Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.9 CrAccepted-AOC NEAR SHIV MANDIR VILLAGE RAJPURA KHARKARI TEHSIL AND DISTRICT BHIWANI 127031 | BHIWANI | HARYANA | 127031 | ₹4.9 Cr Quoted ₹5.0 Cr | L1 | Accepted-AOC Awarded |
| 2 | L2₹5.3 Cr+₹32.7 L (6.58%)Rejected-AOC DHANI CHANDPUR BAWAL ROAD REWARI DHANI CHANDPUR BAWAL ROAD REWARI 123401 | REWARI | REWARI | HARYANA | 123401 | ₹5.3 Cr+₹32.7 L (6.58%) | L2 | Rejected-AOC Refunded |
Tender Value
₹3.6 Cr
EMD Value
₹7.3 L
Closing Date
6 Jan 2022, 5:00 pmClosed
Executive Engineer
Executive Engineer, PH.Engg. Division Mohindergarh
Design, Construction, Erection, Testing and Commissioning of Main Pumping Station of 2.00 MLD with Peak Factor 3.00 and Sewage Treatment Plant of 2.00 MLD based on SBR Technology, Disposal of sludge, laying of 350 mm RCC NP-3 Gravity Main for disposa
2021_HRY_200187_1
SE NNL No.3765 dt.20.07.2021 and 6397 dt.15.12.21
Open Tender
Civil Works
Works
365 days
Satnali, Mohindergarh
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,000
₹7.3 L
28 Feb 2022
17 Dec 2021
6 Jan 2022
17 Dec 2021
6 Jan 2022
17 Dec 2021
Amount
MAIN PUMPING STATION Design, construction, erection, testing and commissioning of MPS of 2.00 MLD with peak factor 3.00 including following components. The MPS broadly consists of Receiving Chamber, Coarse Screen Channel, Fixing of 2 No. Mechanical Coarse Screens, Raw Sewage Sump (Wet Well), Pipe Gallery (Dry Well), Flow Measurement devices, Installation of sewage pumps etc. including Operation & Maintenance for 12 months during defect liability period after trail run of 3 months and five years thereafter as under : (i)K-9 D.I. Pipe of suitable dia at MPS/STP including welding and screwing of Flanges. ISI Marked D.I. fittings, Sluice Valves, Non Return Valves as per requirement even for bye pass arrangement complete in all respects. (ii) 2 No. High Mast of 12 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 8 No. LED energy efficient lamps including fittings on each pole complete in all respects. (iii) Supply and installation of Main Gate of SS-304 Grade 12 ft. wide and 4 ft. wide wicket gate (total weight not less than 500 kg) at main entrance. i(v) The connecting sewer of same diameter and material of construction, laid at adequate depth between existing sewers to newly constructed structures is included in scope of work. (v) All the infrastructure except construction of staff quarter, boundary wall (except main gate) and pathways /roads required to be executed at site to make the MPS functional is included in the scope of work of lump sum job. Note: The size and quantities of all the above components will be as per approved Structural/Hydraulic/ Mechanical/ Electrical Design to be approved by Department before actual execution of work. All DI pipes within the campus at MPS will be provided by the Agency. For fixing pumping machinery it will be responsibility of contractor /agency to divert the flow of existing sewage which may include plugging of sewer and pumping if any. Note : All the pumping machinery, Panel Board Level sensor etc. shall be controlled by PLC & SCADA and shall be synchronized with PLC Panels at MPS & STP site through broad band internet facility.
Providing and Installing 6 No. CCTV Cameras (4 No. Cameras for STP and 2 No. Cameras for MPS) complete as per satisfaction of the Engineer –in- Charge along with 90 days recording (NVR), 32 inch LED Screen, 16 Channel NVR at STP Site and 8 Channel NVR at MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at both the sites i.e. MPS and STP shall be synchronized at STP site including Operation & Maintenance for 12 months during defect liability period after trial run of 3 months and O & M five years thereafter Cameras: At STP Site- 1 Nos PTZ speed dome 360 degree 50X zoom camera, 4 Nos. 12mm lens size, 2 Nos 3.6mm lens size. At MPS site- - 1 Nos PTZ speed dome 360 degree 50X zoom camera, 2 Nos. 12mm lens size, 2 Nos 3.6mm lens size. Make: - Sony/ Canon/Panasonic/ Samsung. CCTV Cameras should be installed and commissioned before starting execution of work.
Construction of HT / LT Panel room, Toilet, Lobby, Office Room, MCC Room, SCADA Room, Lab, including all Sanitary fittings etc. as per drawings at MPS & STP site covered area with RCC framed structure of brick work vitrified glazed tiles flooring, powder coated aluminum frame of size 100mm x 45mm of 10 gauge for chowkhat, 75mm x 45mm of 10 gauge for door frame, 45mm x 45mm of 10 gauge for window frame with 5mm thick glass AIS/Saint Gobain/ Modi Float. Covered Area (400 sqm) including Operation & Maintenance for 12 months during defect liability period after trail run of 3 months and five thereafter.
Bidder Name
Amount
Ravinder Sharma Contractor(GSTN-06APJPR8270D1ZO)
Rakesh Yadav Contractor(GSTN-NA)
Rakesh Yadav Contractor
Ravinder Sharma Contractor
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .