Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.0 LAccepted-AOC | L1 | Accepted-AOC Lowest and reasonable bid | |
| 2 | L2₹18.0 L+₹2.3 L (14.8%)Rejected-Finance RCP GURUDWARA ROAD WARD NO 29 SURATGARH SRI GANGANAGAR 335804 | SURATGARH | SRI GANGANAGAR | RAJASTHAN | 335804 | L2 | Rejected-Finance other than lowest bid | |
| 3 | L3₹19.0 L+₹3.4 L (21.6%)Rejected-Finance | L3 | Rejected-Finance other than lowest bid |
Tender Value
Refer Docs
EMD Value
₹48,540
Closing Date
1 Apr 2025, 6:00 pmClosed
MAJ UDAY SHANKAR ROY
GE (AF) SURATGARH
SPECIAL REPAIR/UPGRADATION TO EXTERNAL ELECTRIC SUPPLY NETWORK INTERNAL WIRING AND CONNECTED E/M WORKS AT BLDG NO P-127 AND P-759 AT AT AF STN SURATGARH
2025_MES_700080_1
8223/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) SURATGARH
As per tender documents
10 documents required · 10 mandatory
₹500
GE (AF) SURATGARH
₹48,540
Yes
13 Apr 2025
4 Mar 2025
3 Apr 2025
4 Mar 2025
1 Apr 2025
18 Mar 2025
Amount
BOQ (SPECIAL REPAIR/UPGRADATION TO EXTERNAL ELECTRIC SUPPLY NETWORK, INTERNAL WIRING AND CONNECTED E/M WORKS AT BLDG NO P-127 AND P-759 AT AT AF STN SURATGARH.)
Taking down carefully unserviceable copper/aluminium point wiring (light, fan, socket or power) complete including fixture and fitting such as switches, ceiling rose lamp holder, regulators, sockets, light fittings, wooden terminal boxes, plastic laminated sheet cover, including taking down of DB’s, meter board any type, complete all as specified and directed.
Dismantling and taking down fluorescent tube light single/double/Bulk Head light of any wattage or size fitting for repair or replacement of burnt/worn out accessories or carrying to MES store(Accessories or components to be provided free for replacment by department), complete all as specified and as directed.
Taking down unserviceable DB's box including MCB's of any size/rating, complete all as specified and directed
M&L for point wiring with single core PVC insulated unsheathed 1100 volts grade FRLS cable of copper conductor multi stranded of size 1.5 sqmm (Nominal size) drawn through and including non metallic rigid PVC conduit medium grade, ISI marked not less then 20mm dia with all accessories like tee, straight joint, L bend etc concealed in wall , ceiling , floor etc, pressed MS Sunken boxes in wall of required size and colour for switches and sockets, 1.5 sqmm (Nominal size) PVC insulated (green insulation) copper conductor FRLS earth continuity cable drawn with wiring and connected to common earth dolly all as specified for one light point/fan point controlled by one SP switch including making good distrubed surface, complete all as specified and directed. Note:- Cost for MS Sunken Boxes, Hylum sheets are cutting, chieseling and cutting the wall/Ceiling for conduit fixing. The disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for point wiring shall be deemed to include the cost of making good.
All as per ser item No 4.00 here-in-before but for one bell point controlled by one bell push, complete all as specified and directed.
All as per ser item No 4.00 here-in-before but for one 5 pin socket out let, 6 amps on same board with the cable 1.5 sqmm size, complete all as specified and directed.
All as per ser item No 4.00 here-in-before but for one 5 pin socket out let, 6 amps on Independent board with the cable 1.5 sqmm size, complete all as specified and directed.
All as per ser item No 4.00 here-in-before but for one power point 6 pin 15 amps socket out let with 2.5 Sqmm stranded copper conductor FRLS cable PVC insulated including earth wire 2.5 sqmm copper conductor FRLS cable connected to earth dolly, complete all as specified and directed.
All asper item ser No 4.00 here in with but for Geyser point for sheet metal enclosure with 2.5 sqmm stranded copper conductor FRLS cable PVC insulated including earth wire 2.5 sqmm copper conductor FRLS cable connected to earth dolly, complete all as specified and directed.
M&L as in replacement submain wiring with two single core 4.0 sqmm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit of size not less than 25mm dia, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 4.0 sqmm multistranded copper conductor cable as continuous earth wire, complete all as sepcified and as directed. Note- (i) The two runs of single core cable and specified earth continuity conductor and PVC conduit with fitting acessories will be measured as one run. (ii) Cost of cutting, chasing and make good to existing surfaces are deemed to be including in the quoted rate by the contractor.
S&F switch piano flush button single pole one way 6 amp 240 volts, complete all as sepcified and as directed.
S&F bell push switch, single pole, one way flush type, 5 amps, 240 volts, complete all as specified and directed.
S&F socket outlet, flush type 2 in 1, 3 pin, 6 amps, 240 volts, complete all as specified and directed.
S & F Socket outlet 2 in 1, 3 pin, 6 and 16 amps, flush type, 240 volts, complete all as specified and directed.
S&F switch piano flush button single pole one way 16 amp 240 volts, complete all as specified and directed.
S&F of ceiling rose, surface type, 65mm x 50mm, 3 terminal, complete all as specified and directed.
S&F of bell multi music type, 230 volt AC, single pole, complete all as specified and directed.
S&F of lamp holder, PVC/polycarbonate type, insulated body with back plate of batten fitting, complete all as specified and directed.
S&F LED lights fitting 1x 20W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceilingrose, complete all as specified and directed.
S&F LED 2'x2'size backlit panel light 36 Watt environmental friendly, new generation, aesthetically designed, ultra modern recess mounting luminaries with high brightness SMD LEDs as light source 28 Watt with nominal system lumen output of 2800 lumens and a minimum system efficiancy of 100 lm/W. The luminarie shall have a rated system lifetime of 50,000 burning hours at L70. The luminarie should have a color temperature of 6500K and CRI > 70. The luminarie shall meet IP 66 rating and IK 09 rating with THD < 20% and PF >0.9 complete with all accessories, complete all as specified and directed.
S&F LED sleek mirror light fitting 10 watt provided with high output diffuser 2 feet, 230 Volts complete LED tube rod 10 watt with all accessories, pre wired and including connecting up with twin core copper conductor cable, complete all as specified and directed. Make : Havells/Bajaj/polycal/C&S/CG.
S&F LED bulkhead luminaire 10 watt, wall/surface mounted complete with LED lamp 10 watt, all accessories, pre-wired including providing flexible copper wire, twin core cable PVC insulated sheathed, complete all as specified and directed .
S&F of LED bulb 10 watt, complete all as specified and directed. Make - Crompton or equivalent to Polycab/Havells.
S&F in replacement of LED building security light 30 watt, 230V with lens and toughen glass top.The luminarie should have a color temperature of 6500K, IP 65 complete PF > 0.95 with all accessories and including connecting up to ceiling rose with 0.5 sqmm three core copper flexible conductor cable, One GI medium grade 20/25 mm dia bracket of total length 50 cm and fixed to wall with 2 Nos MS Clamp and fastener, complete all as specified and directed. Make- CG or equivalent in /Wipro/Havells/Bajaj
Taking down ceiling fans of any sweep and any size including cable connections and disconnecting of fan blades and removing the fan with blades and deposit to store yard for further hanging in its original position or any other position including as per direction of Engineer-in-Charge including it's fitting and fixtures after carrying out service includes cleaning, greasing and oiling, painting of fan with one coat of synthetic enamel spraying painting including marking of MES number with black paint after preparation of surface reassembling the fan etc including testing, complete all as specified and directed. Note : Any damage has to be made good by the contractor to make the item functional after testing.
Taking down wall mount fans of any sweep and any size including cable connections as it is in working condition for further hanging in its original position or any other position including as per direction of Engineer-in-Charge including it's fitting and fixtures after carrying out service includes cleaning, greasing and oiling, after preparation of surface reassembling the fan etc including testing, complete all as specified and directed. Note :- Any damage has to be made good by the contractor to make the item functional after testing.
Taking down exhaust fans of any sweep and any size including cable connections and removing the exhaust fan with blades deposit to store yard as it is in working condition for further fixing in its original position or any other position as per direction of Engineer-in-Charge including it's fitting and fixtures after carrying out service i.e. cleaning, greasing and oiling, painting of exhaust fan with one coat of synthetic enamel spraying painting including marking of MES number with black paint after preparation of surface reassembling the fan etc including testing, complete all as specified and directed.
S&F steel body Exhaust fan, 300 mm sweep, AC, single phase, with blades, and frame and louvers complete with all accessories and electric connection including making necessary holes in walls, complete all as specified and directed. (Make : Bajaj Model : Maxima DXL or equivelant of make as per List of Manufacturer's as approved)
S&F fan step regulator, 120W 230 volts, 50 HZ, AC supply, complete all as specified and directed.
M&L as in replacement submain wiring with two single core 6.0 sq mm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit of size not less than 25mm dia, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 6.0 sqmm multistranded copper conductor cable as continuous earth wire, complete all as specified and directed. Note- (i) The two runs of single core cable and specified earth continuity conductor and PVC conduit with fitting acessories will be measured as one run. (ii) Cost of cutting, chasing and make good to existing surfaces are deemed to be including in the quoted rate by the contractor.
M&L as in replacement submain wiring with two single core 2.5 sqmm PVC insulated FRLS multistranded copper conductor cable (for Bulding Security light) drawing into and including rigid non metallic PVC conduit of size not less than 25mm dia, medium grade ISI marked with all conduit fittings & fixing accessories and one single core 2.5 sqmm multistranded copper conductor cable as continuous earth wire, complete all as specified and directed. Note- (i) The two runs of single core cable and specified earth continuity conductor and PVC conduit with fitting acessories will be measured as one run. (ii) Cost of cutting, chasing and make good to existing surfaces are deemed to be including in the quoted rate by the contractor.
S&F sheet metal enclosures single pole and neutral earth enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amps, 240 volts, complete all as specified and directed.
S&F sheet metal vertical TPN double door DB 4 Way, 415 Volt, TPN with 200 amps rated bus bar and with neutral, earthing bar and din rail, complete all as specified and directed.
S&F in replacement of MCB distribution board, IP 43 protection, double door, metal enclosure, SPN, 230 Volts, 12 way with 200 amps rated bus bar and with neutral, earthing bar complete one, complete all as specified and directed.
S&F in replacement of MCB distribution board, IP 43 protection, double door, metal enclosure, SPN, 230 Volts, 8 way with 200 amps rated bus bar and with neutral, earthing bar complete one, complete all as specified and directed.
S&F in replacement of MCB distribution board, IP 43 protection, single door, metal enclosure, SPN, 230 Volts, 4 way with 200 amps rated bus bar and with neutral, earthing bar complete one, complete all as specified and directed. Make- Legrand or equivalent of Schneider/ABB Note-item No 34 to 38: cutting of the wall for DB fixing. The disturbed surfaces of wall for DB shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for DB fixing shall be deemed to include the cost of making good.
S&F MCCB four poles, 100 amps, breaking capacity 16 KA confirming to IS-8828, 415 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed.
S&F MCCB four poles, 63 amps, breaking capacity 16 KA confirming to IS-8828, 415 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed.
S&F in replacement of 240V, 10 KA 'C' curve miniature circuit breaker (MCB) of single poles and Netural current carrying capacity 32 to 63 AMP, complete with connection testing and commissioning, complete all as specified and directed.
S&F in replacement of 240V, 10 KA 'C' curve miniature circuit breaker (MCB) of single poles, current carrying capacity 6 to 32 AMP, Complete with connection testing and commissioning, complete all as specified and directed.
M&L for earthing complete for bldg with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected to galvanized earth wire 4.00mm dia by means of nuts, bolts, thimbles, check nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) with fair finish , internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of 22 gauge, 8 mesh per liner inch, 80mm thick PCC pit cover 320mm x 320mm of RCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) reinforced with XPM JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of earth wire protected by 15mm dia medium grade GI pipe and watering GI pipe shall be 20mm bore medium grade etc complete, all excavation and earth work & connecting the earthing to an earthing test point main switch board as specified and testing on completion, complete all as specified and directed.
M&L for cutting openning through brick wall 230mm thick built in cement motar suitable for exhaust fan 300mm seep including making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 type B-1 as required, complete all as specified and directed.
Taking down existing old unserviceable underground LT cable upto 70 Sqmm, 3.5 core, removal from trenches/ wall/pole and removed from site, complete all as specified and directed by Engineer-in-Charge.
Supply and laying LT UG armoured XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs of size 300 sqmm 3.5 core, complete all as specified and directed.
Supply and laying LT UG armoured XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs of size 70 sqmm 3.5 core, complete all as specified and directed.
Supply and laying LT UG XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs of size 50 sqmm 3.5 core, complete all as specified and directed.
Excavation in trenches in soft/loose soil not exc 1.5 mtr wide and not exc 1.5 m in depth for laying of cables and getting out of excavated material, complete all as specified and directed by Engineer-in-charge.
Returning filling in including spreading leveling, watering and well ramming in layer not exe. 25 cm in soft/ loose soil, complete all as specified and directed.
Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
M&L for brick of common burnt clay, sub class 'B' old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other, complete all as specified and directed.
M&L for river bed fine sand in trenches/ ducts 15 cm under cable and 8 cm above the cable for cushioning/protection to cable including spreding, levelling and get thick 18cm after hand punning, complete all as specified and directed. Note:- For the purpose of measurment planned thickness shall be taken
S&F for galvanised iron steel tubes, ISI marked light grade of size 50mm bore for cable protection on the wall under road under drains, complete all as specified and directed.
Material and labour for cutting of road, cutting chases pining in making good to facing where required to edges of landing road, hard standing, etc. and cutting chases for concealed water tubing making good exc. 20 cm but not exc. 60 cm width and digging of excavation 40 cm but not exc. 1 m depth in bituminous road / concrete surface and making good as existing surface by using 0.63 mm hard core as required including premixed high performance cold mix patching material ideal for instant as require high quality repairs to bituminous as well as concrete surface all as specified and as directed by Engr-in-Charge.
Supply and installation in replacement of LT Electric control panel, cubical type, for out door use, dust & vermin proof floor mounted made out of CRCA steel sheet of 3.15 mm thick and 2.00 mm thick other parts and angle iron legs of size 50mmx50mmx6mm having front and rear hinged doors with front openable shutters for each MCCB with spreader & extended rotary handle having hinges on one side and locating arrangements with screws type on other sides completely with fully enclosed bus bar chamber, having electrolytic high conductivity insulated bas bar made but of aluminium strips of rating 1000 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter, Ammeter and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete all as ncluding necessary PCC work of height 45 cm from the ground level and equipped with the following items. Note: Drawing and all materials viz MCB/MCCB/ instruments etc. for LT panel shall be got approved by GE before fabrication. Rate for MCCBs, MCBs, instruments is included in unit rate of items :-
Material & labour in replacement of earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of 25×4mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected up to main DB/LT Panel /Test point and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009(Part-I) complete all as specified and directed. Note : GI strip and protection pipes 40 mm GI light grade up to 7.5 metre is included in unit rate and beyond that the same will be measured separately.
Contract Amount shall be derived after deducting the amount of Schedule of Credit in General Summary on serial page No 17 of tender documents.
SRI SAI CONSTRUCTION COMPANY (BID ID -3270195)
DASHMESH ENTERPRISES (BID ID -3273629)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .