50-75km)
3) TRIBUTARY INTERFACE
i) E1 Interface card (Min. 16 interfaces per card) - 3 MSP
ii) 1X1000 base LX SFP (GIGABIT ETHERNET INTERFACES 10/100 MBPS WITH LAYER-2 SWITCHING)
iii) Ethernet interface 10/100 Mbps with layer-2 switching (Min, 2X1GBPS+4X100/10 Mbps ports) without SFP - 3MSP.
iv) Cabinet Equipment to house SDH Equipment + Optical cards + Tributary Cards, Drop/Insert MUX Equipments and DACS Equipment
v) Digital protection coupler with EI interface with 220V DC power supply.
vi) 220V DC to 48V DC CONVERTER for SDH equipment
vii) Failover Switch/Routers for change over between OFC & VSAT communication for SCADA Data
viii) VOIP Phone
Equipments for establishing SCADA Communication as per Technical Specification :
1. Remote Terminal Unit (RTU)
2. Data Concentrator Unit (DCU)
3. 2 kVA online UPS (230 V AC 1 phase 50 Hz) with Battery set
Cables-Supplying
a) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core
b) Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core
c) Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core
d) Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core
e) Supply Cables-Copper Core with c/s 4.0 sq.mm Multi strand 3 Core for AC input to UPS & UPS to RTU,conforming to KPTCL specifications.
f) Supply Cables-Copper Core with c/s 32.0 sq.mm Multi strand for Battery conforming to KPTCL specifications.
Note : Satellite Communication required will be arranged by SLDC.
Station erection including Designing chargers
POWER TRANSFORMERS:
a) 200MVA, 220/132/11 kV Power Transformer, 3Ph, 50Hz, Core Type, 2 winding Auto Transformer star/Delta, Vector Group: YNa0d11, OLTC, Bushing CT for Tertiary of Ratio 2020/1A, 5P...
Power Transformer:
b) 20 MVA, 132/33kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group DYn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel, Numeri...
Power Transformer:
c) 20 MVA, 132/11kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group DYn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel, Numeri...
CIRCUIT BREAKER : SF-6 Circuit Breaker with rigid bi-metallic terminal connector suitable for Moose/Twin Moose ACSR with spring / semi-pneumatic / pneumatic type operating mechanism and with mounting ...
ii) SF6 Gas circuit breaker with Semi-Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting Structures arrangements with rigid, bi-metallic terminal connectors complet...
iii) SF6 Gas circuit breaker with Semi-Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting Structures arrangements with rigid, bi-metallic terminal connectors comple...
220kV electrically cum manually operated double break type disconnects with solid core insulators, terminal connector suitable for AL. tube/Moose ACSR/Twin Moose ACSR conductor, marshalli...
b) Upright without Earth Switch
i)Live Point Height 8250mm
ii)Live Point Height 5750mm
c) Under hung without Earth Switch
II) 220kV, 1600A, 50kA Double break type.
(i) 3-pole with one earth switch.
ii) 3-pole with two earth switch.
iii) 1-pole (3Phase) Tandem operated ISO without E/S.
II) 220 kV, 1250 A, 50kA for 200MVA Power Transformer Bays & PT bays
a)Upright mounting type without Earth Switch (LPH 8250mm)
b)Upright mounting type without Earth Switch (LPH 5750mm)
c)Underhung mounting type without Earth Switch
V)245kV, 3000A, 50kA Double break type.
(i) 3-pole with one earth switch.
ii) 3-pole with two earth switch.
III. 132kV class Isolators:
132kV, double break electrically cum manually operated isolators with solid core insulator, terminal connector suitable for Al. tube/Moose ACSR/Twin Moose ACSR conductor, ...
b)Upright mounting type without Earth switch(LPH 7000mm)
c)Upright mounting type without Earth switch LPH 5000mm.
d)Underhung Mounting without earth switch
a) Upright mounting type without earth Switch (Live Point Height 7000mm)
b) Upright mounting type without earth Switch (Live Point Height 5000mm)
c) Underhung Mounting without earth switch.
Terminal connectors for Isolators in 220KV PM Mithra sub station shall be as follows :
Rigid type suitable for Twin Moose ACSR conductor - 108 Nos
3)33KV, 800A, 31.5KA Class Double Break Manually operated isolator with terminal connectors suitable for Moose/Drake ACSR/75 mm pipe/63 mm pipe.
a) Upright mounting type with Manually Operated Earth ...
b)Upright mounting type without Earth switch. .(Live point height 3750mm)
c)Upright mounting type without earth switch. (Live point height 4750mm
Terminal connectors for Isolators in 132/33/11 sub station-1+ 2 shall be as follows :
Rigid type suitable for Moose ACSR- 102+1...
CURRENT TRANSFORMERS :
Current transformers including marshalling boxes, Single phase,oil filled outdoor type with rigid bimetallic terminal connectors suitable for Al. Tube/Moose/Twin Moose/Drake AC...
1)220kV, 50kA CT of Ratio 3000-2000/1-1-1-1-1A
For Metering : Accuracy 0.2s, Burden 20 VA
For Differential /Distance protection PS class
Vk = 1600V at 1600/1 A RCt 8ohms,
800V at 800/1A RCt...
2)220kV, 50kA CT of Ratio 1200-800-400-300/1-1-1A with additional 2 Cores of 1200/1A Type-1 (2 nos. main CT is used as NCT)
For Metering : Accuracy 0.2s, Burden 10VA
For Differential /Distance protect...
3) 132kV 40kA CT of Ratio 1000-800-600/1-1-1A [(Required for 200MVA Transformer & bus coupler. and lines)
For Metering : Accuracy 0.2s, Burden 10 VA
For Backup protection : Accuracy 5P20. Burden 30 V...
4) 132 kV class, 40 KA, CT of ratio 600-400/ 1-1-1A for Lines and Bus Coupler
For Backup Protection: 5P20, Burden 30VA
For Metering: Accuracy 0.2S, Burden 10VA
For Differential Protection: PS Class, ...
5)132kV 40kA CT of Ratio 200-100/1-1-1A (Required for 132/33 and 132/11kV Transformer)
Core - 1 : Vk-800 V at 400A, Rct 4 ohm at 400/1A, Accuracy class PS-Dist/Dif
Core- 2 : 10 VA, Accuracy class 0...
33 kV class, 31.5 KA, CT of ratio 400-200/ 1-1-1A
Core - 1 : Vk-240 V, Rct 5 ohm at 400/1A, Accuracy class PS-Dist/Dif
Core- 2 : 10 VA, Accuracy class 0.2s- Metering
Core - 3 : 30 VA, Accuracy cla...
8) 11kV Class, 25kA, NCT of ratio 2000-1200/1-1-1A for (Required for 132/11kV Transformer)
1. All the CTs in each kV class shall be of one and the same make for inter-changeability & reliabilit...
VOLTAGE TRANSFORMERS : Single phase, 3 core, oil filled outdoor type with rigid bimetallic terminal connectors suitable for Moose ACSR/ Al Tube with marshalling box KIOSK as per technical specificatio...
2) 132 kV class 132kV/RT3/110V/RT3/ 110V/RT3/ 110V/RT3
Core - 1 : 300 VA, Accuracy class 0.2-Metering
Core - 2 : 200 VA, Accuracy class 3P-Protection
Core - 3 : 50 VA, Accuracy class 3P. Open delt...
3)33KV, VTs of Ratio 33KV/RT3/110V/RT3-110V/RT3-110V/RT3,
Core-1-Metering - 300VA, Accuracy 0.2
Core-2-Protection -200VA, Accuracy 3P
Core-3-Protection - Open Delta, 50VA, Accuracy-3P
CAPACITIVE VOLTAGE TRANSFORMERS:
245 kV CVT, 4400 pF, 1 Ph CVT with 2 secondaries, terminal connector suitable for Twin Moose ACSR conductor with marshalling box etc., complete as per technical speci...
SURGE ARRESTOR:
Porcelain/Polymer type, with terminal connector suitable for Twin Moose ACSR conductor as per technical specifications.
a) 198kV Metal Oxide with surge counter Arrestor class : Statio...
b) 216 kV, Metal Oxide with surge counter Arrestor class : Station Medium Duty (SM) - Discharge Class 3
Note : Surge arrestors are with surge monitors & insulating base
c) 120 kV, Metal Oxide with surge counter Arrestor class : Station Medium Duty (SM)
Note : Surge arrestors are with surge monitors & insulating base
d)30KV, Metal Oxide with surge counter, station medium duty (SM) - Discharge class-3
e)9 kV, 10 KA with connector and clamp
Control and Relay & Protection Panels complete as per specifications:
I. C&R Panel compatible to IEC 61850 communication protocol for Sub-station Automation System, complete as per technical specific...
2) 220/110/11 kV Power Transformer panel Type 2T1 (as per annexure RPP2-SAS)
3) 220 kV Bus coupler panel Type 2BC (as per annexure RPP1-SAS)
4) 220 kV Bus Bar Protection panel Type 2BBA (as per annexure RPP3-SAS)
5) 132 kV line - Type 1L (as per annexure RPP4-Cable-SAS)
6) 132 kV Bus coupler panel Type 1BC (as per annexure RPP6-SAS)
7) 132/11 kV Transformer panel Type 1T1(as per annexure RPP5-SAS)
8)11 kV line Type 1L (As per Annexure RPP7-SAS) Provision for 2 feeders to be made in one panel and provision for 1 capacitor bank & 1 feeder to be made in one panel)
1) All the C&R panels an...
Installation, integration, testing & commissioning of C&R panels with SAS supplied by a company for new bay extension with their existing Automation System
All types of 220 kV feeder C&R panels with B...
II. Control and Relay Panel complete as per specifications: (For 132/33-11 sub station 1 and 2)
Simplex type 110V DC compatible to SCADA as per EC 61850 Protocol control and relay panels complete as ...
b) For 132kV Bus Coupler
c) For 132/11kV Transformer
d) For 132/33kV Transformer
(1) The Accuracy class of metering core of CTs and also trivector meter of control & relay panels shall be 0.2S class and CVTs & VTs shall be 0.2 Class instead of that specif...
Total Weight of 220kV Station structures & Mounting Structures Including Bolts & nuts at 220/132/11 Kv station, Non Design
Total Weight of 220kV Station structures & Mounting Structures Including Bolts & nuts at 220/132/11 Kv station, Design Based. Note:This Weight Should be same as that indicated in Techno-commercial she...
Total Weight of 220kV Station structures & Mounting Structures Including Bolts & nuts) at 220kv S/S at Ferozabad Non Design
Total Weight of 132kV Station structures & Mounting Structures (Including Bolts & nuts) at 132/33/11kV sub station 1& 2. Non Design
Total Weight of 132kV Station structures & Mounting Structures (Including Bolts & nuts) at 132/33/11kV sub station 1& 2. Design Based. Note:This Weight Should be same as that indicated in Techno-comme...
BUS BAR FORMATION :
a) Formation of Main bus/cross bus (all the three phases in a segment) using Single Moose ACSR Conductor with fixing of insulator spacers, levelling of string conductors to the re...
a) Formation of Main bus/cross bus (all the three phases in a segment) using Quad Bersimis ACSR Conductor with fixing of insulator spacers, levelling of string conductors to the required height above ...
a) Formation of Main bus/cross bus (all the three phases in a segment) using Twin Bersimis ACSR Conductor with fixing of insulator spacers, levelling of string conductors to the required height above ...
b) Formation of Main bus/cross bus (all the three phases in a segment) using Single Moose ACSR / Drake Conductor with fixing of insulator spacers, levelling of string conductors to the required height...
I) RIGID BUS WITH TAPS & CLAMPS : i) Aluminium Tube conforming to 6340 WP of IS-5082 / 1969 (BS 1600-Sch.40) including fixing of clamp, connector jumper, corona ...
iii) 63 mm size for connecting isolator to vertical tap
At proposed 220kV Textile Park S/s-
220kv Side -300mtrs
132kV side- 340 Mtrs
At proposed 132kV Nadisinur S/S
132kV side- 480 Mtrs
iv) 50mm Size for Main Bus -33 KV Side
v) 38mm Size for isolator to vertical tap - 33kV Side
Solid core Bus Post Insulator - Cylindrical Solid core Insulator as per IS:5350, Part-II & III & as per technical specification:
1) For 220kV side -2 units/stack
a) Post Insulators of...
2) For 132kV side -1 unit/stack
At proposed 220kv Textile park
a) Post Insulators of Rigid Bus -86Stacks
b) High level Post Insulators for (200 MVA Tr -6 Nos, 20 MVA Tr -3 Nos.)-9 Stacks
3) For 33kV side -1 unit/stack
At proposed 132kv Nadisinur
a) Post Insulators of Rigid Bus -18Stacks
b) High level Post Insulators for (Tfr )-6 Stacks
At proposed 132kv Keeranagi
a) Post Insulators ...
Auxiliary Transformer:
Erection of Station Auxiliary Transformer with copper windings & oil, cable termination type on both HT & LT, outdoor type, with off load tap changer in steps of 2.5 % as per te...
b) 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn 11
LTAC Panel(Indoor)
1) LTAC panel (indoor ) as per technical specification comprising of voltmete & ammeter, 415V,LTAC Panel (2 I/C ACB 800A+2 O/G SFU 200A+8 O/G SFU 100A+14 O/G SFU 63 A +12 O/G SFU...
2) LTAC Distribution panel ( Indoor), 415V, comprising of Volt meter, Ammeter & 1 I/C MCCB 200A + 2 nos 3 phase, 63A O/G SFU with HRC fuse + 2 nos 3 phase 32A O/G SFU with HRC fuse + 6 nos 3 phase 16A...
AC Distribution box (Outdoor) :
a) AC distribution Box (outdoor):- double front type, 24 terminals, 1200 x 1350 x 600 mm, 2 I / C of 100 Amps, MCCB 20 KA + 24 O / G MCB 16 Amps + 2 O / G of 100 A, HR...
b) AC distribution Box single front type, 6 terminals 750 x 1350 x 300 mm , one I / C of 100 Amps MCCB 20 KA + 6 O / G MCB 16 A + 1 O / G of 100 A, HRC fuse as per technical specifications
c) AC Distribution box (outdoor) Single front type with 6 terminals 1200 x 1350 x 300 mm one I/C of 100 A MCCB 20 KA+ 6 O/G 16 A MCB +1 O/G of 100 A HRC Fuse complete as per technical specifications...
LT Power Cable:
a) Power cable from auxiliary transformer to LTAC panel,
1.1kV PVC insulated 240sqmm Al. cable 3.5 core with glands / lugs/ferruls.
b)1.1kV Class PVC insulated Aluminium power cable (AC supply for lighting & DFDB/SFDB etc., 70 Sq mm, 3.5 core with glands / lugs / ferruls
STATION BATTERY & BATTERY CHARGER:
A) STATION BATTERY SET :
1) 220V, 300 AH Battery set (Plante/Grid Type) with cells & accessories as per technical specifications.
2) 110V, 200AH Battery set (Plante/Grid/Nickel Cadmium Type) with cells & accessories as per technical specifications
B) BATTERY CHARGER :
1) Battery charger suitable for '2 X 220 V, 300 AH, with float (2 Nos) & float cum boost (2 Nos) type battery charger including control panels, change over arrangements etc., com...
2) Battery charger- suitable for '2 X 110 V, 200 AH, Battery set (Plante/Grid/Nickel Cadmium Type)consisting cells as per specifications- 15 A float and 30 A boost (with float and boost battery charg...
PVC insulated Copper Control Cable with Lugs / Ferrules as per technical specifications.
A) 1.1 kV class. Size of cable:
1) 19 Core 2.5 Sq.mm.Copper Control Cables
2) 14 Core 2.5 Sq.mm.Copper Control Cables
3) 10 Core 2.5 Sq.mm.Copper Control Cables
4) 7 Core 2.5 Sq.mm.Copper Control Cables
4) 5 Core 2.5 Sq.mm.Copper Control Cables
5) 4 Core 2.5 Sq.mm.Copper Control Cables
6) 4 Core 6.0 Sq.mm.Copper Control Cables
8)4 Core 4 Sq.mm.Copper Control Cables
12)2 Core 6 Sq.mm.Copper Control Cables
13)2 Core 2.5Sq.mm.Copper Control Cables
B) Copper PVC Instrumentation Cable, Armoured (Screened Cable) Copper Cable with glands/ lugs/ferrules :1P X 0.5 Sq mm screened cable
11 kV Switchgear:-
1) 11kV, 25KA, Metal Clad VCB Switchgear,1600A for 1 Incomer & 1250A for feeders (I/C+5F+2CB +1AP) SAS compatible as per tchnical specification. Annunciator panel shall be simplex p...
11kV Switchgear
2) 11kV, 25kA, Metal Clad VCB Switchgear (1600A for Incomer and 1250A for feeders), outdoor type, each comprising of 2IC+12F+1BC+4CB+1AP (Remote Annunciation cum Control panel) with C...
11kV XLPE insulated UG Cable as per Technical specifications:
a) 11 kV XLPE, 95 Sq mm Aluminium cable- 3 core (for 2 Auxiliary transformers from the 11KV switchgear)
b) 11 kV XLPE cable, 1000 Sq. mm Aluminium cable- 3 Runs per phase of 1CX1000 Sq.mm cable from 110/11KV Transformers to 11KV Switchgear.
c) 11 kV XLPE cable, 240 Sq. mm Aluminium cable- 3 core to be run from 11KV Switchgear to 11KV take off DP structure & 11KV Capacitor Bank.
Cable Termination Kit suitable for following sizes as per Technical specifications:
A. Indoor type:
a) Heat shrinkable type Cable termination kits suitable for 1C x 1000 Sq.mm XLPE cable
b) Heat shrinkable type Cable termination kits suitable for 3C x 240 Sq.mm XLPE cable
c) Heat shrinkable type Cable termination kits suitable for 3C x 95 Sq. mm XLPE cable
B. Outdoor type:
a) Heat shrinkable type Cable termination kits suitable for 1Cx 1000 Sq.mm XLPE cable
b) Heat shrinkable type Cable termination kits suitable for 3Cx 240 Sq.mm XLPE cable
c) Heat shrinkable type Cable termination kits suitable for 3C x 95 Sq.mm XLPE cable
11kV Isolators & DP structure:
1) 11KV isolators, Double Break 400A, 25KA capacity with rigid bi-metallic terminal connectors suitable for coyote ACSR for Capacitor Bank
2) 11 kV isolator, single break 400 A, 25 KA capacity with Roaster switch, with LA with rigid bimetallic terminal connector suitable for coyote ACSR.
4) Double pole structure with 9.5 Mts. RCC poles WL 300 Kgs for mounting 11 kV 400 A SIngle Break Isolators and 9 kV, 10 KA surge arrestor (3 No.) complete set for outgoing feeders
5) Double pole structure with 9.5 Mts. RCC poles WL 300 Kgs for mounting 11 kV 400 A Double Break Isolators and 9 kV, 10 KA surge arrestor (3 No.) complete set for Capacitor Bank
6)DP structure with 9.5 mtr RCC poles, 11 kV 400 A double break isolators, 9 kV, 10 KA surge arrestor (3 No.), H-Frame along with DOLO/HG fuse unit, LTprotection kit/LTD box, LT Trivector meter comple...
Earth Mat formation :
1) Supplying and laying of MS.Flat 75 x 12 mm flat welding and applying ACB paint to welded portion (without Sodium Bentonite clay) as per drawing/standards, if required (all o...
2) Supplying and Grounding of equipment with 75 X 12 mm G.I. Flat and connecting equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling ...
3) Providing 40mm dia M.S.Rod 1.075m long earthmat spikes including heating, bending top 50/75mm overlap flattening and making spike edge at one end driving into the earth below the ground level and ...
4) Grounding of equipment by providing cast iron pipe of 100 mm ID 13 mm thickness, 2.75 metre long with 2 part clamp out of G.I. Flat 50 X 6 mm continuously welded alround the pipe using cast iron we...
5) Supplying & providing 450 mm dia 450 mm height 1.5" to 2" thick hume pipe collar (non pressure type) for earth pits including all lead and lifts etc.,
PLCC equipments
1) Wave Trap with clamps 0.5 mH, 2000A, 50 kA, 50-500kHz Pedestal type Ph-Ph Coupling
2) 40 W Single channel Carrier terminal
3) Coupling device (LMU+LMDU)
4) Co axial cable 75 Ohms
5) PLCC EPAX 16/8/8
6) Battery charger 48V, suitable for 400 AH Battery set
7) Battery set 48V, 400 AH
Note: The PLCC equipment is provisioned for Phase-Phase coupling for 220kV lines.
8)Digital protection coupler 8 command with EI interface with 220V DC power supply.
9) 48V DCDB with independent change over b/w DC Source 1 & DC Source 2,with 20 feeders.
II. SDH EQUIPMENT:
1) (STM-16 MADM UPTO 3 MSP PROTECTED DIRECTIONS)-BASE EQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS,OPTICAL BASECARDS,POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE AND ...
2) TRIBUTARY INTERFACE
i)) Cabinet Equipment to house SDH Equipment + Optical cards + Tributary Cards, Drop/Insert MUX Equipments and DACS Equipment
ii) Digital protection coupler with EI interface with 220V DC power supply.
iii) 220V DC to 48V DC CONVERTER for SDH equipment
iv) Failover Switch/Routers for change over between OFC & VSAT communication for SCADA Data
IV. Equipments for establishing SCADA Communication :
1) Remote Terminal Unit (RTU)
2) Data Concentrator Unit (DCU)
3) 2 kVA online UPS (230 V AC 1 phase 50 Hz) with Battery set
Site Survey Wiring, installation, testiing and commission of DCU (DCU installation to be done in RTU Panel)
4) Integration of RTU, DCU and UPS with field equipments
V.Cables-Laying
a) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core
b) Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core
c) Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core
d) Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core
e) Supply Cables-Copper Core with c/s 4.0 sq.mm Multi strand 3 Core for AC input to UPS & UPS to RTU,conforming to KPTCL specifications.
f) Supply Cables-Copper Core with c/s 32.0 sq.mm Multi strand for Battery conforming to KPTCL specifications.
Note : Satellite Communication required will be arranged by SLDC.
Dismantlng of PI Mounting Structure- 220kV ( 1 for each pole)
Dismantlng of Current Transformers Mounting Structure 220kV
Dismantlng of Voltage Transformers a) 220kV Class CVT
Dismantlng of Double break isolators Mounting Structure 220kV Class i. 3 pole
Dismantling of Lighting/Lightning mast with 50Mtr height: 1 No
Releasing and Re-erection of Existing 220kV Voltage Transformer
Single phase, 3 core, oil filled outdoor type with rigid bimetallic terminal connectors suitable for Moose ACSR conductor with marshall...
Design, developing Structural drawings, foundation design & drawings (for all types of soils), Shop drawings as per the technical specification:
STATION STRUCTURES & MOUNTING STRUCTURES FOR 220kV SUB...
ii) Station Structure Tower - 2T2 with out peak
iii) Station Structure Beam suitable for fixing under hung Isolator - 2B1
iv) Station Structure Beam suitable for fixing without under hung Isolator - 2B2.
B)132kV Side Station Structures:
i)Station Structure Tower - 1T1 with peak
ii) Station Structure Tower - 1T1 with peak 2.5 mtrs extension
iii) Station Structure Tower - 1T2 with out peak.
iv) Station Structure Beam suitable for fixing under hung Isolator - 1B1
v)Station Structure Beam suitable for fixing without under hung Isolator -1B2
C)132kV Side Mounting Structures:
i) 132 kV Isolator Live point height 7000 mm
ii) 132 kV Isolator Live point height 5000 mm
iii) Current transformer 132 kV CTs & 11kV NCT's
iv). Voltage transformer 132kV
v) Lightening Arrestor 120kV
vi)Post insulators for rigid bus 132 kV side
vii)For High Post Insulator for Transformers
(b) For 200MVA, Transformer
132kV side - 6 Nos. (Bolted Type Foundation)
132/11kV transformer - 3 nos.
viii)11kV UG cable terminating structure for 1CX 1000sq.mm cable (11kV side of 20MVA Power Transformer)
Foundation design & drawings (for all types of soils), Shop drawings as per the technical specification:
a) 200MVA, 220/132/11 kV Power Transformer
b) 20 MVA, 132/11kV Power Transformer
c) 20 MVA, 132/33kV Power Transformer
d) 145kV, 3150A, 40 kA Class SF-6 Circuit Breaker
Mandatory Spares
Mandatory Spares:
I) Power transformer
1) Oil Collecting bottle
2) Terminal connector clamps
a. Suitable for 245kV class bushing to suit single Moose ACSR
b. Suitable for 132kV class bushing to suit single Moose ACSR conductor
c. Suitable for 33kV class bushing to suit single Moose ACSR conductor
a. Drain valve (100mm to 200mm size)
(i) 220kV and above class
ii) 110kV and above class
b. Top/Bottom filter valve (50mm to 100mm size)
(i) 220kV and above class
ii) 132kV and above class
c. Top/Middle/Bottom Oil sampling valve with plug (15 to 25mm)
(i) 220kV and above class
ii) 132kV and above class
d. Header pipe valve
e. Gate/Butterfly valves of various sizes ranging from 50mm to 200mm
(i) 220kV and above class
ii) 1320kV and above class
5) Prismatic Gauge
6) Starters, contactors, relays
7) Pressure Relief Device (PRD or PRV)
8) Oil Surge relay
9) Bucholtz relay
10) Tap position indicator
11) Fixed and moving contacts for diverter switch
12) Fixed and moving conatcts for selector switch 220kV and above class
13) WTI with 4 contatcs, 15 meters capillary length with built in CCU RTD and external remote indicator, range 0-150 deg C with SCADA/SAS compatibility
14) OTI with 2 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator range 0-150 deg C with SCADA /SAS compatibility
15) PT 100 sensor along with probe of suitable lengths
II) Circuit Breaker (CB)
1) Closing coil with resistor
a) for 220kV CB
b) for 132kV CB
2) Tripping coil with resistor
a) for 220kV CB
b) for 132kV CB
3) Terminal Pad
a) for 220kV CB
b) for 132kV CB
4) Terminal connector
a) for 220kV CB
b) for 132kV CB
5) SF6 gas cylinders filled with SF6 gas suitable for 1 no of CB(220kV CB,1320kV & 33kV CB)
1) Copper contact finger male & for female
2) Terminal Connector
3) Terminal Pad
4) Relays Panel spares
i) All type of numerical relays
ii) Tripcircuit supervision relay(2Nos)
iii) Self reset trip relay [1No. each type]
iv) Hand reset trip relay[1No. each type]
v) Timer relay [1No. each type]
vi) DC supervision relays
vii) Flag relays [1No. each type]
viii) Auxillary relays [1No. each type]
V) Mandatory spares for SAS
1) Bay control unit with configuration software
2) Ethernet switch of each type
3) Optical fiber cable of longest length
VI) Maintenance & Testing equipment:
i) Fully automatic Tan delta & capacitence test kit
ii) Portable dissolved gas analyser
iii) SF6 gas filling adaptor kit for circuit breaker
iv) Micro ohm meter (1.0 micro-ohm to 199.99micro ohm)
v) BDV test kit (Digital)
vi) Circuit Breaker operational analyzer-DCRM
vii) Numerical relay testing kit
viii) Digital DC insulation tester-5kV
ix) Online DC earth fault locator with built-in charger & rechargeable batteries
x) Combined CT & VT analyzer
Total weight of the Towers (High Tensile Steel) excluding Bolt & Nuts. (220 kV Towers) Non Design
Note : Rate to be quoted as per tonne basis.
Total weight of the Towers (Mild Steel) excluding Bolt & Nuts. (220 kV Towers) Non design
Note : Rate to be quoted as per tonne basis.
Total weight of the Bolt & Nuts. (220 kV Towers) Non Design
Note : Rate to be quoted as per tonne basis. Non design
Total weight of the Towers (High Tensile Steel) excluding Bolt & Nuts. (220 kV Towers) Design Based.
Note : Rate to be quoted as per tonne basis. Note :Note:This Weight Should be same as that indicate...
Total weight of the Towers (Mild Steel) excluding Bolt & Nuts. (220 kV Towers) Design Based
Note : Rate to be quoted as per tonne basis.Note:This Weight Should be same as that indicated in Techno-comm...
Total weight of the Bolt & Nuts. (220 kV Towers) Design Based
Note : Rate to be quoted as per tonne basis.Note:This Weight Should be same as that indicated in Techno-commercial sheet of Line supply po...
Total weight of the Towers (High Tensile Steel) excluding Bolt & Nuts. (132 kV Towers) Design Based.
Note : Rate to be quoted as per tonne basis.Note:This Weight Should be same as that indicated in Te...
Total weight of the Towers (Mild Steel) excluding Bolt & Nuts. (132 kV Towers) Design Based
Note : Rate to be quoted as per tonne basis.Note:This Weight Should be same as that indicated in Techno-comm...
Total weight of the Bolt & Nuts. (132 kV Towers) Design Based
Note : Rate to be quoted as per tonne basis.Note:This Weight Should be same as that indicated in Techno-commercial sheet of Line supply po...
Tower Accessories:
1) Number Plates
2) Danger Board
3) Circuit Plates
4) Phase Plates (Set of 3 Nos.)
5) Earth Bonds 300mm long
6) Earth Bonds 450mm long
i)AAAC Moose Conductor with 1.5% Sag
i) Drake ACSR Conductor with 1.5% Sag
ii)Panther ACSR Conductor with 1.5% sag
I) Insulators Strings suitable for Twin AAAC Moose Conductor as per technical specifications.
NOTE: All the Insulator strings and hardware fittings quoted by the bidder shall be of the same type i.e. ...
B. Suspension insulator strings consisting of any one of the following:
a. Insulator strings consisting of 1X14nos. of 220kV, 90kN Disc insulators.
b. Porcelain long ...
ii)Double Tension Clamp with hardware and arcing horn suitable for 2x16nos. of 220kV, 120kN insulator to suit TWIN Moose ACSR.
iii) Single Suspension Clamp with hardware and arcing horn suitable for 1x14nos. of 220kV, 120kN insulator to suit TWIN Moose ACSR.
iv) Double Suspension Clamp with hardware and arcing horn suitable for 2x14nos. of 220kV, 120kN insulator to suit TWIN Moose ACSR.
II) Insulators Strings suitable for Drake Conductor as per technical specifications.
NOTE: All the Insulator strings and hardware fittings quoted by the bidder shall be of the same type i.e. all the I...
B. Suspension insulator strings consisting of any one of the following:
a. Insulator strings consisting of 1X14nos. of 220kV, 90kN Disc insulators.
b. Porcelain long ...
I) Insulator Hardwares & Clamps suitable for DRAKE ACSR Conductor as per technical specifications:
1.220kV Clamps, Arcing Horns and and Hardwares (Set) complete suitable for Single Tension String f...
2.220kV Clamps, Arcing Horns and and Hardwares (Set) complete suitable for Double Tension String fittings
3. .220kV Clamps, Arcing Horns and and Hardwares (Set) complete suitable for Single Suspension String fittings
II) Insulator strings and clamps for Panther ACSR conductor with Hardwares and Arcing Horns as per technical specifications; (132kV Line)
A. Tension insulator strings consisting of any one of the fo...
II) Insulator strings and clamps for Panther ACSR conductor with Hardwares and Arcing Horns as per technical specifications (132kV Line);
B. Suspention insulator strings consisting of any one of the...
II. Insulator Hardwares suitable for Panther ACSR Conductor as per Technical Specification:
i) 132kV Clamps, Arcing Horns and Hardwares (Set) suitable for Single Tension String fittings.
ii) 132kV Clamps, Arcing Horns and Hardwares (Set) suitable for double Tension String fittings .
iii) 132kV Clamps, Arcing Horns and Hardwares (Set) suitable for Single Suspension String fittings .
iv) 132kV Clamps, Arcing Horns and Hardwares (Set) suitable for Double Suspension String fittings .
ACCESSORIES for AAAC Moose Conductor
a) Mid span compression joint (for AAAC Moose)
b) Repair sleeves (for AAAC Moose )
c) Vibration Dampers (for AAAC Moose )
d)Pre formed armour rods (for AAAC Moose)
ACCESSORIES for Drake Conductor
a) PG Clamps (for DRAKE ACSR)
b) Vibration Dampers (for DRAKE ACSR)
Accessories for Panther ACSR Conductor :
1)MSC Joints (for Panther ACSR)
2)Pre formed armour rods (for Panther ACSR)
3)Repair sleeves (for Panther ACSR)
4)P G Clamps (for Panther ACSR)
5)Vibration dampers (for Panther ACSR)
A) OPGW cable & Accessories as per technical specifications:
1.48 Fibre (DWSM) OPGW fibre optic cable for 220kV LILO line ( inclusive of conductor offline stringing).
2.Suspension Clamp Assembly for 48 fibre OPGW
2.Tension fitting Assembly for 48 fibre OPGW including all accessories for joint box (splicing location)
3.Tension Assembly for dead end for 48 fibre OPGW
4.Tension Assembly -Double Tension pass through for 48 fibre OPGW
5.Vibration dampers for 48 fibre OPGW
6.Down lead clamp assembly for 48 fibre OPGW
7.Joint box for 48 fibre OPGW
8.Tension fiiting Assembly on suspension tower for 48 fibre OPGW including all accessories for joint box (splicing location)
B) FODP 96F: Indoor type (rack mounted with FCPC coupling and pigtails to house LIU) as per technical specifications
C) FODP 48F: Indoor type (rack mounted with FCPC coupling and pigtails to house LIU) as per technical specifications
D) Fibre Optic Approach Cable:
48 Fibre (DWSM) -Including installation hardware set for 48 fibre approach cable as per technical specifications.
Line Erection including design charges
Check Survey and Towers Spotting.
