Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹458.7 CrAccepted-AOC | ₹458.7 Cr Quoted ₹476.0 Cr | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹495.3 CrRejected-Finance HARSH ANAND YEVALEKAR MALA COLLEGE ROAD NASHIK 422005 | NASHIK | NASHIK | MAHARASHTRA | 422005 | ₹495.3 Cr | L2 | Rejected-Finance HIGHEST RATE |
| 3 | Rejected-Technical A 177 OKHLA INDUSTRIAL AREA PHASE I NEW DELHI 110020 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110020 | - | - | Rejected-Technical As per the records made available to this office, The firm is held responsible for mishap happened at Plot No.3 Yerawada, Pune on Dated 03-02-2022 in which five persons were dead due to negligence, this regard the instructions issued by CE Pune |
| 4 | Rejected-Technical DEE VEE HOUSE MAULSHREE VIHAR IN FRONT OF HOTEL BABYLON INTERNATIONAL VIP ROAD RAIPUR 492006 CHHATTISGARH | - | - | Rejected-Technical Non fulfilment of Criteria i.e. simillar type of work hence Disqualified |
| 5 | Rejected-Technical | - | - | Rejected-Technical Litigation as per the record, news published in DT-NEXT news paper Dt.07-01-2022 and petition is pending in High Court of Madras CNR No. HCMA01-152314-2021, that the action of blacklisting is raised against him hence Disqualified |
Tender Value
Refer Docs
EMD Value
₹2.0 Cr
Closing Date
2 Jun 2022, 5:30 pmClosed
Superintending Engineer, Public Works Circle, Sat
Executive Engineer, Public Works Division, Satara Pawai Naka Satara
Construction of 100 Students Capacity Medical College and 500 beded Hospital Building and Related Works At Satara Tal. and Dist Satara. (Including Electrical Works)
2022_PWDRP_773623_1
E-TENDER NOTICE NO. 67 FOR 2021-2022 (form B-2)
Open Tender
Civil Works - Buildings
720 days
At Satara Tal. and Dist Satara.
As per B-2 Tender form
5 documents required · 5 mandatory
₹5,600
₹2.0 Cr
Chief Engineer Public Works Region, Pune., Central
28 Nov 2022
28 Feb 2022
6 Jun 2022
28 Feb 2022
2 Jun 2022
28 Feb 2022
21 Mar 2022
Amount
Construction of granular sub-base by providing close graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader/ Paver on prepared surface and compacting with vibratory roller to achieve the desired density, complete as per clause 401 -- Plant Mix Method and Grading - I Material
Providing and laying in situ cement concrete M -30 with tremix treatment for 200 mm thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mm wide and 20 mm deep with necessary refilling with bitumen ( excluding reinforcement) with coarse and fine aggregate ( VSI grade finely washed crushed sand) etc. complete...
Providing and laying cement concrete pipe of IS 458:2003 NP-3 class of 600mm diameter in proper line, level and slope etc. complete.
Providing and laying cement concrete pipe of IS 458:2003 NP-3 class of 800mm diameter in proper line, level and slope etc. complete.
Providing and laying cement concrete pipe of IS 458:2003 NP-3 class of 900mm diameter in proper line, level and slope etc. complete.
Providing and laying cement concrete pipe of IS 458:2003 NP-3 class of 1000mm diameter in proper line, level and slope etc. complete.
Providing and laying cement concrete pipe of IS 458:2003 NP-3 class of 1200mm diameter in proper line, level and slope etc. complete.
Dewatering on BHP basis by using water pump including diversion of stream, providing cofferdams, earthern bunds etc. as may be necessary for foundation and other parts of the the works and pumping out water during and after excavation as may be required by using 3.0 BHP pump etc. complete. (prior approval of Superintending Engineer will be necessary)
Dewatering on BHP basis by using water pump including diversion of stream, providing cofferdams, earthern bunds etc. as may be necessary for foundation and other parts of the the works and pumping out water during and after excavation as may be required by using 5.0 to 9.0 BHP pump etc. complete. (prior approval of Superintending Engineer will be necessary)
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means
Excavation for foundation in hard murum including removing the excavated material upto distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.50 m) .) By Mechanical Means
Excavation for foundation in Hard murum including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift above 1.5 m) By Mechanical Means
Excavation for foundation in hard murum and boulders including removing the excavated material up to a distance 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5m.) By Mechanical Means
Excavation for foundation in Hard murum and boulders including removing the excavated material upto a distance of 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift above 1.5m.) By Mechanical Means
Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 50 metres beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift above 1.5m) By Mechanical Means
Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 50 metres beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (for all Lift and leads). By Mechanical Means
Disposing the excess excavated material Murum, Earth obtained from the items of excavation and disposing the same off the site and at dumping place approved by the governing authority including loading, unloading and all leads and lifts complete.
Disposing the excess excavated material Excavated Rock obtained from the items of excavation and disposing the same off the site and at dumping place approved by the governing authority including loading, unloading and all leads and lifts complete.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the bottom surface and sides of excavation at the rate of 5 litres of emulsion concentrate of 1.0 percent of chlorophyrifos per square meter of surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) treatment by treating the backfill in immediate contact with foundation at the rate of 5 litres of emulsion concentrate of 1.0 percent of clorophyrifos per square metre of vertical surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per square metre of surface area covering ten years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 C.M. diametre about 30 -60 cm deep at 15 cm c/c as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper.
Filling in plinth and floors with approved excavated material in 15cm. to 20cm. layers including watering and compacting etc. Complete.
Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 cm to 20 cm including watering and compaction etc. Complete.
Providing dry/ trap/ granite/ quartzite/ gneiss rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete.
Providing and filling in the foundation with sand of approved quality including watering, compacting etc. complete. (To be executed with prior approval of Superintending Engineer)
Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete for all floors
Providing structural steel work in trusses, other similar trussed purlins and members with all bracing, gusset plates etc. as per detailed designs and drawings or as directed including cutting, fabricating, hoisting, erecting fixing in position, Making riveted/ bolted/ welded connection and onecoat of anticorrosivepaint and over it 2 coats of oil painting approved quality and shade etc. Complete. for all floors
Providing, fabricating and erecting at site of work the tubular steel structure (shed) as per standard design and specifications having various spans in between trusses and in multiples of standard length of bays as specified as per standard specifications, inclusive of cost of steel tubular trusses, tubular columns purlins, tie runners, foundation bolts, base plates, nuts and bolts, welding wherever required etc. as per detailed drawing inclusive of one coat of anticorrosive paint and two coats of oil painting of approved quality and shade etc. complete. Spec. Number : As directed by Engineer-in-charge for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite /quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. columns as per detailed designs and drawing or as directed including Steel centering formwork, cover blocks laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite /quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawing or as directed including steel centering, formwork,cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel). With fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite /quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mixcement concrete M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for R.C.C.coping to plinth or parapet and sill of doors and windows moulded as per detailed drawings or chamfered as approved by the Engineer including steel centering, formwork, cover blocks, laying/pumping, compacting , curing , finishing and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap / quartzite /granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. for all floors
Providing second class Burnt Brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in plinth as backing in composite masonry including bailing out water manually, striking joints, raking out joints and watering etc Complete.
Providing second class Burnt Brick masonry with conventional/ I.S. type bricks in cement mortar 1:6in superstructure including striking joints, raking out joints, watering and scaffolding etc. Complete
Providing second class Burnt Brick masonry with conventional/ I.S. type bricks in cement mortar 1:4 in half brick thick wall including mild steel longitudinal reinforcement of 2 bars of 6 mm diameter / 2 hoop iron strips 25 mm X 1.6 mm placed at every third course, properly bent and bonded at ends scaffolding, racking out joints and watering etc. complete for all floors
Providing Autoclaved Aerated Concrete Block masonary of conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in superstructure including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972) for all floors
Providing Autoclaved Aerated Concrete Block masonary of conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in Half brick thick wall including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972) for all floors
Providing uncoursed rubble masonry of trap / granite / quartzite / gneiss stones in cement mortar 1:6 in foundation and plinth of inner walls / in plinth of external walls including bailing out water manually , striking joints on un exposed faces and watering etc.complete.
Providing uncoursed rubble masonry of trap / granite / quartzite / gneiss stones in cement mortar 1:6 in superstructure including racking out joints when plastering is to be done / striking joints when no plastering is to be done on inside watering and scaffolding etc.complete.
Providing coursed rubble masonry first sort of trap / granite / quartzite / gneiss stones in cement mortar 1:6 in superstructure including racking out joints on the inside when plastering is to be done, watering and scaffolding etc. complete.
Providing expansion joints in R.C.C. framed structure (interior column) with plain premoulded filler 25 mm thick including fixing T.W. battens on both faces and finishing as directed etc. Complete. for all floors
Providing expansion joints in R.C.C. framed structure (exterior Columns) with plain premoulded filler 25 mm thick and 3 mm thick alluminium plate, hold fast, fixing T.W. battens on internal face, finishing etc. complete as directed for all floors.
Providing expansion joints in R.C.C. framed structure (at floor level) with premoulded filler 25 mm thick and 3 mm thick aluminium plate as required, bitumen poured filler and fixing T.W. battens on rear faces etc. complete as directed. for all floors
Providing expansion joints in R.C.C. framed structure (at terrace level) with premoulded filler 25 mm thick and 3 mm thick aluminium plate as required, bituminous poured filler, fixing lead, flashing on upper side and T.W. battens on inner face finishing etc. Complete as directed. for all floors
Providing cement based water proofing treatment to terraces/Bath/WC (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in C.M.1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with C.M.1:3 admixed with approved water proofing compound and finally top finishing with average 20 mm. thick layers of same mortar added with jute fiber at 1 Kg per bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300mm x 300 mm. making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test etc. Complete. for all floors
Providing water proof bedding for flooring of Bath and WC 25 mm thick in C.M. 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etc. complete. for all floors
Providing and laying jointless Polydee-LM, a highly flexible elastometric coating for RCC / cementitious surface for terrace waterproofing on B.B. Coba / R.C.C, after application of TP-42 Primer on perfectly clean surface (free from loose dust and foreign matter) application of 1st coat of Polydee-LM @ 700 gms/Square Metre and applying 2nd coat of Polydee-LM @ 700 gms/Square Metre and finishing the same with sprinkling the AG-10 granules on the wet coating. (After finishing covering the treatment with 25mm cement plaster for protection with fibrillated 6mm Plyplast fibre @ 125 gms/Square Metre to be paid in separate item.) covering 7 years guarantee on Court Fee Stamp Paper of Rs. 100/- etc. complete for all floors.
Providing and applying a base coat comprising of 1KilogramPolydee-MC and 1Kilogramfresh cement after wetting the surface followed by drying the surface for 2 days, apply primer coat of TP-40 and after drying, applying Polydee-11 two component (mixing ratio 2 A : 1 B) ) Antibacterial food grade coating inside drinking water tank in two coats with time interval of minimum 8 hrs. covering 7 years guarantee on Court Fee Stamp Paper of Rs. 100/- etc. complete. for all floors
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing for basement or underfor all floors on a base of Cement concrete 1:3:6, including sub base of 2.50 centimeter thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike waterproofing liquids, raking of joints upto 35 mm depth, filling the joints with 6 mm size crushed metal, hand grouting with cement slurry, curing and cleaning, with 7 years guarantee on court fee stamp of Rs. 100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete )
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing treatment to vertical outside faces of Reinforced Cement concrete walls of basement or underfor all floors including filling the gap of 25 mm between rough shahabad and R.C.C. walls with cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift method, brushing the joints horizontally with cement slurry mixed with water proofing liquid for width 30 to 35 mm and sloping coping over topmost tile with cement mortar 1:3, butting the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with 7 years guarantee on court fee stamp of Rs.100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete)
Providing internal cement plaster 6 mm thick in a single coat in cement mortar 1:4 without neeru finish to concrete surface in all positions including scaffolding and curing etc. Complete. for all floors
Providing internal cement plaster 12mm thick in single coat in cement mortar 1:4 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etc. complete. for all floors
Providing internal cement plaster 20mm thick in Single coats in cement mortar 1:4 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing etc.complete. for all floors
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete. for all floors
Providing neeru finish to plastered surfaces in all positions including scaffolding and curing etc. complete for all floors
Providing fine cement finish 1.5 mm thick over green plaster surface including scaffolding curing etc. complete. for all floors
Providing patti/ band 75mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. for all floors
Providing patti/ band 100mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. for all floors
Providing patti/ band 150mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. for all floors
Providing and fixing chicken mesh of 22 gauge, with about 30 cm. width at the junction of R.C.C members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /B.B.masonry and or tying by binding wire etc. complete. for all floors
Providing and applying gypsum plaster with finishing with gypsum material in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete. for all floors
Providing and applying Texture plaster with finishing with texture material of approved make in 3 to 4 millimeter thickness on previously plastered surface, including Plaster Groove 6mm thickness or Tape Grooves 35 to 45 mm thickness or as required, in all position including preparing the surface, scaffolding etc. complete. for all floors
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etc complete. for all floors
Providing and laying machine cut machine Polished Kota stone flooring 25mm to 30mm thick and required width in plain/ diamond pattern on bed of 1:6 C. M. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. complete for all floors
Providing and laying machine cut machine polished machine cut Kota stone slabs 20 to 25 mm thick for treads and risers of steps and staircases, with rounded nosing for the treads on a bed of 1:4 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. Complete. for all floors
Providing sills of required material 20mm to 25mm thick, on a bed of cement mortar 1:4 including cement float, filling joints with neat cement slurry, curing, moulding edges, polishing,cleaning complete. b) Granite. for all floors
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing etc. Complete. For Flooring for all floors
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing etc. complete. For Skirting for all floors
Providing 25 mm to 30 mm thick partition of polished black kadappa stone slab of approved quality including giving required size and shape etc. Fixing in cement mortar 1:3 curing and cement etc. complete. b) Both side polish for all floors
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 mm to 20 mm thick on bed 1:6 cement mortar including cement floats striking joints, pointing in C.M. 1:3 curing and cleaning etc. complete. for all floors
Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etc. complete. for all floors
Providing and fixing machine cut mirror polished 18 mm to 20 mm thick telephone black granite / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone partition with full moulding the edges etc. complete . Both side polish for all floors
Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete. for all floors
Providing and laying vitrified rustic matt stone finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10mm thickness and confirming to IS. 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etc. complete. for all floors
Providing and laying vitrified rustic matt stone finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm to 8 to 10mm thickness and confirming to IS. 15622-2006 (Group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and cleaning. etc. complete. for all floors
Providing and fixing green marble of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing / moulding the sharp edges wherever necessary, curing, etc. Complete. for all floors
Providing and fixing heavy duty inter locking concrete Rubber mould glossy paving blocks of 80 mm thickness of having a strength of 400 Kilogram/Sq.cm. of approved quality and shape on a bed of crushed sand of 25 to 30 mm thick including skirting joints and cleaning etc. complete. (using 100% crushed sand) for all floors
Providing leather finished polishing to Granite Stone slab by continuous grinding in 4 coats of different bits to receive rough and matt finish including buffing process before laying and fixing of stone as per drawing and design, including cleaning, washing and finishing etc. complete. for all floors
Providing leather finished polishing to Kota / Marble/ Shahabad/Kadappa Stone slab by continuous grinding in 4 coats of different bits to receive rough and matty finish including buffing process before laying and fixing of stone as per drawing and design, including cleaning, washing and finishing etc. complete. for all floors
Providing and laying telephone black / Amba White / Cadbury brown / Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etc. complete. for all floors
Providing and fixing in required position skirting or dado of polished Kotah Stone slab 25 mm to 30 mm thick fixed on base on plaster of cement mortar 1:4 including cement float, filling joints with cement slurry, curing rubbing, polishing and cleaning complete. for all floors
Providing and applying three coats of water proof cement paint of approved manufacture and of approved colour to new plastered surfaces including scaffolding if necessary, cleaning and preparing the surface, watering for two days etc. complete. for all floors
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etc. complete for all floors
Providing and applying one coat of seal cement primer of approved manufacture and shed including scaffolding preparing the surface by cleaning dirt and other foreign matters, scrapping if necessary including scaffolding etc. complete. for all floors
Providing and applying two coats of textured synthetic paint of approved shade and quality and one coat of primer before applying textured paint including scaffolding if necessary preparing surface by thoroughly cleaning oil, grease, dirt and other materials as required, etc. complete. for all floors
Providing and applying white-wash in two coats on old / new plastered or masonry surfaces and asbestos cement sheets including scaffolding and preparing the surface by brushing and brooming down etc. complete. for all floors
Providing and applying washable oil-bound distemper of approved colour and shade to old and new surfaces in two coats including scaffolding, preparing the surfaces. (excluding the primer coat.) etc. complete. for all floors
Providing and fixing shutter to wall cupboard made from 19 mm thick Teak particle board with approved coloured laminated face 1.5 mm thick bonded with phenol formaldehyde synthetic resin B.W.P. grade including lipping beading iron oxidised fixtures and fastening and oil primer coat etc. complete. (Excluding cupboard frame). for all floors
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300mm x 40mm x 5mm with oil painting, etc. Complete for all floors
Providing and fixing solid core flush door shutter in single leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete. for all floors
Providing and fixing rolling shutter fabricated from steel laths of minimum thickness 0.9 mm with lock plate of 3.15 mm thickness reinforced with 35 x 35 x 5 mm angle section fitted with sliding bolts and handles for both sides, deep M.S. channel section of depth and thickness not less than 65 mm and 3.15 mm respectively with hold fast arrangements, M.S. Bracket plate 300 x 300 x 3.15 mm minimum size and shape with square bar, suspension shaft of minimum 32 mm diameter, hood cover of M.S. sheet not less than 0.9 mm thickness and of any size at top and safety devices including mechanical gear operation arrangement consisting of worm gear wheels and worms of high grade cast iron or mild steel and one coat of red lead primer etc. complete. (I.S. 62481979) (With mechanical gear) for all floors
Providing and fixing collapsible steel gate in one / two leaves with hot rolled vertical channels of 18 x 9 x 3 mm minimum size, crossings of M.S. flats of size 18 x 5 mm T or E section for runner of minimum 40 x 6 mm size for flange, M.S. flat for top runner of minimum size 40 x 12 mm with roller wheels confirming to grade F.G. 150 fitted with snap headed rivets of minimum size 6 mm max. spacing of vertical channels be 100 mm enclosed gate position and clear space of 150 mm between two sets of crossings with hold fasts, stoppers, spaces, handles, locking arrangement and one coat of red lead primer and oil painting etc. complete. (I.S. 105211983). for all floors
Providing and fixing in position. (as per I.S.1868 / 1982) Aluminium sliding window of two tracks with rectangular pipe With powder coating with box having overall dimension 63.50 x 38.10 x 1.02 mm at weight 0.547 Kilogram/Running metre. and window frame bottom track section 61.85 x 31.75 x 1.20 mm at weight 0.695 Kilogram/Running metre. Top and side track section 61.85 x 31.75 x 1.30 mm at weight 0.659 Kilogram/Running metre. The shutter should be of bearing bottom 40 x 18 x 1.25 mm at weight 0.417 Kilogram/Running metre. Inter locking section 40 x 18 x 1.10 mm at weight 0.469 Kilogram/Running metre. And handle section 40 x 18 x 1.25 mm at weight 0.417 Kilogram/Running metre. and top section 40 x 18 x 1.25 mm at weight 0.417 Kilogram/Running metre. As per detailed drawings and as directed by Engineer in charge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 mm thick plain glass with all required screws and nuts etc, complete. for all floors
Providing and fixing in position (as per 1868 / 1982) Aluminium sliding window of three tracks with rectangular With powder coating with box pipe 95 x 38.10 x 0.90 mm at weight 0.637 Kilogram/Running metre. with window frame bottom track section 92 x 31.75 x 1.30 mm at weight 1.070 Kilogram/Running metre.. Top and side track section 92 x 31.75 x 1.30 mm at weight 0.933 Kilogram/Running metre. The shutter should be of bearing bottom 40 x 18 x 1.25 mm at weight 0.417 Kilogram/Running metre. Inter locking section 40 x 18 x 1.10 mm at weight 0.469 Kilogram/Running metre. and handle and top section 40 x 18 x 1.25 mm at weight o.417 Kilogram/Running metre. As per detailed drawings and as directed by Engineerincharge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 mm thick plain glass and aluminium mosquito net shutter with stainless steel jail with all required screws and nuts etc, complete. for all floors
Providing and fixing cold rolled steel hollow door frame 105mm x 60mm for anysizes including hold fast hinges, tie members with red oxide and gray paint etc. complete as per I.S.I. specifications and code of practice prescribed including anticorrosive treatment as directed by the engineer. for all floors
Providing and fixing in position Powder Coated with Box frame aluminium openable window of any size as per detailed drawing and as directed by Engineer incharge with all necessary alluminium sections including necessary fixtures, friction stay hinges and fastening with 5 mm thick clear float glass etc. complete. for all floors
Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 mm x 1.22 mm box type, 5 mm thick sheet glass louvers, of approved quality etc. complete. for all floors
Providing and fixing mild steel grill work for windows, ventilators, etc. 15 Kilogram/Square Metre as per drawing including fixtures necessary welding and painting with one coat of anticorrosive paint and two coats of oil painting complete for all floors.
Providing and fixing 40mm diameter and 1.5 mm thick Stainless steel hand railing in S.S.304 Grade including fabricating ,fixtures, errecting, necessary welding, grinding, finishing, buffing to stainless steel pipe etc. complete for all floors
Providing and fixing 900mm high S.S.304 Grade Stainless steel railing with 40mm diameter and 1.5mm thick at top,40mm diameter and 1.5mm thick vertical supports spaced at 1.5m center to center and 8mm thick toughened glass including fabricating ,fixtures, errecting , necessary welding , grinding , finishing, buffing to stainless steel pipe etc. complete for all floors
Providing and fixing 45 cm wide mild steel ladder of 40mm x 6 mm mild steel flat stringers and steps of 18 mm dia. mild steel bar for water tank including fixing it in (1:2:4) M-15 cement concrete block 60cm x 30cm x 30cm and painting the ladder complete. (Anti Corossive Paint) for all floors
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 mm x 450 mm size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mm thick supports with kadappah top 35 to 40 mm thick and polished granite 16 to 20 mm top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 cm height and top granite of 75 x 40 cm including cutting, opening for sink of required size in kadappah as well as granite etc. complete. (Platform top size 5.00 m x 0.60 m and height is 0.75 m) for all floors
Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc. complete. for all floors
Providing and fixing reinforced cement concrete cover of size 90 cm x 45 cm with frame over inspection chamber etc. complete. Heavy duty (225 Kilogram)
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete. Heavy duty (160 Kilogram)
Providing and fixing 90 cm. x 60 cm. Granite plate engraving 10cm. height letter, figures including painting the letters /figures with approved colour and shade complete. for all floors
Providing and applying antipeel paint of approved make & approved brand exterior Emulsion paint of approved quality, colour and shade to old and new surface in two coats, including exterior acrylic primer coat, scaffolding, preparing the surface etc. complete (Heat Reflective Paint). for all floors
Providing and laying in situ M-20 cement concrete of trap / granite / quartzite / gneiss metal with 15% plum of trap stones for foundation and bedding of retaining walls and jetty etc. including necessary formwork, compacting, curing, bailing out water manually in tidal range etc. Complete.
Providing and fixing factory made door/Window frames of required colour made with wood Polymer composite (WPC) extuded internal ribbed sections conforming to American Society for testing and materials (ASTM) in regard with density, tensile strength, flexural strength, Izod impact, water absorption and screw withdrawal strength with wall thickness of 5mm (+/1mm) and with frames having mitred joints at each corner, joined together by two nos. of 10 x 8 mm & 40 mm long PVC dovetail keys including hard wood piece support along the full vertical and horizontal length in rebate portion hole for fixing hinges and fixtures and the frames fixed to Walls/columns with 15 mm long dash fasteners/holdfasts (dash fasteners/holdfasts to be paid separately) etc. complete as per the direction of Engineer in charge,with prior approval of concerned Superitending Engineer. 1.2 For Profile size of 100 x 50 mm with 32 x 12 mm rebate for all floors
Providing and fixing factory made door/Window frames of required colour made with wood Polymer composite (WPC) extuded internal ribbed sections conforming to American Society for testing and materials (ASTM) in regard with density, tensile strength, flexural strength, Izod impact, water absorption and screw withdrawal strength with wall thickness of 5mm (+/1mm) and with frames having mitred joints at each corner, joined together by two nos. of 10 x 8 mm & 40 mm long PVC dovetail keys including hard wood piece support along the full vertical and horizontal length in rebate portion hole for fixing hinges and fixtures and the frames fixed to Walls/columns with 15 mm long dash fasteners/holdfasts (dash fasteners/holdfasts to be paid separately) etc. complete as per the direction of Engineer in charge,with prior approval of concerned Superitending Engineer. 1.3 For Profile size of 125 x 50 mm with 38 x 12 mm rebate for all floors
Providing and applying two coats Apex Ultima Puranature Anti-Pollution Or equivalent approved brand, paint should decomposes organic substances and inorganic gases(NOx, VOC?s, CO, Sox, for maldehydes, etc.) in presence of natural or artificial light. It contains Graphene and nanoparticles of titanium oxide. and Absorbs CO2 (4.8 Kilogram/15 l). plaster crack should be filled by Acrylic base Crack seal/Textured Crack filler, Paint has to applied on one coat of Apex Ultima Puranature Anti-Pollution Primer or Equivalent. Warranty Should be given by the Manufaturer The work should be done by the Manufacturer Recommended applicator and he should be able to furnish stage wise onsite technical reports from the concerned company technologist. for all floors
Solid Core Flush door Double leaf Providing and fixing factory made solid core flush door shutters in double leaves 35mm thick,decorative type of exterior grade, as per detailed drawings, conforming to I.S.: 2202 ? 1966 (Revised) including approved face veneers on both sides, without glazing and venetians including mat finish stainless steel fixtures and fastening, stoppers and finishing with french polishing etc. (Excluding door frame)(Sample to be got approved from Ex. Engineer before use) Commercial Hard Wood shutter for all floors
Providing and fixing stainless steel (Grade 304) railing made of hollow tubes, channels, plates etc. including welding grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts, etc. of the required size on the top of the floor of the side of waiste slab with suitable arrangement as per approval of engineer in charge (for payment purpose, only the weight of the stainless steel members shall be considered excluding fixing accessories such as nut bolts, fasteners etc.). 50mm dia. pipe, 1.5mm thickness and weight 1.92Kilogram/ r. metre for all floors
Providing & fixing factory-made steel door of Single leaf External Embossed Wood finish type with a.) frame of size 100x58 mm conforming to IS : 4351-2003 , 1.2 mm thick pre galvanized sheet with mitred and welded cones , frame stretches, hinge reinforcing plates , fixing plates and hardware mounting plates and Polyurethane foam infill b.) Shutter of thickness 46mm made of 0.8 mm thick slip coated pre galvanized steel sheet on both sides conforming to ASTM A527/ASTM A525, BS 2989 1994, IS 277 , Zinc coating 120 GSM . Lock formed panels with internal stiffeners of 3mm thick made of galvanized sheet, 3 mm thick hinge reinforcing hardware mounting plates and lock protection with Honey-comb craft paper infill of thickness 150 GSM of load bearing capacity 500 Kilogram/Square Metre. c.) Finish: Powder coated surface finished with thermosetting polyurethane paint of Aliphatic grade of thickness 60-micron d.) Accessories: Min 8 Anchor fastener of HILTI make, min 3 SS Ball Bearing Butt Hinges of Dorset make, Dorset Mortise lock, SS Tower bolt of 200 mm size, Eye hole, Door stopper complete. for all floors
Providing & fixing factory-made Single leaf 2 hour fire rated door as per IS 3614 Part 2 & BS 476 Part 20 & 22, tested to UL 10 C and conforming to NFPA 80 , tested at NTL /CBRI/ARAI of Plain Steel finish type with a.) Frame of size 143x58 mm and thickness of 1.6 mm thick skin pass galvanized iron sheet (Conform to IS 277 ) formed to single or double rebate profile b.) Shutter of 46 mm thickness and constructed from 1.2 mm thick skin pas galvanized iron sheet (Conform to IS 277) infill Rockwool / Mineral wool/ Honey comb craft paper c.) Vision glass of 5mm thick clear/wired glass Circular or Rectangular d.) Finish : Primed with zinc phosphate stoving primer and finished with Polyurethane aliphatic grade or epoxy paint as required of thickness 60 micron e.) Accessories : Min 8 Anchor fastener of HILTI make, min 3 SS Ball Bearing Butt Hinges, Mortise sash lock with lever handle, Mortise dead bolt , Mortise latch , Door closer , Panic bar and external trim lock and Flush bolts complete. for all floors
Providing internal cement plaster 25 mm thick in single coat using Ready to use wall plaster in cement mortar 1:4 to concrete, brick, stone surfaces in all positions including scaffolding and curing. Providing groove at joint of B.B. Masonry and concrete members complete. With Prior Approval of Concerned S.E. for all floors
Providing internal cement plaster 12 mm thick in a single coat using Ready to use wall plaster to concrete or brick surface in all positions including scaffolding and curing complete. Providing groove at joint of B.B. Masonry and concrete members complete. b) cement ratio 1:4 With Prior Approval of Concerned S.E. for all floors
Supply and Installation of translucent roof with DPI Flux standing seam multicell polycarbonate panel system. The system with complete assembly of co extruded UV protected multicell panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of min 12 mm thick of 900 mm (min.) width with angular daylighting concept. Panels shall have minimum six layers with truss bridge design for higher flexibility & strength. Panels with all fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual appearance. Panels shall be manufactured with vertical standing seam at both sides of the panel. Panels shall be fixed on Purlin with snap on connectors with double tooth grip lock locking mechanism and will be secured on MS structure (will be paid Separately) with 3 numbers self-drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005, as per design requirement. Panels must satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min. of 500 Hours as per ASTM G 155. Panels shall not have Yellowness Index as per ASTM D 1925 of 15 units when tested on a sample exposed to UV for 500 Hours as per ASTM G 155. U value shall not be more than 1.6 W/m2K as per EN ISO 10077-2:2018. Panel shall be with additional End cap/Aluminium U/F profile/ Glazing Bar for ends as required. Panel shall be fixed over MS structural steel/MS purlin (paid separately) conforming to the detail technical specifications as per approved architectural drawings. Trained and factory authorized labour with supervision to complete the entire panel installation as per drawing & direction of the engineering in charge. Colour: As per Approval. Approved Make: FLUX by DPI Daylighting or approved equivalent The 12mm thick panels shall be used for a roofing height of upto 15 mtrs. for all floors
Aluminum Louvers to duct:- Providing and fixing in position anodized Aluminum louvers to ducts with 18 Gauge Aluminum box framing 75x50 mm , 18 gauge aluminum strips with approved colour Anodizing as louvers including cutting, bending as per profile, screwing, including all Necessary Fittings & Fixtures , lead lift scaffolding etc completed. for all floors
Cutting down trees including trunks and branches with girths above 30cm to 60cm and stacking the materials neatly with all lifts and lead of 1000m as directed and earth filling in the depression / pit if any. for all floors
Cutting down trees including trunks and branches with girths above 60cm to 90cm and stacking the materials neatly with all lifts and lead of 1000m. as directed and earth filling in the depression/pit if any. for all floors
Clearing and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned up to a lead of 1000 metres including removal and disposal of top organic soil not exceeding 150 mm in thickness. for all floors
Providing earth work in embankment with approved materials obtained from other sources upto lead of 50m. including all lifts, laying in layers of 20cm. to 30cm. thickness breaking clods, dressing to the required lines, curves, grades & section, watering and compaction with vibratory roller with V-Sat attachment to achieve not less than 97 % of standard proctor density etc. complete ( Material obtained from Other sources) for all floors
Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing to proper grade and camber, applying and brooming requisite type of screening/ binding Materials to fill up the interstices of coarse aggregate, watering and compacting with Vibratory roller. to the required density. By Mechanical Means - Grading I (Using Screening Type A (13.2) mm Aggregate) for all floors
RWH - Shallow Percolation Pit providing, constructing 2.0m deep shallow depth percolation pit comprising of 1.0m dia pre-cast RCC rings, 300mm thick side filling around outside of RCC rings (annular space) with 40mm size boulders including filling of percolation pit up to 0.5m depth (from bottom up) with 25-75mm clean washed gravels followed by 0.5m depth of 10-25mm of clean washed stones followed by 0.5m of washed river fine aggregate (crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel/fine aggregate (crushed sand VSI grade finely washed etc.) media layer including covering with RCC slab, manhole frame & cover, PVC rungs etc. including arrangement for inlet & outlet pipe, excavation & backfilling as shown in the drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge
Providing and fixing heavy duty inter locking concrete RUBBER MOULD GLOSSY PAVING BLOCKS of 60 millimeter thickness of having a strength of 400 Kilogram/sq.m of approved quality and shape on a bed of crushed sand of 25 to 30 millimeter thick including striking joints and cleaning etc. complete. (using 100% crushed sand)
Cutting transverse contraction joints 3 to 4 mm wide and depth 60mm. .in concrete slab using concrete cutting machine with diamond studded saw within 48 hours of casting of bay / slab etc. complete including subsequent widening of the groove 8 to 10 mm. wide at top having depth of 15 mm. as directed by Engineer incharge. for all floors
Providing to contraction joints polysuphide sealent (Pouring grade) confirming to BS : 5212 - 1989 into sawed groove widened at top for sealent reservoir of specified size and shape as per detailed drawing including fixing Polyethylene foam backer rod of required diameter (appraox. 25% larger than the initial 3 mm.to 4 mm. joint) overlaid with bond breaking tape as per detailed drawing. Item includes cleaning the joints with water jet / air compressor and allowing joint to become thoroughly dry before sealent is applied and applying primer. (A) Contraction and longitudinal joints (15 mm. deep x 8 mm.wide) for all floors
Painting Line, Dashes, Arrows etc on Roads in two coats on new work with ready mixed road marking paint confirming to I.S. 164 on Bituminous surface including cleaning the surface of all dirt, dust and other foreign matter, demarcation at site and traffic control (Over/Upto __cm wide) (MORTH-803) – a) SurfaceOver 10cm Wide On New Surface for all floors
Supplying and Fixing of Molded Shank Raised Pavement Markers / Cat's Eye made of polycarbonate and ABS moulded body and reflective panels with micro prismatic lens capable of providing total internal reflection of the light entering the lens face and shall support a load of 16000Kilogramtested in accordance to ASTM D 4280 Type H and complying to Specifications of Category A of MORTH Circular No RW/NH/33023/10-97 DO III Dt 11.06. 1997. The height, width and length shall not exceed 50 mm, 100 mm and 102 +/- 2 mm and with minimum reflective area of 13 Sqcm on each side and the slope to the base shall be 35 +/- 5 degree. The strength of detachment of the integrated cylindrical shanks, (of diameter not less than 19 +/- 2 mm and height not less than 30+/- 2 mm) from the body is to be a minimum value of 500 Kilogram. Fixing will be by drilling holes on the road for the shanks to go inside, without nails and using epoxy resin based adhesive as per manufacturer's recommendation and complete as directed by the engineer.The contractor shall submit a two year warranty for satisfactory field performance including stipulated retro-reflectance of the reflecting panel, to the Engineer. for all floors
Providing and Fixing of Median Marker that are made of tough, high impact resistant, injection-molded, thermoplastic body with an isosceles trapezoidal structure of length, width and height not less than 15cm, 10cm and 10cm respectively and thickness not less than 1.8mm, the body structure shall be rounded at its acute angle, all the corners and edges. The plastic used for molding the Median Marker shall have a minimum Notched Izod Impact strength value of 600 J/m at room temperature, when tested in accordance with ASTM D256 and shall retain at least 70% of this value when subjected to accelerated weathering for 1000hrs as per ASTM G155 or UL746C. The logo of the manufacturer shall be embossed on either side of the body in the injection molding process. The Median Marker shall have rectangular-shaped, fluorescent yellow color retro-reflective sheeting of size not less than 8.5cm*8.5cm and with fully reflective micro prismatic cube corners as its retro-reflective elements as per IRC 67 2010 and ASTM D4956 type XI specifications reflectivity values. The retro-reflective sheeting shall be one or both sides of the Median Marker and shall be edge protected with no exposed edges which will prevent edge lifting, vandalism, sheeting damage, etc. The Median Marker shall be fixed by a combination of epoxy adhesive and grouting. for all floors
Providing and fixing reflective fluorescent tape on old road sign board by following the procedure recommanded by manufacturer.Tape shall be consist of white or coloured sheeting having smooth outer surface which has the property of retro-reflection over its entire surface.It shall be weather resistant and show colour fastness.It shall be new and unused and shall show no evidance of cracking,scaling,pitting,blisting,edge lifting and shall have negligible shrinkage or expansion including cleaning / scraping and painting of existing board etc. complete. (Guidance on the recommanded application of each class of tape may be taken from IRC-67) for all floors
Road Marking with Hot Applied Thermoplastic Compound with Reflectorizing Glass Beads on Bituminous Surface- Providing and laying of hot applied thermoplastic compound 2.5 mm thick including reflectorizing glass beads @ 250 gms per Square Metre area, thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform and free from streaks and holes.complete. for all floors
Providing and fixing steel pipe delineators of 10 cm. in diameter and total height of 130 cm, provided with 2 strips of white retroreflective sheeting of size 5 cm. x 32.5 cm. each fixed horizontally and 2 strips of red retroreflective sheeting each having size 5 cm. x 32.5 cm. fixed horizontally at top, with M.S. round cap having diameter 11 cm. and wire mesh at top (10 guage thick) and height of wire mesh 15 cm, M.S. hold fast 6 mm thick with 35 cm. in length, fixing the delineators in C.C. 1:4:8 concrete block of size 25 cm. x 25 cm. x 45 cm. with necessary excavation etc. Complete. for all floors
Fixing in position Cautionary/ Mandatory sign boards in ground with C C 1:4:8 block of 60cm x 60cm x 75cm size etc. complete as directed including all leads. for all floors
Fixing in position Road Junction/ Informatory Sign Board in ground with C.C.1:4:8 block of 60cm x 60cm x 75cm size including all leads complete. for all floors
Supplying M.S. Angle iron post of size 65 mm x 65 mm x 6 mm drilled on top and painted with one coat of epoxy primer and two coats of epoxy finish paint having black and white bands of 25 cm, last part of the post 0.75 m below ground level is painted with three coats of red lead paint with 2 nos. of high tensile G.I. bolt and nut of size 10 mm dia. of 25 mm long including transportation etc. complete. Spec. Number : As per IRC-67, and M.O.R.T. and H. Circular Number RW/NH-33023/31/88 D.O.III Dated 2-5-1994 for all floors
Providing and constructing Information Pillar of Brick Masonry in C.M. 1:6 of size 2.0 m x 0.23m x 1.0 m with base pedestal of size 2.3 m x 0.35 m x 0.45 m (0.3 m above ground), excavtion in ground upto 0.4 m, laying 0.15 m thick 80 mm soling,0.10 m thick c.c. 1:3:6, finishing the pedestal and pillar in cement plaster 12 mm thick in C.M. 1:5 and finishing the pillar with neat cement finish ,applying flat oil paint of approved colour in two coats, including curing, finishing etc complete.(In Strata/Soil __________) Spec. Number :As directed by Engineer-in-charge. a) In Strata other than B.C. Soil for all floors
Providing and fixing of retro- reflectorised informatory sign board rectangular/Square in shape having area greater than 0.9 square meter made out of ___mm aluminum sheet bonded with white retro reflective sheeting of Class __ ( Type IV High intensity micro-prismatic grade sheeting-HIP) having pressure sensitive/heat activated adhesive retoreflective specified back ground, border and back side retoreflctive symbols, letters, numerals, arrow as per IRC:67-2012 Table No 8.3, supported with back support frame 25mm x 25mm x 3mm, duly painted on back side with two coats of grey stove enamel paint and supported on two Number mild steel angle iron post 75 mm x 75 mm x 6 mm, 3.5 mt long firmly fixed to the ground by means of properly designed foundation with M25 grade cement concrete 45 cm x 45 cm x 60 cm, 60 cm below ground level as per approved drawing The angle iron post shall be duly painted with one coat of epoxy primer and two coats of epoxy finish paints having alternate black and white bands of 25 cm width including GI fixures and transportation etc.complete.The nut bolts of board with angle iron post/supporting structure after fixing at site has to be electrically welded. Class B ( Type IV High intensity micro-prismatic grade sheeting-HIP) sheeting shall have 7 years written warranty from the manufacturer and authorised distributor/convertor issued for field performance including the screen printed areas and cut-out sheeting and cut-out durable transparent overlay film and this warranty certificate in original should be submitted to the Engineer in charge by the contractor/supplier. d) 4mm aluminum composite material of Class C for all floors
Providing and casting in situ or precast tapering R.C.C. M-20 Barrier type Kerb without gutter ( as per IRC 86 1983) embedded 125mm below ground level over M-10 PCC finished neatly with C.M. 1:2, setting the same in C.M. 1:2, including the required excavation in any strata and removing the excavated stuff any where in city and redoing the surface as specified and directed by Engineering In-charge. Using Concrete Batching and Mixing Plant for all floors
Providing and fixing in position Guard Railing as per Drg. Number 15 Type C dt. 20-4-79, with 3 rows of 50mm dia. G.I. pipe 30cm a part and fixed in M.S. channels of section 125 x 65 x 6 mm spaced 2.5 C/c 1:2:4 c.c. bedding of size 45 x 30cm. as per detailed drawing, with 3 coats of approved yellow and black paint including necessary excavation in any strata. for all floors
Providing and laying pitching on slopes laid over prepared filter media including boulder apron laid dry in front of toe of embankment complete as per drawing and technical specifications etc. complete. (by stone/boulder) for all floors
Providing and fixing in position after hoisting, precast 1:2 cement mortar reinforced jali 80 mm thick with 3 mm diameter mild steel bar reinforcement, of approved design on both sides, fixing in cement mortar 1:3 and curing etc .complete. for all floors
Providing and laying perforated PVC 160 mm dia pipe in proper line,leveland slope including necessary material fitting etc. Complete. for all floors
Providing and installing bio digester unit based on DRDO technology made of fibre reinforced plastic (FRP) having composition and following technical specifications and including necessary pipe and accessories up to 3 meter length, excluding the necessary excavation for installing the bio digester. Percentage of fibre glass (glass content in fibre glass should be minimum 30%): -33.33% Percentage of polyester resin: - 66.67% Water absorption (as per ASTM):-0.30% Flammability as per ASTM Tensile strength:-115 MPA Specific Gravity at 25 degree centigrade 1.45 Izod impact strength:-65KJ/M2 Heat defection/distort temperature:-65deg C Corrosion resistance (Non Corrosive) fitted with Inlet pipe size rigid PVC: -100mm Outlet pipe size rigid PVC:-80mm Gas outlet rigid PVC with Valve: 20mm Bacteria immobilization PVC mattes (on all partition) With DRDO TOT licensee and latest batch certificate(month & year of supply) and capacity as below k) Up to 400 user size (5mx2.0mx1.5m), Capacity of Biodigester:-15000 liters, Area of top, bottom and side walls: - 41.00 sq.m, Area of partition walls: 12.00sq.m, Total weight of FRP: - 678.80 Kilogram, Bacteria inoculums quantity: - 5200 liters, Minimum thickness of side walls / top and bottom: 8mm, Number of inside partitions: - 4, Minimum thickness of partition wall: 4mm
Providing flush grooved pointing with cement mortar 1:3 for stone masonry work including scaffolding and curing etc. complete. for all floors
Providing and laying cement concrete flooring 50mm thick with M20 cement concrete laid to proper level and slope in alternate bays including compaction, filling joints, marking lines to give the appearance of tiles of 30cm x 30cm or other size laid diagonally/ square etc. finishing smooth (with extra cement) in any colour as directed and curing etc. complete.with Crushed sand VSI Grade for all floors
Providing and fixing black kadappa stone as shelves 25mm. thick machine polished, extending the polish upto 20 cm width on lowerside, rounding corners, laying in position jointing with bedding cement mortar 1:4 proportion curing etc etc. complete. for all floors
Providing and laying matt finish ceramic tiles of having size 30 cm x 30 cm confirming to I.S.15622/2006 (group D II-A) and 7 to 8 mm thick for flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with white/colour cement slurry cleaning curing etc. complete. for all floors
Providing and laying ceramic tiles having size 30 cm. x 60 cm. confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etc. complete.
Providing and fixing 1.5 mm thick polyvenyl venyl chloride flooring including leveling the base with white cement including pasting with appropriate material cleaning the surface etc. complete for all floors
Providing, laying and fixing exterior grade fibrilling fibre reinforcement heavy duty designer cement concrete tiles for Flooring of approved colour and design 22 +/ -2 mm thick bayer colour pigmented as per IS ..1237 - 1980 having compressive strength more than 500 Kilogram/sq.cm reaffirmed in 2006 ,having wert transvrse strenghth of 3.5 / mm 2, water absorption less than 10 % abrasion / wear resistance less than 2 mm ,skid resistance more than 25.0 (ASTM:E303) and no fading as per DIN - 51094 of size 300 x 300 in plan / designed pattern on a bed of 1:4 cement mortar including cement float ,filling joints with neat cement slurry ,curing, polishing and cleaning etc. complete. For flooring. for all floors
Providing and applying plastic emulsion paint of approved quality, colour and shade to old and new surfaces in two coats including scaffolding, preparing the surface. (excluding the primer coat)etc. complete. for all floors
Providing and applying Royale Luxury Emulsion of approved make on internal wall surface as detailed below Scrapping for surface with emery paper and wipe clean for area. wall primer with brush by adding mineral turpentine oil by 8 to 10 % or water by 15 to 20% allowing to dry for 6 to 8 hoursAfter applying Paints or equivalent acrylic wall putty with appropriate prpportion of water of allow to dry for period of 4 to 6 hours of activity. Scrapping with emery paper and wipe clean Applying paints Royale Luxury emulsion 1st coat with brush water content water 40 to 45% or 65 to 70% by role Applying paints Royale luxury emulsion 2nd coat with brush with water content 40 to 45 % or 65 to 70 % by roller. for all floors
Providing and fixing colour coated Zincalume ( R ) AZ150 ( min 150 gms/sq.mt. total on each side ) profiled sheets for roofing. The feed material is manufactured out of nominal 0.45 mm Base Metal Thickness ( BMT ) (0.5 mm TCT ), Hi-strength steel with min.550 MPa yield strength, metallic hot dip coated with Aluminium-Zinc alloy (55% aluminium 43.4% zinc 1.6% silicon) with COLORBOND ( R ) steel quality super durable polyester paint coat ( with inorganic pigment). The paint shall have a total coating thickness of nominal 35 um, comprising of nominal 25 um exterior coat on top surface and nominal 10 um reverse coat on back surface. Profile sheet shall have nom. 950-1050 mm effective cover width and nominal 25-30 mm deep ribs with subtle square fluting in the five pan at nominal 180-250 mm center-to-center. The end rib shall be designed for anti-capillary groove. and return leg. The feed material should have coil manufacturers product details marked a regular interval. Including fasteners with min. fastened with min. 25 um Zinc-Tin alloy coated, Hex head, self-drilling screw etc. complete. (weight of profile 4.52 Kilogram/Square Metre) for all floors
Providing and fixing UPVC Roof made up of 3 layers roofing material of thickness 2mm having width of 1130 mm and of required Length having Tensile strength not less than 330 Kilogram/cm2, including fastening with self drilling screw having washers made of stainless steel etc. complete. for all floors
Providing and fixing 15 mm thick eco-friendly densified edge calcium silicate false ceiling of approved texture of size 595mm x 595mm in true horizontal level, suspended on interlocking metal grid of hot dipped galvanized steel sections (galvanising at @12 gm/sq.m including both sides)consisting of main T runner suitably spaced at joints to get required length and size 24X38mm. made from 0.33mm thick(minimum ) sheet, spaced 1200mm center to center and cross T of size 24X28mm made of 0.33mm thick(minimum ) sheet to be interlocked at the middle of the 1200x600 mm panel to form the grid of size 600x600mm resting on periphery walls/partitions on a perimeter wall angle precoated steel of size 24x24x3000 made of 0.4 mm thick (minimum) sheet with the help of all plugs at 450mm and laying 15 mm thick densified edges calcium silicate ceiling tiles of approved texture (spintone/cosmos/hexa) in the grid, including light fittings , fixtures , smoke detectors etc., wherever required. Main T runners suspended from ceiling with using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling using 12.5mm dia. And 50mm long dash fasteners, 4mm G.I. adjustable rods with galvanized steel levels clips of size 85x30x0.8mm, spaced at 1200mm center to center along main T bottom exposed with 24mm of all T-sections shall be prepainted with polyester baked paint, for all heights, as per specifications, drawings etc. complete.(currently this item should be used only for VIP cabins) for all floors
Providing and Fixing of Mineral Fibre Board Acoustical Suspended Ceiling System with ultima (Bevelled Tegular) Edge Tiles of size 15mm Exposed GRID. The tiles should have Humidity Resistance (RH) of 99%, NRC 0.7, Light Reflectance 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) in module size of 600 x 600 x 20mm , suitable for Green Building application, with Recycled content of 32%. The tile shall be laid on precoated G.I.channel on XL2 Clip having a web height of 32 mm with 15 mm wide T - section flanges colour white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm and 600 mm Cross Tees with a web height of 32 mm and a load carrying capacity of 7.7 Kilograms/M2 and minimum pull out strength of 100 Kilograms.. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system. The Tile and Grid system used together should carry a 10 year warranty. products approved as per GRIHA and BS 476 etc. complete. for all floors
Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.products approved as per GRIHA and BS 476 etc. complete. for all floors
Providing and fixing in position Gypsum board false ceiling with 12.5 mm thick Gypsum boards, screwed/fixed to the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum center to center distance of 600 milimetre perimeter channel and intermediate channels at maximum center to center distance 1200 milimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 milimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all complete. for all floors
Providing and fixing partition of welded mesh of 3 mm dia. wires 50 mm x 25 mm size mesh including integrated non teak seasoned wood frame 80 x 50 mm of vertical and horizontal scantling and finishing with oil painting 3 coats etc. complete for all floors
Providing and fixing fiber glass reinforced polyster door shutter 30 mm thick as per IS 14856 (2000) (Reaffirmed 2006) without ventilator including chromium plated fixtures and fastening with chromium plated handles on both sides, etc complete for all floors
Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150Kilogramcapacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length aluminium tower bolts, 150mm dia. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.complete for all floors
Providing and fixing in position, Single shuttered aluminium extruded powder coated openable door of overall size 0.90 m x 2.40 m with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150Kilogramcapacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length tower bolts, 150mm diam. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.Complete for all floors
Providing and erecting Y type barbed wire fencing with seven rows of wire with 2.45 mm dia G.I. pipe ( Rezan/ concentiDeleted ire 0.75 mm dia ) with hot dip and G.I. coated hooks as per drawing supported on M.S. angle 50 x 50 x 6 mm at 2.5 mtr. c/c including fixing and fastening with wire, painting M.S. angles with one coat of red lead primer and two coat of oil paint etc. complete. for all floors
Providing and erecting chain link fencing 1.6 M. height with G.I. chain link of size 50 x 50 mm, 8 gauge thick and fixed 75 mm above ground level on vertical M.S. Angles of 40 x 40 x 6 mm size, includind excavating pits for foundation and embedded in C.C. block of 1:4:8 mix of size 450 x 450 x 670 mm. at 1.75 M. c/c with iron bar 16mm dia as hold fast including welding link with angle frame at 30 cm c/c with nuts and bolts and horizontal M.S. Angles at top and bottom of 25 x 25 x 5 mm size and vertical M.S. flat 35 x 5 mm and 25 x 5 mm horizontal including cross support of 40 x 40 x 6 mm angles both side at every corner or bend embedded in concrete blocks of 1:4:8 of size 450 x 450 x 670 mm including 3 coats of oil painting etc. complete. for all floors
Providing and fixing double scaffolding system (cup lock type) on the exterior side of building/structure, including additional rows of scaffolding in stepped manner as per requirement of site, made with 40mm dia M.S. tube, placed 1.5 metre centre to centre, horizontal & vertical tubes joint with cup & lock system with M.S. Tubes, M.S. tube challis, M.S. clamps and staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for execution of work of cleaning and/ or pointing and/ or applying chemical and removing it thereafter. The scaffolding system shall be stiffened with bracings, runners, connecting with the building etc, wherever required, if feasible, for inspection of work at required locations with essential safety features for the workmen etc., complete as per directions and approval of Engineer-in-charge. Note:- (1) The elevational area of the scaffolding shall be measured for payment purpose. (2) The payment will be made once only for execution of all items for such works. for all floors
Providing and Laying factory made coloured chamfered edge Cement concrete grass paver blocks of required strength,thickness & size/shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of fine fine aggregate (crushed sand VSI grade finely washed etc.), compacting and proper embedding/laying of inter locking paver blocks into the fine aggregate (crushed sand VSI grade finely washed etc.) bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) and cutting of paver blocks as per required size and pattern, finishing and sweeping extra fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) and complete as per manufacturer spsecifications & direction of Engineer-in-Charge. 60mm thick CC paver block of M-35 grade concrete with approved colour and design & pattern. for all floors
Bamboowood 14mm thick wall Skirting - Providing & fixing in position Phenol bonded Epitome Bamboowood in wall skirting with planks of sizes 14mm thick, 1900mm length (minimum) and 85mm wide (minimum), in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building materials & Technology Promotion Council (BMTPC). The skirting shall be fixed SS screws & rawl plugs, over underlayment of 4mm thick expanded poly ethylene foam sheets having density 40Kilogram/One Cubic Meter, over prepared surface. The Epitome Bamboowood planks shall have minimum density 1000 Kilogram/One Cubic Meter & minimum Hardness 1000 Kilogramf. with Eco friendly UV coating, all complete as per direction of Engineer in-charge for all floors
Bamboowood 20mm thick Decking Outdoor Flooring Tile Providing & fixing in position Phenol bonded Epitome Bamboowood deck flooring tiles with planks of sizes 20mm thick, 1900 mm length and 135mm wide ,in approved colour , texture and finish , having performance Appraisal Certificate (PAC) issued by Building Materials& Technology promotion Council (BMTPC)with necessary profiled edges and groove fixed with 40mm ss screws 3 nos in each tile to frame work made of second class seasoned and treated teak wood of size 38x38 mm placed underneath acoss the tile at both ends and in centre fixed with clips holding in position. The Epitome Bamboowood planks shall have minimum density of 1000 Kilogram/One Cubic Meter & minimum hardness 1000 Kilogramf.all complete as per direction of engineer in-charge. for all floors
Providing and fixing in position U.P.V.C.(Unplasticized Poly Vinyl Chloride) having multi-chambered outer frame section (73 x 50)mm with an outer wall thickness of 2mm & steel reinforcement, multi-chambered slider frame (73x 60) mm with steel reinforcement, multi-chambered slider sash (46x 82) mm with steel reinforcement designed to give optimum strength, 5 mm thick toughened double glass with 12 mm spacer of good quality including alluminium track, Inter-locking profile, coextruded beadings, EPDM gaskets,silicon sealent,sliding handle, fixtures and fastenings (couplings, hinges) including with all required screws and nuts with all necessary U.P.V.C. sections as per the detailed drawing and as directed by Engineer-In-Charge etc. complete. for all floors
Supplying, filling, spreading & leveling stone boulders of size range 5cm to 20cm in recharge pit, in the required thickness, for all leads & lifts, all complete as per the direction of Engineer-in-charge. for all floors
Supplying, filling, spreading & leveling gravels of size range 5mm to 10mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge. for all floors
Supplying, filling, spreading & leveling coarse fine aggregate (crushed sand VSI grade finely washed etc.) of size range 1.5mm to 2mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer in charge. for all floors
Gravel packing in tubewell construction in accordance with IS:4097, including providing gravel: fine/ medium/ coarse, in required grading & sizes as per the actual requirement, all complete as per direction of Engineer in charge. for all floors
Providing and Fixing Sun Louvre panels roll formed, 0.6mm thick, pre-painted stove enameled aluminium strip of a corrosion resistant alloy, including necessary fitting etc. complete, as directed by Engineer in Charge. for all floors
Supplying and spreading geofabric filter layer of Geotextile of Polypropylene multifilament woven to the line, level and grade with pore size less than 0.075 mm and permeability greater than 9.0 litre/Square Metre/second confirming specification IS:1969 and ASTM standard including conveying to the site, joining and stitching with proper overlap and laying at excavated surface in tidal condition as directed by Engineer- in- Charge etc. complete. for all floors
Supply & Fixing of Rectified Porcelain Stoneware Tiles for Ventilated Facades of Specified size as per specification/ site drawings having 6 mm and 9 mm thickness with factory made Kerfs (grooves) as per need and size 600/1200 and 800/1600. The Rectified Porcelain Stoneware Tiles shall possess properties having Water absorption < 0.5% Bending Strength > 40 N/mm2 and are resistant to : UV Light, chemicals, smog, thermal shocks & bacteria. The facade will be made from Nexion Rectified Porcelain Stoneware Tiles (Sintered Compact Surfaces) specified as per ISO 13006 : Annex G- EN 14411 : Annex G : Dry Pressed Ceramic Tiles and all the tests carried out by Italian labs accredited according to ISO/ IEC 17025 : 2005. The Terramilano Fixing sub structure will confirm to Norme Tec niche per le Costruzioni NTC/8 (Technical Standard for construction) guidelines for construction in Italy, Eurocode . for all floors
Supply & Fixing of Rock / Stone Finished outdoor vitrified flooring Tiles 20 mm thick and required width wide in plain pattern including Cement float, filling joints, with neat cement slurry, Natural sand, curing and cleaning complete. with prior approval of concerned Superitending Engineer. for all floors
Dry wall cladding with clay tile; Designing, supplying and fixing of Clay tile of Wienerberger (Red Series or Grey Series) or Equivalent with suitable size and thickness not less than 20 mm as per manufacturer with approved colour and pattern with composition of finest powdered clay and colour mixtures. The clay tile shall be fixed on the suitable farming system by using continuous aluminium profiled section as per manufacturer with suitable size and spacing to withstand the structural design criteria specifled in the technical specification by using necessary HDG brackets, SS316 grade anchor bolts etc as per manufacturer specification. Cladding joints should be with open groove system. with prior approval of concerned Superitending Engineer. for all floors
Providing and Fixing toilet set for differently Abled persons consist of Floor Mounted white vitreous china water Closet including 6 litre capacity white vitreous china flushing Cistern with raised soft-push button, white vitreous china wash basin of size 46 x 36 cm and one no SS 304 hinged rail 76 cms & three no SS 304of (Grab Bar) 60 cms all including cutting and making good the walls and floors wherever required ,seat cover, cistern & wash basin fittings,nuts, bolts and gasket etc complete as per the direction of Engineer-In-charge. for all floors
Providing and fixing ISI marked double swing flush door shutters conforming to IS :2202 (Part I) Non-decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 30 mm thick including ISI marked Stainless Steel L- hinges with necessary screws Fittings & Fixtures per leaf SS kick plates on both sides of the door of 300mm height Heavy Duty satin finish butt SS Hinges (100mm x 75mm x 3mm in size) -4 nos. SS finished lever handle with mortise lock- 1 Number Floor spring- 1 Number 100mm x 100mm safety glass at the specified location for all floors
Providing and applying blue and white coloured thermoplastic road marking paints for marking a 3ft x 3 ft universal accessibility symbol within the parking bay as paer the drawings and up to the satisfaction of the engineer in charge. for all floors
Acrylic tactile audio map Design, supply, fabrication and fixing of acrylic, non glare, tactile audio pictorial building layout as per the approved size, design and make, having 6mm thick acrylic non glare base plate of the approved colour and non glare acrylic cut out symbols and upper case Sans Serif letters of 12mm height, raised 3mm above base plate and Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate. The map to be installed at the specified location as per accessibility standards, shall be oriented to the position of the viewer and to be installed at a height of 800 mm from the finished ground/ floor level and using the necessary hardware specified by the manufacturer and to be installed up to the satisfaction of the engineer in charge. for all floors
Directional signage Design, supply, fabrication and fixing acrylic multilingual Braille (raised dots) directional signboards of size 6" x 9" designed as per accessibility standards and having 4mm thick acrylic base plate with Upper Case San Serif words made of white acrylic non glare cut out letters of height 15mm raised not less than 0.8mm above base plate and the equivalent word written in Hindi with Devnagri non glare acrylic letters of height 15mm raised not less than 0.8mm above base plate and having a non glare acrylic cut arrow pointing in the required direction. Each signboard to be fixed as per manufacturers specifications on the wall at the approved location and at a height of 1200mm from FFL and as per the directions by the engineer in charge. for all floors
Floor Directories Providing and fixing acrylic multilingual Braille (raised dots)ADA compliant modular floor directories system on all floors of size1.5' x 2' , showing the floor plan and the list of rooms on that floor, to be installed on each floor near the staircase, designed as per standards and having 4mm thick blue acrylic base plate with Upper Case San Serif words and symbols made of white acrylic non glare cut out letters of height 20mm raised not less than 0.8mm above base plate and the equivalent word/s written in Hindi with Devnagri non glare imported acrylic letters of height 15mm raised not less than 0.8mm above base plate. Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate. Each directory to be fixed as per manufacturers specifications on the wall at the approved location at a height of 1200mm from FFL and as per the directions by the engineer in charge. for all floors
Providing an ADA compliant Disability Service Desk having a lowered portion (800mm from FFL) and leg space of 450 mm, having the approved design and of the approved make as per manufacturers specifications for all floors
Providing and fixing SS-304 studs having 35mm dia. of the approved brand and make inside the building on all floors in corridors, lobbies level differences etc. as per accessibility standards and as per the installation instructions prescribed by the manufacturer, using the necessary adhesive including finishing work up to the satisfaction of the engineer in charge complete. for all floors
Providing and fixing SS-304 strips of size 280mm x 35mm of the approved brand and make inside the building on all floors in corridors, lobbies level differences etc. as per accessibility standards and as per the installation instructions prescribed by the manufacturer, using the necessary adhesive including finishing work up to the satisfaction of the engineer in charge complete. for all floors
Providing and fixing Braille indicators for handrails of the approved design and make having Braille dots raised 0.5mm above base plate, to be installed at the specified locations as per the directions of the engineer in charge for all floors
ADA compliant modular Multilingual and tactile Emergency evacuation map of each floor indicating the current position of the viewer saying "YOU ARE HERE" of 15mm height letters in red with white bacKilogramround, indicating the emergency exits, locations of fire extinguishers etc. Signs shall have a solid header with the text “EVACUATION PLAN” in contrasting uppercase letters no less than 3/4" in height. The size of the board shall be 2ft x 2ft and shall be installed at a height of 1200mm from FFL and shall be oriented to the position of the viewer as per the direction of the site engineer. for all floors
Fire exit and floor identification signage as per manufacturer's specifications, ADA compliant and modular system for all floors
Supplying and installing of in position the signages " FIRE ORDER" it should contain the following matter on 3mm thick "Opaque" PVC foam board of computerized cut, PVC Non-reflective self adhesive vinyle painted foam board of 3' x 4'.Product to be ADA compliant and modular system. for all floors
Providing an emergency evacuation chair of the approved design, weight and loading capacity for all floors
Providing and fixing the reader of the approved brand and make as per the manufacturers specifications and as per the directions of the engineer in charge for all floors
Providing and fixing the transmitter of the approved brand and make on each floor as per the manufacturers specifications and as per the directions of the engineer in charge for all floors
Providing and fixing SS Braille buttons in the elevator of the approved brand and make to be installed using the specified adhesive and as per the instructions given by the manufacturer for all floors
Providing and fixing of high intensity reflective conspicuity tape 25 to 50mm width, on edges of treads in staircase including, cutting, pasting etc. of make 3M or equivalent brand as per the direction of engineer in charge for all floors
Providing a folding wheelchair of Pioneer Surgicals Brand, model Number PS 809/ equivalent make as per the directions of the engineer in charge. for all floors
Design, supply, fabrication and fixing of SS, non glare Signage board (2 ft. x 2 ft.- 1 Number) for the accessible parking, as per the approved design and make, having 1.2mm thick SS non glare base plate and Grade 2/ Grade 1 Braille (raised dots)to be etched/ engraved and be raised 0.5mm above base plate and Upper Case San Serif words and Universal Accessibility Symbol to be etched/ engraved and signage to be installed at a height of 2100mm from the ground level using a post of MS hollow square section (50mm x 50mm) as per the installation procedure specified by the manufacturer and as per accessibility standards and up to the satisfaction of the engineer in charge. for all floors
Design, supply, fabrication and fixing of SS, non glare multilingual Braille (raised dots) entrance signage (size 1 ft x 1 ft) as per the approved design and make,indicating the name of the building. Having 1.2mm thick SS non glare blue coloured base plate with the 'Universal Accessibility Symbol' and Upper case Sans Serif words of height 15mm engraved on it along with the equivalent word/ s written in Hindi using Devnagri script of height 15mm in white colour. Grade 2/ Grade 1 Braille to be etched/ engraved and be raised 0.5mm above base plate.The signage to be installed at the specified location on the compound wall near the site entrance gate installed at a height of 1200 mm from the finished ground/ floor level, using the necessary hardware specified by the manufacturer and to be installed up to the satisfaction of the engineer in charge. for all floors
Providing and laying in place 300mm x 300mm x 16mm cement tactile directional and warning tiles (for a person with visual impairment)of the approved brand and make and specified colour for outdoor floors such as footpath, courtyard, multimodals location etc. laid on 20mm thick base of cement mortar 1:4 (1 cement: 4 coarse sand) in all shapes and patterns including grouting the joints with white cement with matching pigments etc. complete as per direction of engineer in charge for all floors
Providing and laying in place 300mm x 300mm x 9.8mm vitrified tactile warning and directional tiles of the approved brand, make and colour inside the buildings at in all corridors and lobbies, level differences etc. as per accessibility standards and as per the installation instructions prescribed by the manufacturer including zarri making wherever required and finishing including grouting the joints with white cement with matching pigments etc. up to the satisfaction of the engineer in charge complete. for all floors
Design, supply, fabrication and fixing acrylic multilingual Braille (raised dots) signboards of size 6"x 9" for room titles, designed as per the drawings issued and having 4mm thick blue acrylic base plate with Upper Case San Serif words made of white acrylic non glare cut out letters of height 15mm raised not less than 0.8mm above base plate and the equivalent word/s written in Hindi with Devnagri non glare acrylic letters of height 15mm raised not less than 0.8mm above base plate. Grade 2/ Grade 1 Braille to be integral with the sign face and be raised 0.5mm above base plate.Each signboard to be fixed as per manufacturers specifications on the wall adjoining the respective room door at a height of 1200mm from FFL and as per the directions by the engineer in charge. for all floors
Providing and fixing in place 300mm x 300mm x 3mm polyurethane stick on tactile directional tiles and warning tiles having beveled edges and of the approved brand, make and colour and conforming to ISO 23599: 2012 inside the building on all floors in corridors, lobbies , level differences as per accessibility standards and to be installed as per the installation instructions given by the manufacturer using butyl rubber adhesive and the hardware specified by the manufacturer, as per the direction of the engineer in charge complete. for all floors
Grab bars-Providing SS grab bars set for accessible toilets comprising of 4 nos. Grab bars as specified below.(1 nos. wing grab bar + 1 nos. L shaped grab bar + 2 nos. straight grab bars = 1 typical set) 27a) Swing grab bar (1 NOS) Providing a S.S. 304 SWING HANDICAP GRAB BAR - 700 mm and of DIA: 32MM and thickness 1.5mm of the roved brand and make. 27b) L Shaped grab bar (1 NOS) Providing S.S. 304 L SHAPED DISABLED GRAB BAR of IZE-600MM (H) X 600MM (D) and 32MM DIA. and thickness mm of the approved brand and make. 27c) Straight grab bar (2 NOS) Providing S.STEEL 304 GRAB RAIL (600 MM),32MM DIA. and thickness 1.5mm of the approved brand and make. for all floors
Providing and Fixing Accessible Wayfinding and navigation signage systems - Providing and fixing in location as diected by Engineer in Charge, accessible modular wayfinding and navigational signage system comprising of ADA and Harmonised Guidelines compliant sigange and wayfinding elements, in multilingual, tactile and braille format. Sigange systems to be designed for entire building / complex under consideration for all floors
Providing,aupplying,fabricating and fixing panel of aluminium composite panel cladding in approved shape made out of 4 mm thick ACP sheet material consisting of 3mm thick FR grade mineral core following NBC part IV Fire and life safety (having 2 hours fire resistance in accordance to ASTM E119-12 and BS476 part 6 and 7 class O) sandwitched between two aluminium sheets (each 0.5 mm thick of AA 5005/AA3105 grade) The aluminium composite panel cladding sheet shall be coil coated with kynar 500 based PVDF/Lumiflon based fluropolymer resin (having 70:30 ratio of PVDF and acrylic) coating of approved colour and sg=hade on top face and polymer (service) coating of bottom face as specified using stainless steel screws,nuts,bolts,washers,cleats,weather silicon sealent,backer rods etc .overall weight of the ACP shall not be less than 7.5 Kilogram/Square Metre) for all floors
Providing and fixing in position TMT FE 500, 25mm dia dowel bars precoated with anticorrosive epoxy paint of required Dia. 60 cms. Long and at 30.00 cm. C/C and PVC pipe of 32 mm dia wherever directed including handling, straightening, necessary cutting supported by TMT FE 500, chairs with proper alignment by using properly designed assembly of Bulkheads lubricating half length with bituminous paint as directed etc. complete. for all floors
Supply and installation of ZMS (Nylon) cubicles of width and depth as per specifications/ site drawings. Cubicle height will be 2003 mm. ZMS Series Cubicles: Std Sizes (W x D x H): 900 mm x 1550 mm x 2003 mm, (Height is including 150 mm gap from bottom) Door Width- 600 mmITEM DESCRIPTION Made from solid grade compact high pressure laminate as per IS:2046 and EN-438 manufactured under high specific pressure > 5 MPa and temperature >120?C. All doors will be of single colour and made of 12 mm thick HPL compact panel. All pilasters will be made of 12 mm thick HPL compact panel. All intermediate partitions or dividers will be made of 12 mm thick HPL compact laminate panels. Size of panels to be as per drawing. HARDWARE & ACCESSORIES are Semi-spherical (Top) head frame structure for surface protection. Size to be 50x32x1.6T. Corner joinery section, Size to be 40x16.5x1.8T.U-Channel Wall joinery section, Size to be 22x16x1.6T.Door stopper section, Size to be 21x12.5x1.6T. Stainless steel grade 304 screws, Anti-rotation Nylon polyamide grade-6 expandable wall plugs, The Work shall complete as per drawing , under supervision of engineer in charge, etc complete. for all floors
for all floors METAL FALSE CEILING WITHOUT SUSPENSION SUPPORT FROM TRUE CEILING: Providing & fixing horizontal level suspended metal ceilings comprising of Metalworks F-H 600 Hook-on corridor system manufactured by Armstrong Ceiling Solutions with Rectangular panels made of 0.7mm thick Galvanised Steel (GI) of 120gsm, post coated to Global White colour, suitable for Interior applications and architectural finishes, double grid concealed system and butt joint panels. The panel width shall be 300mm, length ranging from 1500mm to 2660mm. General Specifications:Entire system to be designed for Interior applications, and concealed Grid, Butt joint panels. Panel Specifications: Material: The F-H 600 rectangular Hook-on panels to be made of galvanized steel (GI) of minimum 120gsm hot dipped galvanization (both sides included) as per IS 277 (2003), zero or minimum spangled, in minimum base material thickness of 0.7mm as per in IS:513 (1994). Dimensions: The panel Length varies between 1500mm to 2660mm, panel Width shall be 300mm. The dimensional tolerances for length shall be ±1.0m up to 1000mm L; ±1.5mm between 1001 to 2000mm L; ±2.0mm between 2001 to 3000mm L. The dimensional tolerances for width shall be ±0.5m up to 300mm W. Dimensional Tolerances for panel Thickness / panel width / panel length - to be measured in accordance with TAIM standards. Edge detail: the panels shall ha+A3ve Square Edge, with a 3mm(W) x 8mm(H) black foam gasket glued at the edges, typically on one long and one short side. All adjacent panels shall touch each other forming a butt joint and concealed grid visuals. Upturns: The short side of the panel shall have vertical upturns of minimum 30mm (H) and shall be bent appropriately bent as per the manufacturer‘s specifications for providing hook-on ends. The long side shall have inside horizontal bends of 5-15mm for rigidity and vertical upturns of 40mm (for length ranging from 1251-2660mm). Surface Finish: Plain: The panels shall be in plain unperforated finish (without any acoustical backing / felt). Colour and finishes: The panel surface shall be electrostatically powder coated (post coat) on visible side after mechanical production, using RoHS compliant powder, to achieve coating thickness ranging from 60-80µ and architectural quality finish. The powder coating shall pass Salt Spray Test for 750 Hours as per ASTM B117, QUV –A Test for 1000hours as per ASTM G-154 – (Cycle – 1) and Humidity test for 1000hours as per DIN 50017, 250 hours of condensation test (as per DIN 50017 or DIN EN ISO 6270-1 Norms), UV resistance of 500 hours and 50% gloss retention (as per ASTM G 154 UVB-313 Norms). The powder coating shall have an adhesion of GT0 as per EN ISO 2409. The shade variation across batches shall be delta E (∆e) <1 measured using Excite/BYK Gardner instrument and gloss level of 25±5% at 60˚ as per ASTM D523.The colour / shade to be Global White (Polyester for Interior) as approved by the Architect or Engineer-in-charge. Surface Protection: The visible panel surface shall be protected using a guard film made of LDPE of 50µ thickness, having appropriate surface adhesion (or tackiness) corresponding to surface gloss level. Light reflectance: The panel shall have a Light Reflectance of ≥ 63% in accordance to ASTM 1477-98. Flatness and Sag limit: Panels shall be flattened by precision leveller to minimize sag to less than Length/400mm. The difference between the two diagonal dimensions of the panel to be less than 1mm. The sag to be measured at the center in accordance with TAIM standards. Access and Plenum space: The panels to be Fully Accessible, with system height of 98mm, and would require a plenum height of a minimum 450mm clear space from bare ceiling / rigid structure for installation. Packaging: The Panels shall be packed in wooden crates of appropriate dimensions based on panel sizes. The wooden planks for rates shall have thickness of approx.15mm, width of around 4‖ and gap between two planks around 3‖. Crates to have layer separators of 1‖ x 2‖ dimensions to prohibit load transfer on bottom panels, and the crates lifting to be 2way or 4way. The bottom of crates shall be completely closed, and the panels kept inside shall have cushioning of corrugated sheets or other appropriate material. Installation Specifications: Primary and secondary runners Installation: U-Profiles, spaced at 1200mm, to be suspended from ceiling using clamping brackets and threaded rods OR hanger wires. Hanger wires must be wrapped tightly with 3 full wraps. The J Bars (directional) shall intersect the U-profile at 90° at every module dictated by the panel length. The J-Bar is connected to the U
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting , curing , finishing and rougheningthem if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying in situ /Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. including bailing out water, Steel centering formwork, laying/pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. complete, with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and constructing 75 mm. thick Modified Penetraction Macadam (MPM) road surface including all materials, preparing the existing road surface, spreading 40 mm. stone layers metal 30% crusher broken metal + 70% Hand broken metal (By breaking Rubble obtained by blasting) , heating and spraying the bitumen of specified grade @ 2Kilogram/ Square Metre , spreading 12mm.size chips compacting with three wheel static roller having weight 8 to 10 MT. to achive the desired degree of compaction as per Technical Specification Clause 506 etc.complete, including applying tack coat of specified grade of bitumen at the rate of 0.30KilogramSquare Metre. on existing bitumen surface. (VG-30 bulk bitumen rates are considered to arrive at rates) for all floors
Providing and applying tack coat on the prepared surface heating by fames in Boiler and spraying bitumen with sprayer on Dry / Hungry B.T. surface 3 Kilogram/10 Square Metre. (VG-30 bulk bitumen rates are considered to arrive at rates) for all floors
BITUMINOUS MACADAM:--Providing and laying bituminous macadam using crushed aggregate of Grading 1, premixed wi th bituminous binder , transported at site with VTS, laid over a previously prepared surface , finished to the required grade ,level, alignment ,and rolling to achieve the desired density for 80/ 100 mm compacted thickness with drum mix type hot mix plant with SCADA having complying essential features of Hot mix plant as per IRC-27 2009 specified conditions and attachments such as electronic load sensor based belt conveyers, automatic synchronization of bitumen and aggregate fedder ,built in dust cont roller system and PLC for Drum Mix plant ,Sensor paver ,and Vibratory roller excluding pr ime/ Tack coat etc. complete –Bitumen VG-30 grade 3.30% for all floors
Providing and applying tack coat on the prepared surface heating by fames in Boiler and spraying bitumen set footed in bitumen boiler on B.T. surface 2.5 Kilogram/10 Square Metre.(VG-30 bulk bitumen rates are considered to arrive at rates) for all floors
BITUMINOUS CONCRETE:--Providing and laying bituminous concrete using crushed aggregate of grading 1, premixed with bituminous binder @5.40% by weight of total mix and filler, transported at site with VTS, laid over a previously prepared surface, finished to the required grade ,level, alignment, and rolling to achieve the desired density for 50mm compacted thickness with drum mix plant with SCADA, Sensor paver and Vibratory roller excluding prime/Tack coat etc. complete --Bitumen of specified grade with stone dust filler. (VG-30 bulk bitumen rates are considered to arrive at rates) for all floors
Supplying hard murum/ kankar at the road site, including conveying and stacking complete. for all floors
Spreading hard murum/ soft murrum/ gravel or kankar for side width complete for all floors
Compacting the hard murum side widths including laying in layers on each side with vibratory roller including artificial watering etc. complete. for all floors
Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate ( VSI grade finely washed crushed sand) conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, , cement content not to be less than 150 Kilogram/ One Cubic Meter, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant/ Weigh batch mixer, transported to site with all leads and lifts, laid with a paver with electronic sensor /by suitable means as approved by Engineer-in-charge , compacting with vibratory roller, finishing, curing and including preparation of sub-grade surface if required etc. complete.
Design, supply, fabrication & erection of approved structural glazing using specially designed Vertical Mullion & Horizontal Transoms of Required size & as per architect's approved Grid work with aluminium rectangular sections to be fixed in masonary at interval of eachfloor on concrete slab with 80 mm x 100 mm x 5mm thick galvanized M & Langle fixed on wall side with raw bolt size of 10 mm x 90 mm with necessary bolts & washers / nuts for the plumb the linelevels. the glass panel's shall be fixed on a specially designed architectural sub- frame using Dow Corning 995 strural sealant & GE Silicon (SSG - 4000) sub frame would be fixed on main frame grid in amanner that no aluminium frame is visible from outside & groovesbetween the glass panel shall be filled with weather sealant of Dow corning 789 / GE Sil proof to made it air tight, water proof & dustfree thus giving it a flush look outside. Glass will be of 6 mm thickGlaverbel reflective type with heat strenghthened Toughened for all floors
Providing and fixing in position to the exact profile and prestressing the high tensile strands to specified ultimate strength, standard end anchorages, cable ducts, grouting ducts after prestressing and bearing plates with wedges as per detailed drawings including necessary plant and machinery for prestressing etc. complete. for all floors
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap / granite /quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap / granite /quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mixcement concrete M-40 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M-40 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
providing and fixing oval type under counter wash hand basin of 16 inch x 22 inch size and of special colour shade having telephonic black / coloured granite of 180 mm thick stone black kadappa framework including chromium plated coupling bottle - Trap using CERA company or equivalent oval typa wash basin model no 3448 as per detailed drawing or as directed by engg incharge etc complete. (Counter size 1.20 m x 0.60 m ) for all floors
Casement window double panels with S.S. friction hinges (300 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. (Area of window above 0.75 One Square Meter upto 1.50 One Square Meter) for all floors
Providing and applying 2 Coats of high quality acrylic copolymer matt latex low VOC emulsion paint of approved shadethat gives smooth, flat and washable and durable finishing of approved make. Paint should have good flow levelling property with good colour retention and incan antibacterial property. Paint has to be applied on smooth and uniform surface prepared by an acrylic copolymer low VOC & Odour putty. This surface should be primed with water based low VOC acrylic copolymer based primer sealer that has incan antibacterial property. The work activity should cover all aspects of applying paints from surface preparation, filling to erecting and dismantling of scaffolding, finishing the surface etc as directed by Engineer in charge. for all floors
Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap / quartzite /granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix C.C. M-30 of trap metal for RCC rectangular grid beam with slab as per detailed design and drawing or as directed including dewatering if necessary, steel centering, formwork, cover blocks, laying/pumping,compacting , curing , finishing and roughening them to form surface with C.M. 1:3 of sufficient minimum thickness to give smooth and even surface or roughening them if special finish is to be provided and curing complete (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete batch mix plant (pan mixer). With fine aggregate (Crushed sand VSI Grade) for all floors
Providing and laying Cast in situ/Ready Mix C.C. M-40 of trap metal for RCC rectangular grid beam with slab as per detailed design and drawing or as directed including dewatering if necessary, steel centering, formwork, cover blocks, laying/pumping,compacting, finishing the form surface with C.M. 1:3 of sufficient minimum thickness to give smooth and even surface or roughening them if special finish is to be provided and curing complete (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) for all floors
CP SANITARY Providing and fixing sink cock with regular swinging spout (Wall Mounted Model) with wall flange with approved make including other necessary fitting, etc. complete as directed by Engineer in charge. for all floors
Providing and fixing C.P. BIB cock with wall flange of approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge. for all floors
Providing and fixing Hand shower (health faucet) with 8mm dia. 1m long flexible tube having wall hook with approved make including necessary sockets/ union nut etc. complete as directed by Engineer in Charge. for all floors
Providing and fixing Shower Head with shower arm of approved make shower tube hand shower with Divertor of spout including all necessary pipe fittings and connections etc. complete as directed by Engineer in charge. for all floors
Providing and fixing Shower Head, with shower arm of approved make Mixer of including all necessary pipe fittings and connections etc. complete as directed by Engineer in charge. for all floors
Providing and fixing Oval Type Under Counter Wash Hand Basin of 420 x 590 x 195mm size with pillar cock, C.P.Angular stop cock, long thread of approved make continental including SS bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 mm thick fixed on Black Kadappa Framework, etc. Complete as directed by Engineer in charge. for all floors
Providing and fixing Table top white wash basin of size 120x635x405mm rubber plugs and brass chain, with pillar cock, C.P.Angular stop cock long thread, continental including S.S. bottle trap of approved make having necessary pipe connection up to the outside face of the wall.etc complete as directed by Engineer in Charge. for all floors
Providing and fixing white Opal series European type wall-hung, of size 400 mm x 370 mm x 575mm with approved make flush valve including soil pipe, vent pipe upto outside face of wall, 100mm dia C.I. plug bend inlet pipe all fittings, cutting & making good walls, floors etc as directed by Engineer in charge. for all floors
Providing and fixing Orissa Pan of size 580x445x260 mm with approved make flush valve including trap, C.I. soil and vent pipe upto outside face of wall including 100mm dia. C.I. plug, bend and necessary pipe connection, etc complete. As directed by Engineer in charge. for all floors
Providing and fixing C.P. a 2-Way BIB cock with wall flange of approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge. for all floors
Providing and fixing white glazed urinal of size 710x460x300mm with sensotronic concealed type flushing valve for urinal with complete kit having fittings, inlet pipe with stop tap, brackets for fixing the cistern, 32mm diameter P.V.C. flush pipe with fitting and flushing arrangement including lead soil pipe, lead trap & soil pipe connection upto the outside face of wall etc complete. for all floors
Providing and fixing wall-hung white wash basin of size 470x575x190mm of approved make half pedestal, pillar cock, C.P. Angular stop cock, long thread continental including S.S. bottle trap of having necessary pipe connections up to the outside face of the wall.etc complete. for all floors
Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc. complete. for all floors
Providing and fixing partition with kadappa stone of all sizes and 25 mm thick polished on both side and edges to original including fixing in position in cement mortor 1:4 curing polishing, cleaning etc complete. for all floors
Providing and fixing chromium plated towel rod 16 mm dia and 75 cm. in length including all accessories complete. for all floors
Providing and fixing stainless steel sink of size 600 x 510 x 200 mm including coupling, outlet pipe, elbow and other necessary fitting, finishing etc. complete. for all floors
Providing and fixing C.P. Angular stop clock with wall flange of approved make continental including necessary sockets/union nut etc. complete. for all floors
Providing and fixing Glass self 125 mm wide and 600 mm long with necessary chromium plated brackets providing T.W.gutties etc. complete for all floors
Providing and fixing 25mm diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangement and lock.[Without chamber]. for all floors
Providing and fixing 50mm diameter water meter with non-return valve including strainer,sockets/ union nut and including water meter box making locking arrangement and lock. [without chamber] for all floors
Providing and fixing 100mm diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangement and lock.[Without chamber]. for all floors
Providing and fixing screw down for 25 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete for all floors
Providing and fixing screw down for 32 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete for all floors
Providing and fixing screw down for 40 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete for all floors
Providing and fixing screw down for 50 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete for all floors
Providing and laying cast iron pipes of B class of 150mm diameter with sockets and spiget ends/ flanges and cast centrifugally/ vertically including specials, laying pipes and back filling the trench complete including excavation. for all floors
Providing and making flanged connection for the 150mm diameter cast iron pipe line including painting rubber insertion, nuts and bolts etc. complete. for all floors
Providing and fixing 75 mm dia stabiliser pipe/ P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc.complete for all floors
Providing and fixing 100 mm dia stabiliser pipe/ P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc.complete for all floors
Providing and fixing P.V.C. Rain water pipes of 160mm outer diameter and having wall thickness of 2.2 to 2.7 mm confirming to I.S. 13592-1992 including proper rainwater receiving recess with P.V.C. plug, bend, necessary fittings, such as, offsets, shoes, including fixing the pipe on wall using approved wooden cleats projecting 25mm to 40mm from face of wall a fixing with clips of approved quality and number ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on C.C. or masonry blocks, including necessary scaffolding and maintenance for 3 yrs for any leakages or dislocations of pipes. All the P.V.C. fittings and additional 2 piece socket clips shall be got approved from engineer in charge etc. Complete. for all floors
Providing and fixing P.V.C. Rain water pipes of 110mm outer diameter and having wall thickness of 2.2 to 2.7 mm confirming to I.S. 13592-1992 including proper rainwater receiving recess with P.V.C. plug, bend, necessary fittings, such as, offsets, shoes, including fixing the pipe on wall using approved wooden cleats projecting 25mm to 40mm from face of wall a fixing with clips of approved quality and number ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on C.C. or masonry blocks, including necessary scaffolding and maintenance for 3 yrs for any leakages or dislocations of pipes. All the P.V.C. fittings and additional 2 piece socket clips shall be got approved from engineer in charge etc. Complete. for all floors
Providing and fixing in position UPVC ultra violet stabilized 110 mm outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement etc. complete for all floors
P.V.C. pipe 50mm dia.10kg/cm2 pressure(class IV) for all floors
EXTERNAL DRAINAGE Providing and fixing 15cm x 10cm salt glazed stoneware gully trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron lid and cast iron grating for the gully trap. for all floors
Providing and laying 100 mm dia salt glazed stoneware pipe including fittings such as bends, tees, single junction, double junctions laying, jointing (including excavation and refilling the trenches) complete. for all floors
Providing and laying concrete pipes of I.S.NP. class of 150mm diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. for all floors
Providing and laying concrete pipes of I.S.NP. class of 225mm diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. for all floors
Providing and laying concrete pipes of I.S.NP. class of 300mm diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. for all floors
Providing and constructing Brick Masonry Inspection Chamber 60cm x 45cm x 90cm including 1:4:8 cement concrete foundation 1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and with frame fixed in cement concrete with R.C.C. Cover medium duty 140Kilogram with frame etc complete. for all floors
Providing and constructing Brick Masonry inspection trap Chamber 90cm x 45cm including 1:4:8 C.C foundation, 1:2:4 C.C.channels/half round glazed stoneware pipe channel, salt glazed stone-ware intercepting trap with rodding pipe set in 1:4:8 cement concrete block, brick masonry plastering inside and Outside, fixed in cement concrete with R.C.C. Cover medium duty 140 Kilogram. etc complete for all floors
Providing and constructing Brick Masonry Inspection Chamber 90cm x 45cm With R.C.C. raft in B.C. soil area including cost of reinforcement, 1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and airtight with 75 mm thick R.C.C. cover medium duty 140Kilogram etc. Complete. for all floors
Providing and laying cement concrete pipe of IS 458:2003 NP-2 class of 450mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. for all floors
Providing and constructing Ductile Iron circular manhole 45 cm dia. At top 90 cm at bottom up to 1.80 meter to 2.70 meter depth including excavation, laying 1:4:8 cement concrete bedding 15 cm thick burnt brick mansonry with 1:1 cement mortar plaster 25 mm thick inside and outside 20 mm (1:3) ductile iron heavy type cover with ring 125Kilogramin weight. High strength. More life and Durability, Good Antiskid Grip, Suitable to heavy theatric loading, Light weight casting after cost benefits for Transportation Refilling etc. as per requirement. with prior approval of concerned Superitending Engineer for all floors
C.I. Steps for Manhole ..for all floors
EXTERNAL WATER SUPPLY Providing and fixing 40 mm. dia Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements etc. complete. for all floors
Providing and making ISI Mark ferrule connection of 25mm dia.to water main including ferrule coupling cast iron bell mouth cover, built in non return valve and fixing including excavation and reinstatement complete. for all floors
Providing and making ISI Mark ferrule connection of 50mm dia.to water main including ferrule coupling cast iron bell mouth cover, built in non return valve and fixing including excavation and reinstatement complete. for all floors
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 50mm dia.
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 65mm dia
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 80mm dia.
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 100 mm dia
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 150mm dia.
Supplying & erecting cast iron double flange butterfly valve complete as per specification no. FFVL/BFV 200mm dia.
Supplying and erecting cast iron double flange NRV complete as per specification no. FFVL/NRV .. 100 mm dia
Supplying and erecting end line strainer for positive suction complete as per specification no. FFVL/ELS .. 100 mm dia
Supplying and erecting elastomeric nitrile rubber / foam tube type sleeves for over coating and insulating on provided PC / copper pipes having 9 mm thickness and following inner diameter / sizes for solar water heater system. 22mm
Fixing 3 layer PP-R (Polypropylene Random Copolymer) pipes SDR 7.4 / PN 16, UV stabilized & anti-microbial fusion welded,as perIS:15801 & having thermal stability for hot & cold water supply, including all PP-R plain & brass threaded polypropylene random fittings, including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (diameter below are ID of pipe) (for cold and hot water piping) 20mm pipe
25mm pipe
32mm pipe
40mm pipe
50mm pipe
65mm pipe
80mm pipe
Providing and fixing stainless steel Dirty Utility sink of size 800 x 600 x 450 mm, with SS back panel with long body Bib cock with 110mm outlet with 110mm dia PVC P-trap inlet including coupling, outlet pipe, elbow and other necessary fitting, finishing etc. with SS frame on 4 legs & supports as per consultants drawing. for all floors
Providing and fixing stainless steel Bed pan sink of size 600 dia x 450 mm deep, conical funnel shape design with SS back panel with CP health faucet with 1.5m CP braided hose, CP angle cock with 110mm outlet with 110mm dia PVC P-trap inlet including coupling, outlet pipe, elbow and other necessary fitting, finishing etc. with SS frame on 4 legs & supports as per consultants drawing. for all floors
Providing and fixing stainless steel scrub sink of size 600 x 600 x 300 mm,with SS back panel with long body Bib cock swivel type, elbow operated with 50mm outlet with 50mm dia PVC P-trap inlet including coupling, outlet pipe, elbow and other necessary fitting, finishing etc. with SS frame on 4 legs & supports as per consultants drawing. for all floors
Providing and fixing SS 'Y' type strainer with watch glass and cleaning back-flush valve.,with MTA/FTA for all leads and lifts, testing etc. complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.) 25mm
Providing & fixing gun metal horizontal wafer type non return valve conforming to IS 778 and tested to a pressure not less than 15 Kg/Sq.cm, Including rubber gasket, flanges, union, nuts, bolts & washers complete as required., for all leads and lifts, testing etc. complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.) 25mm
Closed Cell Thermoplastic Elastomer PU foam Insulation over pipes and fittings. (for Hot water supply) 50 mm dia, Insulation thickness 25mm
Providing and fixing UPVC Floor trap (multi-type - 7") of self cleansing design with water seal not less than 50 mm, 3 nos. of 40mm waste water connections, including cost of cutting and making good the walls and floors where required Including CP grating, including square C.P. brass grating with C.P. brass frame with anti-cockroach trap including fixing to the floor with cement mortar and colour grout etc., for all leads and lifts, testing etc. complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.) for all floors
Polypropylene soundproof pipes as per EN 1451 tested for soundproofing test as per EN 14366 for Soil and Wastewater pipes including all fittings e.g. (plain or door) bends, junction, offsets, access pieces, clean-outs, cowls, jointing with rubber ring joint (push-fit) including cutting chase or holes in walls and floors and making good where required including fabricated pipe supports, GI brackets, clamps, U-clips etc complete. 75mm pipe
110mm pipe
Polypropylene Floor trap 7'' (multi-type) of self cleansing design with water seal not less than 50 mm, saddle piece for 50mm waste water connections, set in cement concrete 1:2:4 mix complete including cost of cutting and making good the walls and floors where required.100 mm dia and 300mm long upstand pipe fix on floor trap with end cap. for all floors
Providing and laying cement concrete pipe of IS 458:2003 NP-2 class of 600mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. for all floors
fixing in position PN16 rated Ecofit: (Georg Fischer)(HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. 25mm pipe
32mm pipe
40mm pipe
50mm pipe
65mm pipe
80mm pipe
100mm pipe
Providing and fixing Hot dipped Galvanized Iron Puddle flange, both side flanged ends, to be inserted in RCC Tank as per Consultants drawing, with required welding with reinforcement steel, for all leads and lifts, testing etc. 50mm pipe
80mm pipe
150mm pipe
200mm pipe
Providing Sleeves in slab / beam for pipes, with PVC type B pipe, upto 450 mm long 75mm dia.
110 mm dia
150 mm dia
Providing Core Cut in slab / beam for pipes, upto 300mm deep 63 mm dia
125 mm dia
160 mm dia
Providing & constructing Valve chamber of following size in B.B. masonry 230mm thick upto 1m depth and 350mm thick below 1.m depth in cement mortar 1:3, with foundation concrete 200mm thick in C.C. 1:4:8, and top FRP medium duty cover with frame, plastered on both faces in cement mortar 1:3, 20mm thick finished with neat float, including curing, cost of all labour, material, excavation, dewatering, backfilling, loading, unloading and transportation charges of material, including providing & fixing in position CI steps etc. complete 600 X 450 mm
Providing and fixing Top Manhole Cover for Water Tanks of FRP (Medium Duty) 600X600 with FRP frame, for all leads and lifts, testing etc.
Estimate no : 131901 of 2021-2022 Supplying and erecting H.M.S. P.V.C. conduit 20 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting HMS P.V.C. conduit 25 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting PVC slotted box trunking of size 60x45 mm. with accessories on wall/ceiling as per specification No: WG-MA/SLBOX.[ MSEDCL Meter board]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting green colour earthing with 1x 2.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW[T2-1702 + T3-852=2812][Rate As Per Note Rates for the earth wire shall be calculated as one half rate of mains of bunch of two wire.
Supplying and erecting mains with 2x4 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW[ TYPE2- 1704, TYPE3- 852=2556 x 10 %= 2812 mtr]
Supplying and erecting green colour earthing with 1x 4 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW[ type 4 & EB (1080 +82)= 1162 X 10%= 1279 M] [Rate As Per Note Rates for the earth wire shall be calculated as one half rate of mains of bunch of two wire.]
Supplying and erecting mains with 4x 6 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting ISI mark modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.[ for each bldg Lift shaft and M/c room 8 x 2 lift = 16 nosx 4 bldg= 64 nos ]
Supplying and erecting ISI mark modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type switch 16 / 20 A with indicator, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type 3 pin 6A multi sockets with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type T.V. socket single outlet, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI marked modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 modules duly erected.[ FOR Lift shaft] [1-8-28]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 modules duly erected
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting 6 to 32 A SPMCB suitable to fix in 1 module of modular switch in provided box complete & duly concealed with necessary material and connected.
Point wiring point wiring for light/fan/bell concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm. (2+1E) FR grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW
Point wiring point wiring for independent plug, concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm (2+1E) FR grade copper wires, modular type switch and socket, earthing and required accessories as per specification No WG-PW/SW
Wiring for plug on board with Switch socket concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW
Secondary point wiring for additional light/ bell 17, concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR/FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW
Supplying and erecting telephone copper cable 2 pair with 0.5 mm dia. laid in provided PVC casing capping/ conduit as per specification No. WG-TW
Supplying and erecting jelly filled unarmoured telephone copper cable 10 pair with 0.5 mm dia. laid in provided PVC casing capping / conduit as per specification No. WG-TW
Supplying and erecting jelly filled armoured telephone copper cable 50 pair with 0.5 mm dia. laid in provided trench as per specification No. WG-TW
Supplying, installing, testing and commissioning of Main Distribution Frame (MDF) Box 50x50 pairs as per specification No. WG-TW
Supplying, installing, testing and commissioning of junction box suitable for 10 pairs as per specification No. WG-TW[
Supplying, installing, testing and commissioning of 10 pair module for connection & disconnection of telephone cable as per specification No. WG-TW
Supplying and installing UTP networking cat-6 cable suitable for LAN / WAN Computer net-working as per specification No. WG-COC/NC
Supplying and installing UTP networking cat-6 armoured cable suitable for LAN / WAN Computer net-working as per specification No. WG-COC/NC[ for BSNL]
Supplying and fixing 2 meter length, UTP patch cord of cat 6 type in position as per specification No. WG-COC/PC
Supplying, fixing, and configuring web smart power over ethernet switch of 24 ports on provided rack or as directed as per specification No. WG-NWC/ENS
Supplying and fixing 6U wall mount rack (Dimension-DxWxH – 450x550x367 mm) as per specification No. WG-NAS/RAK
Supplying and erecting LED square / circular 9 to 12W down lighter having pressure die-cast aluminium housing, opal translucent cover, mounting arrangement with board for surface type or spring loaded mounting clips for flush type complete.[ For Dean bunglow]
Supplying and erecting corridor/passage light fitting (2 feet) including 9W LED lamp, comprises of extruded channel in plastic silver grey colour & with same plastic end cap on provided PVC block / wooden board.
Supplying and erecting decorative oval bulk head edge-lit 10W LED luminaire comprising of high brightness LEDFitting on provided PVC block / wooden board.
Supplying and erecting LED 18W tube light fitting (4 feet) with polycarbonate housing, heat sink, integrated HF electronic driver complete.
Supplying and erecting bulkhead fitting suitable for upto LED upto 12W fixed on wall. As per specification no. FG-IDF/BHF[
Supplying and erecting ding dong / electronic musical type call bell with heavy duty coil suitable to operate on 230V A.C. supply erected on polished double wooden block/sunmica block of suitable size
Supplying and erecting LED Street light fitting suitable for above 40W to 48W lamp, including lamp, with PF > 0.95 class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete per specification No . FG-ODF/FLS2.
Supplying and erecting street light Wall bracket made from 40 mm. dia ‘B’ class G.I. pipe 1.2 m in total length complete as per specification no. FG-BKT/WB
Supplying and erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base
Supplying and erecting regular/ standard model ceiling fan of 900 /1050 mm. sweep complete erected in position as per specification no. FG-FN/CF
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected in an approved manner.
Supplying and erecting five star rated energy saving Ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF
Supplying and erecting storage type horizontal / vertical water heater 15 litres capacity with BEE 5 star rating high impact resistance engineering plastic body on wall / loft complete duly tested and marking sr. no. and date of erection. specification no. AP-WH/STWH
Providing fibre reinforced pvc flexible pipe upto 1m length with brass locking nuts and washers and clips at both ends suitable for hot water and cold water both (1set of 2 nos) complete
Supplying, installing, testing and commissioning of 1400 VA to 1600 VA Digital pure sine wave inverter based on Insulated Gate Bipolar Transistor (IGBT) technology single phase 230V,50 Hz complete as per specification no. AP-INV (Without batteries)
Supplying and erecting 12 V/180Ah tubular battery with battery terminal wire, duly charged complete with 36 months warranty complete
Supplying and erecting four pole metal clad ON LOAD change over switch 415V,100A erected on angle iron /GI frame complete.
Supplying, erecting and marking SPMCB 6A to 32A, C-series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking SPMCB 6A to 32A, B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking DPMCB 6A to 32A, C- series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB
Supplying and erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP / TP of 24 poles/8 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted SPMCB of 24 poles, on iron/ GI frame/wooden board.(horizontal busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 poles for incoming and 10 poles for outgoing SP MCB’s on iron/ GI frame as per specification no. SW-SWR/MCBDB
Providing and erecting 4 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB
Providing and erecting 3 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ At DG panel 11]
Providing and erecting 4 Pole MCCB of 200A,415V capacity with short circuit rating 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB
Providing and erecting 4 Pole MCCB of 250A,415V capacity with short circuit rating 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[DG
Supplying, fixing, and commissioning 2 pole,RCBO (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 6/10/16/20/25A, as per specification no SW-RCCB/RCBO[DB INCOMER T2-48+T3-24+EB-1=73]
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 32A/40A as per specification no SW-RCCB/RCBO[ INCOMER FOR DB T4- 24=24]
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 63A as per specification no SW-RCCB/RCBO[ FOR LIFT of T2- 4+ T3-2+ T4-2+EB-1= 9]
Supplying and erecting air circuit breaker manually operated drawout type of 1000A rated at 50º C without deration, 500V, 3 pole having short circuit rating 50 kA (Ics=Icu=Icw for 1s), with standard accessories and thermal magnetic release on provided iron frame as per specification no.SW-SWR/ACB[ main incomer LT panel]
Supplying, erecting, testing and commissioning of SF 6 Insulated 22kV, 630A, 16kA/3sec, 4 way outdoor, extensible motorised SCADA compatible RMU as per electric supply company specification consisting of 2 nos. feeder with load break switch and 2 nos. feeder with VCB as per specification no. SW-HTS / RMU SCADA ( FOR MSEDCL-2LBS +2VCB)
Supplying and erecting HRC fuse cartridge 415V 100A complete.
Supplying and erecting HRC fuse cartridge 415V 200A complete.
Supplying and erecting porcelain/epoxy bus bar support complete erected in provided MS box for 400A complete.
Supplying and erecting metal work in CRCA sheet with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete
Supplying and erecting GI sheet 1 mm (20 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint.[ for 160 kVA DG set shed 5 x 7=35 sq mtr]
Supplying and erecting acrylic sheet 3 mm thick to be used for covering the CRCA sheet boxes etc. including cutting, drilling, and pasting or fixing with nut bolts/ screws etc. complete. [0.105*96=10.08]
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.[ 50x50x5 mm equal angle of wt. 3.8 kg/mtr For panels, 10.1 mtr= 38.38 kg + MSEDCL METER PANEL - 9.4 mtr x 4 bldg 37.6 m x 3.8 = 142.88 kg + DG shed -330 kg total =38.38+142.88+330=511.26
Supplying and erecting self-locking arrangement with keys in duplicate, made of brass duly erected, flush with surface of panel / cupboard.
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require capacity with 99.9% aluminium purity with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB[ attached
Supplying and erecting static energy meter with 240V 50 Hz. AC supply 5 to 30 A, ISI mark, accuracy class 1.0 with backlit LCD display, (measuring and display kWh, V, I, kW six month history of energy and MD in kVA ) with transparent hinge type box complete erected on polished teak wood board duly wired with required size of weather proof PVC wires duly tested by electric supply company.[ T2-48+T3-24=72]
Supplying and erecting static energy meter with 3 X 240V 50 Hz. AC supply 10 to 60 A, ISI mark, accuracy class 1.0 with backlit LCD display, (measuring and display kWh only) with transparent hinge type box complete erected on polished teak wood board duly wired with required size of weather proof PVC wires duly tested by electric supply company.[ T4-24+EB-1+ Common of 4 Bld.=29]
Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measures & displays trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.
Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc.[ LT panel -15 +15=30]
Supplying and erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.[ lt panel- 16 + D.G -1]
Supplying, erecting & terminating XLPE armoured cable 3 core 2.5 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[
Supplying, erecting & terminating XLPE armoured cable 3 core 4 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ for booster pump]
Supplying, erecting & terminating XLPE armoured cable 3½ core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ Bunglow]
Supplying, erecting & terminating XLPE armoured cable 3½ core 70 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ DG set to bldgs]
Supplying, erecting & terminating XLPE armoured cable 3½ core 95 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ LT FP to all bldgs]
Supplying, erecting & terminating XLPE armoured cable 3½ core 120 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½core 240 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ TRF to LT FP BLDG 300]
Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[LIFT supply all bldg -]
Supplying, erecting & terminating 3 x 95 sq. mm. aluminium 22 kV(E), XLPE armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification no.CB-HT[ FOR MSEDCL RMU TO DTC TFR]
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 2.5 to 16 sq. mm. cable, with necessary material as per specification no. CB-JT/LT[ 50
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 25 to 50 sq. mm. cable, with necessary material as per specification no. CB-JT/LT[ bldg ]
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 70 to 95 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 120 to 185 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 240 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/22 kV ( E ) XLPE HT cable 3x up to 95 sq. mm. with necessary material as per specification no. CB-JT/HT
Supplying and laying (including excavation) 15 cm dia RCC Hume pipe with coupling collar of standard thickness at required depth up to 90 cm below road / ground surface, for enclosing provided cable & necessary back filling with light ramming to make the road/ground surface as it was (Except bitumen carpet).
Supplying and laying (including excavation) 25 cm dia RCC Hume pipe of standard thickness at required depth up to 90 cms. below road / ground surface, for covering provided cable & necessary back filling with light ramming to make the road/ground surface as it was (Except bitumen carpet).
Supplying and erecting FRP box of size 150 x 125 x 100 mm, 2.7 mm thick complete on pole/wall as per specification no. CB-SB f
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.[15x 6 Bldg=90]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP[ for ,TFR N- 2 DG N -2 =4]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP.[ 820 mtr x 1.25 kg/ mtr of 25x 5 mm patti= 1025 kg]
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.[ Schedule attached 50x 5 mm G.I patti 2.5 kg / mtr x 68 mtr= 170 kg]
Supplying, installing, testing and commissioning of 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, oil immersed and naturally cooled outdoor type, copper wound transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40oC by thermometer in oil and 45oC by the resistance in winding at full load rating, with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%, with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 - 2014 energy efficiency level II with necessary permissions of Electrical Inspector, as per specification no SS- TR.
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG[ for DG Set]
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.[ DG ]
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD[ DG 4 nos]
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3Kv
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness upto 33 kV
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.[ bldg-6 +DTC- 1= DG -1]
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.[ 4 bldgs panel room x 7 nos = 28 nos+ Bunglow -01 nos =29 ]
Supplying, Erecting and Commissioning of diesel generating set with alternator of 160 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel etc. as per specification no. GEN-DG[ for resdl bldg. common load like pump, Lift, pssage, & DEAN Bunglow ]
Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of above 140 kVA upto 180 kVA capacity Single/Three phase, 230/415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GEN-AMF.
Supplying, installing, testing and commissioning of with perfect aligning, proper levelling of booster pump of 450 LPM at 35 m head 7.5 HP (5.5 KW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/BP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) fitted with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting fire brigade header of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FBC
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and installing pressure gauge of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying, installing, testing and commissioning of manual call point (Pill box) with break glass push button in metal enclosure complete as per specification no. FF-FAAS/MCP32+8+8+6=54]
Supplying, installing, testing and commissioning of hooters with CRCA enclosure complete as per specification no. FF-FAAS/HTR
Supplying, installing, testing and commissioning of FRLS, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU ADD NOTE for FRLS[ 1027+513+513+176= 2229]
Supplying, installing, testing and commissioning of 2 Zones Microprocessor based conventional fire alarm control panel (FACP) with standard accessories complete as per specification no. FF-FAAS/FACP[ 2+1+1+1=5]
Excavating soft murum / soft soil road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site good complete.[ 4m x 1.15x 1.2= 5.52]
Supplying & spreading stone metal 25 mm size for 100 mm depth above the ground level complete DTC .5x5 x.1= 2.5m3 DG ST 7x4x 0.1 =2.8m3= 5.3]
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) for for 160 kva DG SET [ 1150x 4000x 1500 =6.9 m3]
SITC of Electric Traction Passenger Lift with · Rated capacity :- 8 Passenger/544Kg · Floors :- G+1 floor (7 Stops/7 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 800 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1300.mm wide x 1100mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 2200mm wide x 3000mm deep. 1500mm Pit depth,2200mm Overhead.LIFT WITHOUT DUPLEX Note 1) General ;-Job includes entire procedure of obtaining all necessary erection permission & Licence t work the Lifts from Electrical Inspector ( Lifts) with submission to the engineer in charge. 2) Warranty ;- Job concern three years onsite warranty for all the lifts parts with FCAMC as per the mainteance scehdule [17-1-3]
Supply Installation commissioning of 4 MP Full HD IP Dome/Bullet Camera Image Sensor 1/3" 4 megapol progressivescan CMOS Effective Pixels 2304 (H) 1296 (V) Electronic Shutter Speed Auto Manual 1-1/100000 s Min Illumination 0.5 lux. F21 (Color): 0 lux (R LEDS on IR Distance-nupto 100 m (30 m) Day/Night -auto (ICR)/Color/BW Backlight Compensation-BLC/HLC/DWDR White Balance Auto Manual Gain Control - Auto/Manual Noise Reduction - 30 Privacy Masking- Up to 4 areas Lens Focal Length- 2.8 mm Horizontal Angle of View 92 86-28 Compression H.265 (Main/High/Baseline Profile) /MJPEG Resolution 3. MP (2304x1296) 1080p Main Stream 4 MP.30 fps 16x Digital zoom 60 fps, Resolution- Verifocal lens, 320 db Corridor Mode Support Network Protocol IPv4/IPv6 HTTP HTTPS TCP/IP UDP UPnP ICMP IGMP RTSP RTP SMTP NTP DHCP DNS PPPoE DDNS FTP IP Filter QoS Compatibility -nONVIF Profile S CGI Max. User Access 20 users Mobile App for iPhone iPad Android Phone and Tablet Power Supply PoE (802.3af) 12 V DC Working Environment -22°F to 140°F (-30°C to 60°C). 10% to 100% RH. condensing Ingress Protection IP66 Vandal Resistance IK10 Regulatory FCC Part 158 Class B (3 years warranty)
Supplying, Installation Testing and Commissioning of 2 MP bullet with MOTORISED VARIFOCAL lens and audio io with extemal microphone with having following features Max 2MP (1920-1080) resolution I and brusted Min illumination: Color: 0.095 Lux (30IRE). BAW: 0 Lux OR LED on) 2.8-12mm (4.3X) varifocal lens field of view: H: 103.80-32.40 I V: 53.70-18.40/ D: max 30s @2M all resolutions (H.265/H.264), H.265, H.264 codec supported, multiple streaming motion detection tampering, defocus detection micro SD/SOHC/ SDXC memory slot(128GB), PoE/12V DC IR vieable length 30m IP 66, IK10 Hallway view support LDC support 106071.00 each 106071.00 Rarita TEDAMAX Model specific UL CE & FCC certification (With Threa (Sony, Samsung, Honeywell) (Non CSR) 3Year Warranty)]
Supply and Installation of 4 TB (7200 RPM) Surveillance hard disk 4 TB storage capacity with SATA suppon 6GB NCQ 64 MB cache 3.5 inches(3 years warranty)
Supplying Erecting and Commissioning of 16 channel professional series 4K HD Network Video Recorder Smart H.265+/ Max 320Mbps Incoming Bandwidth Up to 12MP Resolution for Preview and Playback. Bit Rate 16Kbps-20Mbps per channel 2HDMI/ZVGA simultaneous video outputgy to enhance the storage reliability when the network break down. Quad-Core embeded processor. 8 SATA II Ports. Up to 6 TB for each HDD for 48TB Storage 2 RJ45 part (10/100/1000Mbps) Indepenndent of Joint Networking Analytical Features Like ANPR. People Count, face Detection, Missing/Abondoned Objects, Tripwire and Intrusion alarms, Smart FAN To achieve High Cooling Effect Automatic Network Replenishment (ANR) Technology Network Video Recorders with the ANR function automatically store video data on an IP camera SD card when the network is disconnected. After recovery of the network, the NVR automatically retrieves the videodata stored on the camera.[ three year warranty]
Supply installation and commissioning of 42" Full HD VGA DVL 2 x HDMI LAN USB RGS In out Avin Component in wit ready speakers professional full HD display complete with mounting hardware and software 200 templete included to create your own content manage content with suggested PC or mobile device A professional display backed by three years onsite/offsite warranty and dedicated B2B support (3 years warranty)
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants..For distributing from Domestic Ground Water Tank to Domestic Over Head Tank Pump (RSDL Bldg BLOCK - 10,11 ) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 65 LPM, Individual Pump Discharge = 35 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 1 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr.[FOR TYPE III & IV]
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants.For distributing from Domestic Ground Water Tank to Domestic Over Head Tank Pump (RSDL BLDG-Block - 12) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 150 LPM, Individual Pump Discharge = 80 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 4 HP, Approx. Individual Pump Electrical Requirement = 2 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr. [TYPE II]
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants.For distributing from Domestic Ground Water Tank to Domestic Over Head Tank Pump ( RSDL Bunglow ,Block 9) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 90 LPM, Individual Pump Discharge = 50 LPM ,Approximate Head in m ( H ) = 25 m , Pump Qty - 2 working + 1 standby ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 1 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr.[for eXECUTIVE BUNGLOW ]
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants.For distributing from Flushing Ground Water Tank to Flushing Over Head Tank Pump ( RSDL BLDG Block 10,11,12 ) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 100 LPM, Individual Pump Discharge = 50 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 2 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr. [FOR TYPE II,III, & IV]
Supply & Erecting of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter:a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.036 µΩm, Tensile strength - 120 to 240 MPa or N/mm², Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2.
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Flat roof Conductor Holder suitable for 8mm dia to be fixed above flat roof without puncturing RCC/Surface at every 1 Mtr to meet the requirements for IS/IEC 62305.
Supply & Erecting of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross junction. Test Parameter Salt Spray Test ( IEC 62561-1) - No sign of Corrosion
Supply & Erecting of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion piece should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor . Test Parameter: Electrical Resistivity Test-0.036 µΩm Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.
Supply & Erecting of air termination rod of 2 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning events Buttons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6.
Supply & Erecting of Stainless Steel Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor , Test Parameter: Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Earth termination inside the concrete and soil. Test parameter: Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec(IS3043/IEEE80); Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. Tensile Test 290 to 510 N/mm². Adhesion no peel or crack & Bend test no seperation of Cu, Cu Coating thickness min. 70µm. Tested as per IEC 62561-2.
Supply & Erecting of Stainless steel Conductor Holder for fixing the 8mm/10 mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467.
Providing and Back filling back filling ground enhancing compound 25 kg bag complete.
Supply & Erecting of Earthrod clamp made for terminating cable / flat conductor.
Supply & Erecting of Earth Chamber Inspection Pit made up of Poly propylene material [ NON CSR]
Estimate no : 131902 of 2021-2022 Supplying and erecting H.M.S. P.V.C. conduit 20 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC
Supplying and laying HMS PVC conduit 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.[for sub main
Supplying and erecting HMS P.V.C. conduit 25 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting mains with 2x1.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting green colour earthing with 1x 1.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting green colour earthing with 1x 2.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x4 sq.mm F.R copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting ISI mark modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.[ LIFT SHAFT - 30 + ELV ROOM -6=36]
Supplying and erecting ISI mark modular type switch 16A duly erected on provided plate and box with wiring connections complete.[ 7 X 1 BDG=07]
Supplying and erecting ISI mark modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete
Supplying and erecting ISI mark modular type T.V. socket single outlet, duly erected on provided plate and box with wiring connections complete.[ 2 x 2=2]
Supplying and erecting ISI marked modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.[ 22]
Supplying and erecting ISI mark modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. Note: Add Rs 57/- for additional two module box with double mounting plate if required.
Supplying and erecting ISI mark modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 modules duly erected.[ for LIFT SHAFT]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module dulyerected flush to wall with required chiselling and finishing withcement mortar / POP as per required to match the background
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Point wiring point wiring for light/fan/bell concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm. (2+1E) FR grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW
Point wiring point wiring for independent plug, concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm (2+1E) FR grade copper wires, modular type switch and socket, earthing and required accessories as per specification No WG-PW/SW
Wiring for plug on board with Switch socket concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW[ 233 x 1 = 233]
Secondary point wiring for additional light/ bell , concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR/FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW[ 129 nos x 1 bldg=129]
Supplying and erecting telephone copper cable 2 pair with 0.5 mm dia. laid in provided PVC casing capping/ conduit as per specification No. WG-TW
Supplying and erecting jelly filled unarmoured telephone copper cable 10 pair with 0.5 mm dia. laid in provided PVC casing capping / conduit as per specification No. WG-TW
Supplying and erecting jelly filled armoured telephone copper cable 50 pair with 0.5 mm dia. laid in provided trench as per specification No. WG-TW
Supplying, installing, testing and commissioning of Main Distribution Frame (MDF) Box 50x50 pairs as per specification No. WG-TW
Supplying, installing, testing and commissioning of junction box suitable for 10 pairs as per specification No. WG-TW[
Supplying, installing, testing and commissioning of 10 pair module for connection & disconnection of telephone cable as per specification No. WG-TW
Supplying, installing, testing and commissioning of digital (hybrid) type EPABX of 3 x 8 extensions complete.
Supplying and installing UTP networking cat-6 cable suitable for LAN / WAN Computer net-working as per specification No. WG-COC/NC
Supplying and installing UTP networking cat-6 armoured cable suitable for LAN / WAN Computer net-working as per specification No. WG-COC/NC
Supplying and fixing 2 meter length, UTP patch cord of cat 6 type in position as per specification No. WG-COC/PC
Supplying, fixing, and configuring broadband ADSL router with all accessories, on provided rack or as directed as per specification No. WG-NWC/ADSL
Supplying and fixing 6U wall mount rack (Dimension-DxWxH – 450x550x367 mm) as per specification No. WG-NAS/RAK
Supplying and fixing manageable wireless dual-band 802.11 n/ac unified wireless access point in WLAN network as per specification no. WG-NAS/LAP1
Supplying, fixing, and configuring 8-ports managed gigabit switches layer-2, 10/100/1000 base-T PoE smart switch plus 2 SFP only complete.
Supplying, fixing, and configuring 48 ports managed gigabit switches layer-2 48 10/100/1000Base-T ports L2+ Management Switch with 4 10GE SFP+ ports complete
Supplying and erecting LED square / circular 9 to 12W down lighter having pressure die-cast aluminium housing, opal translucent cover, mounting arrangement with board for surface type or spring loaded mounting clips for flush type complete.[ 729 X1 =729]
Supplying and erecting corridor/passage light fitting (2 feet) including 9W LED lamp, comprises of extruded channel in plastic silver grey colour & with same plastic end cap on provided PVC block / wooden board.[ 154 X 1 =154]
Supplying and erecting decorative oval bulk head edge-lit 10W LED luminaire comprising of high brightness LED [2-1-21] Fitting on provided PVC block / wooden board.
Supplying and erecting LED 18W tube light fitting (4 feet) with polycarbonate housing, heat sink, integrated HF electronic driver complete.[ PANTRY 28 x 1=28]
Supplying and erecting bulkhead fitting suitable for upto LED upto 12W fixed on wall. As per specification no. FG-IDF/BHF[ LIFT shaft-7 + TERRACE -18 = 25 X 1=25 ]
Supplying and erecting LED street light fitting suitable above 26W to 36W lamp, including lamp, with PF > 0.95 class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete as per specification No FG-ODF/FLS2.
Supplying and erecting street light Wall bracket made from 40 mm. dia ‘B’ class G.I. pipe 1.2 m in total length complete as per specification no. FG-BKT/WB
Supplying and erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected in an approved manner.
Supplying and erecting five star rated energy saving Ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF
Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original.
Supplying and erecting four pole metal clad ON LOAD change over switch 415V,100A erected on angle iron /GI frame complete.
Supplying, erecting and marking SPMCB 6A to 32A, C-series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB[ 555X 1= 555]
Supplying, erecting and marking SPMCB 6A to 32A, B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB[ 235 x1= 235 ]
Supplying, erecting and marking DPMCB 6A to 32A, C- series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB[ for shaft ltg 8 x 1= 24]
Supplying, erecting and marking FPMCB 6A to 32A in provided distribution board as per specification no. SW-SWR/MCB[ 11 X 1=11]
Supplying and erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP /TP MCBs of 12 poles/4 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted SP / TP MCBs of 36 poles/12 ways on iron/ GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 poles for incoming and 2 poles for outgoing SPMCBs on iron/ GI frame as per specification no. SW-SWR/MCBDB
Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 poles for incoming and 6 poles for outgoing SP MCB’s on iron/ GI frame as per specification no. SW-SWR/MCBDBTV & INTERNET]
Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 poles for incoming and 10 poles for outgoing SP MCB’s on iron/ GI frame as per specification no. SW-SWR/MCBDB[ 8 floor x 1 =08 nos]
Supplying and erecting CRCA sheet metal one way enclosures suitable for DP MCB /TP MCB /FP MCB erected on angle iron/GI frame complete.
Supplying and erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted suitable for 3 pole MCCB as incomer & outgoing SP MCB (36 poles) or TP MCB of 12 ways (36 poles) on iron/ GI frame. (vertical busbar type) as per specification no. SW-SWR/MCBDB1[ hostel]
Providing and erecting 4 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ In DB=8]
Providing and erecting 3 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ per floor DB]
Providing and erecting 4 Pole MCCB of 315/400A, 415V capacity with short circuit rating 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ main & DG panel]
Supplying, fixing, and commissioning 2 pole RCBO (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 32A/40A as per specification no SW-RCCB/RCBO[ in SPN DB 2 IN 2 OUT 227 x 1 = 227]
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 32A/40A as per specification no SW-RCCB/RCBO
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 63A as per specification no SW-RCCB/RCBO[ hostel 12]
Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for above 250A upto 630A MCCB complete.
Supplying and erecting SS enclosure for MCCB suitable for upto 100A MCCB complete.
Supplying and erecting metal work in CRCA sheet with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.[ ATTACHED]
Supplying and erecting GI sheet 1 mm (20 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint.[ 6m x 4 m =24 sq mtrx 3 =72sq mtr]
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.[ 250 kVA D.G shed, 430 KG]
Supplying and erecting self-locking arrangement with keys in duplicate, made of brass duly erected, flush with surface of panel / cupboard.
Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measures & displays trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.
Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc.[ D.G panel- 1 X 3 =6 ]
Supplying and erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.[ l D.G -3]
Supplying, erecting & terminating XLPE armoured cable 3 core 2.5 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ lift shaft ltg 27 m x 2 +15= 70 x 4 lift = 280 mtr x 1 bldg.]
Supplying, erecting & terminating XLPE armoured cable 3 core 4 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ for booster pump] 52 m x 1 bldg =156 ]
Supplying, erecting & terminating XLPE armoured cable 3½ core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[hostel for panel to floor db 178 m x1 = 178 M
Supplying, erecting & terminating XLPE armoured cable 3½ core 150 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ 20 X 1= 20 MTR]
Supplying, erecting & terminating XLPE armoured cable 3½core 240 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ main panel room to Hostel panel 250 mtr x 3 run =1000 m X 1 =1000 M]
Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ for water pump ]
Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ lift power supply hostel bldg 390 x 1 =390 M ]
Supplying, erecting & terminating XLPE armoured cable 3 core 6 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU[ FLOOR DB TO Common DB 85 m x 1 =85 m]
Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU[ for lift 61 m x 1 =61]
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 240 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Supplying and laying (including excavation) 25 cm dia RCC Hume pipe of standard thickness at required depth up to 90 cms. below road / ground surface, for covering provided cable & necessary back filling with light ramming to make the road/ground surface as it was (Except bitumen carpet).
Providing and erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.[ 20x 1=20]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP[ DG N -=2]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP[ DG B-2 + hostel panel -2x 1 =2 + AMF-2+ LIFT-8 = Total =15 ]
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP.[copper earthing ]
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG[ 250 kva 15 x1 DG Set ]
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.[ 1 DG set 4*1=4]
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD[ DTC + DG 1 nos]
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3 Kv
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness upto 33 kV[ 9 sq mtr x 3= 27 sq mtr]
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.[ panel , D.G Set]
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.[ hostel 1 bldg x 7 floor =7= 07 nos]
Supplying, Erecting and Commissioning of diesel generating set with alternator of 250 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel, etc and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of above 200 kVA upto 250 kVA capacity Single/Three phase, 230/415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GEN-AMF.
Supplying and erecting flat flexible 3 core 4 sq mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete.
Supplying, installing, testing and commissioning of with perfect aligning, proper levelling of booster pump of 450 LPM at 35 m head 7.5 HP (5.5 KW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/BP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP[ for GF + 6 floor =7 floors x 4 shafts =28 x 1= 28 nos]
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) fitted with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting fire brigade header of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FBC
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and installing pressure gauge of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying, installing, testing and commissioning of manual call point (Pill box) with break glass push button in metal enclosure complete as per specification no. FF-FAAS/MCP[ 32x 1= 32]
Supplying, installing, testing and commissioning of hooters with CRCA enclosure complete as per specification no. FF-FAAS/HTR
Supplying, installing, testing and commissioning of FRLS, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU [ NOTE for FRLS 1440x 1=1440]
Supplying, installing, testing and commissioning of 2 Zones Microprocessor based conventional fire alarm control panel (FACP) with standard accessories complete as per specification no. FF-FAAS/FACP[ 1x 1]
Excavating soft murum / soft soil road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site good complete.[ DG foundation 32.4 m3 + DG shed 5m3 = 38 m3]
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) for 250 kva 4.8 x 1.5 x 1.2= 10.8 M3X 1 set= 10.8 m3+ othr- 2 = say13 ]
Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose).[ for panels, DG shed etc]
SITC of Electric Traction Passenger Lift with · Rated capacity :- 8 Passenger/544Kg · Floors :- G+1 floor (7 Stops/7 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 800 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1300 mm wide x 1100 mm deep x 2200 mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.· Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 1800 mm wide x 2000mm deep.1500mm Pit depth, 1800mm Overhead. General ;- Job includes entire procedure of obtaining all necessary erection permission and licence to work the lift from Electrical Inspector ( LIFTS) with submission to the Engineer in charge 2) Warranty ;- Job cover three year s onsite warranty for all the lift parts with FCAMC as per the maintenance schdule .
SITC of Electric Traction Passenger Lift with · Rated capacity :- 8 Passenger/544Kg · Floors :- G+6 floor (7Stops/7 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR · Rated speed :- 1.0mps VS[ WITH DUPLEX CONTROL] · Doors type :- COPO/TOPO Doors with frame having clear opening of 800 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1300mm wide x 1100mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 1800mm wide x 2000mm deep. 1500mm Pit depth,1800mm Overhead. 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule Note 1 and 2 above shall be included in item description. [17-1-3]
SITC of Electric Traction Passenger Lift with · Rated capacity :- 14 Passenger/952Kg · Floors :- G+6 floor (7 Stops/7 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 900 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1000mm wide x 2400mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 1800mm wide x 3000mm deep, 1500mm Pit depth 1800mm Overhead.LIFT RATE 1791363/- NOTE A3- 5X 165891/- =829455/-165891/- +, C1-31974 /-,+F- 8X 3261/-=26088/- TOTAL 267880/-General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule Note 1 and 2 above shall be included in item dscription.
Supply installaton and commissinoing of 42" Full HD VGA DVL 2 X HDMI LAN USB RGS in out Avun component in wifi ready speakers professional full HD dispaly complete with mounting hardware and software 200+ template included to create your own content manage content with suggested PC or mobile device A proffessional display backed by three years onsite / offsite warranty and dedicated B2B support ( 3 year warranty) [35-1-33]
"Supply, installation, testing & commissioning of Main LT Panel of Hostel Building as per Specification The panel shall be fabricated out of 14/16 swg CRCA SHEET STEEL with powder coating of approved shed. Multi function electronic meter with kW and pf display for Incomer & Outgoing Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C MCCB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxillary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 25 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) Trip status for BMS compatible @ RS 485 system. O/G MCCB should have Following accessories; 1) Protection - LSI -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Thermal Magnetic based 5) ICU = ICS =25 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. Incomer: 315 A FP MCCB 25 KA FOR MAIN PANEL, 315 A FP MCCB 25 KA FOR DG, 315 A ATS, 315 A FP MCCB 25 KA FOR OUTGOING Busbar : 400 A TPN 25 kA AL Tinned Busbar Outgoiing: 100 A TP MCCB 25 KA -7 Nos, 63 A TP MCB 10 KA-5 NOS, 40 A TP MCB 10 KA-2 NOS, 25 A TP MCB 10 KA-4 NOS, 16 A TP MCB 10 KA-2 NOS, 16 A SP MCB 10 KA-4 NOS.
"Supplying, Erecting, Testing Commissioning of Heat pump System of following Capacity Rated Capacity -5kL tank, Heat Pump Capacity -34 kW Heat pump with a minimum COP of 3.8, Rated Voltage - 415 V, 3 phase, 50 Hz supply. Along with internal Control panel with Complete Electrical Protection For Field Issues • Under/ Low Voltage Protection • Single Phasing/ Phase Missing & Reversal Protection • Compressor Overload Protector • Pump Overload Protector • MCB/Fuse As Standard, with related cable harnessing, System required CPVC interconnecting piping with poly-olefin based insulation sheet and required circulation pump with 120 degree hot water seal with base frame with automation. Head flow as per heat pump system. MS tank 6mm shell and 8mm dish with Zinc thermal coat to be considered "for Hostel Block no. 6- student capacity 186 x 25 ltr = 4650 ltr peroposed -1 no [12-5-3]
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants..For distributing from Domestic Ground Water Tank to Domestic Over Head Tank Pump (Block ,6 HOSTEL) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 65 LPM, Individual Pump Discharge = 35 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 1 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr. [12-1-4]
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants.For distributing from Flushing Ground Water Tank to Flushing Over Head Tank Pump (Block 6 Hostel) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 100 LPM, Individual Pump Discharge = 50 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 2 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr.
Supply and Installation of 4 TB (7200 RPM) Surveillance hard disk 4 TB storage capacity with SATA suppon 6GB NCQ 64 MB cache 3.5 inches(3 years warranty)
Supplying Installation Testing and Commissioning of 2 MP Bullet with MOTORISED VARIFOCAL lens and udio io with externl microphone having following featuresMax. 2MP (1920*1080) resolution. Min illumination : Color : 0.095Lux (30IRE) B/W : 0 Lux (IR LED on)2.8~12mm (4.3X) varifocal lensfield of view :H:103.80 -32.40 /V:53.70-18.40/D:121.90- 37 .10120db WDRmax 30 fps @ 2M all resoluations (H.265/H.264)H.265 ,H.264 codec supported intellegnt anylusis like motion detection with metsdata tempering defocus detedtion.128 GB micro SD/SDHC/SDXC memory slot PoE/12V DCIR vieble length 20m motion dtection zone min 4 Zones Multiple staming up to 3 reofile Modl specific UL CE & FCCC Certification { for three year warranty]
Supplying Installing Cofiguring & Commissioning of 16 Channel NVR With upto 16 cameras complete similar to Hikvision make DS7P16NI-K4 Video/Audio input IP Video input 16 Ch Two way audio input 1-ch,RCA(2.0Vp-p,1kohm)Network incoming bandwidth 180 Mbps,outgoing Bandwidth 80 Mbps,Remote Connection 128 Video/Audio output Recording Resolution6MP/5MP/3MP/1080P/UXGA/72 0PVGA/4CIF/DCIF/2CIF/CIF/QCIF Frame rate main Stream: 50 fps(P)/60fps(N) CVBS output 1-ch,BNC(1.0 Vp-p,75 ohm) Resolution :704x576(PAL): 704x 480(NTSC) HDMI/VGA output 1ch,Resolution 1920x1080P/60 Hz,1600x1200/60Hz,1280 x1024/60 Hz,1280x720/60Hz,1024x768/60Hz Audio Output 1-ch,RCA(Linear 1Kohm) Decoding Live View/Play back Resolution 6MP/5MP/3MP/1080P/UXGA/720P/VGA/4 CIF/DCIF/2CIF/CIF/QCIF Capability 16 Ch@1080p Hard disk 4 SATA Interface for 2 HDDs1DVD-R/W(default) or 4HDDs eSATA/eSATA interface capacityupto 6TB Capacityfor each diskGeneral power supply 100-240VAC,6.3A,50-60Hz Consumption with out hdd 20W Working Temprature- 10 Degree - 55 Degree(14 F - 131F) Working Humidity 10% - 90% Chassis 19- inch rack Mounted 1.5U ChassisDimensions(WxDxH)(445x390x70 mm 16049 [ THREE YEAR WARRANTY] [1-1-3]
Supply installation commissioning of 4 MP Full HD IP DOME/ BULLET Camera image sensor 1/3 " 4 megapixel progressive scan CMOS Effective pixels 2304 H X 1296 V Electronic shutter speed Auto/ Man 1-1 / 100000 s min. illumination 0.5 lux F2.1 color ; 0 lux IR LEDs on IR distance- nUp to 100 ft 30 m day / night- auto ICR/Color/BW Backligt compensation -BLC/HLC/DWDR white balance- Auto/ mnual Noise reduction- 3D privacy msking up to 4 areas Lens focal length -2.8 m Horizontal angle of view 92 86- 28 Compression H 265 ( Main/ High/ Base line profile) MJPEG Resolution 3MP ( 2304 X 1296) 1080p Main stream 4MP, 30 fps 16X Digital zoom 60 fps resolution - verifocal lens, 320 db corridor mode support Network Protocol IPv4/ IPv6 HTTP HTTPS TCP/IP UDP UPnP ACMP IGMP RTSP RTP SMTP NTP DHCP DNS PPPoE DDNS FTP IP filter QoS compatibility -nONVIF profile S CGI Max. User access 20 users mobile app - for iphone ipad Android phone and tablet powr supply PoE (802.3 af) 12 V DC working enviornment - 22F to 140 F ( -30 C to 60C) 10 % to 100 % RH condensing ingress protection IP66 vandan resistance - IK 10 Rgulatory FCC part 15B Clas B ( 3 year warranty)44X 3=168]
Supply & Erecting of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter: a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.036 µΩm, Tensile strength - 120 to 240 MPa or N/mm², Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2.
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Flat roof Conductor Holder suitable for 8mm dia to be fixed above flat roof without puncturing RCC/Surface at every 1 Mtr to meet the requirements for IS/IEC 62305.
Supply & Erecting of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross junction. Test Parameter Salt Spray Test ( IEC 62561-1) - No sign of Corrosion
Supply & Erecting of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion piece should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor . Test Parameter: Electrical Resistivity Test-0.036 µΩm Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.
Supply & Erecting of air termination rod of 2 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of air termination rod of 3 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning events Buttons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6.
Supply & Erecting of Stainless Steel Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor Test Parameter: Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Earth termination inside the concrete and soil. Test parameter: Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec(IS3043/IEEE80); Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. Tensile Test 290 to 510 N/mm². Adhesion no peel or crack & Bend test no seperation of Cu, Cu Coating thickness min. 70µm. Tested as per IEC 62561-2.
Supply & Erecting of Stainless steel Conductor Holder for fixing the 8mm/10 mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467.
Providing and Back filling back filling ground enhancing compound 25 kg bag complete.[9-3-2]
Supply & Erecting of Earthrod clamp made for terminating cable / flat conductor.
Supply & Erecting of Earth Chamber Inspection Pit made up of Poly propylene material [ NON CSR]
Estimate no : 131903 of 2021-2022 Supplying and erecting H.M.S. P.V.C. conduit 20 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting HMS P.V.C. conduit 25 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.[ 9922m ]
Supplying and laying HMS PVC conduit 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.[ 31435 m]
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting PVC box trunking of size 50x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting PVC box trunking of size 75x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting PVC box trunking of size 75x75 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW[NOTE]
Supplying and erecting mains with 2x1.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW[ Note for FRLS]
Supplying and erecting mains with 2x2.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW[ For FRLS note subtract 25 from rate of FRLSH =59.78]
Supplying and erecting ISI mark modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.[ 1656m]
Supplying and erecting ISI mark modular type switch one way 16 / 20 A, duly erected on provided plate and box with wiring connections complete with neon indicator.
Supplying and erecting ISI mark modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. Note: Add Rs 57/- for additional two module box with double mounting plate if required.
Supplying and erecting ISI mark modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting ISI mark modular type 3 pin 6 / 10A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 modules duly erected[ for lift shaft].
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background ]
Point wiring Point wiring for light/fan/bell concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLS grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW[ LT- 1564)+(CF-1253)+(Bell-10)+(EF-82)=2909]
Wiring for plug on board with Switch socket concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW[ 637]
Secondary point wiring for additional light/ bell 17, concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR/FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW[ 1886]
Point wiring for independent plug in ISI mark HMS PVC conduit with 1.5 sq.mm (2+1E )FR LS grade copper wire,modular type switch, earthing and required accessories as per specification No: WG-PW/SW[1-9-32] RATE AS PER NOTE
Supplying and erecting CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) square / round shape suitable for 19 to 24 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting square shaped CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) 600x600mm suitable for 36 W-40W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting rectangular shaped CRCA /die-cast aluminium powder coated housing LED panel (slim edge-lit) 300x1200mm of suitable for 36 to 40 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting bulkhead fitting suitable for upto LED upto 12W fixed on wall. As per specification no. FG-IDF/BHF[ LIFT SHAFT28 =28]
Supplying and erecting LED Flood light fitting of 50W, including lamp, with PF > 0.95,class IP 65 and above class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete per specification No FG-ODF/FLS-2
Supplying and erecting LED Flood light fitting of 90-100W, including lamp, with PF > 0.95, class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete per specification No FG-ODF/FLS-2[ at lift room for terrace Area illumination 4 room x 4 =16 nos]
Supplying and erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected in an approved manner.
Supplying and erecting five star rated energy saving Ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF[ 1440]
Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original.
Supplying and erecting B grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire.1460]
Supplying, erecting and marking SPMCB 6A to 32A, C-series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB[ 1311
Supplying, erecting and marking SPMCB 6A to 32A, B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking DPMCB 6 A to 32 A B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB[ LIFT SHAFT LTG & Terrace LED flood]
Supplying, erecting and marking TPMCB 6 A to 32A in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking TPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking FPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB[ TPNDB for LIFT = Booster pump-1]
Supplying and erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP / TP of 24 poles/8 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB[ Lift-6]
Supplying and erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP /TP MCBs of 12 poles/4 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB[AC-12 +Emergency-12, Lecture hall-8=32+1=33]
Supplying & erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP / TP MCB of 36 poles/12 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB[LTG-11, RAW-12, UPS-12, Lecture Hall-12= 47 nos
Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 poles for incoming and 10 poles for outgoing SP MCB’s on iron/ GI frame as per specification no. SW-SWR/MCBDB[ 4 th floor lab Skill dvpt]
Supplying and erecting original 1.25 mm CRCA sheet metal enclosures with 20A. 2 pin plug & earth socket and 20A. 3 pin plug top with 20A/30A single pole MCB complete erected on angle iron/ GI frame.
Supplying and erecting CRCA sheet metal one way enclosures suitable for DP MCB /TP MCB /FP MCB erected on angle iron/GI frame complete.
Supplying and erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted suitable for 3 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles) on iron/ GI frame. (vertical busbar type) as per specification no. SW-SWR/MCBDB1[ lift & pump]
Providing and erecting 4 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ AHU 63 Amp-4 + UPS -8 Note for 4 pole]
Providing and erecting 4 Pole MCCB of 250A,415V capacity with short circuit rating 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ note for 4 pole]
Providing, erecting and commissioning 4 pole RCCB only of electromagnetic type with 30/100/300 mA sensitivity and having capacity of 16/25A complete as per specification no. SW-RCCB/RCCB[ At DB]
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 32A/40A as per specification no SW-RCCB/RCBO[ at DB]
Supplying, fixing and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 63A as per specification no SW-RCCB/RCBO
Supplying and erecting porcelain/epoxy bus bar support complete erected in provided MS box for 200/300A complete.
Supplying and erecting SS enclosure for MCCB suitable for upto 100A MCCB complete.
Supplying and erecting metal work in CRCA sheet with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.[For UPS panels 4 X 234 KG= 857+ for emergency panel-170x 2= 340 total 1197]
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.[ Stand for NCSR contol panels, CCTV, othr any ]
Supplying and erecting self-locking arrangement with keys in duplicate, made of brass duly erected, flush with surface of panel / cupboard. [6-1-20]
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require capacity with 99.9% aluminium purity with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB[ 210 +240=450
Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measures & displays trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.
Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc.
Supplying and erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.
Supplying, erecting & terminating XLPE armoured cable 3 core 2.5 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ lift shaft lighting 560 + for flood light on terrace 500=1110]
Supplying, erecting & terminating XLPE armoured cable 3 core 4 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ booster pump & other-50+ Industrial plug-20=70 mtr]
Supplying, erecting & terminating XLPE armoured cable 3½ core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ common ltg Panel
Supplying, erecting & terminating XLPE armoured cable 3½ core 35 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ Lecture hall supply ltg]
Supplying, erecting & terminating XLPE armoured cable 3½ core 95 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ Main Change over panel to common panel
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3½ core 185 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ DG Set to SYNCH panel & Synch panel to Change over panel & TFR to change over panel]
Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL[ FOR LIFT]
Supplying, erecting & terminating XLPE armoured cable 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU[ all DB;s UPS]
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 70 to 95 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 120 to 185 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Supplying and erecting G.I. pipe ‘A’ class 40 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE[ at terrace for enclosing Flood light cables]
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete
Supplying and laying including excavation of suitable width & depth up to 90 cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete
Supplying and erecting FRP box of size 150 x 125 x 100 mm, 2.7 mm thick complete on pole/wall as per specification no. CB-SB
Providing and erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories.[ Main panel to Elect shaft= 120 m]
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 400 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing and erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware in approved manner.
Providing and erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of 400 mm width & 20 mm height complete with necessary hardware in approved manner.
Providing and erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of 500 mm width & 20 mm height complete with necessary hardware in approved manner.
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP[ (DG B- 2 X 2 =4 no)+ (SYNCH panel-2 )+( Main CO panel-2)+ (BUS panel-1 no )+( Lift 4 x 2 =8 nos)= TOTAL -17]
Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials, testing & recording the results as per specification no ESE -LA[ UPS 4 X 2 =8 nos + DG NX 4=12 no]
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3kV
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness upto 33 kV
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.[ 5]
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.[ floor 170 Rmtr / 20 mtr =9 x 5= 45 + LG -5= 50 nos
Supplying, Erecting and Commissioning of diesel generating set with alternator of 320 kVA output continuous rating, 3 phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, alongwith standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel etc. and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of above 250 kVA upto 320 kVA capacity Single/Three phase, 230/415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GENAMF.[Rate282515-28251.50=254263.50+5887=260150.50]
Supplying, installing, testing and commissioning of with perfect aligning, proper levelling of booster pump of 450 LPM at 35 m head 7.5 HP (5.5 KW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/BP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) fitted with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting fire brigade header of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FBC
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and installing pressure gauge of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Excavating soft murum / soft soil road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site good complete.[ 4.8 x 1 x 2025= 9.72 x 2 =19.44m3]
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps).[ 4.8X 2025 X1.5= 14.58X 2 DG set=29.16 say30m3]
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with · Rated capacity :- 15 Passenger/1020Kg · Floors :- L+ G+4 floor (6Stops/6 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR/MRL [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1000mm wide x 2400mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth,1800mm Overhead. Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth,1800mm Overhead.ADD NOTE A4- 4X170885/-+ C1-31974/- + F- 22827/- Total 2639866/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule. [17-1-7]
DG SYNK PANEL Supply, installation, testing & commissioning of DG SYNCHRONISING PANEL (Location- Near DG) The panel shall be compartmental type with Aluminumbus bar and separate cable and bus bar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxiliary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Short-circuit, 2) ON/OFF - Auxiliary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. INCOMER Incomer-1= 415V , 500A, 4P, MCCB of 50KA - 1No Incomer-2= 415V , 500A, 4P, MCCB of 50KA - 1No synchronizing controller for each DG set Incomer 500 A FP MCCB 50 KA- For Bus-Coupler OUTGOING FEEDERS. 415V , 500A, 4P, MCCB of 50KA - 2No BUSBAR RATINGS 415V, 500A, 3Ph, 4wire 50Hz, Aluminumbus bars (91E electrical grade) having withstand ability symmetrical fault level of 50 KA for 1 Sec.
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with · Rated capacity :- 15 Passenger/1020Kg · Floors :- G+3 floor (4Stops/4 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR/ [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR & MRL] · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1000mm wide x ..2400mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. · Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth,1800mm Overhead. Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth,1800mm Overhead.ADD NOTE A4- 2 X170885/-+ C1-31974/- +E- 40464+F- 5 X 3261= 16305/-+ Total 2332038/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule.
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with · Rated capacity :- 15 Passenger/1020Kg · Floors :- G+3 floor (4Stops/4 Landings) · Travel :- 3 to 4.2 mtrs · Location of Lift Machine:- MR/ [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR ] · Rated speed :- 1.0mps VS · Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames · Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. · COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor · Clear Car size of 1000mm wide x 2400mm deep x 2200mm high · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings · Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class · ARD complete with necessary SMF VRLA batteries · Fireman controller having fireman switch at fire Landing, · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. · Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength · Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. · Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth, 1800mm Overhead. NOTE A4- 2 X170885/-+ C1-31974/- +F- 5 X 3261= 16305/-+ Total 2291574/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule. [17-1-7]
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with • Rated capacity :- 15 Passenger/1020Kg • Floors :- G+4 floor (5Stops/5 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR/ [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR ] • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • Clear Car size of 1000mm wide x 2400mm deep x 2200 mm high • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth, 1800mm Overhead. NOTE A4- 3 X170885/-= 512655/- + C1-31974/- +E1- 40464/-F- 6 X 3261= 19566/- Total 2506184/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule. [17-1-7]
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with • Rated capacity :- 15 Passenger/1020Kg • Floors :- G+4 floor (5Stops/5 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR/ [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR ] • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • Clear Car size of 1000mm wide x 2400mm deep x 2200mm high • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth, 1800mm Overhead.NOTE A 4- 3 X170885/-= 512655/- + C1-31974/- +E1-+ F- 6 X 3261= 19566/- Total 2465720/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule [17-1-7]
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with • Rated capacity :- 15 Passenger/1020Kg • Floors :- L+ G +4 floor (6Stops/6 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR/MRL [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • Clear Car size of 1000mm wide x 2400mm deep x 2200mm high • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2600mm wide x 3000mm deep, 1500mm Pit depth,1800mm Overhead.ADD NOTE A4- 4X170885/-+ C1-31974/- +E1-40464/-F- 22827/- Total 2680330/- 1)General ;-job includes entire procedure of obtaining all necessary erection permission & licence to work the lift from electrical inspector ( Lifts ) with submission to the Engineer Incharge. 2] Warranty ;- job cover three years onsite warranty for all the lift parts with FCAMC as per the maintenance schedule [17-1-7]
MAIN CHANGEOVER PANEL-A Supply, installation, testing & commissioning of Main Changeover Panel The panel shall be compartmental type with Aluminumbus bar and separate cable and bus bar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxiliary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Short-circuit, 2) ON/OFF - Auxiliary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. A. EB INCOMER(EB INCOMER-1 )- 1 NOS 415V , 500, 4P, MCCB of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, MCB - 3 Nos. 500/5A, CL-1, 10VA CT's with tape wound - 3 nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT B.DG INCOMER (DG INCOMER-1 ) - 1 NOS 415V , 500, 4P, MCCB of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, MCB - 3 Nos. 500/5A, CL-1, 10VA CT's with tape wound - 3 nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT C.E+M INTER LOCKING BETWEEN MSEDCL INCOMER AND DG INCOMER D. BUSBAR RATING- 415V, 600A, 3Ph, 4wire 50Hz, Aluminumbus bars (91E electrical grade) having withstand ability symmetrical fault level of 50 KA for 1 Sec. E. OUT GOING FEEDER FROM 500A BUS BAR-1 I. 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 3 No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) II. 415V ,100A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 2 No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) III. 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 5 No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) IV. 415V,32A, 4P, MCB of 10KA('B' Curve) - 9 No's.( for Lighting DB). V. 415V ,40A, 4P, MCB of 10KA('C' Curve) - 9 No's.( for RP DB) VI. 415V ,40A, 4P, MCB of 10KA('C' Curve) - 9 No's.( for AC DB) VII. 415V ,40A, 4P, MCB of 10KA('C' Curve) - 4 No's. SPARE
MAIN CHANGEOVER PANEL-B Supply, installation, testing & commissioning of Main Changeover Panel The panel shall be compartmental type with Aluminumbus bar and separate cable and bus bar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxiliary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Short-circuit, 2) ON/OFF - Auxiliary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. A. EB INCOMER(EB INCOMER-1 )- 1 NOS 415V , 500, 4P, MCCB of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, MCB - 3 Nos. 500/5A, CL-1, 10VA CT's with tape wound - 3 nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT B. DG INCOMER (DG INCOMER-2 ) - 1 NOS 415V , 500, 4P, MCCB of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, MCB - 3 Nos. 500/5A, CL-1, 10VA CT's with tape wound - 3 nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT C. E+M INTER LOCKING BETWEEN MSEDCL INCOMER AND DG INCOMER D. BUSBAR RATING- 415V, 600A, 3Ph, 4wire 50Hz, Aluminum bus bars (91E electrical grade) having withstand ability symmetrical fault level of 50 KA for 1 Sec. E. OUT GOING FEEDER FROM 500A BUS BAR-1 I. 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 2No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) II. 415V ,100A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 5No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) III. 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS - 5 No's 6A, 6KA, MCB - 3 Nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) IV. 415V ,32A, 4P, MCB of 10KA('B' Curve) - 10 No's.( for Lighting DB) V. 415V ,40A, 4P, MCB of 10KA('C' Curve) -10 No's.( for RP DB) VI. 415V ,40A, 4P, MCB of 10KA('C' Curve) - 10 No's.( for AC DB) VII. 415V ,40A, 4P, MCB of 10KA('C' Curve) - 4 No's. SPARE
BUS COUPLER PANEL Supply, installation, testing & commissioning of BUS COUPLER PANEL FOR MAIN C/O PANEL A & B The panel shall be compartmental type with Aluminum bus bar and separate cable and bus bar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxiliary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Short-circuit, 2) ON/OFF - Auxiliary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. BAS COUPLER BETWEEN TWO MAIN CHANGEOVER PANEL A & B 415V , 500, 4P, MCCB of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, MCB - 3 Nos. 500/5A, CL-1, 10VA CT's with tape wound - 3 nos. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) BUSBAR RATING- 415V, 600A, 3Ph, 4wire 50Hz, Aluminum bus bars (91E electrical grade) having withstand ability symmetrical fault level of 50 KA for 1 Sec.
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants..For distributing from Domestic Ground Water Tank to Domestic Over Head Tank Pump (Block 2 medical college bldg.) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 65 LPM, Individual Pump Discharge = 35 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 1 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr [ NON CSR].
Supply, Installation, Testing And Commissioning of Compact Self Contained Skid Mounted Hydro-pneumatic System. Vertical / Horizontal In-Line, multistage, centrifugal pumps with SS-304 casing and impeller and SS-316 shaft, CI base & head TEFC motor (with mechanical seal).Pre-charged diaphragm pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete. Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and delivery header, pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer)Vendor to submit performance curves and technical catalogue of the proposed model for review & approval by electrical & PHE consultants.For distributing from Flushing Ground Water Tank to Flushing Over Head Tank Pump (Block 2 - Medical college bldg) = Horizontal / Vertical Multistage,System Discharge ( Q ) = 100 LPM, Individual Pump Discharge = 50 LPM ,Approximate Head in m ( H ) = 35 m , Pump Qty - 1 working + 1 supporting ,One working pump on VFD , Maximum starts & Stops per Hrs. - 30 nos ,Approx. System Electrical Requirement = 2 HP, Approx. Individual Pump Electrical Requirement = 1 HP ,Diaphragm type pressure tank Capacity in lit : -100 ltr. [ NON CSR]
Supplying & erecting on line UPS with 3 Phase Input & 3 Phase Output, With Inbuilt Isolation Transformer of 40 kVA capacity complete with standard features,along with necessary SMF batteries(12v/65AH- 34Nos.) for 30 mins battery backup, Batteries along with MS battery Stand & and Interlinked with others.[ NON CSR]
Supply & Erecting of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter: a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.036 µΩm, Tensile strength - 120 to 240 MPa or N/mm², Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2.
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Flat roof Conductor Holder suitable for 8mm dia to be fixed above flat roof without puncturing RCC/Surface at every 1 Mtr to meet the requirements for IS/IEC 62305.
Supply & Erecting of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross junction. Test Parameter Salt Spray Test ( IEC 62561-1) - No sign of Corrosion
Supply & Erecting of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion piece should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor . Test Parameter: Electrical Resistivity Test-0.036 µΩm Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.
Supply & Erecting of air termination rod of 2 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of air termination rod of 3 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of air termination rod of 4 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning events Buttons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6.
Supply & Erecting of Stainless Steel Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor Test Parameter: Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Earth termination inside the concrete and soil. Test parameter: Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec(IS3043/IEEE80); Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. Tensile Test 290 to 510 N/mm². Adhesion no peel or crack & Bend test no seperation of Cu, Cu Coating thickness min. 70µm. Tested as per IEC 62561-2.
Supply & Erecting of Stainless steel Conductor Holder for fixing the 8mm/10 mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467.
Providing and Back filling back filling ground enhancing compound 25 kg bag complete. [9-3-2]
Supply & Erecting of Earthrod clamp made for terminating cable / flat conductor.
Supply & Erecting of Earth Chamber Inspection Pit made up of Poly propylene material [ NON CSR]
Estimate no : 131904 of 2021-2022 Supplying and erecting H.M.S. P.V.C. conduit 20 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting HMS P.V.C. conduit 25 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.[LS For Furniture & any Other Purpose]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW[NOTE]
Supplying and erecting mains with 2x1.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x2.5 sq.mm FRLS copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW[ For FRLS note subtract 2% from rate of FRLSH =61-61*2%=59.78]
Supplying and erecting ISI mark modular type switch 16 / 20 A with indicator, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. Note: Add Rs 57/- for additional two module box with double mounting plate if required.
Supplying and erecting ISI mark modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Point wiring for light/fan/bell concealed type in min 20 mm ISI marked HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLS grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW
Wiring for plug on board with Switch socket concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW[ 637]
Secondary point wiring for additional light/ bell 17, concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR/FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW[ 2345]
Point wiring for independent plug in ISI mark HMS PVC conduit with 1.5 sq.mm (2+1E )FR LS grade copper wire,modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Supplying and erecting CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) square / round shape suitable for 19 to 24 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting rectangular shaped CRCA /die-cast aluminium powder coated housing LED panel (slim edge-lit) 300x1200mm of suitable for 36 to 40 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting decorative oval bulk head edge-lit 10W LED luminaire comprising of high brightness LED Fitting on provided PVC block / wooden board.[LS]
Supplying and erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected in an approved manner.
Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 375/380 mm. 1400 RPM complete erected in position as per specification no. FG-FN/EXF
Supplying and erecting five star rated energy saving Ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF[ 1440]
Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original.
Supplying and erecting B grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire.[0.5*50=25]
Supplying, erecting and marking SPMCB 6A to 32A, C-series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB[ 1311
Supplying, erecting and marking SPMCB 6A to 32A, B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking TPMCB 6 A to 32A in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking TPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB [MAIN PANEL]
Supplying, erecting and marking FPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB [MAIN PANEL]
Supplying & erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted SP /TP MCBs of 12 poles/4 ways, on iron/ GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying & erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted SP / TP MCBs of 24 poles/ 8 ways on iron/ GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying and erecting original 1.25 mm CRCA sheet metal enclosures with 20A. 2 pin plug & earth socket and 20A. 3 pin plug top with 20A/30A single pole MCB complete erected on angle iron/ GI frame.
Supplying & erecting original 1.25 mm CRCA sheet metal enclosures with 30A, 3 pin plug & earth socket and 30 A 3 pin plug top with 30A triple pole MCB complete erected on angle iron/ GI frame.
Supplying and erecting CRCA sheet metal one way enclosures suitable for DP MCB /TP MCB /FP MCB erected on angle iron/GI frame complete.
Providing and erecting 3 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB [MAIN PANEL]
Providing & erecting 4 Pole MCCB of 200A,415V capacity with short circuit rating 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB [MAIN PANEL]
Supplying and erecting ON LOAD four pole automatic transfer switch suitable for 415V, 200A, 50 Hz capacity with enclosure, automatic/manual inbuilt time delay, high transfer speed, excellent breaking capacity, superior making capacity,compact & light weight, erected on provided angle iron / GI frame and connected with provided leads complete.[MAIN PANEL]
Supplying, fixing, and commissioning 4 pole RCBO ( (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 32A/40A as per specification no SW-RCCB/RCBO[ at DB]
Supplying and erecting porcelain/epoxy bus bar support complete erected in provided MS box for 200/300A complete.
Supplying and erecting SS enclosure for MCCB suitable for upto 100A MCCB complete.
Supplying and erecting metal work in CRCA sheet with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.[DG SHED]
Supplying and erecting self-locking arrangement with keys in duplicate, made of brass duly erected, flush with surface of panel / cupboard.
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require capacity with 99.9% aluminium purity with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB
Supplying and erecting dual source intelligent flush mounted panel meter three phase four wire (IPM) 415V CT/ PT site programmable class I flush mounted (96 x 96mm) meter with voltage, current, frequency, power factor ,ON hrs, kWh, EB and DG set metering with LED display(excluding CT'S) complete with RS 485 communication protocol, class I accuracy and wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.
Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc.
Supplying and erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.
Supplying, erecting & terminating XLPE armoured cable 3½ core 150 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3core 4 sq. mm. copper conductor continuous 5.48 sq.mm. (12 SWG) G.I. earth wire complete erected with glands& lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. copper conductor continuous 5.48 sq.mm. (12 SWG) G.I. earth wire complete erected with glands& lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. copper conductor continuous 5.48 sq.mm. (12 SWG) G.I. earth wire complete erected with glands& lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 120 to 185 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 200 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing & erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of 200 mm width & 20 mm height complete with necessary hardware in approved manner.
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP
Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials, testing & recording the results as per specification no ESE -LA
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG [4 (L) X 1.15( W) X 1.85 (H)]
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3 Kv
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.[ 5]
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.
Supplying, erecting and commissioning of diesel generating set with alternator of 125 kVA output continuous rating, 3 phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled /liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours,along with standard accessories, self-excited, self-regulated,screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil,diesel etc. as per specification no. GEN-DG
Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of above 100 kVA upto 125 kVA capacity Single/Three phase, 230/415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GENAMF.[ NOTE 111098 reduce rate by 10%=99988.2 + labour 3809/- = 103797.2]
Excavating soft murum / soft soil road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site good complete.[ 4.8 x 1 x 2.25=10.80]
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included).[ 4.8X 2.25 X1.5= 16.20
Supply & Erecting of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter: a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.036 µΩm, Tensile strength - 120 to 240 MPa or N/mm², Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2.
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Flat roof Conductor Holder suitable for 8mm dia to be fixed above flat roof without puncturing RCC/Surface at every 1 Mtr to meet the requirements for IS/IEC 62305.
Supply & Erecting of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross junction. Test Parameter Salt Spray Test ( IEC 62561-1) - No sign of Corrosion
Supply & Erecting of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion piece should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor . Test Parameter: Electrical Resistivity Test-0.036 µΩm Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.
Supply & Erecting of air termination rod of 2 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of air termination rod of 3 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter:Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of air termination rod of 4 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2
Supply & Erecting of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the requirement of IS/IEC - 62305
Supply & Erecting of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning events Buttons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6.
Supply & Erecting of Stainless Steel Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor Test Parameter: Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Earth termination inside the concrete and soil. Test parameter:Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec(IS3043/IEEE80); Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. Tensile Test 290 to 510 N/mm². Adhesion no peel or crack & Bend test no seperation of Cu, Cu Coating thickness min. 70µm. Tested as per IEC 62561-2.
Supply & Erecting of Stainless steel Conductor Holder for fixing the 8mm/10 mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply & Erecting of UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467.
Providing and Back filling back filling ground enhancing compound 25 kg bag complete.
Supply & Erecting of Earthrod clamp made for terminating cable / flat conductor.
Supply & Erecting of Earth Chamber Inspection Pit made up of Poly propylene material
Estimate no : 131905 of 2021-2022 Supplying and erecting HMS P.V.C. conduit 25 mm. dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC
Supplying and laying HMS PVC conduit 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting PVC box trunking of size 50x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting PVC box trunking of size 75x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting PVC box trunking of size 75x75 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX.
Supplying and erecting ISI mark modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type switch 16 / 20A with indicator, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting ISI mark modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. Note: Add Rs 57/- for additional two module box with double mounting plate if required.
Supplying and erecting ISI mark modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 modules duly erected.[FOR LIFT]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.[FOR AC & Utility Area]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background ] [For PC ]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.[For Bed Switch
Supplying and erecting 16 to 32 A DPMCB suitable to fix in 2 module of modular switch in provided box complete & duly concealed with necessary material and connected.[For Bed Switch board]
Supplying and erecting square / round shaped CRCA /diecast aluminium powder coated housing LED panel (slim edge-lit) light suitable for 13W to18W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) square / round shape suitable for 19 to 24 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting square shaped CRCA /die-cast aluminium powder coated housing LED panel light (slim edge-lit) 600x600mm suitable for 36 W-40W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying and erecting rectangular shaped CRCA /die-cast aluminium powder coated housing LED panel (slim edge-lit) 300x1200mm of suitable for 36 to 40 W with provision for plane front frame with translucent cover fixed to the housing complete.
Supplying & erecting LED 20W tube light fitting (4 feet) with aluminium housing, heat sink, integrated HF electronic driver complete.
Supplying and erecting bulkhead fitting suitable for upto LED upto 12W fixed on wall. As per specification no. FG-IDF/BHF [for LIFT Shaft]
Supplying and erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades, wire mesh, duly erected in an approved manner.
Supplying and erecting five star rated energy saving Ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF[ 1440]
Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original.
Supplying and erecting B grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire.1460][As Per FALSE Celing Height]
Supplying, erecting and marking SPMCB 6A to 32A, B- series (for lighting) in provided distribution board as per specification no. SW-SWR/MCB [ For Lift]
Supplying, erecting & marking DPMCB 6A to 32A, C- series (for motor/power) in provided distribution board as per specification no. SW-SWR/MCB [For Lift ]
Supplying, erecting and marking TPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB [For Lift ]
Supplying, erecting and marking FPMCB 40A to 63A in provided distribution board as per specification no. SW-SWR/MCB [ For Lift ]
Supplying and erecting triple pole and neutral distribution board (TPNDB) surface/ flush mounted SP / TP of 24 poles/8 ways on iron / GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB[ For Lift] ]
Providing & erecting 3 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB [for ups]
Providing & erecting 3 Pole MCCB of 200A,415V capacity with short circuit rating 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB[ For Ups]
Supplying, fixing and commissioning 2 pole,RCBO (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 6/10/16/20/25A, as per specification no SW-RCCB/RCBO [FOR LIFT]
Supplying, fixing and commissioning 4 pole RCBO (residual current breaker with overcurrent short circuit 10 kA and earth leakage protection), with 30/100/300 mA sensitivity and having capacity of 63A as per specification no SW-RCCB/RCBO [For Lift
Supplying and erecting SS enclosure for MCCB suitable for upto 100A MCCB complete. [For Ups]
Supplying and erecting SS enclosure for MCCB suitable for 125A to 200A MCCB complete.[ For UPS]
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [For Cable Tray
Supplying, erecting & terminating XLPE armoured cable 3½ core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 35 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 70 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 95 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 120 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 150 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3½ core 185 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½core 240 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 300 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE unarmoured cable 1 core 50 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel /distribution boards / pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE unarmoured cable 1 core 70 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel/distribution boards / pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE unarmoured cable 1 core 95 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel /distribution boards / pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE unarmoured cable 1 core 120 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel /distribution boards / pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE unarmoured cable 1 core 150 sq. mm. copper conductor complete erected with provided lugs, laid in provided control panel /distribution boards / pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 70 to 95 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing and erecting epoxy straight through joint outdoor/indoor for LT XLPE armoured cable 120 to 185 sq. mm. cable, with necessary material as per specification no. CB-JT/LT
Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 400 mm width & 100 mm height comprising all required standard accessories.
Providing and erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories.
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing and erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 400 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Supplying and erecting GI earth wire of high purity of different sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws in an approved manner.
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with insulating and non-corrosive bond in an approved manner with required joints As per specification no. EA-EP.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with insulating and noncorrosive bond in an approved manner with required joints As per specification no. EA-EP.
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG [750 KVA DG- 8500(L) X 2500(W) X 29705(H)][(11+11+4+4=38][500 KVA DG-6000(L) X 2000(W) X 2250(H)][8+8+5+5=26][38*6+26*2=280]
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.[4*8=32]
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS:15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3 kV
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness upto 33 kV
Supplying and erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.[ 5][GR-12+FIRST-6+SECOND-6+THIRD-6+FOURTH-6=36]
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.[PASSAGE AREA]
Supplying, erecting and commissioning of diesel generating set with alternator of 500 kVA output continuous rating, 3Phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled /liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours,along with standard accessories, self-excited, self-regulated,screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising of meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil,diesel etc. and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Supplying, erecting and commissioning of diesel generating set with alternator of 750 kVA output continuous rating, 3 phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled /liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours,along with standard accessories, self-excited, self-regulated,screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising of meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel etc. and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Excavating soft murum / soft soil road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site good complete.[ (9.1 x 1 x 3.1 =28.31 m3* 6=169.86)+(6.6*1*2.6=17.16*2=34.32)=204.18]
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps)[ (9.1 x 2.5 x 3.1 =70.52 m3* 6=423.15)+(6.6*2.5*2.6=42.9*2=85.8)=508.95] [16-3-5]
SITC of Electric Traction Passenger Lift with • Rated capacity :- 10 Passenger/680Kg • Floors :- G+1 floor (5Stops/5 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 800 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor Item No Short Description Unit Material Labour Total (1) (2) (3) (4) (5) (6) 250 • Clear Car size of 1300 mm wide x 1350mm deep x2200mm high • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2000mm wide x2400mm deep , 1500mm Pit depth, ,1800mm Overhead.[17-1-4][A-1519881] LIFT NO-1 ADD ON NOTE A2 For Lift having 800mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrowsindicators, extension of guide rails, shaft wiring with trunking, traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete (160270*3)=[B-480810] NOTE C1 For Lift travelling above First floor & up to Sixth floor [C-31974] NOTE F For vision panel having Size 100mm wide x 200mm high covered with fire rated laminated glass, having punched Jali as a part of the door panel SS sheet itself.
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with • Rated capacity :- 20 Passenger/1360Kg • Floors :- G+1 floor (5Stops/5Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 1200 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm,thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights,blower/fan for ventilation & SS chequered plate flooring, handrails,mirror, emergency light etc. • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI,scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR & FCC/ground floor • Clear Car size of 1300.mm wide x 2400mm deep x 2200 mmhigh LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery,adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2200mm wide x3000mm deep, 1500mm Pit depth, 1800mm Overhead.[17-1-10][A-2262786] • LIFT NO 3,6,9,11,13,17,18,19,21,23,25 ADD ON NOTE A6 For Lift having 1200mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons arrowsindicators, extension of guide rails, shaft wiring with trunking, travelling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete(182348*3=[B-547044]) NOTE C1 For Lift travelling above First floor & up to Sixth floor [C-31974] NOTE F For vision panel having Size 100mm wide x 200mm high covered with fire rated laminated glass, having punched Jali as a part of the door panel SS sheet itself. =3261*6=19566 [TOTAL A+B+C+D=2861370]
"SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with • Rated capacity :- 20 Passenger/1360Kg • Floors :- G+1 floor (5Stops/5Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR • Rated speed :- 1.0mps VS • Doors type :- COPO/TOPO Doors with frame having clear opening of 1200 mm wide x 2000 mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves/frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm,thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights,blower/fan for ventilation & SS chequered plate flooring, handrails,mirror, emergency light etc." "• COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI,scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car,LMR & FCC/ground floor • Clear Car size of 1300.mm wide x 2400mm deep x 2200 mm high LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings" "• Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class • ARD complete with necessary SMF VRLA batteries • Fireman controller having fireman switch at fire Landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18"" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work" "• Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery,adequate size core cuts if required & scaffolding for erecting guiderails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. • Lift shaft available having clear size of 2200mm wide x3000mm deep, 1500mm Pit depth, 1800mm Overhead.[17-1-10][A-2262786] • LIFT NO 5,12 & 24" ADD ON "NOTE A6 For Lift having 1200mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrowsindicators, extension of guide rails, shaft wiring with trunking, travelling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete (182348*3=B-547044)" "NOTE C1 For Lift travelling above First floor & up to Sixth floor [C-31974]" "NOTE E1 For Duplex Lift control system [D-40464]" "NOTE F For vision panel having Size 100mm wide x 200mm high covered with fire rated laminated glass, having punched Jali as a part of the door panel SS sheet itself. =3261*6=[E-19566] TOTAL-(A+B+C+D+E=2901834)"
Point wiring for light/fan/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) HFFR grade copper wires,modular type switch, earthing and required accessories as per specification No: WG-PW/HW
Wiring for plug on board with Switch socket concealed type, copper wiring and earthing and with modular accessories
Secondary point wiring for additional light/ bell , concealed type in min 25 mm PVC conduit with 1.5 sq.mm. (2+1E) HFFR grade copper wires with required accessories
Point wiring for independent plug in ISI mark HMS PVC conduit with 1.5 sq.mm (2+1E )HFFR grade copper wire,modular type switch, earthing and required accessories
Supplying and erecting mains with 2x1.5 sq.mm and earthing with 1x1.5 Sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting earthing with 1x1.5 Sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting mains with 2x2.5 sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting earthing with 1x2.5 Sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting mains with 2x4.0 sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting earthing with 1x4 Sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting mains with 4x4.0 sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supplying and erecting mains with 4x6.0 sq.mm HFFR copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars
Supply, installation, testing & commissioning of DG SYNCHRONISING PANEL (FORM 4B TYPE 6) including AMF for all DG sets The panel shall be compartmental type with Aluminium busbar and separate cable and busbar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE& BMS COMPATIBLE Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxillary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 65 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. INCOMER-1 Incomer-1= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-2= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-3= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-4= 415V , 800A, 4P, ACB of 65KA - 1No sychronizing controller for each DG set Incomer INCOMER-2 Incomer-5= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-6= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-7= 415V , 1250A, 4P, ACB of 65KA - 1No Incomer-8= 415V , 800A, 4P, ACB of 65KA - 1No sychronizing controller for each DG set Incomer BUS COUPLER BETWEEN TWO INCOMING SOURCE 415V , 4000A, 4P, ACB of 65KA - 1No OUTGOING FEEDERS FROM INCOMING SOURCE -1 415V , 4000A, 4P, ACB of 65KA - 1No-FOR MAIN ELECTRICAL PANEL-1 415V , 4000A, 4P, ACB of 65KA - 1No-SPARE OUTGOING FEEDERS. 415V , 4000A, 4P, ACB of 65KA - 1No--FOR MAIN ELECTRICAL PANEL-2 415V , 4000A, 4P, ACB of 65KA - 1No--FOR MAIN ELECTRICAL PANEL-3 415V, 4000A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65 KA for 1 Sec.(WITH 100% NEUTRAL).
SITC OF MAIN ELECTRICAL PANEL-COMMON ELE & EME ELE PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 630A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 630/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT BUS COUPLER BETWEEN COMMON ELECTRICAL & EMERGENCY ELECTRICAL SERVICES 415V , 630A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No OUTGOING FEEDERS FROM EMERGENCY ELE. SERVICES BUSBAR 415V ,315A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - FIRE PANEL 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - VENTILATION PANEL 415V ,250A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - STEIRCASE & LIFT PRESSUERIZATION PANEL 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -3 No's - SPARE OUTGOING FEEDERS FROM COMMON ELE. SERVICES BUSBAR 415V ,80A, 4P,MCCB of 16KA with Microprocessor based having O/C+S/C PROTECTIONS -9 No's - For HEAT PUMPS 415V ,63A, 4P,MCCB of 16KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - For STP 415V ,63A, 4P,MCCB of 16KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - For ETP 415V ,63A, 4P,MCCB of 16KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - For WTP 415V ,32A, 4P,MCB, C-curve -4 No's - PUMPS 415V ,32A, 4P,MCB, C-curve -4 No's - FAÇADE,LANDSCAPE,STREET LIGHTING DB 415V ,63A, 4P,MCCB of 16KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - SPARE 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 25 KA for 1 Sec.
SITC OF MAIN ELECTRICAL PANEL-BLOCK-A The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 1600A, 4P, ACB (EDO) of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 1600/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V ,1000A, 4P, ACB(MDO) of 36KA with THERMAL BASED RELEASES having O/C+E/F+S/C PROTECTIONS (WITH RS 485 COM.PORT) -2 No's - for TWO bus bar of A Block 6A, 6KA, C CURVE MCB - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,125A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - For UPS of Block-A 6A, 6KA, C CURVE MCB - 2 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,315A, 4P,MCCB, B-curve -1 No's - FOR MRI ROOM 415V ,200A, 4P,MCCB, B-curve -1 No's - FOR CT SCAN 415V ,125A, 4P,MCCB, B-curve -4 No's - FOR 4 NOS OF X-RAY ROOMS 415V ,63A, 4P,MCCB, B-curve -4 No's -AHU 415V ,32A, 4P,MCB, C-curve -3 No's - ULTRA SOUND ROOMS-3 NOS 415V ,32A, 4P,MCB, C-curve -3 No's - MINOR OTS-3 NOS 415V ,32A, 4P,MCB, C-curve -1 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,32A, 4P,MCB, B-curve -1 No's - For Basement Lighting DB 415V ,32A, 4P,MCB, C-curve -1 No's - For Basement RAW Power DB 415V ,160A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - Spare 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 1800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 60 KVA UPS-1 415V , 160A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 60 KVA UPS-2 415V , 160A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -1 No's - SERVER ROOM 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,40A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE SITC OF BLOCK-A 1st FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -6 No's -AHU 415V ,32A, 4P,MCB, C-curve -3 No's - MINOR/labour OTS-3 NOS 415V ,32A, 4P,MCB, C-curve -1 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,63A, 4P,MCCB, B-curve -3 No's -SPARE 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF BLOCK-A 1st FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -6 No's -AHU 415V ,32A, 4P,MCB, C-curve -3 No's - MINOR/labour OTS-3 NOS 415V ,32A, 4P,MCB, C-curve -1 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,63A, 4P,MCCB, B-curve -3 No's -SPARE 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF BLOCK-A 2nd FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 400A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 400A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,315A, 4P,MCCB, B-curve -1 No's -CSSD 415V ,100A, 4P,MCCB, B-curve -4 No's -AUTO CLAV 415V ,63A, 4P,MCCB, B-curve -3 No's -AHU 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,32A, 4P,MCB, C-curve -1 No's - LIGHTING DB'S 415V ,63A, 4P,MCCB, B-curve -3 No's -SPARE 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF BLOCK-A 3rd FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -4 No's -AHU 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,32A, 4P,MCB, C-curve -1 No's - LIGHTING DB'S 415V ,63A, 4P,MCCB, B-curve -3 No's -SPARE 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF BLOCK-A 4th FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, -10 No's -AHU 415V ,63A, 4P,MCCB, B-curve -4 No's -LIFT 415V ,25A, DP,MCB, C-curve -4 No's - LIFT LIGHTING 415V ,40A, 4P,MCB, C-curve -1 No's -ENDOSCOPY 415V ,32A, 4P,MCB, C-curve -1 No's - TERRACE DB 415V ,32A, 4P,MCB, C-curve -1 No's - AC DB 415V ,40A, 4P,MCB, C-curve -1 No's - RAW POWER DB'S 415V ,32A, 4P,MCB, B-curve -1 No's - LIGHTING DB'S 415V ,63A, 4P,MCCB, B-curve -3 No's -SPARE 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 150 A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF Distribution Board-12 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 32 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP B CURVE MCBs - 36 nos.
SITC OF Distribution Board-8 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 32 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP C CURVE MCBs - 24 nos.
SITC OF Distribution Board-6 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 32 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP B CURVE MCBs - 18 nos.
SITC OF Distribution Board-4 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 32 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP B CURVE MCBs - 12 nos.
SITC OF Distribution Board-12 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 40 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP C CURVE MCBs - 36 nos.
SITC OF Distribution Board-8 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 40 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP C CURVE MCBs - 24 nos.
SITC OF Distribution Board-6 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 40 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP C CURVE MCBs - 18 nos.
SITC OF Distribution Board-4 Way TPN 7 Segment Double Door DB AS PER IEC 61439 Incomer - 40 Amp , 10 KA , FP C CURVE MCB- 1 nos Sub-Incomer - 25 Amp , 10 KA , DP RCCB- 3 Nos Outgoing- 6 to 10 Amps, 10 KA, SP C CURVE MCBs - 12 nos. "Panel Requirement for Sr.No.107 to 122 & 131 to 143 The LV switchboard shall be type tested assemblies, all type tests as defined in latest IEC 61439-1&2 Also it should comply IEC 61641 Internal arc withstand for 65kA for 0.3 Sec LT panels must be built up from compartment housing, circuit breakers, control-gear, relays, busbars, controls and other items of equipment as per BOQ. Low Voltage switchgear. control gear must comply IEC 60 947 AS 13947 The Short circuit current with minimum duration of 1sec for LV switchgear panels shall be as indicated in SLD. The LV Main Switchboard shall be identical in mechanical construction to the LV Switchboard which had been type-tested by an acceptable, multi-fold design with impact test IK07-IK 10 The design temperature for the equipment provided in the main low voltage switchboards shall be +50°C. the switchboard shall be of form 4b, for form separation only metallic compartmentalization shall be used, Hylem /PVC sheets shall not be allowed Switchboard panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness not less than 2.0 mm. Busbars shall be made of high conductivity, and high strength Aluminum E91 grade Busbars shall be of rectangular cross sections, not more than 6mm thickness better suitable for full load current for phase bus bars and half/ full rated current for neutral bus bar or as stipulated in schedule of quantities. Busbar shall be suitable to withstand the stresses of fault level as specified in schedule of quantities. " The material and the spacing of the Busbar supports should be same as per the type tested assembly Busbar shall be tin plated with silver contacts. The cables and control wires shall be suitable for withstanding 105 deg C. Paint shall be RAL 7032 powder coated or as per the directives of engineer in charge. The APFC /RTPFC panels must be designed, tested & manufactured as per IEC61439- 1 & 2 & IEC 61921 reference standard:
Supply, installation, testing and commissioning of Aluminum 1000A 50kA SC for 1 sec Sandwich type BBT The BBT should be totally type tested as per IEC 61439-6. The Bus bar trunking must be with Copper/ Bimetal Contact, with Tin plated Aluminium (3L+N+PE) 100% N with 50% Integral / Internal Earth. The BBT must be of insulation Class F & operating voltage -1000V,impulse withstand of 8kV & Housing of minimum 1.5mm Electro-galvanized steel. The housing enclosure must be electrostatic powder coated of suitable shade. The BBT must of IP 54 indoor. The total bus bar assembly & installaion at site must comply Seismic zone 4. Straight Length of Fededer/Plug in type with hanging brackets,end cover/end Caps as per design requirement & site Condition
Supply, installation, testing and commissioning of flange end with adoptor box, copper flexibles as per design requirement and site conditions suitable for aluminium 1000A 50KA Sandwich type BBT.
Supply, installation, testing and commissioning of Phase cross-over / expansion joint as per design requirement and site conditions suitable for aluminium 1000A 50KA Sandwich type BBT.
Supply, installation, testing and commissioning of Support hanger as per design requirement and site conditions suitable for aluminium 1000A 50KA Sandwich type BBT.
Supply, installation, testing and commissioning of Fabrication support & Hardware suitable for aluminium 1000A 50KA Sandwich type BBT.
Supply, installation, testing and commissioning of Tap-off boxes tested as per IS 61439-6 of 100A Tap of boxes (IP 54) made up of 1.6mm thick sheet steel encloser duly powder coating on existing rising mains complete with 4P MCCB 36 KA 4P LSI with eathing connection point and safety interlock.
Supply, installation, testing and commissioning of Tap-off boxes tested as per IS 61439-6 of 125A Tap of boxes (IP 54) made up of 1.6mm thick sheet steel encloser duly powder coating on existing rising mains complete with 4P MCCB 36 KA 4P LSI with eathing connection point and safety interlock.
Supply, installation, testing and commissioning of Tap-off boxes tested as per IS 61439-6 of 160A Tap of boxes (IP 54) made up of 1.6mm thick sheet steel encloser duly powder coating on existing rising mains complete with 4P MCCB 36 KA 4P LSI with eathing connection point and safety interlock.
SITC OF MAIN ELECTRICAL PANEL-BLOCK-B & E The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 1250A, 4P, ACB (EDO) of 50KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 1250/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V ,1000A, 4P, ACB(MDO) of 36KA with THERMAL BASED RELEASES having O/C+E/F+S/C PROTECTIONS (WITH RS 485 COM.PORT) -2 No's - for TWO bus bar of B & E Block 6A, 6KA, C CURVE MCB - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,125A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - For UPS of Block-B 6A, 6KA, C CURVE MCB - 2 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - For UPS of Block-E 6A, 6KA, C CURVE MCB - 2 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,63A, 4P,MCCB, B-curve -2 No's -AHU 415V ,32A, 4P,MCB, C-curve -3 No's - MINOR OTS-3 NOS 415V ,63A, 4P,MCB, C-curve -2 No's - DEEP FREEZER & COLD STORAGE 415V ,32A, 4P,MCB, C-curve -2 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -2 No's - AC DB 415V ,40A, 4P,MCB, C-curve -2 No's - RAW POWER DB'S 415V ,32A, 4P,MCB, B-curve -1 No's - For Basement Lighting DB 415V ,32A, 4P,MCB, C-curve -1 No's - For Basement RAW Power DB 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 1250A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 60 KVA UPS-1 415V , 125A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 60 KVA UPS-2 415V , 125A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -1 No's - SERVER ROOM 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,40A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 25 KVA UPS-1 415V , 63 A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 25 KVA UPS-2 415V , 63 A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,40A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE
SITC OF BLOCK-B & E 1st FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -2 No's -AHU 415V ,32A, 4P,MCB, C-curve -2 No's - DRYING & PACKING 415V ,32A, 4P,MCB, C-curve -2 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -2 No's - AC DB 415V ,40A, 4P,MCB, C-curve -2 No's - RAW POWER DB'S 415V ,63A, 4P,MCCB, B-curve -6 No's -SPARE 415V ,40A, 4P,MCB, C-curve -6 No's - SPARE BUSBAR RATING 415V, 200A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF BLOCK-B & E 2nd FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -2 No's -AHU 415V ,32A, 4P,MCB, C-curve -2 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -2 No's - AC DB 415V ,40A, 4P,MCB, C-curve -2 No's - RAW POWER DB'S 415V ,63A, 4P,MCCB, B-curve -6 No's -SPARE 415V ,40A, 4P,MCB, C-curve -6 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 25 KA for 1 Sec.
SITC OF BLOCK-B & E 3RD FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 100A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -2 No's -AHU 415V ,32A, 4P,MCB, C-curve -2 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -2 No's - AC DB 415V ,40A, 4P,MCB, C-curve -2 No's - RAW POWER DB'S 415V ,63A, 4P,MCCB, B-curve -6 No's -SPARE 415V ,40A, 4P,MCB, C-curve -6 No's - SPARE BUSBAR RATING 415V, 125A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 25 KA for 1 Sec.
SITC OF BLOCK-B & E 4TH FLOOR ELECTRICAL PANEL- The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE INCOMER-1 FROM BUSBAR-1 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. INCOMER-2 FROM BUSBAR-2 415V , 160A, 4P, MCCB of 25KA having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. ELECTRICAL + MECHANICAL INTERLOCKING BETWEEN TWO INCOMER OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -4 No's -LIFT 415V ,63A, 4P,MCCB, B-curve -1 No's -PUMP 415V ,63A, 4P,MCCB, B-curve -2 No's -AHU 415V ,32A, 4P,MCB, C-curve -2 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -2 No's - AC DB 415V ,40A, 4P,MCB, C-curve -2 No's - RAW POWER DB'S 415V ,40A, 4P,MCB, C-curve -2 No's - TERRACE DB DB'S 415V ,62A, DP,MCB, C-curve -4 No's - LIFT LIGHTING 415V ,63A, 4P,MCCB, B-curve -6 No's -SPARE 415V ,40A, 4P,MCB, C-curve -6 No's - SPARE BUSBAR RATING 415V, 200A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 25 KA for 1 Sec.
SITC OF MAIN ELECTRICAL PANEL-BLOCK-C The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 630A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 630/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - FOR UPS LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - FOR AHU 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - FOR LIFT 415V ,100A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - FOR LIFT DB 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -6 No's - FOR PUMPS 415V ,32A, DP,MCB, B-curve -2 No's - For LIFT SHAFT 415V ,32A, 4P,MCB, B-curve -4 No's - For Lighting DB'S 415V ,32A, 4P,MCB, C-curve -7 No's - For RAW Power DB 'S 415V ,32A, 4P,MCB, C-curve -7 No's - For AC Power DB 'S 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - SPARE 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 25 KVA UPS-1 415V , 63A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 25 KVA UPS-2 415V , 63A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -1 No's - SERVER ROOM 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,32 A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE
SITC OF MAIN ELECTRICAL PANEL-BLOCK-D The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 800A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 1600/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V ,800A, 4P, ACB(MDO) of 36KA with THERMAL BASED RELEASES having O/C+E/F+S/C PROTECTIONS (WITH RS 485 COM.PORT) -2 No's - for TWO bus bar of D Block 6A, 6KA, C CURVE MCB - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,80A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - For UPS of Block-D 6A, 6KA, C CURVE MCB - 2 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,32A, 4P,MCB, B-curve -1 No's - For Basement Lighting DB 415V ,32A, 4P,MCB, C-curve -1 No's - For Basement RAW Power DB 415V ,63A, 4P,MCCB, B-curve -4 No's -AHU 415V ,32A, 4P,MCB, C-curve -4 No's - MEDICAL EQUIPMENTS 415V ,32A, 4P,MCB, C-curve -8 No's - LIGHTING DB'S 415V ,32A, 4P,MCB, C-curve -8 No's - AC DB 415V ,40A, 4P,MCB, C-curve -8 No's - RAW POWER DB'S 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,63A, 4P,MCCB, B-curve -4 No's -SPARE 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 1000A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 40 KVA UPS-1 415V , 80A, 4P, MCCB of 16KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 40 KVA UPS-2 415V , 80A, 4P, MCCB of 16KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -1 No's - SERVER ROOM 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,40A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE
SITC OF MAIN ELECTRICAL PANEL-BLOCK-F The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 415V , 630A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 630/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - FOR UPS LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -6 No's - FOR AHU 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - FOR LIFT 415V ,100A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - FOR LIFT DB 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -6 No's - FOR PUMPS 415V ,32A, DP,MCB, B-curve -2 No's - For LIFT SHAFT 415V ,32A, 4P,MCB, B-curve -4 No's - For Lighting DB'S 415V ,32A, 4P,MCB, C-curve -7 No's - For RAW Power DB 'S 415V ,32A, 4P,MCB, C-curve -7 No's - For AC Power DB 'S 415V ,63A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - SPARE 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
SITC OF UPS OUT PUT PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE UPS INCOMER-1 FROM 25 KVA UPS-1 415V , 63A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. UPS INCOMER-2 FROM 25 KVA UPS-2 415V , 63A, 4P, MCCB of 25KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTION- 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. BOTH UPS WORK PARELLALY WITH LOAD SHARING & SYNKING OUTGOING FEEDERS. 415V ,63A, 4P,MCCB, B-curve -1 No's - SERVER ROOM 415V ,25A, 4P,MCB, B-curve -6 No's - For ALL FLOOR E. LIGHTING DB'S 415V ,32 A, 4P,MCB, C-curve -6 No's - For ALL FLOOR UPS DB'S 415V ,40A, 4P,MCB, C-curve -4 No's - SPARE "Panel Requirement for Sr.No.107 to 122 & 131 to 143 The LV switchboard shall be type tested assemblies, all type tests as defined in latest IEC 61439-1&2 Also it should comply IEC 61641 Internal arc withstand for 65kA for 0.3 Sec LT panels must be built up from compartment housing, circuit breakers, control-gear, relays, busbars, controls and other items of equipment as per BOQ. Low Voltage switchgear. control gear must comply IEC 60 947 AS 13947 The Short circuit current with minimum duration of 1sec for LV switchgear panels shall be as indicated in SLD. The LV Main Switchboard shall be identical in mechanical construction to the LV Switchboard which had been type-tested by an acceptable, multi-fold design with impact test IK07-IK 10 The design temperature for the equipment provided in the main low voltage switchboards shall be +50°C. the switchboard shall be of form 4b, for form separation only metallic compartmentalization shall be used, Hylem /PVC sheets shall not be allowed Switchboard panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness not less than 2.0 mm. Busbars shall be made of high conductivity, and high strength Aluminum E91 grade Busbars shall be of rectangular cross sections, not more than 6mm thickness better suitable for full load current for phase bus bars and half/ full rated current for neutral bus bar or as stipulated in schedule of quantities. Busbar shall be suitable to withstand the stresses of fault level as specified in schedule of quantities. " The material and the spacing of the Busbar supports should be same as per the type tested assembly Busbar shall be tin plated with silver contacts. The cables and control wires shall be suitable for withstanding 105 deg C. Paint shall be RAL 7032 powder coated or as per the directives of engineer in charge. The APFC /RTPFC panels must be designed, tested & manufactured as per IEC61439- 1 & 2 & IEC 61921 reference standard:
Supply, Installation, Testing & Commissioning of transformer with all standard accessories like : Oil level Gauge, Oil conservator with Drain Plug, Bottom Filter valve with Plug, Earthing terminals, Colling Radiators with shut-off valve, Air release valve with plug, Lifting Lugs, Jacking Lugs, Underbase with Bi-directinal Rollers, Cast Iron Wheels, Inspection Chamber, Tank cover lifters, HV LV Cable box, Dehydrating Silica Gel Breather, OLTC with RTCC panel with AVR, Conservator oil filling hole with plug, Explosion vent with Diaphrgm, XLPE HV cable box, Additional Neutral terminal.(Note : Quote for MSEDCL approved specification of transformer as specified by them).The Distribution Transformers shall conform to IS: 1180 (Part 1) : 2014 amended up to date or other International Standards for equal or better performance. The Distribution Transformer shall bear level 2 (star 1 of BEE) ratings label approved by BIS (Bureau of Indian Standard) as per IS 1180 (Part-1):2014. 22/0.433 kV 2500 KVA
Supply Installation & Commissioning of 60kVA Easy UPS with temp sensor & SNMP card Supply of Battery 12V 75 AH Amar Raja Quanta - 1PF, 1.7ECV 30 min backup time Supply of Local Accessories (Rack, Interlinks, Battery Circuit breake ,Cabling between UPS and the Battery upto 10Mtr distance) for each 60kVA External 60kVA Aluminium Output Transformer
Supply Installation & Commissioning of 40kVA Easy UPS with temp sensor & SNMP card Supply of Battery 12V 65 AH Quanta - 1PF, 1.7ECV, 30 min backup time Supply of Local Accessories (Rack, Interlinks, Battery Circuit breake ,Cabling between UPS and the Battery upto 10Mtr distance) for each 40kVA External 40kVA Aluminium Output Transformer
Supply Installation & Commissioning of 30KVA Easy UPS with temp sensor & SNMP card Supply of Battery 12V 42 AH Quanta - 1PF, 1.7ECV, 30 min backup time Supply of Local Accessories (Rack, Interlinks, Battery Circuit breake ,Cabling between UPS and the Battery upto 10Mtr distance) for each 30KVA External 25kVA Aluminium Output Transformer
Supply, Installation, Testing & Commissioning of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Earth termination inside the concrete and soil. Test parameter: Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec(IS3043/IEEE80); Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. Tensile Test 290 to 510 N/mm². Adhesion no peel or crack & Bend test no seperation of Cu, Cu Coating thickness min. 70µm. Tested as per IEC 62561-2.
Supply, Installation, Testing & Commissioning of Exothermic Welding - Including welding mould, corrosion tape and other accessories for welding confirms the requirements of IEEE 837:2014 : T-Joint X- Joint, L -Joint, Straight joint. (For 10mm conductor)
Supply of Rust resistant non corossive 10 mm dia Copper bonded round conductor used for Riser inside the concrete and soil (Integrated down conductor). Including stainless steel Straight Connector at every 4 Mtr of integrated down conductor, Copper Bonded Bonding clamp for interconnecting 10 mm Round Conductor with reinforcement rebar at every 3Mtr inside the concrete,Tested as per IEC 62561-2.
Supply, Installation, Testing & Commissioning of Stainless steel Earthing stud with connector & suitable Clamp of dimension 70 x 70 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305.
Supply, Installation, Testing & Commissioning of 8mm dia Aluminum alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm².Test Parameter:a.Lightning impulse current of 100kA for 10/350 µsb.Electrical resistivity - 0.036 µΩm, Tensile strength - 120 to 240 MPa or N/mm², Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2.
Supply, Installation, Testing & Commissioning of UV resistance Nylon/PU Conductor Holder for Parapet wall for holding 8 mm dia Aluminium alloy round Conductor
Supply, Installation, Testing & Commissioning of UV resistance Nylon/PU roof conductor holder for flat roof with concrete block for fixing 8 mm dia Aluminium alloy Solid Round Conductor in the terrace flat surface at every 1 mtr
Supply, Installation, Testing & Commissioning of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor at cross junction.Test ParameterSalt Spray Test ( IEC 62561-1) - No sign of Corrosion
Supply, Installation, Testing & Commissioning of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion piece should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor . Test Parameter:Electrical Resistivity Test-0.036 µΩmSalt Spray Test - No Sign of Corrosion Tested as per IEC 62561-1
Supply, Installation, Testing & Commissioning of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.
Supply and Installation of air termination rod of 3 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter:Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm²Salt Spray Test-No sign of corrosionTested as per IEC 62561-1&2
Supply, Installation, Testing & Commissioning of SS Foldinng clamp to meet the requirement of IS/IEC - 62305
Supply, Installation, Testing & Commissioning of Earthing stud & suitable Clamp of dimension 70 x 70 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305. (for interconnecting Air termination and structral down conductors)
Supply, Installation, Testing & Commissioning of connecting point for Earth stud with to meet the requirements of IS/IEC 62305.
Supply, Installation, Testing & Commissioning of 18 mm copper bonded Solid Steel Round Conductor with minimum coating thickness 70µm as integrated down conductor. Including 18mm stainless steel Straight Connector at every 5 Mtr, MS cross connector for 18 mm round conductor inside concrete, Copper Bonded Bonding clamp for interconnecting 18 mm Round Conductor with reinforcement rebar at every 3Mtr inside the concrete, MS Diagonal clamp for interconnecting horizontal 10 mm Conductor with reinforcement rebar at every 3Mtr inside the concrete, suitable cross connector for conductor.Tested as per IEC 62561-2.
Supply, Installation, Testing & Commissioning of Stainless steel Earthing stud with fixing clamp accessories used in structural steel ring earthing system to meet the requirements of IS/IEC 62305
Supply, Installation, Testing & Commissioning of Stainless steel Earthing stud with fixing clamp accessories of dimension 70 x 70 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305.
Supply, Installation, Testing & Commissioning of Stainless steel Earthing stud with fixing clamp accessories of dimension 100 x 70 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305
Estimate no : 131906 of 2021-2022 Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV(ST.pole FRP to Fitting)
Supplying and erecting LED street light fitting suitable for 60W lamp, including lamp, with PF > 0.95 class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete as per specification No FGODF/FLS-2.
Supplying and erecting LED street light fitting suitable for above 70W- 75W lamp, including lamp, with PF > 0.95 class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete per specification No FG-ODF/FLS2
Supplying and erecting LED street light fitting suitable for above75W - 90W lamp, including lamp, with PF > 0.95 class IP 65 and above housing of pressure die cast aluminium alloy and heat sink extruded aluminium complete per specification No. FG-ODF/FLS2.
Supplying, erecting & marking TPMCB 6 A to 32A in provided distribution board as per specification no. SWSWR/MCB
Providing & erecting 4 Pole MCCB upto 100A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB(Rate As per Note)
Providing & erecting 4 Pole MCCB upto 200A, 415V, with short circuit rating 25 kA (Ics=100% of Icu ),adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB(Rate As per Note)
Supplying and erecting SS enclosure for MCCB suitable for upto 100A MCCB complete.
Supplying and erecting SS enclosure for MCCB suitable for 125A to 200A MCCB complete.
Supplying and erecting hylam sheet/ ebonite 6 mm thick for covering wall entries including cutting, drilling and fixing with nut bolts / screws etc. complete.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 , 3x240V,50 Hz with optical & RS 232 port, backlit LCD, measures & displays trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.
Supplying, erecting, testing, commissioning 22 KV HT metering cubical (compact type) approved by MSEDCL/licensee fabricated with 2mm.(14 SWG) M.S.sheets with supporting angle and channel, painted with powder coating / epoxy paint of required shade copper bus bar size 25x6 mm electronic security lock and heavy duty mechanical lock, with counter meter for measuring no of times the opening of doors, top side cover ( CT,PT cover) interlock with meter doors, epoxy coated 3 nos CT having required ratio between 50/5 A to 100/5 A, VA10, class 0.2S, 22000/V3/110/V3 VA 50, class 0.2 epoxy terminal block suitable for provided trivector meter, and provision for incoming and outgoing cables etc. complete duly tested by licensee with necessary test certificates and erected on provided plinth/ cc foundation[HT NET METER AS PER MSEDCL SPECIFICATIONS]
Supplying, erecting & terminating XLPE armoured cable 3½ core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 120 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3½ core 185 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL(ST pole to ST pole)
Providing and erecting Heat shrinkable indoor termination kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 sqmm to 400 sq. mm. with necessary material as per specification no. CB-JT/HT
Supplying , erecting & terminating 3 x 95 sq. mm. aluminium 22 kV(E), XLPE armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification no.CB-HT
Supplying , erecting & terminating 3 x 120 sq. mm. aluminium 22 kV(E), XLPE armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification no. CB-HT
Supplying , erecting & terminating 3 x 300 sq. mm. aluminium 22 kV(E), XLPE armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification no. CB- HT
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/22 kV ( E ) XLPE HT cable 3x up to 95 sq. mm. with necessary material as per specification no. CB-JT/HT
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT
Supplying & laying (including excavation) 15 cm dia RCC Hume pipe with coupling collar of standard thickness at required depth up to 90 cm below road / ground surface, for enclosing provided cable & necessary back filling with light ramming to make the road/ground surface as it was (Except bitumen carpet).
Supplying & laying (including excavation) 25 cm dia RCC Hume pipe of standard thickness at required depth up to 90 cms. below road / ground surface, for covering provided cable & necessary back filling with light ramming to make the road/ground surface as it was (Except bitumen carpet).
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
Providing & erecting 9 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 155 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials, testing & recording the results as per specification no. EA-EP
Providing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.l. Rod complete with all materials as per specification no. EAEP
Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP.
Supplying and erecting Annealed bare copper wire of high purity of different sizes used for earthing on wall with necessary copper clamps fixed on wall/cable/conduit with screws in an approved manner.
Supplying and erecting GI earth wire of high purity of different sizes used for earthing or any other purposes on wall with necessary G. I. lamps fixed on wall/cable/ conduit with screws in an approved manner.
Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 315 kVA, oil immersed and naturally cooled outdoor type, copper wound transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40oC by thermometer in oil and 45oC by the resistance in winding at full load rating, with HV tapping (with off load tap changer) off Load +5 to 10 in steps of 2.5%, with standard accessories complete with test certificate with losses below 1077 Watts at 50% load, 3255 Watts at 100% load as per IS:1180 - 2014 energy efficiency level II with necessary permissions of Electrical Inspector, as per specification no SS- TR. [Rate as per Note For indoor type transformer add Rs. 15000/- in overall rate of transformer.]
Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, oil immersed and naturally cooled outdoor type, copper wound transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40oC by thermometer in oil and 45oC by the resistance in winding at full load rating, with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%, with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 - 2014 energy efficiency level II with necessary permissions of Electrical Inspector, as per specification no SS- TR. [Rate as per Note For indoor type transformer add Rs. 15000/- in overall rate of transformer.]
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG [6*1]
Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete.
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
Providing printed instruction chart for treating persons suffering from electric shock, printed in English & Marathi and duly laminated complete.
Providing pair of duly tested rubber hand gloves as per IS :47705 suitable for working upto 22 kV supply complete.
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 EACH. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors, anti-septic solution, etc. (All above contents shall be of standard makes)
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 & CPRI tested having 2 mm thickness upto 3.3 kV
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 & CPRI tested having 3mm thickness upto 33 Kv
Supplying shock proof leather safety shoes of electrical grade of standard size as IS :11226, 14544 duly tested, withnecessary test certificate from manufacturer.
Supplying and erecting D.C.P. type fire extinguisher 9 kg capacity cartridge type with Gun Metal cap 150 gram CO2 gas cartridge, powder and brackets conforming to IS 2171-1985 and complete erected with necessary clamps made from 50x6 mm M.S. flat with nuts & bolts grouted in wall complete.
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S.flat with nut & bolts grouted in wall complete.
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete.
Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete.
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel,concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal /conical GI pole).
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel,concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 9m & 10m high octagonal /conical GI pole).
Supplying,laying (including excavation) and jointing 300 MM RCC NP2 class pipes conforming to IS:458 - 2003 in prepared trenches in grade and level, including hoisting, making collar joints in cement mortar 1:1, including cost of jointing material like cement, sand etc. and hydraulic testing of the pipes at factory as well as on site as per the stipulation in relevant IS code etc. complete. including dewatering wherever necessary.
Providing & constructing inspection chamber of 600(L) x 600(W) X 750(D) (internal) size in B.B. masonry 230mm thick upto 1.5m depth and 350mm thick below uuto 1.0m depth in cement mortar 1:6, with foundation concrete 200mm thick in C.C. 1:4:8, and top R.C.C. heavy duty cover with frame, plastered on both faces in cement mortar 1:6, 20mm thick finished with neat float, including curing, cost of all labour, material, loading, unloading and transportation charges of material, including providing & fixing in position CI steps etc. completet.
Providing & constructing inspection chamber of 1000(L) x 1000(W) x 1000(D) (internal) size in B.B. masonry 230mm thick upto 1.5m depth and 350mm thick below uuto 1.0m depth in cement mortar 1:6, with foundation concrete 200mm thick in C.C. 1:4:8, and top R.C.C. heavy duty cover with frame, plastered on both faces in cement mortar 1:6, 20mm thick finished with neat float, including curing, cost of all labour, material, loading, unloading and transportation charges of material, including providing & fixing in position CI steps etc. completet. (Excluding the cost of excavation and including dewatering if required)
Providing & constructing inspection chamber of 1200(L) x 1200(W) x 1200(D) (internal) size in B.B. masonry 230mm thick upto 1.5m depth and 350mm thick below uuto 1.0m depth in cement mortar 1:3, with foundation concrete 200mm thick in C.C. 1:4:8, and top R.C.C. heavy duty cover with frame, plastered on both faces in cement mortar 1:3, 20mm thick finished with neat float, including curing, cost of all labour, material, loading, unloading and transportation charges of material, including providing & fixing in position CI steps etc. completet. (Excluding the cost of excavation and including dewatering if required)
Supply, installation, testing & commissioning of MAIN ELECTRICAL PANEL FOR HOSTEL, KINTEEN & DINNING AREA (Location- Substation Room) The panel shall be fabricated type with IP 43 protection(With Metal Door). The panel shall be compartmental type with Aluminium busbar and separate cable and busbar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE& BMS COMPATIBLE This panel should include Bus bar mounting Surge Protection Device Type 1 Tested as per IEC 61643-11:2011 & UL 1449 4th edition. : 3 NOS Multi function electronic meter with kW and pf display for Incomer:. Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxillary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB/MMCB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. 10) Electrical & Mechanical Inter-locking. O/G ACB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based 5) ICU = ICS =50 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers 9)9) ACB/MMCB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. 10) Electrical & Mechanical Inter-locking. For more details refer Main SLD. Incomer: 500 A FP MCCB 50 KA FOR: TRANSFORMER-1 500 A FP MCCB 50 KA FOR: TRANSFORMER-2 500 A FP MCCB 50 KA FOR: TRANSFORMER-3 BUS- COUPLER 500 A FP MCCB 50 KA FOR: BUS COUPLER-1 BETWEEN TR-1 & TR-2 500 A FP MCCB 50 KA FOR: BUS COUPLER-2 BETWEEN TR-2 & TR-3 M+E INTERLOCKING BETWEEN INCOMER MCCB & BUS COUPLER MMCB Outgoing TR-1 BUSBAR: 315 A TPN MCCB 25 KA FOR: HOSTEL 250 A TPN MCCB 25 KA FOR: APFC PANEL-1 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 315 A TPN MCCB 25 KA FOR: 2-NOS-SPARE 200 A TPN MCCB 25 KA FOR: 2-NOS-SPARE Outgoing TR-3 BUSBAR: 315 A TPN MCCB 25 KA FOR: HOSTEL 250 A TPN MCCB 25 KA FOR: APFC PANEL-1 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 315 A TPN MCCB 25 KA FOR: 2-NOS-SPARE 200 A TPN MCCB 25 KA FOR: 2-NOS-SPARE Bus Bar-1 OF TR-1 with 650 Amps Aluminium (Electrical Grade). Bus Bar-2 OF TR-2 with 650 Amps Aluminium (Electrical Grade). Bus Bar-2 OF TR-3 with 650 Amps Aluminium (Electrical Grade).
Supply, installation, testing & commissioning of MAIN ELECTRICAL PANEL.(MEDICAL COLLEGE, HOSTEL,STUDANT ACTIVITY CENTER) (Location- Substation Room) The panel shall be fabricated type with IP 43 protection(With Metal Door). The panel shall be compartmental type with Aluminium busbar and separate cable and busbar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE& BMS COMPATIBLE This panel should include Bus bar mounting Surge Protection Device Type 1 Tested as per IEC 61643-11:2011 & UL 1449 4th edition. : 3 NOS Multi function electronic meter with kW and pf display for Incomer:. Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxillary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 50 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB/MMCB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. 10) Electrical & Mechanical Inter-locking. O/G ACB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based 5) ICU = ICS =50 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers 9)9) ACB/MMCB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. 10) Electrical & Mechanical Inter-locking. For more details refer Main SLD. Incomer: 500 A FP MCCB 50 KA FOR: TRANSFORMER-1 500 A FP MCCB 50 KA FOR: TRANSFORMER-2 500 A FP MCCB 50 KA FOR: TRANSFORMER-3 BUS- COUPLER 500 A FP MCCB 50 KA FOR: BUS COUPLER-1 BETWEEN TR-1 & TR-2 500 A FP MCCB 50 KA FOR: BUS COUPLER-2 BETWEEN TR-2 & TR-3 M+E INTERLOCKING BETWEEN INCOMER MCCB & BUS COUPLER MMCB Outgoing TR-1 BUSBAR: 315 A TPN MCCB 25 KA FOR: HOSTEL 250 A TPN MCCB 25 KA FOR: APFC PANEL-1 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 315 A TPN MCCB 25 KA FOR: 2-NOS-SPARE 200 A TPN MCCB 25 KA FOR: 2-NOS-SPARE Outgoing TR-3 BUSBAR: 315 A TPN MCCB 25 KA FOR: HOSTEL 250 A TPN MCCB 25 KA FOR: APFC PANEL-1 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 200 A TPN MCCB 25 KA FOR: FOR KITHCEEN & DINNING 315 A TPN MCCB 25 KA FOR: 2-NOS-SPARE 200 A TPN MCCB 25 KA FOR: 2-NOS-SPARE Bus Bar-1 OF TR-1 with 650 Amps Aluminium (Electrical Grade). Bus Bar-2 OF TR-2 with 650 Amps Aluminium (Electrical Grade). Bus Bar-2 OF TR-3 with 650 Amps Aluminium (Electrical Grade).
Supply, installation, testing & commissioning of PROJECT COMMON ELECTRICAL PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB-INCOMER-1 415V , 200A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 200/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT DG-INCOMER-1 415V , 200A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 200/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT 200 A ATS SWITCH BETWEEN TWO INCOMER OUT GOING OF ATS SWITCH 415V , 200A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 200/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT DUAL SOURCE METER(DSM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V , 100A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 1No-FOR WTP 415V , 63A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 1No-FOR STP 415V , 32A, 4P, MCB of 10KA - 1No-FOR DOMASTIC WATER SUPPLY PUMP OF UGT-1 415V , 32A, 4P, MCB of 10KA - 1No-FOR DRINKING WATER SUPPLY PUMP OF UGT-1 415V , 32A, 4P, MCB of 10KA - 1No-FOR DOMASTIC WATER SUPPLY PUMP OF UGT-2 415V , 32A, 4P, MCB of 10KA - 1No-FOR DRINKING WATER SUPPLY PUMP OF UGT-2 415V , 32A, 4P, MCB of 10KA - 1No-STREET LIGHT CKT-8 NOS 415V , 63A, 4P, MCCB of 25KA with MICROPROCCESER BASED having O/C+S/C PROTECTIONS - 4 No-SPARE 415V , 32A, 4P, MCB of 10KA - 1No-4 NOS-SPARE
Estimate no : 131907 of 2021-2022 Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete.
Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts grouted in wall complete.
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 32 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 40 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe above ground of ‘C’ class ERW of size 200 mm dia with necessary fittings complete as per specification no. FF-PP
Providing coating of bitumen paint & 4mm thick wrapping for underground 100 mm ring main of fire fighting system.
Supplying and erecting cast iron double flange sluice valve 150mm dia. complete as per specification no. FF-VL/SV
Supplying and erecting cast iron double flange sluice valve 200 mm dia. complete as per specification no. FF-VL/SV
Supplying & erecting cast iron double flange butterfly valve of size 75/80 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 100 mm dia. complete as per specification no. FF-VL/BFV
Supplying & erecting cast iron double flange butterfly valve of size 150 mm dia. complete as per specification no. FF-VL/BFV
Supplying and erecting cast iron double flange NRV of size 100 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting cast iron double flange NRV of size 150 mm dia complete as per specification no. FF-VL/NRV
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) fitted with necessary accessories complete as per specification no. FF-FFA/HV
Supplying fire fighting reinforced rubber lined (R.R.L.) hose pipe, 63mm dia, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying & erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting fire brigade header of 150 mm dia, for supplying water in fire tank complete as per specification no. FFFA/ FBC
Supplying and erecting fire brigade header (Siamese connection) of 150 mm dia for supplying water to wet riser system complete as per specification no. FF-FFA/SMC
Supplying and installing air vessel of 300 mm dia 1.5m in height M.S. tank installed inside pump house / on terrace complete as per specification no. FF-FFA/ACT
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and installing pressure gauge of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification no. FFFFA/PG
Supplying and installing pressure switch with 12/15 mm dia isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Supplying and erecting one no. brass orifice plate having 6 mm. thickness, 140 mm outer dia and required/proper diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP
Supplying and erecting M.S./CRCA cabinet for housing Fire Brigade / SIEMESE connections (size 1250 x 400 x 300 mm.)made from 16 SWG sheet and angle iron 25 mm. x 25 mm. x 4 mm. having front doors with viewing glass (8" x 6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour.
Supplying, erecting, testing and commissioning of 15 mm (½") dia. NBCM Body chrome finished quartzoid bulb sprinkler having 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR
Supplying, erecting, testing and commissioning vane type water flow detector suitable for detecting flow of water in wet sprinkler pipe of main line or branch lines of 100 mm dia having following features 1) Visual switch activation 2) Rugged switch assembly 3) Heavy duty aluminium pipe saddles 4) Durable metal enclosure 5) Steel U bolts for secure mounting 6) Two SPDT ( Single pole double track ) synchronised switches 7) serviceable without draining pipes
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps).
Supplying and erecting 100 mm dia. cast iron foot valve at position with necessary materials complete.
Supplying, installing, testing and commissioning with perfect aligning, proper levelling of fire service main multi stage pump, of 2400 LPM at 88 m head centrifugal type, 75 HP (55 kW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/MSC
Supplying, installing, testing and commissioning with perfect aligning, proper levelling of fire service main multi stage pump, of 2800 LPM at 105 m Head centrifugal type, 120 HP, (90 kW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/MSC
Supplying, installing, testing and commissioning with perfect aligning, proper levelling of jockey pump of 240 LPM at 105 m head 20 HP (15 kW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/JP
Supplying, installing, testing and commissioning with perfect aligning, proper levelling of booster pump of 450 LPM at 35 m head 7.5 HP (5.5 KW), 3 phase, 415 volt, 50Hz or of suitable HP with suitable stages as per specification no. FF-MFP/BP
Supplying and erecting D.O.L. Starter 400V. 3 phase, 50 cycles with no volt coil and overload element with necessary materials and connected to supply upto 7.5 H.P.
Supplying & erecting Dewatering Submersible pump set 415V, 3 phase, 50C/s, A.C. supply of 1.5 KW/ 2 H.P., of 2 to 17 m head with 600 to 100 LPM discharge, non-clogging minimised abrasive wear, large impeler clearance & maintenance free pump set with water proof cable duly sealed with epoxy material built in protection to prevent the motor from burn out due to abnormal operation. specially designed high efficiency motor with F class insulation & the pump mechanically sealed in the oil chamber,. etc. complete as per specification no. DWP- SMP
Supplying, installing, testing, and commissioning portable fire extinguishers of Mechanical foam type fire extinguishers 50 Lts. Capacity with intial filling in brand new cylinder with powder coated finish ,fitted with gun metal union, high pressure CO2 gas cartridge ,hose and ABS type branch pipe and wall mounting bracket etc. complete, confirming to IS : 10204 (Non-CSR)
Supplying, installing, testing, and commissioning standard response conventional sprinkler quartzoid bulb type with 15mm screwed end connection of 79 deg. C.temperature rating K80 and orifice shall not be less than 6mm sprinklers shall be UL listed / FM approved with chrome finished.(Non-CSR)
Supplying, installing, testing, and commissioning of Sprinkler Flexible drop pipes with 1500mm long(UL Listed) made of Corrugated SS Tubing to with stand 16 Bar pressure with welded reducer on one end to directly accommodate sprinkler & female check-nut on the other end to connect to the branch pipe with supports complete(Non-CSR)
Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome platedbrass, BSPT, K-factor as per design consideration complete as required and coverage of 2.5 meter either side.(Non-CSR)
Supplying, installing, testing, and commissioning standard response conventional upright sprinkler quartzoid bulb type with 15mm screwed end connection of 68 deg. C. temperature rating K80 and orifice shall not be less than 6mm sprinklers shall be UL listed / FM approved with chrome finished.(Non-CSR)
Supplying, installing, testing, and commissioning of Deluge valve of 100mm dia comprising of a main gate valve, in and pressure guage, water motor gong, test connection of adequate size with valve and other accessories complete as per NFPA standard including relevent trimkits and solenoid valve with mating flanges suitable to be activated by the Flow Switches including power and control wiring upto panel & ON/OFF arrangement and associated works.
Supplying, installing, testing, and commissioning of self Luminous Exit Sign in accordance with BS5499as per sample approved by incharge (FIRE EXIT 300mm X 150mm)
Supplying, installing, testing, and commissioning of FIRE PUMPS - DIESEL ENGINE DRIVEN Supply, installation, testing and commissioning of Diesel Engine driven fire pump suitable for automatic operation comprising of the following: Horizontally mounted end suction single/multi stage, single/multi outlet centrifugal pump, suitable for operation on 415 volts ± 10%, 3 phase, 50 HZ A.C supply, complete with flexible coupling and coupling guard as required. Fire pump having C.I. body, bronze impeller and S.S. Shaft with mechanical seal, capable for delivering 2800 LPM of water at 105 mts. head to ensure a minimum pressure of 3.5.kg/cm2 at the terrace/farthest hydrant. The pump should meet the condition of Local fire Authority/NBC). Water/Air Cooled Diesel engine (4/6 CYLINDER ENGINE) of speed 1800 RPM for the above pump with automatic starting mechanism (AMF autostart panel complete with necessary relays like no volt relay, over voltage and low voltage relays, contactors, timer, pressure switch etc. as required for the auto start of the diesel engine in case of power failure complete with all accessories, wiring & cabling) and other accessories including fuel tank (fabricated from 3mm MS sheet painting with two coats of synthetic enamel paint over a coat of primer)
Estimate no : 131908 of 2021-2022 Supplying and erecting iron, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3½ core 185 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 35 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 3½ core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 4 core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 4 core 35 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 4 core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XLPE armoured cable 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories.
Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 200 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Providing & erecting Hot dipped galvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner.
Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with insulating and non-corrosive bond in an approved manner with required joints As per specification no. EAEP
Supplying and erecting 20mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FFFFA/ARV
Supplying, erecting & terminating XLPE armoured cable 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. FIRE DAMPER
Supplying and fixing of External Thermal duct insulation with 2 layer protective coating over closed cell Nitrile rubber (Class “O”) insulation on ducting after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation.All air ducts be it supply air in the return air path, both the supply and return air above the false ceiling of the conditioned space, in the conditioned space or in the non conditioned area inside the building and outside the building, shall be coated with STARBOND 30-36 / FOSTER 30-36 in conjunction with facotry laminated 7 mil woven fiber glass cloth on insulation finally finished with 2 layers of STARBOND 30-36 to provide complete seal against air and moisture complete as per specifications and as required. Insulation material for Duct shall be anti-microbial closed cell Elastomeric Nitrile Rubber. Thermal conductivity of the insulation material shall not exceed 0.038 W/moK or 0.212 BTU / (Hr-ft2-oF/inch) at an average temperature of 30oC. Density of the nitrile rubber shall be 40-60 Kg/m3. The product shall have temperature range of –40 oC to 105oC. The insulation material shall be fire rated for Class 0 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 1 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be not less than 0.024 perm inch (2.48 x 10-14 Kg/m.s.Pa i.e. µ=7000: Water vapour diffusion resistance). Thermal conductivity of the material shall not be affected by ageing, as per DIN 52616 The smoke density of the material as per AS-1530.3 shall not exceed 1.The material shall be antimicrobial as per ISO 22196, C1338 and ASTM G21-96. There shall be no growth of fungus and mold. 19mm (16.23.1) [cpwd]
Supplying and fixing of External Thermal duct insulation with 2 layer protective coating over closed cell Nitrile rubber (Class “O”) insulation on ducting after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation.All air ducts be it supply air in the return air path, both the supply and return air above the false ceiling of the conditioned space, in the conditioned space or in the non conditioned area inside the building and outside the building, shall be coated with STARBOND 30-36 / FOSTER 30-36 in conjunction with facotry laminated 7 mil woven fiber glass cloth on insulation finally finished with 2 layers of STARBOND 30-36 to provide complete seal against air and moisture complete as per specifications and as required. Insulation material for Duct shall be anti-microbial closed cell Elastomeric Nitrile Rubber. Thermal conductivity of the insulation material shall not exceed 0.038 W/moK or 0.212 BTU / (Hr-ft2-oF/inch) at an average temperature of 30oC. Density of the nitrile rubber shall be 40-60 Kg/m3. The product shall have temperature range of –40 oC to 105oC. The insulation material shall be fire rated for Class 0 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 1 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be not less than 0.024 perm inch (2.48 x 10-14 Kg/m.s.Pa i.e. µ=7000: Water vapour diffusion resistance). Thermal conductivity of the material shall not be affected by ageing, as per DIN 52616 The smoke density of the material as per AS-1530.3 shall not exceed 1.The material shall be antimicrobial as per ISO 22196, C1338 and ASTM G21-96. There shall be no growth of fungus and mold. 25mm (16.23.2) [cpwd]
Supply, Installation, Testing & Commissioning of AHRI Certified minimum 400 TR (ACTUAL CAPACITY) 3W+1SB VFD driven Water cooled screw Chiller with Unit mounted VFD complete with multiple, semi hermetic twin screw compressors working on R134a Refrigerant, water cooled shell and tube flooded type condenser, water cooled shell and tube flooded/Falling film type evaporator, with victaulic couplings for end connection for evaporator and condenser, first charge of refrigerant, oil, micro-Processor based Control panel with Modbus RS485/Bacnet protocol for hook up with BMS, Single refrigerant circuit, electrical panels, interlocking of safety switches, spring type isolators for vibration isolation to be provided. Design Conditions - Cooling capacity - Minumim 400 TR ( At Design conditions given below) Chilled water Inlet/Outlet Temperature - 12.2 / 6.7 Deg C Fouling factor for Evaporator - 0.0005 FPS Condenser water Inlet / Outlet Temperature - 32 / 37 Deg C Fouling Factor for condenser - 0.001 FPS No of tube Passes - 2 Power - 415 V +/- 10 %, 50 Hz supply Maximum power consumed - Not greater than 0.73 IkW/TR at design condition at 100 % load. NPLV greater than 9.3 COP @ AHRI Greater than 5.8 Note: 1) AHRI Certificate of offered chiller model to be submit along with offer 2) Chiller should unload from 100% to minimum 15% Design capacity 3) VFD shall be of Air cooled unit mounted 4) Water side pressure drop in chiller and condenser should not be more than 7 meter 5) Compressor shall be of OEM make only 6) Heat exchangers shall be with ASME U stamping. Chiller manufacturing to be done in ASME certified facory and factory should have ASME certification (NON CSR)
PRIMARY CHILLED WATER PUMPS (3W + 1S) Supply, Installation, Testing and Commissioning of Inline Centrifugal pumps factory assembled and tested for rated efficiency complete with TEFC motor, common base frame, mechanical seals, vibration isolators, including flexible connections etc. The pumps shall be suitable for operation on 415 +/- 10% V, 50 Hz, 3 Ph AC supply. FLOW - 960 USGPM HEAD - 25 Mtrs. RPM - 1400 NMT (Non CSR)
SECONDARY CHILLED WATER PUMPS ( 3W 1S) Supply, Installation, Testing and Commissioning of Inline Centrifugal pumps factory assembled and tested for rated efficiency complete with TEFC motor, common base frame, mechanical seals, vibration isolators, including flexible connections etc. The pumps shall be suitable for operation on 415 +/- 10% V, 50 Hz, 3 Ph AC supply. FLOW - 960 USGPM HEAD - 50 Mtrs. RPM - 1400 NMT (NON CSR)
Variable Speed Pumping System ( VSPS): Supply of VSPS for Secondary Chilled Water pumps in parallel operation having VFD ( 3 nos),individual VSD with inbuilt Master and Slave PID Controller in VSD with enclosure having necessary incomer ( considering 3 pumps ) , isolators in incoming & outgoing for each VSD, view panel , terminals , cooling fan and cabling( power & control ) with M.S frame for mounting . VSPS shall consist of necessary Differential pressure transmitters. The PID controller shall be able to communicate with BMS. . (NON CSR)
Supply, Installation, Testing and Commissioning of Differential pressure sensor for chilled water Pumps (NON CSR)
Supply, Installation, Testing and Commissioning of Differential Pressure Transmitter (1 Nos each per floor to the farthest AHU/FCU) (NON CSR)
Supplying, installing, testing and commissioning of PRESSURISED COLD WATER EXPANSION TANK WITH AIR SEPARATER with S.S braided pipe flexible connector suitable for total volume of water in cold water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep cold water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and 20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank and air separator must be constructed in accordance with section VIII of the ASME Boiler and pressure vessel (Unfired)code and stamped 125 PSI working pressure. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures and safety fixtures required for proper functioning of the complete hydronic system. The expansion tank shall be supplied along with pressurization unit. The pressurization unit shall consist of two No.(1 working+1 stand-by) high pressure pumps of suitable pressure rating mounted on M.S. frame, complete with interconnecting piping, isolation valves, NRV, Y-strainer, Pressure gauge, pressure transmitter, auto-logic panel(IP 55) with dry-run protection, electrical MCB and interconnecting wiring. The unit shall be housed in powder-painted canopy suitable for external installation, if required.The capacity of tank shall be 2000 litres approx. (for chilled water system).
Supply, Installation, Testing & Commissioning of Induced Draft Cooling Tower Twin Cell complete with FRP Basin, Base Supports in GI, Munters Fills, Nozzels, FRP Moulded Fan, ECBC Code 2007 efficient Fan Motor (IS-12615) at 1400 RPM, Inlet & Outlet & Drain Connections. The Cooling Tower Shall be CTI Approved with advanced drift eliminators. Suitable for Capacity: 480 TR Water Flow Rate: 1200 GPM Ambient wet Bulb Temperature: 26.1 Deg C Entering water Temperature: 34 Degc C Leaving water Temperature: 29 Deg C (NON CSR)
Condenser Water Pumps ( 3W + 1S) Supply, Installation, Testing and Commissioning of Inline Centrifugal pumps factory assembled and tested for rated efficiency complete with TEFC motor, common base frame, mechanical seals, vibration isolators, including flexible connections etc. The pumps shall be suitable for operation on 415 +/- 10% V, 50 Hz, 3 Ph AC supply. Water Flow Rate: 1200 GPM Head: 25 M (NON CSR)
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d450x45.4/5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d315x28.6x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d280x28.6x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d225x22.7x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d160x16.4x5000mm
NSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d140x14.6x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d110x11.4x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d90x8.2x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d75x6.8/5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d63x5.8/5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d50x4.6x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d40x3.7x5000mm
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation) Supply& fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. PreInsulated with nitrile rubber wih Nylonn Cloth. 0.026 W/m.K. Thickness of 25m for dia110 and below, 32mm for above dia110mm. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d32x3.0/5000mm
CHILLED WATER PIPING WITH INSULATIONSupply, installation and testing of PN16 rated (HDPE) EN ISO 15494.Pipes insulated with 50mm PUF insulation covered with polysterene sheet and finsihed with chicken wire mesh and sand cement plaster and 2 layers of tarfelt sheething for burried pipes. Necessary hard neoperene rubber saddles type piping supports to be provided at regular intervals. The piping flange connection bolts and nuts should be of hot dipped galvanised.The pipes should be laid over RCC blocks. Plastic sticker type Water flow directions to be pasted on the supply and return chilled water pipes. Note: Only End flanges to be used for capping of pipes. Pipes to be covered with plastic cap on both ends to prevent entry of soil prior to installation. "Table E" of BS code for flange thickness to be adhered. (NON CSR) Pipe PE100 black SDR11 d450x45.4/5000mm
CHILLED WATER PIPING WITH INSULATIONSupply, installation and testing of PN16 rated (HDPE) EN ISO 15494.Pipes insulated with 50mm PUF insulation covered with polysterene sheet and finsihed with chicken wire mesh and sand cement plaster and 2 layers of tarfelt sheething for burried pipes. Necessary hard neoperene rubber saddles type piping supports to be provided at regular intervals. The piping flange connection bolts and nuts should be of hot dipped galvanised.The pipes should be laid over RCC blocks. Plastic sticker type Water flow directions to be pasted on the supply and return chilled water pipes. Note: Only End flanges to be used for capping of pipes. Pipes to be covered with plastic cap on both ends to prevent entry of soil prior to installation. "Table E" of BS code for flange thickness to be adhered. (NON CSR) Pipe PE100 black SDR11 d315x28.6x5000mm
CHILLED WATER PIPING WITH INSULATIONSupply, installation and testing of PN16 rated (HDPE) EN ISO 15494.Pipes insulated with 50mm PUF insulation covered with polysterene sheet and finsihed with chicken wire mesh and sand cement plaster and 2 layers of tarfelt sheething for burried pipes. Necessary hard neoperene rubber saddles type piping supports to be provided at regular intervals. The piping flange connection bolts and nuts should be of hot dipped galvanised.The pipes should be laid over RCC blocks. Plastic sticker type Water flow directions to be pasted on the supply and return chilled water pipes. Note: Only End flanges to be used for capping of pipes. Pipes to be covered with plastic cap on both ends to prevent entry of soil prior to installation. "Table E" of BS code for flange thickness to be adhered. (NON CSR) Pipe PE100 black SDR11 d280x28.6x5000mm
Supply, Installation, Testing & Commissioning of Butterfly Valves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum claddingwith extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 250 mm dia ( Gear Type )
Supply , Installation, Testing & Commissionig of Butterfly Valves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 200 mm dia ( Gear Type )
Supply, Installation, Testing & Commissioning ofButterfly Valves alves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 150 mm dia
Supply, Installation, Testing & Commissioning of Butterfly Valves alves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 100 mm dia
Supply, Installation, Testing & Commissioning of Butterfly Valves alves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 80 mm dia CPWD 16.7.1.5
Supply, Installation, Testing & Commissioning of Butterfly Valves alves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 65 mm dia
Supply, Installation, Testing & Commissioning of Butterfly Valves alves with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum claddingwith extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 50 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Ball Valve (NON CSR) 40 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Ball Valve (NON CSR) 32 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Ball Valve (NON CSR) 25 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified (NON CSR) 65 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified (NON CSR) 50 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified (NON CSR) 40 mm dia CPWD 16-7-4-8
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified (NON CSR) 32 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified (NON CSR) 25 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Non Return Valve ( Dual Plate ) (NON CSR) 200 mm dia (CPWD 16.7.3.1)
Supply of Manual Balancing Valve with pressure measuring ports as per specification (NON CSR) 200 mm dia
Supply of Manual Balancing Valve with pressure measuring ports as per specification (NON CSR) 150 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Supply of 2-WAY BALANCING VALVE built in measuring facility with C I body flanged construction with EPDM coated disc with long pitchof following sizes: (NON CSR) 65 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Supply of 2-WAY BALANCING VALVE built in measuring facility with C I body flanged construction with EPDM coated disc with long pitchof following sizes: (NON CSR) 50 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Supply of 2-WAY BALANCING VALVE built in measuring facility with C I body flanged construction with EPDM coated disc with long pitchof following sizes: (NON CSR 40 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Supply of 2-WAY BALANCING VALVE built in measuring facility with C I body flanged construction with EPDM coated disc with long pitchof following sizes: (NON CSR 32 mm dia
Supply, Installation, Testing & Commissioning of Chilled Water Circuit Valves & Gauges with insulation insulated with insulation of 20 mm thick closed cell nitrile rubber class O. Thermal Conductivity of insulation shall be less than 0.036 W/(mK) The insulation shall be covered with 1 mm thick polythene sheets double wrapped and held with PVC tape and then covered with 26 Gauge Aluminum cladding. Supply of 2-WAY BALANCING VALVE built in measuring facility with C I body flanged construction with EPDM coated disc with long pitchof following sizes: (NON CSR 25 mm dia
Supply installation of chilled water flow switch for water flow rate and for feedback of chilled water flow rate to the building management system (NON CSR)
Providing, fixing, testing & commissioning of resilient rubber lined double arch vibration eliminators suitable for raw water up to 45 deg. C temperature to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.(PN 16 rating) 200 mm dia
Pressure Gauges: Providing & fixing of Pressure gauges with syphon in brass with cr plating & niddle valve with nitrile rubber insulation tubing as per specification. (NON CSR)
SITC of Mercury in glass industrial thermometer in SS-304 casing with 0.5C least count, range 0-50 C. Brass oil filled thermowell of 1/2" size.
CONDENSOR WATER PIPING : Supply fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d450x45.4/5000mm
CONDENSOR WATER PIPING : Supply fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d280x28.6x5000mm
CONDENSOR WATER PIPING : Supply fixing in position PN16 rated (HDPE) EN ISO 15494.Pipes cut to required length and installed with all Electrofusion joints. The quote shall include necesseary supporting arrangement and Electrofusion fittings like elbow, 'T', reducer, flanges, GI bolts, flanges, gasket etc. including fixing the pipe with GI clamps at 1.00m spacing where ceiling-hung. This includes the cost of cutting, chases making holes and making good the same including testing of joints complete as per direction of Engineer in charge. (NON CSR) Pipe PE100 black SDR11 d225x22.7x5000mm
VALVES AND FITTINGS :Suppy, Installation of Valves WITHOUT insulation as per specifications. Butterfly Valves with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts without insulation. Valves should be rated for PN 16 - pressure rating. (NON CSR) 250 mm dia ( Gear Type )
Supply, installation of POT Strainers (NON CSR) 250 mm dia
Supplying, fixing, testing and commissioning of Non Return Valve with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. It shall be of wafer type preferably with flanged ends. It should be tested for required hydrostatic pressure for shell & seat as per OEM & shall be suitable for maximum working temperature of 80 degree C (approx.).250 mm dia
Supply installation of Manual Balancing Valve with pressure measuring ports as per specification (NON CSR) 250 mm dia
Supply installation of Anti Vibration Bellow (NON CSR) 250mm
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 16 TR : Dehudified CFM - 10400, FA CFM - 1000 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 4.5 TR : Dehudified CFM - 2300, FA CFM - 250 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 18 TR : Dehudified CFM - 6800, FA CFM - 650 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 22 TR : Dehudified CFM - 9200, FA CFM - 900 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 20 TR : Dehudified CFM - 8000, FA CFM - 900 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, suitable for Outdoor installation, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug type Blower, VFD compatible IE3 efficient Motors, Post EU-8 Filter, Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 100mm AHU : Floor Mounted - 8 TR : Dehudified CFM - 3200, FA CFM - 300 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and Commissioning of Air Handling Units, 50 mm Thick Double skin type, Ceiling Suspended, Pre EU-4 Filter, CHW Coil, UV Lamps, Plug/DIDW type Blower, VFD compatible Motors,Vibration Isolators, Opposed blade type Dampers at Supply / Return /Fresh / Relief Air, Fire rated flexible connections etc. ( Fan Motor should be Flame Proof and Fan to be Spark resistant construction.) AHU ESP: 40mm AHU : Ceiling Suspended -10TR : Dehudified CFM - 4000, FA CFM - 400 : Coil In 22.9 deg.C DB / 13.7 deg.C WB : Coil Out 8.4 deg.C DB / 7.9 deg.C WB
Supply, Installation, Testing and commissioning of Ceiling suspended 4 way Cassette units along with blower, motor, Pre filter, Chilled water coils, Inbuilt drain pump, drain tray and all other required accessories, with following capacities: 1.0 TR
Supply, Installation, Testing and commissioning of Ceiling suspended 4 way Cassette units along with blower, motor, Pre filter, Chilled water coils, Inbuilt drain pump, drain tray and all other required accessories, with following capacities: 1.5 TR
Supply, Installation, Testing and commissioning of Ceiling suspended 4 way Cassette units along with blower, motor, Pre filter, Chilled water coils, Inbuilt drain pump, drain tray and all other required accessories, with following capacities: 2 TR
Supply, Installation, Testing and commissioning of Ceiling suspended 4 way Cassette units along with blower, motor, Pre filter, Chilled water coils, Inbuilt drain pump, drain tray and all other required accessories, with following capacities: 2.5 TR
Supply, Installation, Testing and commissioning of Ceiling suspended 4 way Cassette units along with blower, motor, Pre filter, Chilled water coils, Inbuilt drain pump, drain tray and all other required accessories, with following capacities: 3 TR
Supply, Installation, Testing and commissioning of Treated Fresh Air units with required fan, filters, CHW coils and other accessories 4 TR, 800CFM, 25mm ESP
SITC of 100 mm dia disc valves for toilet exhaust
Supplying, installing, testing and commissioning of Drain Piping - 25 NB PVC hard pipe having minimum 3 mm wall thickness, insulated with with 9 mm thick cross linked Polyethylene tube sections laminated with aluminium foil, joints to be sealed with solvent based adhesive & 2" aluminium adhesive tape.
Supplying, installing, testing and commissioning of Drain Piping - 40 NB PVC hard pipe having minimum 3 mm wall thickness, insulated with with 9 mm thick cross linked Polyethylene tube sections laminated with aluminium foil, joints to be sealed with solvent based adhesive & 2" aluminium adhesive tape.
Supplying, installing, testing and commissioning of Drain Piping - 50 NB PVC hard pipe having minimum 3 mm wall thickness, insulated with with 9 mm thick cross linked Polyethylene tube sections laminated with aluminium foil, joints to be sealed with solvent based adhesive & 2" aluminium adhesive tape.
Supplying, installing, testing and commissioning of Drain Piping - 80 NB PVC hard pipe having minimum 3 mm wall thickness, insulated with with 9 mm thick cross linked Polyethylene tube sections laminated with aluminium foil, joints to be sealed with solvent based adhesive & 2" aluminium adhesive tape.
Supplying, installing, testing and commissioning of Drain Piping - 100 NB PVC hard pipe having minimum 3 mm wall thickness, insulated with with 9 mm thick cross linked Polyethylene tube sections laminated with aluminium foil, joints to be sealed with solvent based adhesive & 2" aluminium adhesive tape.
Supply, Installation, testing & commissioning of Galvanised Sheet (GI) Ducting Smacna Standards , turning vanes, with proper duct sealing etc with RTV duct Sealant, complete with supports ,Pressure tested with aqueous base smoke generator etc all as per specifications. 24 Guage
Supply, Installation, testing & commissioning of Galvanised Sheet (GI) Ducting Smacna Standards , turning vanes, with proper duct sealing etc with RTV duct Sealant, complete with supports ,Pressure tested with aqueous base smoke generator etc all as per specifications. 22 Guage
Supply, Installation, testing & commissioning of Galvanised Sheet (GI) Ducting Smacna Standards , turning vanes, with proper duct sealing etc with RTV duct Sealant, complete with supports ,Pressure tested with aqueous base smoke generator etc all as per specifications. 20 Guage
Supply, Installation, testing & commissioning of Galvanised Sheet (GI) Ducting Smacna Standards , turning vanes, with proper duct sealing etc with RTV duct Sealant, complete with supports ,Pressure tested with aqueous base smoke generator etc all as per specifications. 18 Guage
Supply, installation, testing and commissioning of opposed blade aluminium volume control dampers with black mat finish in supply air duct collars,Damper shall be with 16G GSS body and blades shall be with aluminium airfoil construction. complete with neoprene rubber gaskets,nuts, bolts, screws linkages, flanges etc. as per approved shop drawings and specifications.
Supply, Installation, Testing & Commissioning of Underdeck Roof insulation with 30 mm thick Nitrile Rubber Fixed to the underside of the slab. The slab surface shall be thoroughly cleaned, and adhesive applied to the slab surface and the insulation materisl, the insulation shall be fixed at 2ft x 2ft grid of self tapping screws. The Insulation shall be temporarily Held by means of adhesive, and reinforce the insulation with GI Lacing wire.
Supply & Installation of Acoustic Insulation of ducts with Open Cell Nitrile rubber Insulation Material with density 140-160 kg/m3 10 mm thick
Supply, Installation of Room Temperature/RH Sensor
Supply, Installation of Room Temp/RH Transmitter
SITC OF MAIN ELECTRICAL PANEL-AC PANEL The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE EB INCOMER-1 1) Incomer ACB with tripping mechanism in case of Fire. Outgoing Feeders: 2)Outgoing MCCB for 400 TR Watercooled Chiller ( 3W+1SB) 3)Outgoing MCCBs with VFD with Bypass Arrangement Starters forPrimary Pumps(3W+1SB) for 400 TR Chiller 4)Outgoing MCCB for secondary Pump control Panel 5)Outgoing MCCBs with VFD with Bypass Arrangement Starters forCooling Tower Fans (3 Working) 6)Outgoing MCCBs with VFD with Bypass Arrangement Starters for Condenser water Pumps as per pump specification (3W + 1S) 7) Spare MCCB 20% 415V , 1600A, 4P, ACB (EDO) of 36KA with MICRO PROCESSOR BASED RELEASES having O/C+E/F+S/C PROTECTIONS(WITH RS 485 COM.PORT) - 1No ON,OFF & TRIP Indication Lamps - 1 No 6A, 6KA, C CURVE MCB - 3 EACH. 1600/5A, CL-1, 10VA CT's with tape wound - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) MULTI FUNCTION METER (MFM) WITH RS 485 COM.PORT OUTGOING FEEDERS. 415V ,1600A, 4P, ACB(MDO) of 36KA with THERMAL BASED RELEASES having O/C+E/F+S/C PROTECTIONS (WITH RS 485 COM.PORT) -2 No's - for TWO bus bar of A Block 6A, 6KA, C CURVE MCB - 3 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,500A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -3 No's - AC CHILLER-1,2,3 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE 415V ,315A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -1 No's - COLLING TOWER 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE 415V ,100A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -6 No's - For AC CHILLAR PUMPS-1,2,3 6A, 6KA, C CURVE MCB - 2 EACH. LED Type R - Y - B Phase Indicating Lamps -3 No's (1 set) 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -2 No's - COOLING TOWER PUMPS 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE 415V ,315A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 1800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec. COOLING TOWER PUMPS 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE 415V ,315A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,200A, 4P,MCCB of 25KA with Microprocessor based having O/C+S/C PROTECTIONS -4 No's - Spare 415V ,32A, 4P,MCB, C-curve -4 No's - SPARE BUSBAR RATING 415V, 1800A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 36 KA for 1 Sec.
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 4.5 TR AHU, 1 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 4.5 TR AHU, 1.5 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 8 TR AHU, 1.5 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 16 TR AHU, 2 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 18 TR AHU, 2 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 20 TR AHU, 2.5 Kw Heater
Supply, Installation, testing and commissioning of Individual Electrical panel for each AHU The Panel should consist of Incomer MCCB, Contactors, DOL / Star - Delta starters, Relays, Push button ( On/Off/Reset ), Indicating Lamps ( Start / Stop / Trip ) etc.By- pass DOL starter to be included in case of VFD. Each panel should have VFD suitable to AHU motor rating with necessary instrument for cooling fan, inlet louvers & Filters for VFD , view panel, necessary relays & contactor, Potential free contacts for BMS application, interlocks etc. as per specification. Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application). For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contact for connections to the Building Automation System. Panel to monitor and control process parameters like Temperature,RH, Set points, Switchin ON and OFF of machines, feedback from sensors,Heater Thyristors, etc. Panel should have spare I/Os for future requirements. 22 TR AHU, 2.5 Kw Heater
Supply, Installation Testing & Commisioning of Local push button station in FRP contruction with Start push button and emergency mushroom type stop button.
Supply, Installation of fresh air dampers with bird screen
Supply, installation, testing & commisioning of magnehelic gauges across OT rooms & Critical areas AHU Filters for differential pressure. This includes SS box to mount these units & neessary tubing & other accessories to get these units functioning (-6 to +6 mm of WG). It should be complete in all respect.
Supply, installation of Differential pressure transmitters,integrated with blower VFD, Range 0-150mm
Supply, Installation of Differential pressure switch for EU - 4 filters 0-25mm
Supply, Installation of Differential pressure switch for EU - 8 filters 0-50mm
Providing & Fixing Pressure test points along with necessary fitting and accessories on CHW piping (Non CSR)
Providing & Fixing Temperature test points along with necessary fitting and accessories on CHW piipng (Non CSR)
Supply, Installation, Testing & Comissioning of Electrical tubular finned heaters with thyristor control, dully installed in ducts 1 kw
Supply, Installation, Testing & Comissioning of Electrical tubular finned heaters with thyristor control, dully installed in ducts 1.5 Kw
Supply, Installation, Testing & Comissioning of Electrical tubular finned heaters with thyristor control, dully installed in ducts 2 Kw
Supply, Installation, Testing & Comissioning of Electrical tubular finned heaters with thyristor control, dully installed in ducts 2.5 Kw
Supply, installation, testing and commissioning of duct mounted air purification system/ cell based on Photohydroionization cell with the capability to produce friendly oxidizers like Ionized Hydro Peroxides, Super Oxide Ions, Hydroxides Ions with quad metalic coating (Rohdium, silver, copper and titanimum) and duly enclosed by a poly casing tube that should prevent glass or mercury leakage into the conditioned/ served space. The honeycomb matrix shall not be accepted. The units should be designed after undertaking a load factor calculation for No. specific area where the equipment is to be installed. The load shall clearly state the number of units required vis-à-vis the wattage of the units for submital. The system shall be capable of reducing microbial bacteria, virus and spores , VoC’, odors and particulates matter. The equipment shall conform to UL 1598 CAN/CSA C222 EN60335-1, EN60335-2-65, EU standards, certifications shall be submitted along with the technical submital.OT 4500 CFM
Supply, fabrication, installation and testing the non-porous flexible connections constructed of fire resistance flexible, double canvas connection with resistoflex material as per the approved shop drawings.
Supplying, fixing testing commissioning of supply air diffusers (Flat face type) of powder coated & made from extruded aluminium section with aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with removable central core and concealed key operation for volume control damper.Complete as required.
Supplying, fixing testing commissioning of return air diffusers (Flat face type) of powder coated & made from extruded aluminium section without aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with removable central core..Complete as required.
Supply, installation, testing and commissioning of pressure relief damper to be installed in Lift Lobbies,Staircase & OT rooms with pre set pressure rating
Harsh Constructions Pvt Ltd
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid