Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.4 CrAccepted-AOC UNIT VIII PLOT NO 7 BHOINAGAR BHUBANESHWAR ODISHA 751012 | KHORDHA | ODISHA | 751012 | ₹12.4 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹16.1 CrRejected-AOC | ₹16.1 Cr | L2 | Rejected-AOC L2 Bidder |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹19.6 Cr
EMD Value
₹39.3 L
Closing Date
26 Mar 2022, 4:00 pmClosed
Chief Engineer, Srinagar Smart City Ltd.
1st Floor Budshah Building Lal Chowk Srinagar.
Supply, Installation, Testing And Commissioning, including Operation And Maintenance for 5 Years Of Various Selected Buildings Under City Illumination Plan Of Srinagar
2022_SSC_164297_1
E-N.I.T NO. 31-SSCL OF 03-2022 DT. 12-03-2022
Open Tender
Electrical and Maintenance Works
180 days
Srinagar
Refer to Standard Bid Document
4 documents required · 4 mandatory
₹20,000
Yes
CEO Srinagar Smart City Ltd
₹39.3 L
Yes
Office of Chief Engineer, Srinagar Smart City Ltd.
21 Nov 2022
14 Mar 2022
28 Mar 2022
14 Mar 2022
26 Mar 2022
14 Mar 2022
19 Mar 2022
Amount
Khanqah-e-Moula
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1A).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10°x50° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 500 lumen (Tolerance ±15%), 10°x60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 500 lumen (Tolerance ±15%), 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10°x25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 750 lumen (Tolerance ±15%), 10x25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 25 watts, System lumen output should not be less than 1500 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 500 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 500 lumen (Tolerance ±15%), 10x25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 30° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10° x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply and erection of 6000mm high decorative pole made out MS Pipe Ø76.1mm confirming to YSt 210 and facilitating the luminaire mounting at the top. The pole shall be surface mounted on a concrete foundation. The base plate of the of the pole shall be E 250 grade MS 200 mm x 200mm, 12mm thick confirming to IS2062:2011 shall be facilitated with elongated slots to suit the 300mm, J-type, M16 bolts, Grade 4.6 that shall be provided with suitable nuts and plain washers. The structurally sound pole emerging out of the base plate shall be architecturally designed with a decorative cast aluminium causeway base cover minimum Ø330mm x 500mm (H), above which the leaf decoration cast aluminium structure Ø 150mm is aesthetically positioned. Mounted flower pot. The grade of pressure diecast material shall be ADC12. A GDC embellishment is provided at appropriate height enhancing the decorative outlook of the pole. The grade of gravity die cast material shall be LM6. The Pole welding shall be done with certified welders using a V groove technique with a high end MIG welding process. A base compartment with a die cast aluminium door contoured to the poles's shape housing the gear tray, prewired with 2 way connector. The surface preparation of the pole & components shall be done by shot blasting which is environmentally safe eliminating the chemical and acid use and ensuring the thoroughremoval of impuritise like, rust, oxides and other unwanted particles from the suface for high standard coating. The surface finish of the pole shall be Zinch rich primer coat & pure polyester powder coating or epoxy zinc phosphate primer followed by the environmentally stable Polyurethane based paint. Pole must be connected to earthing. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated posttop of system lumen output should not be less than 3000 lumen (Tolerance ±15%), the power consumption should not be more than 60 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80 (All the technical parameters of luminaire need approval from lighting designer)
Dastgeer Sahib
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1B).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumens (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 30° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerence ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerence ±15%), The power consumption should not be more than 18 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10x60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Naqashband Sahib
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1B).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 750 lumen (Tolerance ±15%), 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor mounted IP66, trick washer light fixture, mounting brackets/clamps (as per application). System lumen output should not be less than 400 lumen (Tolerance ±15%), The power consumption should not be more than 6 watts, wall washer optics, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Bilal Mosque
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerence ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerence ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerence ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor mounted IP66, round up light fixture, mounting brackets/clamps (as per application). The power consumption should not be more than 8 watts, System lumen output should not be less than 400 lumen (Tolerance ±15%), 10° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be antiue brass with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. Fixture size should not be more than dia-80mm and height 70mm. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor mounted IP66, trick washer light fixture, mounting brackets/clamps (as per application). System lumen output should not be less than 400 lumen (Tolerance ±15%), The power consumption should not be more than 6 watts, wall washer optics, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Emporium Building
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerence ±15%), The power consumption should not be more than 15 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumen (Tolerance ±15%), The power consumption should not be more than 10 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 1000 lumen (Tolerence ±15%), 15° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 10 watts, System lumen output should not be less than 300 lumen (Tolerance ±15%), 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumen (Tolerance ±15%), The power consumption should not be more than 10 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumen (Tolerence ±15%), The power consumption should not be more than 10 watts, 30° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerence ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated decorative hanging light of system lumen output should not be less than 1000 lumen (Tolerance ±15%), the power consumption should not be more than 25 watts, CCT 3000K. As per detailed drawing no. LUC/SN/HL-01 (All the technical parameters of luminaire need approval from lighting designer)
Srinagar Smart City Office
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 10 watts, 15° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerence ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 25 watts, System lumen output should not be less than 2000 lumen (Tolerence ±15%), 15° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware, equiepment/controller, software etc. for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Shareef Rehmatan (Shia) Mosque
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumens (Tolerance ±15%), The power consumption should not be more than 10 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
J & K Bank
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural wall mounted IP66, square/round down light fixtre. System lumen output should not be less than 600 lumen (Tolerance ±15%), The power consumption should not be more than 10 watts, 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be integrated non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Budshah Tomb
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 30° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
SPS Library
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 600 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 600 lumen per meter (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 24 watts, 10° x 50° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 24 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Tourist Reception Center
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 600 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural pole mounted IP66, gobo projector mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 50 watts, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Asia Craft Buildings
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 25 watts, System lumen output should not be less than 1500 lumen (Tolerance ±15%), 10 x 50° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 500 lumen (Tolerance ±15%), The power consumption should not be more than 10 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Red Buildings opposite to pratap park
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
SPS Museum
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Temple near Shergarhi-Budshah Bridge
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10°x25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Rama koul Temple near Ali kadal
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1500 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10°x25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Shergarhi from jhelum river side
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10° x 60° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 25 watts, 10° x 25° beam angle with tolerance of ±15%, CCT 4000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 600 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Raghunath Temple near fateh kadal
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10°x25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 10° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 15 watts, System lumen output should not be less than 750 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply and erection of 6 meter high decorative pole of made in which pole pedstal should made of cast aluminium and pole should be GI in ribbed form. Thickness of the GI pole should be 3.2mm and aluminium pedstal thickness 6.5mm. Aluminum casted embalishments. Complete pole should be painted in PU paint and dark grey color. Base plate 300mm x 300mm x 10mm suitable to mount the pole on a concrete foundation. Pole must be connected to earthing.
Supply installation testing & commissioning of exterior rated posttop of system lumen output should not be less than 3000 lumen (Tolerance ±15%), the power consumption should not be more than 60 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80 (All the technical parameters of luminaire need approval from lighting designer)
SBI Bank
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10°x25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10°x60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10°x25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 750 lumen (Tolerance ±15%), The power consumption should not be more than 15 watts, 10°x25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Guruduwara-Singh Sabha near Amira kadal
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 1000 lumen (Tolerance ±15%), The power consumption should not be more than 18 watts, 10°x60° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 12 watts, System lumen output should not be less than 600 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 300mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 12 watts, System lumen output should not be less than 600 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Guruduwara-Rainawari Chhatti patshahi
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T1C).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 600 x H 600 x D 300 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete
Supplying, erecting & marking FPMCB 40A to 63A B series
Supplying, erecting & marking TPN MCB 6A to 32A, B series in
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Termination Junction box : Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Empty encloser for led driver : Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 16 sq. mm. copper conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Supplying, erecting & terminating XLPE armoured cable 1100 V. 2 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
GI Conduit : Supplying & erecting G.I. pipe ‘A’ class 40 mm dia. Erected for enclosing XLPE armoured cable on wall/pole
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 10° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 30° beam angle with tolerance of ±15%, CCT 2200K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 4000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 12 watts, System lumen output should not be less than 600 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 4000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 1000mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 18 watts, System lumen output should not be less than 1000 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, 500mm long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 12 watts, System lumen output should not be less than 600 lumen (Tolerance ±15%), 10 x 25° beam angle with tolerance of ±15%, CCT 2700K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be remote non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
Supply and erection of 6000mm high decorative pole made out MS Pipe Ø76.1mm confirming to YSt 210 and facilitating the luminaire mounting at the top. The pole shall be surface mounted on a concrete foundation. The base plate of the of the pole shall be E 250 grade MS 200 mm x 200mm, 12mm thick confirming to IS2062:2011 shall be facilitated with elongated slots to suit the 300mm, J-type, M16 bolts, Grade 4.6 that shall be provided with suitable nuts and plain washers. The structurally sound pole emerging out of the base plate shall be architecturally designed with a decorative cast aluminium causeway base cover minimum Ø330mm x 500mm (H), above which the leaf decoration cast aluminium structure Ø 150mm is aesthetically positioned. Mounted flower pot. The grade of pressure diecast material shall be ADC12. A GDC embellishment is provided at appropriate height enhancing the decorative outlook of the pole. The grade of gravity die cast material shall be LM6. The Pole welding shall be done with certified welders using a V groove technique with a high end MIG welding process. A base compartment with a die cast aluminium door contoured to the poles's shape housing the gear tray, prewired with 2 way connector. The surface preparation of the pole & components shall be done by shot blasting which is environmentally safe eliminating the chemical and acid use and ensuring the thoroughremoval of impuritise like, rust, oxides and other unwanted particles from the suface for high standard coating. The surface finish of the pole shall be Zinch rich primer coat & pure polyester powder coating or epoxy zinc phosphate primer followed by the environmentally stable Polyurethane based paint. Pole must be connected to earthing. (All the technical parameters of luminaire need approval from lighting designer)
Supply installation testing & commissioning of exterior rated posttop of system lumen output should not be less than 3000 lumen (Tolerance ±15%), the power consumption should not be more than 60 watts, 360° symmetrical optics, CCT 3000K. Single piece with circular shaped plant made of die cast aluminum using pressure die-casting process,with a decorative pineapple which is also made of die cast aluminum using pressure die-casting process, fixed on the top.Auxiliary and optical compartment can be accessed by tilting the top frame. Bottom frame in single piece, made of die cast aluminum using pressure die-casting process witha three curved uprights decorated which is also made of die cast aluminum using pressure die-casting process, fixed at the bottom with a hole (28 mm) for fixing to support. Frosted Screen made of polymethylmethacrylate (PMMA) moulded in a single piece using Injection moulding process. Screen's Impact resistance: IK06. Pure polyester powder coating in the same color as of the pole/as per the lighting consultant. Optical Compartment IP Rating - IP 66. Height – 700mm, Dia. - 470mm, Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 4kv(an additional surge protection device of 10kV also provided in-built the fixture). Modular (2 X 2) refractive lens in PMMA with Type-II/III/IV photometric distribution options. protection screen in extra-clear tempered glass with impact resistance IK 08.LM80 (All the technical parameters of luminaire need approval from lighting designer)
500 Chinar Trees
Exterior LT Panel : Supply installation, testing & commissioning of LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screw less glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. (as per the SLD attached no. LUC/S.S.C/SLD/T2B).
Cubical : Supplying and erecting IP66 Box opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts, Built in dimensions W 300 x H 300 x D 150 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying, erecting & marking SPN MCB 6A to 32A, B series (for lighting)
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral
Supplying & erecting single phase 2 wire system having in built astronomical adjustable programmable timer with minimum 5 years battery backup, 2 pole contactor upto 60 A, with maintenance mode to switch ON
Cable : Supplying, erecting & terminating XLPE armoured cable 1100 V. 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe
Earthing System : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete.
Exterior Luminaires : Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot and adjustable mounting brackets/clamps (as per application). System lumen output should not be less than 2000 lumen (Tolerance ±15%), The power consumption should not be more than 30 watts, 30° beam angle with tolerance of ±15%, CCT 3000K. The housing material should be extruded aluminum, powder-coated finish, luminaire body color should be similar to the facade color surface where luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, SDCM≤4. The driver should be integrated non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP66 connectors are inclusive. Minimum IK06. Operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS certified. This includes all the required hardware for successful operation of the luminaire. (All the technical parameters of luminaire need approval from lighting designer)
M M Brothers