Check survey using their own equipment for 220kV Plain terrain
1.The survey covers the scope as defined in Technical Specifications & As per volume VI of Comm...
Check Survey and Towers Spotting.
Check survey using their own equipment for 132kV Plain terrain
Conducting drone survey of Transmission Lines for collection of data along with Aerial inspection of EHV Line Corridor using LIADR method for measurement of Vertical, horizontal and ground clearances ...
Stringing of ACSR Conductor without allowing the conductor to touch the ground and without damaging the conductor as per specifications.
Paving out conductor from anchor to anchor normally spaced at ...
2.Drake ACSR Conductor
3.Panther ACSR Conductor
Erection of 220kV Transmission Line Towers Non Design (including tower accessories etc., except GI angle, Barbed wire & Grounding materials) as per specifications.
1.The Bidders are required to...
Erection of 220kV Transmission Line Towers Design Based (including tower accessories etc., except GI angle, Barbed wire & Grounding materials) as per specifications.
1.The Bidders are required t...
Erection of 132kV Transmission Line Towers (including tower accessories etc., except GI angle, Barbed wire & Grounding materials) as per specifications.
1.The Bidders are required to quote the r...
Supplying and fixing AC devices:
i) Supplying and fixing GI angle iron 45 x 45x5mm (1Mtr length) with cleats, bolts nuts as per specification and fixing above 0.5 mts length each at inner and outer s...
ii) Supplying and fixing Barbed wire as per specifications.
Grounding of towers including cost of 40 mm dia 2.5 mm thick,class 'C' G.I. Pipe of 3 metres length as per specification with 50 X 6 mm GI Flats 3 metre long, salt, charcoal, including excavation char...
OPGW cable & accessories:
1) Installation, testing & commissioning of 24F/48F OPGW cable along with associated hardware fittings as per technical pecification for OFFLINE condition
2)Joint box for 48 fibre OPGW
3) FODP 96 F: Indoor type rack mounted with FCPC coupling & pigtails to house LIU).
4) FODP 48 F: Indoor type rack mounted with FCPC coupling & pigtails to house LIU).
5) Fibre Optic Approach cable:
48 fibre(DWSM)-including installation hardware set for 48 fibre approach cable
Dismantling Portion:
Note : 1) The Released materials shall be transported to the nearest Stores(Operations) of KPTCL.
2)The rates quoted for releasing/dismantling shall also include the charges for ...
ii) Dismantling of Existing super structure/tower materials ( 1No 220kV DC D+0 Tower (5.258MT)
Design, developing Structural drawings, foundation drawings (for all types of soils), Shop drawings, Proto assembly inspection and Prototype testing with +6mtr body extension (upto destruction) of 22...
ii)220kV NB DC 'B'-type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
iii)220kV NB DC 'C'-type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
iv)220kV NB DC 'D'-type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
Design, developing Structural drawings, foundation drawings (for all types of soils), Shop drawings, Proto assembly inspection and Prototype testing with +6mtr body extension (upto destruction) of 13...
ii)132kV NB MC 'B' type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
iii)132kV NB MC 'C' type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
iv)132kV NB MC 'D' type Normal, +3Mtr, +6Mtr, +9Mtr, +12mtr , +15mtr & +18mtr
Design, developing Structural drawings, foundation drawings (for all types of soils), Shop drawings, Proto assembly inspection and Prototype testing with +6mtr body extension (upto destruction) of 13...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Construction of Embankment with approved materials deposited at site from roadway cutting and excavation from drain and foundation of other structures graded with desired compaction. (Royalty shall be...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Earth work excavation for pipeline trenches in all kinds of soils by mechanical means as per drawing and technical specifications, including setting out, construction of shoring, strutting, barricadin...
Construction of Embankment by excavating the available approved Gravel/ Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/ basalt crushed graded coarse aggregates and fine agg...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/ basalt crushed graded coarse aggregates and fine...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in super structure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) in...
Providing and constructing load bearing wall with Solid Concrete blocks of size 400x200x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2...
Providing and Applying CFTRI approved two component flexible polymer modified acrylic cementitious waterproofing coating with a mix ratio of (5 Liquid :7 Powder) to the RCC surface like Roof, bathroom...
Providing and laying Pitching on slopes laid over prepared filter media including boulder apron laid dry in front of toe of embankment complete as per drawing and Technical specifications Stone/Boulde...
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 g/m2 (bot...
Providing 12 mm cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding,...
Providing 15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of mix: 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corne...
Providing 20 mm cement plaster of mix :1:4 (1 cement: 4 fine sand) to brick/stone masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, includi...
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 ...
Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and jo...
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, e...
Providing skirting, dadooing, rises of steps with white glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and jointed with white cement slurry over existing rough plaster surface using glazed ti...
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 g/L and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shad...
Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67L/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint ...
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two coats on new work after thoroughly brooming the surface to remove all dirt, dust, mortar drops and for...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 m...
Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance plus or minus 1mm), with wall thickness 2.0 mm (plus or minus 0.2 mm), ...
Providing & fixing of 3-track x 2-panel sliding windows made out of multi chambered UPVC(Matching to RAL-9016) sections and with minimum TiO2(Titanium Dioxide) at 6PHR with TPE(Thermo Plastic Elastom...
Providing & fixing of louvered ventilator made out of multi chambered UPVC(Matching to RAL-9016) sections and with minimum TiO2(Titanium Dioxide) at 6PHR with TPE(Thermo Plastic Elastomer) and lead fr...
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. compl...
Providing and fixing bright finished brass butt hinges with necessary screws etc. complete : 125x85x5.5 mm (heavy type)
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitt...
Providing and fixing to existing door frames Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsatura...
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be...
Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually co...
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard ...
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the w...
Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Oval shape ...
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS: 12701 marked, with cover and suitable locking arrangment and making necessary holes for inlet, outlet and ov...
Providing, Laying and Fixing of GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings (excluding the cost of fittings) with cuts and threads wherever necessary, includin...
Providing and fixing PTMT stop cock of approved quality and colour:20 mm nominal bore, 89 mm long, weighing not less than 88 g
Providing and fixing PTMT stop cock of approved quality and colour: 15 mm nominal bore, 86 mm long, weighing not less than 88 g
Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of appro...
Constructing brick masonry chamber of internal dimension 450x450mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plaster...
Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plaster...
Providing and fixing SFRC frame and cover conforming to IS 12592 (part-I)-1988 and IS 12592 (part-II)- 1991 with latest amendment, including cutting slabs to the required size for the opening and fixi...
Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and ...
Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and ...
Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and ...
Providing and fixing Rainy dual capacity self-cleaning roof top rain water harvesting filter or equivalent filter of FL-500 specification suitable for a catchment area of about 500Sqm.
Providing, Single Phase Submersible Pump Sets of 100mm dia (4 inch) suitable for bore well confirming to IS 8034-2000 specifications, to work site with testing of as per instructions of engineer incha...
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a primi...
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direct...
Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and...
Providing PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Providing PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, co...
Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, co...
Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, co...
Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, co...
Supply of ISI mark 175mm nominal bore,plain and steel casing pipe grade of steel Fe 410 of wall thickness conforming to IS 4270-2001 and latest ammendments, electrical resistance welded steel tubes, m...
Providing and laying at site of work MS casing caps as per IS 1239 (part- II) 1982 with all latest amendments if any for any dia. The thickness of plate used for covering one end shall be 3mm (minimum...
Geophysical investigation at site for sinking borewells for supplying drinking water to the habitation either through the Hand Pump MWS or P.W.S.S, by vertical electrical sounding by adopting Venner o...
Providing Submersible Pump Set of 150mm dia suitable for bore well and confirming to IS 8034-2000 ; 3Phase, SS Bowl & Impeller with Low volt Motor as per specifications, to work site as per...
SUBMERSIBLE CABLE
Supply and delivery at site Brand new best make PVC insulated cable of Flat 3 core (sheathed) of nominal cross sectional area as per IS 694-1990 with ISI Mark and as per its latest a...
PRESSURE GAUGE :
Supply and delivery at site of brand new best make pressure gauge bourdon type as per IS 778/1984 with ISI Mark and as per its latest amendments - Size 100 mm
Supply and delivery at site of brand new best make gate valve as per IS 778/1984 with ISI Mark and as per its latest amendments Size 50 mm
NON - RETURN VALVE :
Supply and delivery at site of brand new best make non-return valve as per IS 778/1984 with ISI Mark and as per its latest amendments Size 50 mm
ix) Control Panel BOARD-A:
Supply, installing,testing and commissioning COMMON control panel consisting of the following INCOMING:1 No set of Phase indicating lamps with SFU of suitable rating 1 No, A...
POWER CAPACITOR:
Supply and delivery at site best indigenous brand new power capacitor as per IS 2834/1986 with latest amendments with KPTCL authorities and erection, electrification and commissioning...
Supply and delivery at site delivery of best indigenous brand new MCB (Miniature Circuit Breakers) of required capacity as per IS 88228/1978 and its latest amendments and with ISI Mark of 6/10/16...
Erection elctrification & Commissioning works of pumpsets :
Labour charges for Erection, Electrification and commissioning of Pump sets, including aligning and balancing of all items including supp...
Erection of panel board & meter board Unit :
Labour charges for erection of outdoor type panel board and meter board units with all necessary materials and labour, tools and equipmentsincluding provi...
Main connections:
Providing main connection from pole PVC insulated sheathed steel wire cable in new trench as per IS 1554/ 1988 with latest amendments with ISI mark from KPTCL pole to meter board un...
Earthing: Providing and fixing and wiring earth electrode for grounding circuits IC cutouts and other equipments on the meter board in the pit. The pits should be filled up with equal proportion of sa...
Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete....
Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work sit...
Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work sit...
Point wiring using Copper wire without switch.
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth ...
Point wiring using Copper wire without switch.
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth w...
Point wiring using Copper wire without switch.
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using copper PVC insulated multi strand 2x1.5Sqmm copper wire without...
Point wiring using Copper wire without switch.
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using copper PVC insulated multi strand 2x1.5Sqmm copper wire without...
Point wiring using Copper wire without switch.
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using copper PVC insulated multi strand 2x1.5Sqmm copper wire without...
Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and runni...
Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and runni...
Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks an...
Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks an...
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A One Way Switch
Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using...
Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using...
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 32A DP Switch
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6/16A Universal Socket
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293 TV/Telephone Socket
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall ...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 8...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1...
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 16A One Way Switch
Supplying and fixing one of 230 V Ding dong bell and a flush type bell push with gang box fixed on necessary wooden or rawl plugs using NF screws with Remote. Ding Dong Bell
Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete. 12" Sweep (300 mm)
Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete. - 15" Sweep (450mm)
Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc., for operation on 230 volts, 50 cycles. Single phase AC supply conforming to ISS-374-1979 and with double ba...
Fixing a ceiling/wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 A. ceiling rose, necessary le...
Fixing one exhaust fan after making a suitable notch in the wall and finishing with cement mortar and colouring to match the existing wall or brackets, with bolts and nuts and a 5 A, ceiling rose with...
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. Stepped Fan Regulator Two Module
Supplying and fixing regular MCB distribution boards on wall / wood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase ...
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 p...
Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capa...
Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capa...
Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 32-40A 4 pole
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable 2Pair
Supplying and drawing 3 core flat PVC sheathed submersible pump cable manufactured with electrolytic grade copper with flexible copper with low resistance conductor confirming to13:8130-1984 and virgi...
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for work...
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc using 40mm dia 2.9mm thick 2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixed o...
GI/Copper strips for grounding connections, using necessary fixing materials as required. 600x600x3mm copper plate
Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. And M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. ...
Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage curr...
Supplying, fixing and wiring 0 to 1500amps CT operated AC analog type Ammeter With out CT
Supplying and fixing Electronic Trivector Meter (ETV) suitable for operation LT operation and -CT operated meter in polycarbonate body in class 0.5 accuracy as per IS 14697 and completely wired
Supplying, fixing and wiring rotary selector switch suitable for Ammeter
Supplying, fixing and wiring 50/5 to 400/5A 5VA burden Current Transformer Class 0.5 accuracy with Tape Wound.
Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C.
Supplying ......... A rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator wh...
Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50HzAC with latest micro controller based, digital read out of percentage leakage curr...
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of O...
Supplying of Switch disconnector fuse unit (TPN) HRC type (but without HRC fuses). With AC-23A duty and as per IS- 13947. 125 A
Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polyc...
Fabricating supplying and mounting MS box made out ....SWG suitable for floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped...
Supplying of recess mounting non integrated type LED down light 18W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT...
Supplying of feet -PVC Batten with integrated LED tube LED light fitting 1 x 4ft - 36/40 W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 8...
Supplying of feet -PVC Batten with integrated LED tube LED light fitting 1 x 2ft - 9/10 W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. ...
Supply of round/square recess/surface mounted rolling type LED Down light withLED square or round down light 5-6W GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewire...
Fabricating, supplying and erection of ... ms long hot dip Galvanized Octagonal hot dip Pole with BSEN 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate with door opening arrangements...
Fixing all types and all capacities of fluorescent /falseceiling/ spot light/CFL/LED fittings indoor on the wall/ceiling/rafters/girders using 23/0.0076" twintwisted PVC insulated wires, required No...
Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires
Supplying.....litres capacity vertical/horizontal type wall mounting Electrical water heater with 22 SWG copper/SS sheet metal inner Container tinned inside and anticorrosive paint outside and 20 SWG ...
Erection charges for fixing a ... litres capacity wall mounting electric geysers using bolts, flat at one end nut and washers at the other end for through bolts and nuts and washers with 150x450x600mm...
Supplying ......TR split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed compressor with air cooled condenser, motor capacitor and start run cap...
Supplying ......TR split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed compressor with air cooled condenser, motor capacitor and start run cap...
Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipe...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipe...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipe...
Providing and fixing Modular multi-diameter cable sealing system which is waterproof,fire proof& rodent proof consisting of frames,blocks and accessories to be installed wherever the electrical(power/...
Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ra...
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Iv...
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With water thinnable cement primer on wall surface having VOC content less tha...
Providing and laying 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nomin...
Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height....
Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with vibratory rolle...
Cutting transverse contraction joints 3 to 4 mm wide and depth 60mm in concrete slab using concrete cutting machine with diamond studded saw within 4-8 hours of casting of bay / slab etc. complete inc...
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two coats on new work over an under coat of suitable shade with ordinary paint of appro...
Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) greater than 78, solar reflection greater than 0.70 and initial emittance greater than 0.7...
Providing 12 mm cement plaster finished with a floating coat of neat cement of mix :1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, prov...
Providing and laying vitrified floor tiles with thickness 9-10 mm in different sizes with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, lai...
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per
Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of appr...
providing and fixing factory made ISI marked GI steel Metal emergency exit doors, including cost of materials, labour usage charges of machinery complete as per specification and as per the direction ...
Dismantling dressed stone work ashlar face stone work, marble work or precast concrete work manually/ by mechanical means including stacking of serviceable and disposal of unserviceable material to th...
Demolishing cement concrete manually/ by mechanical means including disposal of material to the appropriate disposal area as per direction of Engineer-in-charg
Dismantling and stacking to the appropriate disposal area as per direction of Engineer-in-charge, fencing posts or struts including all earth work and dismantling of concrete etc. in base of: R.C.C.
Dismantling expanded metal or I.R.C. fabrics with necessary battens and beading including stacking the serviceable material to the appropriate disposal area as per direction of Engineer-in-charge.
Removal, stacking and respreading of existing jelly as per the directions of the engineer in charge of the work including all costs labour, loading, unloading, transportation etc., complete and any ot...
Providing and installing at site of work P.V.C. pipes including cost of pipes and specials and labour, including lowering into trenches, laying true to line, level and perfect linking at joints leak p...
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40 mm dia 2.90 mm thick GI pipe 2.5m long buried in a pit . The pit shoul...
Providing and filling joint sealing compound as per drawings and technical specifications with coarse sand and 6 per cent bitumen by weight
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS C...
Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mor...
Providing 15 mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement: 4 fine sand) including rounding off corners wherever required smooth rendering, providing and removi...
30mm thick factory made polyvinyl chloride (PVC) door shutter made of a uPVC hollow section of size 60x30mm and wall thickness 2 mm (plus or minus 0.2 mm), with inbuilt decorative moulding edging on o...
Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. ...
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard ...
Providing and fixing granite stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal parti tions by cutting a chase of appropriate width with ...
Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing : Rectangula...
Providing and fixing brass bib cock of approved quality 20 mm nominal bore
Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per s...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe wi...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe wi...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe wi...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe wi...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pip...
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipe...
Providing Submersible Pump Set of 150mm dia suitable for bore well and confirming to IS 8034-2000;3Phase, SS Bowl & Impeller with Low volt Motor as per specifications, to work site as per necessary am...
Supplying and fixing sheet Metal box made out of 18SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 100 x 75 x 65 mm
Supplying and fixing sheet Metal box made out of 18SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 135 x 75 x 65 mm
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing m...
Supplying&fixingofPorcelainfusechannelwithcutoutonexisting wooden/panel using necessary nuts, bolts and washers. 100 A
Supplying of on load change over switches 4 poles,AC-23A Duty,415V,50Hz,AC Supply. With all accessories. (SMEnclosure Sheet Metal Execution) 100 A
Supplying, fixing and wiring 3 Phase Digital Ammeter / Voltmeter
Supplying, fixing and wiring Electronic Trivector Meter (ETV) 5 to 32/63A three phase 4wire whole current class-1 Accuracy Energy Meter.
Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C.
Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. And M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. ...
Supplying exhaust fan of 1440 RPM of 300mm (12") size with bracket blades complete for light duty suitable to operateon 230V 50Hz, AC Supply.
Supplying wall mounting fan suitable to operate at single-phase 230v AC supply. 400 mm Sweep
GI/Copper strips for grounding connections, using necessary fixing materials as required. 25 x 3 mm Copper strip
Grounding of equipment with 50 x 6 mm G.I. Flat and connecting equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of holes and conne...
Providing and laying flooring and steps fine machine polished granite stone slabs 20 mm thick on cement mortar bed 1:6, 20 mm thick, and joints finished with cement mortar 1:3 over existing cement con...
Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and jo...
Providing skirting, dadooing, rises of steps with colour glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and jointed with white cement slurry over existing rough plaster surface using glazed t...
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 g/L of approved brand and manufacture, including applying additional c...
Supplying PVC flexible conduit pipe ....mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using N...
Supplying And Fixing Metal Fan Box with Round Hook.
Supplying and Fixing of ---- mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket street light fitting of all capacities to GI or GI or rail or RCC pole / wa...
Extra length of GI pipe of class B 19mm dia for down rod.
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of O...
Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capa...
Supplying, fixing andwiringResidualcurrentcircuitbreaker(RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 16A-25A 2 pole
Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 63 A 4 pole
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Two Way Switch
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Three Way socket
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Bell Push
Supplying And fixing/replacing of 6/16/32A electrical accessories on existing switch board. 6A Pendant Holder.
Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capa...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite /trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant I...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge.No...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT PM Mitra.pdf
Tender Document • 0.31 MB
Technical Specifications PM Mitra.zip
Tender Document • 69.75 MB
Revised Sec 11a Techno Commercial Sheet PM Mithra.xlsx
Tender Document • 1.43 MB
Drawings PM Mithra.zip
Tender Document • 61.67 MB
Amendment-1 PM Mithra.pdf
Others - Amendment-1 • 0.16 MB
Prebid Proceedings PM Mithra.pdf
Others - Prebid Proceedings • 0.10 MB
Circulars and Guidelines.zip
Tender Document • 3.64 MB
Clarification-1 PM Mithra.pdf
Others - Clarification-1 • 0.21 MB
Revised Tender Document PM Mithra.docx
Tender Document • 0.55 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .