Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.2 CrAccepted-AOC | ₹1.2 Cr | 1 | Accepted-AOC Being lowest and reasonable rates |
| 2 | 2₹1.3 Cr+₹3.3 L (2.72%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹1.3 Cr+₹3.3 L (2.72%) | 2 | Rejected-Finance Being not lowest tenderer |
| 3 | 3₹1.3 Cr+₹6.5 L (5.27%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | ₹1.3 Cr+₹6.5 L (5.27%) | 3 | Rejected-Finance Being not lowest tenderer |
| 4 | 4₹1.3 Cr+₹6.5 L (5.32%)Rejected-Finance 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.3 Cr+₹6.5 L (5.32%) | 4 | Rejected-Finance Being not lowest tenderer |
| 5 | 5₹1.3 Cr+₹7.6 L (6.22%)Rejected-Finance | ₹1.3 Cr+₹7.6 L (6.22%) | 5 | Rejected-Finance Being not lowest tenderer |
Tender Value
Refer Docs
EMD Value
₹2.2 L
Closing Date
13 Feb 2021, 6:00 pmClosed
CWE Utilities
HQ CWE (U) Delhi Cantt - 10
AUGMENTATION OF 11 KV SUBSTATIONS, 11 KV/0.415 KV DISTRIBUTION NETWORK, PROVN OF RMUS AND OUTDOOR VCBS FOR 4/6/8 POLE STRUCTURE AND SCADA SYSTEM FOR 11 KV NETWORK AT DELHI CANTT-10
2021_MES_409911_1
89035/CWE(U)/D-36/2020-21/E8
Open Tender
Civil Works
Item Rate
120 days
GE U Electric Supply
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,000
Yes
₹2.2 L
Yes
30 Mar 2021
19 Jan 2021
15 Feb 2021
19 Jan 2021
13 Feb 2021
8 Feb 2021
Amount
Dismantling of HT concrete pole including earth work and breaking of PCC etc complete and depositing in low line area complete all as specified and directed
Dismantling of cross Arms of MS channel or Angle iron or flat iron sections from pole including earthing complete all as specified and directed.
Dismantling air break gang operated switches vertical/horizontal mounted on 4/6 Pole structures including operating mechanism complete all as specified and directed..
Dismantling of insulators of any type and size mounted on 4/6 Pole structures complete all as specified and directed.
Dismantling carefully Old unserviceble ACSR conductor jumper from 4/6/8 pole structhure complete all as specified and directed.
Disconecting Electric supply, taking down the HT cables carefuly of any size from HT PCC pole and reconected to RMU complete all as specified and directed. Note:- Necessary excavation, earth work, sand , PCC covers, cable jointing Kit etc should be measured and paid separately under relevant items of this BOQ.
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and five outgoing (7 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incommer and 05 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically welded minimum 2.5 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site complete all as specified & as directed. ( Location :- Subraminiam Line, Naraina Pump house and Kabul Line area - 02 Nos)
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch >>s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
(B) (i) Out going VCBs - 05 Nos consisting of following - function unit consist of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 630 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. live cable LED indicators thrugh capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also current also relay shall record minimum 5 fault records with time stamping - 01 Alaram trip indication 6 window annunciator for transformer faults Mechanical ON/OFF/EARTH indication -01.
(ii) Auxliary contacts on load switch are 1 No+2NC & Auxiliary on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01. Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) Auxliary relay for transformer protection -05 Nos.
(C) Additional equipment deliverd separately or mounted seperatly, Bus connected with battery charger and inbuilt battries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 va, 0.5 class for measurement with volts meter(ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and battries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintance manual - o1, installation and commissioning manual - 01, cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth as per OEM Specification. NOTE :- (a)The above module consisting of two Load break Switch and 05 VCBs shall be alligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete. (b) Cost of provn of plinth for RMU as per OEM drawing is deemed to be included in the cost.
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and three outgoing (5 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incommer and 03 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically welded minimum 2.5 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site complete all as specified & as directed. (Location :- ME Line, Dental officers Mess, 505 ABW and 17 Sikh-li unit line)
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch >>s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
(B) (i) Out going VCBs - 03 Nos consisting of following - function unit consist of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 630 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. live cable LED indicators thrugh capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also current also relay shall record minimum 5 fault records with time stamping - 01 Alaram trip indication 6 window annunciator for transformer faults Mechanical ON/OFF/EARTH indication -01.
(ii) Auxliary contacts on load switch are 1 No+2NC & Auxiliary on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01. Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) Auxliary relay for transformer protection -03 Nos.
(C) Additional equipment deliverd separately or mounted seperatly, Bus connected with battery charger and inbuilt battries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 va, 0.5 class for measurement with volts meter(ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and battries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintance manual - o1, installation and commissioning manual - 01, cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth as per OEM Specification. NOTE :- (a)The above module consisting of two Load break Switch and 03 VCBs shall be alligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete. (b) Cost of provn of plinth for RMU as per OEM drawing is deemed to be included in the cost.
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and four outgoing (6 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incommer and 04 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically welded minimum 2.5 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site complete all as specified & as directed. (Location :- COD depot area)
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch >>s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
(B) (i) Out going VCBs - 04 Nos consisting of following - function unit consist of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 630 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. live cable LED indicators thrugh capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also current also relay shall record minimum 5 fault records with time stamping - 01 Alaram trip indication 6 window annunciator for transformer faults Mechanical ON/OFF/EARTH indication -01.
(ii) Auxliary contacts on load switch are 1 No+2NC & Auxiliary on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01. Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) Auxliary relay for transformer protection -04 Nos.
(C) Additional equipment deliverd separately or mounted seperatly, Bus connected with battery charger and inbuilt battries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 va, 0.5 class for measurement with volts meter(ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and battries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintance manual - o1, installation and commissioning manual - 01, cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth as per OEM Specification. NOTE :- (a)The above module consisting of two Load break Switch and 04 VCBs shall be alligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete. (b) Cost of provn of plinth for RMU as per OEM drawing is deemed to be included in the cost.
Supplying, laying and testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches /under road/ ducts / encased in GI pipe / fixed to pole etc complete all as specified and directed of following sizes:-
95 Sqmm 3 core
120 Sqmm 3 core
185 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core
120 to 185 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core
120 to 185 Sqmm 3 core
Excavation in trenches not exceeding 1.5 meters wide & not exceeding 1.5 meters in depth for laying of cable and getting out in soft/loose soil including trimming the sides forming bottom surfaces to required level complete all as specified and as directed.
Supply and spreading fine river sand in trenches for cushioning of under ground cable complete all as specified and as directed. Note : Measurement shall be taken after punning down.
Supply and laying factory made non-reinforced precast concrete cable cover class HV type-I with size 300mmx180mmx40mm all as specified and directed.
Returning, filling in including spreading leveling, watering and well ramming in layers not exceeding 25 cms thick in each layer of soil complete all as specified and directed.
Removing excavated material to a distance n.exc 50 meters and depositing where directed at a level not exceeding 1.5 mtrs above the starting point all as specified and directed.
Horizontal boring holes upto 2 m deep in soil for laying HDPE pipes and getting out and disposal of spoil to a distance of n exc. 50 m, max 150 mm bore complete all as specified and directed.. Note:- The HDPE Pipes should be measured and paid separately under respective items of this BOQ.
M/L for HDPE pipe,of size 140 mm dia suitable for 0.6 MPA working pressurewith all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (Earth pit not less than 3.5 meter deep below ground level) with top edge of plate not less than 2.5 meter below normal ground level, connected with and including galvanised iron earth strip 32 X 6mm by means of nuts, bolts, check nuts and washers of galvanised iron or steel and provisions of charcoal dust and common salt packed all around the earth plate and testing on completion complete all as specified, directed and shown in Electrical Plate number 3 of MES SSR Part-I NOTES : The quoted rates shall be deemed to include the cost of (a) Excavation and earth work in any type of Soil. (b) PCC pit in cement concrete 1:3:6 mix, type B-1, Pre cast RCC cover with suitable handle, 40 mm thick in RCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/Sq metre. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc (d) 40 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead (e)Requisite quantity of common salt and charcoal in alternate layers completely packed as directed (f) Testing of earthing on completion.
S&F 4 mm dia MS wire 75x75mm mesh, made upto into mattress or cages appx 2.0 mtr height and fixed with flate iron/angle by welding in position and directed including complete all as specified and directed. Note:- MS angle, MS flat, Nuts, Bolts and washer will be measured and paid separately.
M & L for two coats of synthetic enamel paint of silver colour on steel surfaces over a coat of red oxide primer including preparation of surfaces complete all as specified.
M&L for MS work of angles for post and struts of fencing around transformer plinth etc drilling holes, flate iron fillet for securing wire mess by welding to angle iron frame and framed work as in door/ gate of angle and wire mess. Door to be fixed by 03 Nos 100mm long hinges and one sliding door bolt of 300mm long for locking arrangement complete all as specified including dismantling of old unserviciable MS work complete all as specified and directed.
Material and labour for cement concrete type D-2, 1:4:8 (using 40 mm graded crushed stone aggregate) for sub floors, sub-bases, floors, foundation and paving etc complete all as specified and directed .
M&L Brick work with sub-class 'B' bricks, straight or curved on plane exc 6 m mean radius, built in cement mortar 1:6 complete as specified and directed including dismantling of old unservicable brick work complete all as specified and directed.
M&L Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cement complete all as specified and directed.
Material and labour for cement concrete type C-2, 1:3:6 (using 40 mm graded crushed stone aggregate) in foundation filling and mass in foundation,including pilasters, buttresses columns,pillars,boundary pillars and posts etc complete all as specified and directed .
Material and labour for coarse aggregate filling using stone gravels, rounded, of size n exc. 43 mm suitable to site, in the area covered by four pole structures complete all as specified and directed.
Supply installation & commissioning of 110V/30A SCR controlled Float Cum Boost Battery Charger unit including battery bank comprising 2 Volts/100 AH Cells - 55 Nos sealed maintenance free battery. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion . During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DC digital ammeter , DC digital voltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness ,
louvers for ventilation , gland plate will be provided for cable entry from bottom . The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:- Location :- ME line Sub Stn, AOC Sub Stn, BOR Sub Stn. (a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1 (c) On load input power factor - > 0.8 (d) On load unit watt efficiencies-> 80% (e) No load losses of complete charge-< 10% (f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell . (j) Float charging -2.15 V/Cell (k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode. (l) Reverse polarity -No damage will caused . A visual indication for reverse polarity will appear with an audio alarm. (m) Short circuit-MCB protecton provided. Make of battery charger. Statcon/Sinetrac/Amar Raja Make of batteries. Exide/Amaron
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .