| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.4 CrAccepted-AOC 46 LOWER GROUND FLOOR CHARMWOOD PLAZA EROS GARDEN FARIDABAD HARYANA 121009 | FARIDABAD | FARIDABAD | HARYANA | 121009 | ₹1.4 Cr | 1 | Accepted-AOC Contract awarded to M/s Ace marketing Pvt Ltd after negotiation |
| 2 | 2₹1.4 Cr+₹76,400 (0.55%)Rejected-Finance 143 INDUSTRIAL AREA PHASE 2 PANCHKULA HARYANA | PANCHKULA | PANCHKULA | HARYANA | ₹1.4 Cr+₹76,400 (0.55%) | 2 | Rejected-Finance L2 |
| 3 | 3₹1.5 Cr+₹10.5 L (7.53%)Rejected-Finance | ₹1.5 Cr+₹10.5 L (7.53%) | 3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹2.7 L
Closing Date
12 Apr 2023, 2:00 pmClosed
Executive Engineer
Water Services (Mech) Division, Karnal
Supply, Erection and commissioning of V.T. Pumps, Motors, and starter panel etc. (replacement of old VT pumps/Motors and additional VT pumps) at various Permanent pump houses under W.S. Mech. Sub Division Jind
2023_HRY_268414_1
1068/26A dated 16.03.2023
Open Tender
Miscellaneous Goods
Tender
120 days
Karnal
Please refer Tender documents.
2 documents required · 2 mandatory
₹15,000
₹2.7 L
22 Sept 2023
24 Mar 2023
12 Apr 2023
24 Mar 2023
12 Apr 2023
24 Mar 2023
Amount
Supply, Erection and commissioning of Axial/ mixed flow, water lubricated, vertical turbine pump, having discharge capacity of 20 Cs with lift approx 15 ft. with y-body along with Bend with operating speed of 960 RPM including 12 MTR. (6+6) with M.S. Delivery pipes with both sides bends with support of suitable thickness with bituminous based paint including both sides flanges welded, H.T. Nut and bolt complete and complete in all respects as per technical specification approved by I&WRD Haryana. 1. Beri-khera pump house at RD 111000/R On Hansi Br. (01 no.)
Supply, Erection and commissioning of 100 HP Fully automatic starter with ATS, 400 Ampere MCCB, Contactors, microcontroller based protection relay CTs with all allied accessories and with suitable capacitor bank, bus bar, push button, relay, button ,thimble meters lugs etc.in all respect with a MS Channel (1 feet up from floor) with latest amendment suitable for 20 cus VT pump all allied accessories with compatible cable upto motor for V.T. Pump of 20 cus capacity as per specification approved by Department. 1. Beri-khera pump house at RD 111000/R On Hansi Br. (01 no.)
Supply, Erection and commissioning of 100 HP, 3-phase, 415 VOLT (+10%) 50HZ (+3%), 960 RPM, 6-Pole IE1 TEFC continuous duty vertical flanged mounted solid shaft squirrel cage induction motor as per technical specification approved by I & WR Department, Haryana. 1. Beri-khera pump house at RD 111000/R On Hansi Br. (01 no.)
Supply, Erection and commissioning of M.S. Delivery pipe 445.2 mm inner dia. (in approximate 6-mtr. Length each pipe) and each pipe end welded with flanges made of thickness 8 mm MS plate as per approved specification and made ( including HT Nut & bolt , Rubber sheet and other fitment accessories required along with required. 1. Beri-khera pump house at RD 111000/R On Hansi Br. (18 Mtr.)
Supply, Erection and commissioning of ṂCCB of Capacity of 200 Amp. With 50 HP Fully automatic star delta starter with ATS including all accessories having 01 no. incomer of MCCB 200 Amp. And MCCB/MCB of sufficient capacity of light load, star, delta and main contactors of sufficient capacity, indicators, relay, voltmeter, power factor meter, push button, relay, button, thimble meters lugs etc. in all respect with a Mms Channel (1 feet up from floor) with latest amendment suitable for 10 cus VT pump all allied accessories with compatible cable upto motor for V.T. Pump of 10 cus capacity as per specification approved by Department. 1. Ritoli pump house at RD 124000/R on Hansi Br. (01 no.) 2. Lajwana pump house at RD 7000/R on Bhiwani Br. (01 no.) 3. Meherda pump house at RD 0/R on Bhiwani Br. (01 no.)
Supply, Erection and commissioning of Axial/ mixed flow, water lubricated, vertical turbine pump, Having discharge capacity of 10 cus with lift approx 15 ft. with Y-body along with Bend with operating at speed of 1440 RPM including bends with support 8mm thickness with bituminous based paint including both sides flanges welded, H.T. Nut and bolt complete and complete in all respects as per technical specification approved by I & WRD Haryana. 1. Ritoli pump house at RD 124000/R on Hansi Br. (01 no.) 2. Lajwana pump house at RD 7000/R on Bhiwani Br. (01 no.) 3. Meherda pump house at RD 0/R on Bhiwani Br. (01 no.)
Supply, Erection and commissioning of 50 HP, 415 VOLT(+ 10%) 50HZ (+3%), 1440 RPM, 4 Pole IE1 TEFC continuous duty vertical flanged mounted solid shaft squirrel cage induction motor as per technical specification approved by I & WR Department, Haryana 1. Ritoli pump house at RD 124000/R on Hansi Br. (01 no.) 2. Lajwana pump house at RD 7000/R on Bhiwani Br. (01 no.) 3. Meherda pump house at RD 0/R on Bhiwani Br. (01 no.) 4. Siwana mall/R pump house RD 80700 ON Bhambhewa Drain. (01 no.) 5. Beri-khera pump house at RD 111000/R On Hansi Br. (01 no.)
Supply, Erection and commissioning of 30 HP, 415 VOLT(+10%) 50HZ (+3%), 1440 RPM, 4 Pole IEI TEFC continuous duty vertical flanged mounted solid shaft squirrel cage induction motor as per technical specification approved by I & WR Department, Haryana. 1. Jamni pump house at RD 131000/L on Hansi Br. (01 no.)
Supply, Erection and commissioning of M.S. Delivery pipe 341.4 mm inner dia. (in approximate 6 mtr. Length each pipe) and each pipe end welded with flanges made of thickness 6mm MS plate as per approved specification and made ( including HT Nut & bolt , Rubber sheet and other fitment accessories required along with required. 1. Ritoli pump house at RD 124000/R on Hansi Br. (30 Mtr.) 2. Lajwana pump house at RD 7000/R on Bhiwani Br. (12 Mtr.) 3. Meherda pump house at RD 0/R on Bhiwani Br. (12 Mtr.)
Avon Engineering Company
Sahil Engg. Works
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .