Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12,640Accepted-AOC 357 A NEW CHOUKSEY NAGAR LAMBAKEDA BHOPAL M P | BHOPAL | MADHYA PRADESH | ₹12,640 Quoted ₹5.8 L | L1 | Accepted-AOC Work Order Issued |
| 2 | L2₹12,640+₹33,589.55 (5.76%)Accepted-AOC | ₹12,640+₹33,589.55 (5.76%) Quoted ₹6.2 L | L2 | Accepted-AOC 2nd Bid Rank So Ernest Money Return |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹6.3 L
EMD Value
₹12,640
Closing Date
11 Jan 2021, 5:00 pmClosed
P. E. M.P. P.H.I.D.C.L Indore Division No.2 Indor
G-13, 1st Floor, R.S.S. Nagar, M.I.G. Colony, Indore
External Electrification Work for RFSL Lab Rau Indore
2020_MPPHC_120878_1
11/2020-21
Open Tender
Electrical Works
Item Rate
60 days
Indore2
As Per Nit
2 documents required · 2 mandatory
₹2,000
₹12,640
18 Feb 2021
30 Dec 2020
13 Jan 2021
30 Dec 2020
11 Jan 2021
30 Dec 2020
Amount
Supplying and erection single length support for 33KV/11KV line complete with aligning and keeping it in truly vertical position, including digging pit of required size in all type of soil/rocks, filling with 1:3:6 cement concrete of0.50 mtr. dia. around the pole up to ground level includingmuffing of 0.45 mtr. dia. from ground level to 0.45 mtr. high as per specifications with 20 cm. thick base foundation in1:4:8 cement concrete as required, refilling the pit withboulder and soil as required, including painting of pole withbitumen paint below GL and two coats of red oxide and two coats of aluminium paint or synthetic enamel paintas directed etc as per specification complete The depth of burying of pole shall be 1/6th of the length of pole.H beam 152x152mm or 150x150mm 37.1 Kg./M. weight
A. 11M.long
B. 13 M.long
STAY SET :Supplying and erection of GI/MS stay set complete with stay rod, anchor plate of size 300x300x5mm, thimble,stay rod, anchor plate of size 300x300x5mm, thimble,stay clamp, turn buckle, bow tightener etc. with stay wire, strain insulator, nut bolts as per specifications including excavation in all type of soil / rocks and foundation in cement concrete 1:3:6 of required size and other necessary materials complete as required as per specifications. GI Stay Rod 20mm dia 1.8 m long with 7/4mm stay wire for HT line
Stay Rod 16mm
AAAC CONDUCTOR :Supplying and drawing ACSR/AAAC conductor of approved make with stringing making off complete with binding at existing insulator, jointing, jumpering, teeing off connecting etc. as required and clearing of obstacles (if any).
(A) AAAC Conductor 55 sqmm aluminum or Equivalent (Rabbit) (0.05sqinch)
(B) AAAC Conductor 80 sqmm aluminum or Equivalent (Raccoon) (0.10 sqinch)
Supplying and fixing of Angle/ channel/flat iron, V cross Arms reinforcement of RSJ jolt/ flat iron fittings for overhead lines and poles such as cross arms/ bracket/ clamps/ stiffness for poles etc. all required steel work including' cutting to size making proper shapes drilling scan welding etc. including nuts & bolts plan & spring wisher and other necessary material including one coat of red oxide and two coat of aluminum paint etc. as required. Chequre plate/ Tenstion plate atc.
Supplying and fixing Polymer type 11 K.V. pin insulator with G.I. pin of approved make on existing pole or bracket with necessary materials and hardware complete as required.
Supplying and fixing polymer type 11 K.V. disc (strain) insulator of approved make on existing pole or bracket with necessary materials and hardware complete as required.
Providing and fixing ear thing arrangement for H.T./L.T. poles with G.I. wire of 115 turn of 50mm dia. connection with bracket/ cross arm/ pole with 4mm dia. G.I. lead through 20 mm dia. G.!. Protection pipe of length from bottom of pole to 2 meter above ground level, packing of charcoal powder and salt as per specification including excavation of pit in all type of soil / rock etc. complete.
DANGER CAUTION PLATES :Providing and fixing enamelled danger caution plate/board on existing electric poles or wherever required of size 250x200 mm, made of 1.6mm thick mild steel sheet and vitreous enamelled white, with latest, figures and the conventional skull and cross-bones in signal red colour (as per IS-5-1978 with latest amendment) on the front side.The rear side of the plate shall also be enamelled. The corner of the plate shall be rounded off with required material such as screws, wires clamps, nut bolts etc. complete 33 KV/11 KV
Supplying and fixing 12x16 gauge barbed wire antidumping device (900 mm and3.5kg wire on pole) around the existing H.T. pole and sub station poles for safety measures as per IE rules including all staples and all other necessary materials complete as per mpseb specification.
Supplying, installing, connecting, testing and commissioning of approved make distribution transformer 4 star rating of accepted standard specification oil filled, core type aluminum wound out door type 11/ 0.4: KV step down with drain and filler . Value with locking arrangement two ear thing terminals, lifting arrangements and first filling of oil, conventional unit, including installation on existing D.P. structure.
(A) DTR 200 KVA BIS Certified EE Leval II
Providing and fixing outdoor type pole mounting weather, dust and vermin proof L.T. distribution box made of 14/16 gauge, M.S. sheet with clamping arrangements, lockable hinged door duly painted on all sides with red oxide antirust and corrosion treatment two coats of synthetic enamel paints of approved make and shade, consisting of following fittings. L.T. Distribution box suitable for 63/100/200.KVA.transformer (without TPN switches) with required Amp MCCB/Isolator on incoming side and PF HRC units on outgoing side.
(A) For 200 KVA Transformer (200 A. mccb of 9 HRC fuse of 160A. & 9 no J type al hook.) Complete as required as per MP SEB latest Specification.
Commissioning of D P structure over existing support with panting in an approved manner consisting of following :- (A) D. C. cross arm with clamp, nuts & bolts (100x50x6 mm only ) - 1 set (B) 11 KV D. O. fuse unit, lightings arrangement and AB swich mounting channel with nuts and bolts (75x 40x 6 mm channel) of require - 1 set (C) 11 KV Polymer AB swich as required - 1 set (D) Transformer mounting cross arms / channels with clamps nuts and bolts (100 x 50 x 6 mm channel ) - 1 set (E) 11KV Polymer Do fuse unit ( set of 3 no.) - 1 set (F) Transformer clamping set (50x50x6 mm angle ) with nuts and bolts etc. complete - 1 set (G) Transformer belting set (50x50x6 mm angle) with nuts and bolts etc. complete - 1 set (H) 11 kv polymer lightning arrestor ( 9 kv gapless type ( 5 kA ) for DTR ) ( set of 3 No.) - 1 set (I) supplying , fixing, testing and connecting of complete earling set of 7 No. as per MPMKVVC.Ltd. circular No DS CO M/EZ/ WS/1516/DT 17-03-2008 and approved dwring for transformer sub - station including all materials GI Strips, GI wires, Charcoal power salt excavation of pits in all types of soils/rocks etc. as required complete .( 1 set of 7 Nos.) -1 set (J) Distribution panel mounting channel and clamp with nuts & bolts etc. (75 x 40 x 6 mm channel ) 1 – set (K) Supplying , fixing, testing and Commissioning of DTR Meter LT. 3 phase 4 wire 3X240 volts I 3 A. LTCT operated 3 phase 4 wire 3x63, 5 volts , LB = 5 amps lmax 10 amp trivector meter glass of accuracy 0.5s DLMS complaint category a meter along with GSM ( GPRS compactable ) modems with box i/c all accessories and formalities as per MPPKVVCL as required. or 3P 4w - 5A LTCT class 5s DLMS compliant type c. rs - 232. Port box MRI LTCT 100/5A i/c meter box with TTB etc as required. (L) SF & T and HT tape for covering LT bushing i/c windings and blower hitting complete minimum 30 meter or as required.
D.P. Structure Complete as above (A to L)
Supplying ,laying ,testing, and commissioning of P V C insulated PVC heavy duty power cable confirming to lS 15541964 with upto date ammnandentment,1100 volt grade cable Of approved make in trench ,G I pipe Air (laying on pole) trench, i/c cost of excavation in any type of soil/rock etc. including connection through lugs by cramping method glands etc as required as per specification. (A) Supplying laying testing and commissioning.UnArmoured single core XLPE insulated aluminum conductor cable.
(b) 150 sq mm.
(b) 300 sq mm.
Supplying and erection of G.I. guarding of required size on existing HT/LT lines as required as per specifications. (A) Carpet/Cradle type 8 SWG (4 mm. dia.)
Supply & fixing fencing of chain link mesh 100 x 100 mm, 12 SWG GI wire for for D.P. structure electric sub-station including single post of angle iron size 50x50x5mm, 2.5 mt long should be provided up to 2.00 mt. apart or as required .The panel frame with required angle iron/ flat iron members /cross members including mesh welded in frame panel, shall be erected between the post. The angle iron post shall be erected in cement concrete 1:2:4 ( 20 mm graded metal ) foundation, including excavation of pit and refilling the same The fencing shall be provided with one entrance gate including locking arrangement as required as per specification. The height of fencing shall be 2 mt. above ground level. Fencing shall be painted with required shade. (A) Upper & lower frame of fencing will be of MS angle (25X25X4) mm size. (B) MS strip of (25X5) mm flat shall be used fro cross bracing of fencing
(C) Double Gate (2nos. 2.5’X5’) of MS angle (50X50X6)mm. bracing of 25X5 mm flat with mesh & locking arrangement.Complete as above ( A to C) – one job.
B L JAIN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .