Providing 315KVA,33KV/0.440KV Transformer and 33KV RMU for city bus depo at Jadhavwadi, Chhatrapati sambhajinagar.
2026_ASCDC_1335563_1
ASCDCL/2026/497
Open Tender
Electrical Works
Percentage
Chhatrapati Sambhajinagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,360
₹4.7 L
15 Sept 2026
7 Sept 2026
15 Sept 2026
7 Sept 2026
14 Sept 2026
7 Sept 2026
7 Sept 2026 - 9 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Electrical Works | |||||
| 1.01 | Providing & erecting 4 Pole MCCB, 415V, up to 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB (DSR NO.5-5-1) | 5 | Nos | 6,970 | ₹34,850 |
| 1.02 | Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB (DSR NO.5-5-3) | 1 | Nos | 13,310 | ₹13,310 |
| 1.03 | Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB (DSR NO.5-5-4) | 1 | Nos | 19,030 | ₹19,030 |
| 1.04 | Providing & erecting 4 Pole MCCB 415V, 630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB (DSR NO.5-5-7) | 1 | Nos | 33,017 | ₹33,017 |
| 1.05 | Supply, installation, testing and commissioning of outdoor type, metal enclosed, SF₆ insulated, extensible 33 kV Ring Main Unit (RMU) suitable for a configuration of 2 Incoming + 4 Outgoing feeders (2+4), comprising LLVVVV + Metering (M) arrangement, complete in all respects. The RMU shall be of modular construction with 2 Load Break Switch (LBS) incomers (630A) and 4 Vacuum Circuit Breaker (VCB) outgoing feeders (630A), all suitable for 33 kV, 50 Hz system, with short circuit withstand capacity of minimum 25 kA for 3 seconds. The VCB feeders shall be equipped with numerical protection relays having O/C, E/F protection with IDMT characteristics, while LBS feeders shall have fault make capacity and earthing switches with interlocking. The unit shall be fully SF₆ gas insulated, hermetically sealed, maintenance free, with IP67 rating for gas tank and IP54 for enclosure, suitable for outdoor installation. It shall include busbar system, internal arc classification AFLR, mechanical and electrical interlocks, mimic diagram, position indicators, spring charged/manual motorized operation, and provision for SCADA compatibility with RTU interface. The metering panel (M) shall be provided with CTs, PTs, ABT compliant energy meter with accuracy class as per utility norms. The RMU shall be complete with cable termination kits, gland plates, control wiring, space heaters, illumination, marshalling terminals, and all accessories. The equipment shall conform to IEC 62271-200, IEC 62271-100, IEC 62271-102 standards and relevant IS standards, and shall be approved by local utility. The scope shall include factory testing, routine/type test certificates, site installation, earthing, testing, commissioning, and handing over complete system as per the directions of Engineer-in-Charge. (As per approved market rate) | 1 | Nos | 96,00,000 | ₹96,00,000 |
| 1.06 | Supply, installation, testing and commissioning of outdoor type, metal enclosed, SF₆ insulated, extensible 33 kV Ring Main Unit (RMU) suitable for 6-way LBS configuration (LLLLLL), complete in all respects. The RMU shall consist of six Load Break Switch (LBS) feeders, each rated 630A, suitable for 33 kV, 50 Hz system, with fault making capacity and short-time withstand current of minimum 25 kA for 3 seconds. Each way shall be provided with ON/OFF/EARTH positions with fully interlocked earthing switches, ensuring safe operation and maintenance. The unit shall be fully gas insulated, hermetically sealed, maintenance-free for life, with IP67 protection for SF₆ tank and minimum IP54 for outer enclosure, suitable for outdoor installation. The RMU shall have internal arc classification AFLR, robust busbar system, mechanical position indicators, mimic diagram, padlocking arrangement, and manual spring-assisted operation with provision for motorized operation if required. The panel shall be provided with cable termination compartments suitable for XLPE cables, detachable gland plates, and adequate space for heat shrink/plug-in terminations. It shall include all control wiring, interlocks, danger plates, space heaters, illumination (if applicable), and earthing terminals. The RMU shall be compatible for future SCADA integration, if required. The equipment shall conform to IEC 62271-200, IEC 62271-102 and relevant IS standards, and shall be approved by the local utility. The scope shall include factory routine/type tests, supply of test certificates, complete erection, earthing, testing, commissioning, and handing over the system in fully operational condition as directed by the Engineer-in-Charge. (As per approved market rate) | 1 | Nos | 63,00,000 | ₹63,00,000 |
| 1.07 | Supplying, installing, testing and commissioning of 33 kV, 630 A,Vacuum Circuit Breaker (VCB) with internal arc classification, suitable foroutdoor/indoor application as specified, complete with all accessoriesand auxiliaries, erected on provided civil foundation/MS channels/cable trench, including control and protection panel, numerical relays, interlocking system, cable termination arrangements for 33 kVXLPE cables, earthing, local and remote operation facility, and all associated works, conforming to relevant IEC 62271-100 and IEC 62271-200 standards (As per approved market rate) | 1 | Nos | 15,00,000 | ₹15,00,000 |
| 1.08 | Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for up to 250A MCCB.(DSR No. 5-11-14) | 3 | Nos | 1,259 | ₹3,777 |
| 1.09 | Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for above 250A up to 630A MCCB.(DSR No. 5-11-15) | 3 | Nos | 1,870 | ₹5,610 |
stage.html
html • 0.02 MB
tech_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
RFPRMU1.pdf
Tender Documents • 2.90 MB
BOQ_2284527.xls
BOQ • 0.39 MB
NITRMU.pdf
Additional Documents • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .